Stanley 204143 User manual

All manuals can be found at
www.stanleymobileapps.com
iQ Controller
Installation and Operation Manual
204143
FOR SWING AND FOLD DOORS

GENERAL DESCRIPTION
Intended Use
This manual provides abbreviated descripve informaon, wiring instrucons, and tune-in instrucons for the
iQ controller used with Magic-Swing™ and Magic-Force™. The manual is intended as a quick-reference guide.
Aachment 7 illustrates the iQ controller controls and indicators.
Applicability
This manual is applicable on iQ control boxes used with Magic-Swing and Magic-Force operators.
Precautions
Magic-Touch Hold Open Time must be a minimum of 3 seconds to ensure compliance with ANSI/BHMA 156.19 “American
Naonal Standard for Power Assist and Low Energy Power Operated Doors,” or most current ANSI/BHMA standards
specicaons.
All ANSI/BHMA and UL Requirements in Aachment 8 must be met before the door is put into operaon.
1
Copyright 2019, Stanley Access Technologies, LLC. . All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
10.18.2019
2 Document 204143 REV 5 • www.stanleyaccess.com • 1.800.7.ACCESS
Table of Contents
General Description ..........................................................................................................................2
Intended Use ..............................................................................................................................................................2
Applicability ................................................................................................................................................................ 2
Precautions.................................................................................................................................................................. 2
Features and Functions .......................................................................................................................................... 3
Wiring Instructions ...........................................................................................................................6
Evaluate Power Requirements ............................................................................................................................. 6
Connecting Main Power Wiring .......................................................................................................................... 6
Connecting Breakout Status Signal Wiring (Magic-Swing Operators) ................................................ 6
Connecting Breakout Status Signal Wiring (Magic-Force Operators) ................................................. 8
Wiring the Operator Switch Module (Magic-Force Operators) .............................................................. 9
Wiring the Operator for Required Handing (Magic-Force Operators) ..............................................10
Wiring the Power Close Speed Module ........................................................................................................10
Wiring the “ON/OFF/HOLD OPEN” Switch and Power Switch ..............................................................10
Wiring the Door Activation or Safety Device ...............................................................................................10
Wiring Swing Guard T ...........................................................................................................................................11
Wiring Bodyguard-T ..............................................................................................................................................11
Wiring Superscan-T ...............................................................................................................................................11
Wiring Holding Beam............................................................................................................................................11
Wiring Other Sensors ............................................................................................................................................11
Tune-In Instructions........................................................................................................................12
Tuning in the iQ Using the Controller Pushbuttons .................................................................................12
Index Tables ..............................................................................................................................................................13
Status Codes .............................................................................................................................................................17
Door States................................................................................................................................................................18
Final Tune-In Adjustments ..................................................................................................................................19
Attachments ....................................................................................................................................20
Attachment 1: Breakout Status Wiring for Magic Swing Operators ............................. 20
Attachment 2: Magic-Force Wiring Diagram .....................................................................................21
Attachment 3: Magic-Swing Wiring Diagram ....................................................................................22
Attachment 4: Monitored Sensor Wiring Diagrams .......................................................................23
Attachment 5: Non-Monitored Sensors Wiring Diagram ...........................................................37
Attachment 6: iQ Terminal Block Connections ..................................................................................40
Attachment 7: iQ Controls and Indicators ...........................................................................................41
Attachment 8: ANSI/BHMA and UL Compliance Requirements ..............................................43
Attachment 9: Hand Held Device Troubleshooting Aid ...............................................................45
Attachment 10: Recommended Values for Door Configurations ...........................................46
Attachment 11: iQ Controller Fine Tuning ...........................................................................................47

iQ Control Box
10.18.2019
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204143 REV 5 3
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
2S Operation
ON = push switch to open, push switch to close;
OFF = 2S mode disabled.
Close Position Tolerance: Distance from full close that the door transions from close check to full closed. This parameter
is used when the door can’t get closed and to eliminate recycles caused by obstrucons. This sets the posion where the
controller interprets the door as fully closed.
Close Obstruction Time: The amount of me in increments of 0.1 seconds the spring applies force when almost stopped
or stopped when the controller indicates a state of 09. Before increasing this parameter, check for mechanical issues.
Fire Alarm Mode:
0 = OFF:Keeps the Fire Alarm Mode OFF.
1 = OPEN: If not already Fully Open, the controller will ignore sensors and open the door slowly. If the door was
previously obstructed, it will remain at the parally opened posion. The controller will cause the door to remain
open/parally opened for the duraon of the Fire Alarm acvaon.
2 = CLOSE: Ignore Sensors and Hold Open Switch Mode: If the door is Fully Closed, the controller will ignore
acvaon sensors. If not already Fully Closed, the controller will ignore sensors, Hold Open, and close the door.
If the door is obstructed, it will not recycle and leave the motor drive in “freewheel”.
3 = OPEN WITH RETRY: If not already Fully Open, the controller will ignore sensors and open the door slowly.
If the door becomes obstructed, it will pause for 0.5 second and reaempt opening. The controller will cause the
door to remain open/aempt opening for the duraon of the Fire Alarm Acvaon.
4 = CLOSE: Ignore Hold Open Funcon Switch Mode: If the door is Fully Closed, the controller will ignore
acvaon sensors. If not already Fully Closed, the controller will ignore the Hold Open but observe sensors normally
if in automac or one way. If the door is obstructed, it will not recycle and leave the motor drive in “freewheel”.
Hold Beam Type: Selects the hold beam type to be used for monitored or non-monitored applicaons.
Monitored Hold Beams: Photobeam Pro or Optex OS12CT. Refer to wiring diagrams per applicaon.
Hold Open Delay: Amount of me the door stays open aer all sensors have cleared.
I/O Configuration
: Allows Motor 2 Power Close Relay feedback to be used instead of funcons normally used with the
selected input:
0 = Default
1 = TB5-7: Motor 1 Relay Feedback, TB3-9 Motor 2 Relay Feedback. OPEN: If not already Fully Open, the
controller will ignore sensors and open the door slowly. If the door was previously obstructed, it will remain at the
parally opened posion. The controller will cause the door to remain open/parally opened for the duraon of
the Fire Alarm acvaon.
2 = TB2-5: Motor 1 Relay Feedback, TB3-9 = Motor 2 Relay Feedback. If the door is Fully Closed, the controller will
ignore acvaon sensors. If not already Fully Closed, the controller will ignore sensors, Hold Open, and close the
door. If the door is obstructed, it will not recycle and leave the motor drive in “freewheel”.
Lock Delay: This allows the lock to mechanically unlock before door moon. Lock Delay only occurs when the door is full
closed (when the control displays 00). When the door is acvated while the door is open, no Lock Delay occurs. Lock Delay
will always occur if a door posion switch is acve. Value is in 0.1 second increments.
Lock Logic: Select to choose desired lock logic:
0 = Fail Safe: Unlocked when power is removed.
1 = Fail Secure: Locked when power is removed.
Lock Release Time: The amount of me (in seconds) that the door will press closed before going open when the lock
needs to release at the closed posion. The value of zero disables the lock release.
Lock Release Torque: The torque used in the lock release state. This parameter sets the maximum current available
to the motor which is directly proporonal to the door force.
Magic Touch Engagement: Determines how smooth the door is to push aer a Magic Touch acvaon.
Magic Touch Hold Open Time: Delay that the door stays open aer all sensors have cleared aer a Magic Touch operaon.
Parameter is in seconds, with increments of 0.1 seconds.
Magic Touch Sensitivity: Sets the threshold for manual acvaon. Seng of 1 is most sensive. This seng is raised
if false acvaons are seen.
Manual Mode Sensor Override: When set to ON the door sensors on the approach side will only be acvated when a push
plate, Magic Touch, or other Knowing Act acvaon signal is used.
= NOT SELECTABLE BY KEY PAD/PUSH BUTTONS
Features and Functions

iQ Control Box
4 Document # 204143 REV 5 • www.stanleyaccess.com • 1.800.7.ACCESS
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
10.18.2019
Motor Starting Speed: Aects the smoothness of the transion to powered door moon aer manual door use.
No Reverse on Obstruction: Door will not recycle on close obstrucon. Used in Low Energy only.
Off Mode: If set to close, all sensors are ignored when funcon switch is o.
Open Acceleration: Aects how responsive the door is to speed changes in the opening direcon. This parameter is used
when the door is lagging open speed. Startup torque and startup length should be invesgated prior to increasing. This
parameter aects all open moon speeds: open speed, open check speed, open learn speed, as well as open braking.
Open Braking: Adjusts how quickly the door slows down prior to check speed. Increasing this parameter increases
braking power.
Open Check Length: The percent of door travel in which the door starts to slow down to open check speed. This parameter
typically is adjusted based on door weight and open speed seng.
Open Check Obstruction Time: The amount of me in increments of 0.1 seconds that the door applies force when almost
stopped or stopped when the controller indicates a state of 04. Before increasing this parameter, check for mechanical
issues, as well as speed and torque parameter sengs.
Open Check Recycle Speed: The percent of Open Speed that is used when recycling in the Open Check Length.
Open Check Speed: The speed used during normal operaon in the open check state 04 prior to arriving at full open.
This speed is set to determine how fast the door arrives at full open aer open speed. This parameter sets the target speed
seng. Other parameters like open check torque, open acceleraon, and open braking, as well as door properes like
fricon, door length, and door weight aect door speed.
Open Check Torque: The torque used during normal operaon in open check state. This torque must be set to comply with
ANSI/BHMA door force requirements. This parameter sets the maximum current available to the motor which is directly
proporonal to the door force. This torque seng is used in conjuncon with Open Check Speed.
Open Learn Speed: The speed used on power up, during FIS, aer an obstrucon, and return from breakout. The controller
display may indicate either 02 or 04 as a door state and sll use Open Learn Speed based on the condions listed prior. This
speed is typically set higher than check speed, to allow faster door moon when not in the check zones, but sll slower door
moon than normal operaon. This parameter sets the target speed seng. Other parameters like open learn torque, and
open acceleraon as well as door properes like fricon, door length, and door weight aect door speed.
Open Learn Torque: The torque used on power up, during FIS, aer an obstrucon, and return from breakout. This torque
must be set to comply with ANSI/BHMA door force requirements. This parameter sets the maximum current available to the
motor which is directly proporonal to the door force. This torque seng is used in conjuncon with open learn speed.
Open Obstruction Time: The amount of me in increments of 0.1 seconds the door applies force when almost stopped or
stopped when the controller indicates a state of “02”. Before increasing this parameter, check for mechanical issues, as well
as speed and torque parameter sengs.
Open Speed: The speed used during normal operaon in the opening state 02. This parameter sets the target speed seng.
Other parameters like open torque, open startup torque, open startup length, and open acceleraon, as well as door
properes like fricon, door length, and door weight aect door speed.
Open Startup Length: The percent of door length in which the Open Startup Torque parameter is used. These parameters
are used to overcome fricon encountered at the beginning of open door moon. This parameter should be set as low as
possible to ensure reliable operaon.
Open Startup Torque: Open Startup Torque used when entering the opening state 02 and recycles. It is used for a
congurable door length (determined by the Open Startup Length parameter). Aer this door length, the torque seng
will revert to the Open Torque. This torque should be set greater than Open Torque to ensure that the controller can start
door moon, overcome stac fricon, and avoid obstrucons. This torque must be set to comply with ANSI/BHMA door
force requirements. This parameter sets the maximum current available to the motor which is directly proporonal to
the door force.
Open Stop: The distance from full open that the door will stop in 0.1 degree increments. This parameter is used to minimize
excessive oscillaons that are seen at full open.
Open Torque: The torque used during normal operaon following the end of Open Startup Length. This torque must be set to
comply with ANSI/BHMA door force requirements. This parameter sets the maximum current available to the motor which is
directly proporonal to the door force. This torque seng is used in conjuncon with Open Speed.
Operate Delay: Delays the moon of the door aer the operate signal is received. Value is in 0.1 second increments.
Overspeed Braking Angle: Determines the posion the door transions to Open Check during manual operaon following
a Knowing Act. Seng the value to 99 disables the transion to Open Check.
Overspeed Resistance: Sets the sensivity to external factors that allow the door to be used manually. Increasing this
parameter will desensize door moon to factors such as wind, stack pressure, and manual use.
Features and Functions (continued) = NOT SELECTABLE BY KEY PAD/PUSH BUTTONS

iQ Control Box
10.18.2019
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204143 REV 5 5
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
Power Assist at Closed Mode: Reduces the inial force required to iniate door moon when Magic Touch or
Power Assist is enabled.
00 = OFF
01 = ON at Closed Door Posion: When DPS contact is closed, Power Assist at Closed is enabled.
02 = Sensor Controlled: DMA1, DMA2, DMS1, DMS2, OHP and Power Close Cancel / Power Assist inputs will enable Power
Assist at Closed when sensor is acve.
Power Assist Enable: This feature allows the operator to assist the user so that the door is easier to open during
manual operaon.
Power Assist Open Braking: Sets the amount of resistance the operator provides as the door approaches full open when
Power Assist is enabled. Decreasing this parameter will provide greater resistance provided by the Power Assist funcon.
Power Assist Torque: Sets the amount of helping force during manual operaon.
Power Close Angle: The angle at which the motor starts to assist the spring while closing. If set to 90, the motor will always
be assisng from full open.
Power Close at Closed Enable: Power Close at Closed Enable is used to maintain the door pressing at full closed (state 22).
Power Close at Closed Torque: Power Close Torque is the torque used during Power Close at Closed operaon. This torque
must be set to comply with ANSI/BHMA door force requirements. This parameter sets the maximum current available to the
motor which is directly proporonal to the door force.
Power Close Check Angle: The angle at which the door starts to slow down to Power Close Check Speed. This parameter
typically is adjusted based on door weight and Power Close Speed seng. This value should be lower than the
Power Close Angle.
Power Close Check Speed: This is the speed used during normal operaon in the Power Close check state prior to
arriving at full closed. This parameter sets the target speed seng. Other parameters like Power Close Speed,
Power Close Check Angle, and Power Close Check Torque, as well as door properes like fricon, door length,
and door weight aect door speed.
Power Close Check Torque: The torque used during normal operaon in Power Close check state. This torque must be set
to comply with ANSI/BHMA door force requirements. This parameter sets the maximum current available to the motor
which is directly proporonal to the door force. This torque seng is used in conjuncon with Power Close Check Speed.
Power Close Enable: Power Close allows the motor to assist the spring close to help overcome wind and stack pressure.
This feature requires a Power Close Speed Module (part #517864) connected to the controller. Ensure forces are in
compliance with applicable ANSI/BHMA Standard. To achieve this, door mounted sensors may be required to disable Power
Close when a person is nearby.
Power Close Obstruction Time: The amount of me in increments of 0.1 seconds that the door applies force when almost
stopped or stopped (when the controller indicates a state of 18). Before increasing this parameter, check for mechanical
issues, as well as Power Close Speed, Power Close Torque, Power Close Check Speed, and Power Close Obstrucon Speed
parameter sengs.
Power Close Speed: The speed used during normal operaon in Power Close (state 18). This speed is set to change how
long it takes the door to reach the Power Close Check Angle. This parameter sets the target speed seng. Parameters such
as Power Close Torque and door properes like fricon, door length, and door weight aect door speed.
Power Close Torque: The torque used during Power Close operaon. This torque must be set to comply with ANSI/BHMA
door force requirements. This parameter sets the maximum current available to the motor which is directly proporonal to
the door force. This torque seng is used in conjuncon with Power Close Speed.
Safety Logic: Selects sensor type to be used for monitored or non-monitored applicaons. Monitored Sensors may require
use of alternate wiring.
Stall Sensor Ignore Position: Ignores the stall sensor input from a percentage of the total door open. The full open
posion is 100 percent.
Stall Torque: Stall Torque is the torque used aer obstrucon and during stall events in the state of “15” or “16”. This
parameter aects the amount of force the door takes to push open while in stall.
Unlock Time: The me that the lock/strike is unlocked. This me starts when the door begins to open. The total me that
the lock/strike is unlocked is the Lock Delay plus the Unlock Time. Unlock Time is 0 to 9.8 seconds. Each increment is 0.1
seconds. When set to 99 the lock/strike will stay unlocked unl the door returns to the closed posion (99 is the only value
that is based on door posion and not me).
Features and Functions (continued) = NOT SELECTABLE BY KEY PAD/PUSH BUTTONS

iQ Control Box
6 Document # 204143 REV 5 • www.stanleyaccess.com • 1.800.7.ACCESS
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
10.18.2019
WIRING INSTRUCTIONS
Evaluate Power Requirements
EVALUATE door system power requirements as follows:
• ENSURE power source is a dedicated 115 VAC, 50/60 Hz source with 20A circuit rang per two controllers.
• ENSURE power source is not shared with other equipment, i.e., cash registers, EAS systems, or other
electromagnetic interference generators.
Connecting Main Power Wiring
Warning: To prevent injury to personnel, incoming electrical power to header must be de-energized before
connecng control box electrical harness to electrical service.
• DE-ENERGIZE incoming electrical power to header.
• Refer to Aachments 2, 3, and 4, and using the wire nut provided, CONNECT ground wire assembly (P/N
711527) to electrical service ground wire.
• In a concealed locaon inside the header (not visible from the exterior of the header), DRILL a hole for a
No. 8 screw.
• INSTALL ground wire ring terminal and star washer onto the No. 8 screw provided, and FASTEN screw, star
washer, and ground wire to header.
• In a concealed locaon inside the header, DRILL a second hole for a No. 8 screw.
• INSTALL power line harness 412544 ring terminal and star washer onto the No. 8 screw provided, and FASTEN
screw, star washer, and ground wire to header.
• Using the wire nuts provided, CONNECT power line harness 412544 to electrical service as follows:
• CONNECT power pigtail assembly black wire to black (line) service wire.
• CONNECT power pigtail assembly white wire to white (neutral) service wire.
Connecting Breakout Status Signal Wiring (Magic-Swing Operators)
Warning: To prevent injury to personnel and damage to equipment, control box power must be de-energized
before connecng breakout status signal wiring.
Caution: If the motor is running and the breakout status switch is not connected, arcing across the breakout
switch contacts can occur. This will result in damage to the breakout switch. To prevent damage from switch
contact arcing, the breakout status switch must always be connected.
NOTES:
The breakout status switch must be used in all applicaons where there is no posive door stop in the
breakout direcon.
The auxiliary switch is the breakout status signal switch. The auxiliary switch was formerly the open check switch
on the operator switch plate (top cam).
• Refer to Aachment 1, and CONNECT breakout status wiring.
• REMOVE quick-connect terminal (brown wire) from the normally open terminal of the auxiliary switch
(formerly open check switch), and INSTALL onto normally closed terminal.
2
Connued Next Page

iQ Control Box
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204143 REV 5 7
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
• SET the auxiliary cam for approximately 3° acvaon (toward breakout direcon), and ADJUST cam as necessary
to trip the corresponding micro switch prior to acvaon of the breakout switch.
• CONNECT yellow jumper wires installed on the single/dual motor harness
as follows:
a. INSTALL stripped end of rst jumper wire (from posion 3 of the 8-pin connector on operator harness) into
terminal 9 of control box connector TB3.
b. INSTALL stripped end of second jumper wire (from posion 5 of the 8-pin connector on operator harness)
into terminal 10 of control box connector TB3.
NOTE: In a swing-pair applicaon, the breakout switches of each operator need to be wired in series to en-
sure that the control box will not open the doors if either breakout status switch is acvated.
• IF applicaon is a pair of swing doors, PERFORM the following:
a. REPEAT the previous two steps for the second door operator.
b. CONNECT stripped end of one yellow jumper wire from each operator to terminals 9 and 10 of control box
connector TB3.
• Using a wire nut, CONNECT remaining wire from rst operator to remaining wire on second operator.
• VERIFY breakout status/breakout cam is properly set as follows:
a. Refer to Figure 1, and visually INSPECT cams for proper seng.
b. UNPLUG TB3 from control box.
NOTE: When checking breakout status switch connuity, the switch is rst checked with the door closed,
then again with the door in the breakout (negave 3°) posion. In a swing-pair applicaon, both doors can
be tested at the same me in the closed posion. However, the doors must be tested individually when
checking switch connuity with the doors in the breakout (negave 3°) posion.
c. ENSURE door is in the closed posion.
d. Using a mulmeter, CHECK connuity between TB3 terminals 9 and 10, and ENSURE there is connuity.
e. PUSH door in the breakout direcon, and HOLD door at approximately the negave 3° posion.
f. Using a mulmeter, CHECK connuity between TB3 terminals 9 and 10, and ENSURE there is an open circuit.
g. RELEASE door.
h. PLUG TB3 into control box.
TOP CAM = AUX SWITCH
CENTER CAM = EMERGENCY BREAKOUT SWITCH
BOTTOM CAM = CLOSE CHECK SWITCH
EMERGENCY SWITCH
N.C.: RED
N.O.: YELLOW
COM.: BLACK
OPEN CHECK SWITCH
N.O.: BROWN
COM.: ORANGE
CLOSE CHECK SWITCH
N.C.: WHITE
COM.: BLUE
TOP CAM = AUX SWITCH
CENTER CAM = EMERGENCY BREAKOUT SWITCH
BOTTOM CAM = CLOSE CHECK SWITCH
RH SHOWN LH SHOWN
Figure 1. Breakout Status/Breakout Cam Settings (Magic-Swing Operators)
COM
N.O.
N.C.
COM
N.O.
N.C.
COM
N.C.
COM
N.O.
N.C.
N.O.
Connued From Previous Page

8 Document # 204143 REV 5 • www.stanleyaccess.com • 1.800.7.ACCESS
Connecting Breakout Status Signal Wiring (Magic-Force Operators)
Warning: To prevent injury to personnel and damage to equipment, control box power must be de-energized
before connecng breakout status signal wiring.
Caution: If the motor is running and the breakout status switch is not connected, arcing across the breakout
switch contacts can occur. This will result in damage to the breakout switch. To prevent damage from switch
contact arcing, the breakout status switch must always be connected.
NOTE: The breakout status switch must be used in all applicaons where there is no posive door stop in the
breakout direcon.
• SET “POWER” switch to OFF.
• IF single-operator applicaon, PERFORM the following:
a. INSTALL one breakout status switch wire to terminal 9 of control box connector TB3.
b. INSTALL second breakout status switch wire to terminal 10 of control box connector TB3.
• IF dual-operator applicaon, PERFORM the following to put the breakout switches in series:
a. INSTALL one breakout status switch wire from one operator to terminal 9 of control box connector TB3.
b. INSTALL one breakout status switch wire from second operator to terminal 10 of control box connector TB3.
c. CONNECT remaining two yellow breakout status switch wires together with a wire nut.
• VERIFY breakout status/breakout cams are properly set as follows:
a. Refer to Figure 2, and visually INSPECT cams for proper seng.
b. UNPLUG TB3 from control box.
NOTE: When checking breakout status switch connuity, the switch is checked twice; rst with the
door closed, then with the door in the breakout (negave 3°) posion. In a swing-pair applicaon, both
doors can be tested at the same me in the closed posion. However, the doors must be tested
individually when checking switch connuity with the doors in the breakout (negave 3°) posion.
Figure 2. Breakout Status/Breakout Cam Settings
Magic Force Operators (Continued next page).
BREAKOUT CAM
BREAKOUT STATUS CAM
CLOSE CHECK CAM
AUXILIARY CAM
INCREASE
BREAKOUT
ANGLE
DECREASE
BREAKOUT
ANGLE
CAM ROTATION
INCREASE
CLOSE CHECK
ANGLE
DECREASE
CLOSE CHECK
ANGLE
CAM ROTATION
SEE DETAIL A
RIGHT HAND OPERATOR
INITIAL CAM SETTINGS (LOOKING DOWN AT OPERATOR SPINDLE)
ROTATE BREAKOUT CAMS COUNTER-CLOCKWISE UNTIL RAISED PORTION OF BREAKOUT STATUS CAM JUST CONTACTS SWITCH ROLLER.
ROTATE CLOSE CHECK CAM CLOCKWISE UNTIL RAISED PORTION OF CAM ACTUATES SWITCH, THEN ROTATE CAM 10 DEGREES COUNTER-CLOCKWISE.
ROTATE AUXILIARY CAM AS DESIRED.

iQ Control Box
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204143 REV 5 9
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
AUXILIARY CAM
CLOSE CHECK CAM
DECREASE
CLOSE CHECK
ANGLE
INCREASE
CLOSE CHECK
ANGLE
CAM ROTATION
BREAKOUT STATUS CAM
BREAKOUT CAM
DECREASE
BREAKOUT
ANGLE
INCREASE
BREAKOUT
ANGLE
CAM ROTATION
SEE DETAIL B
LEFT HAND OPERATOR
INITIAL CAM SETTINGS (LOOKING DOWN AT OPERATOR SPINDLE)
ROTATE BREAKOUT CAMS CLOCKWISE UNTIL RAISED PORTION OF BREAKOUT STATUS CAM JUST CONTACTS SWITCH ROLLER.
ROTATE CLOSE CHECK CAM COUNTERCLOCKWISE UNTIL RAISED PORTION OF CAM ACTUATES SWITCH, THEN ROTATE CAM 10 DEGREES CLOCKWISE.
ROTATE AUXILIARY CAM AS NEEDED
c. ENSURE door is in the closed posion.
d. Using a mulmeter, CHECK connuity between TB3 terminals 9 and 10, and ENSURE there is connuity.
e. PUSH door in the breakout direcon, and HOLD door at approximately the negave 3-degree posion.
f. Using a mulmeter, CHECK connuity between TB3 terminals 9 and 10, and ENSURE there is an open circuit.
g. RELEASE door.
h. PLUG TB3 into control box.
Wiring the Operator Switch Module (Magic-Force Operators)
• Refer to Aachment 2 and CONNECT switch module harness 413791 to dual-adjustment closing speed
control connector J4.
• IF auxiliary posion switch will be used, refer to Figure 3, and PERFORM the following:
a. LIFT switch module release lever up, and SLIDE switch module out of operator housing.
b. CONNECT wiring to auxiliary posion switch terminal block as shown.
c. SLIDE switch module into operator housing unl switch module release lever snaps into place.
SWITCH MODULE
MCB006
SWITCH MODULE RELEASE LEVER
(PRESS LEVER UP TO RELEASE SWITCH MODULE)
AUXILIARY POSITION SWITCH
TERMINAL BLOCK
NORMALLY CLOSED CONTACT
COMMON
NORMALLY OPEN CONTACT
OPERATOR HOUSING
Figure 3. Wiring the Auxiliary Position Switch (Magic-Force Operators)
Figure 2. Continued.
Breakout Status/Breakout Cam Settings - Magic Force Operators

iQ Control Box
10 Document # 204143 REV 5 • www.stanleyaccess.com • 1.800.7.ACCESS
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
10.18.2019
Wiring the Operator for Required Handing (Magic-Force Operators)
NOTE: Operator cams are factory-set for right hand operaon.
• Refer to Figure 4, and DETERMINE door handing.
• CONNECT operator harness from close speed module to control box motor 1 and motor 2 connectors,
if applicable
Wiring the Power Close Speed Module
Refer to Aachment 2 and CONNECT the Power Close Speed Module.
Wiring the “ON/OFF/HOLD OPEN” Switch and Power Switch
• Refer to Aachment 2, and CONNECT ON/OFF/HOLD OPEN switch wiring as follows:
TB2 Terminal Connection Switch Wire Color
1 Hold Open Yellow
2 Common Orange
3 Automac On Violet
• SET POWER switch to OFF.
• CONNECT POWER switch harness 516857-1 to power harness 415000.
• CONNECT line connect harness 412544 to power harness 415000.
Wiring the Door Activation or Safety Device
NOTE: Aachments 2, 3, and 4 illustrate typical wiring for various devices. Though the specic device may not be
shown, this aachment can be used as a general guide. Specic wiring instrucons from the manufacturer must
also be consulted.
Refer to Aachments 2, 3, 4 and applicable manufacturer’s instrucons, and CONNECT door acvaon
or safety device.
LEFT HAND
DOOR
OPENING
MOTION
RIGHT HAND
Figure 4. Door Handing

iQ Control Box
10.18.2019
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204143 REV 5 11
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
Wiring Swing Guard T
Caution: Do not connect Swing Guard T Daughter Board or Sensors unl control box is fully tuned.
NOTE: Select Swing Guard T when in Step 9 of Table 1 if tuning with pushbuons, even though Swing Guard T
has not been connected at this me. If tuning with ‘Hand Held Device’, select Swing Guard T for Safety Logic.
1. Set DIP switches on the Swing Guard T Controller so that the sensor is always enabled (DIP switch 3
DOWN for auto).
2. To perform a first learn on the Swing Guard T system, Manual Mode Sensor Override must be set to OFF or
the door will not open and the learn will not complete. Once the learn is complete, set Manual Mode Sensor
Override to ON.
3. Wire SU100 into TB4.
NOTE: Do not use purple wires on Swing Guard T Controller wire harness.
TB1 Terminal Connection Swing Guard T Wire Color
1 (+) Power for Swing Guard T Red
2 Serial Communicaon Green
3 Serial Communicaon White
4 (-) Power for Swing Guard T Black
NOTE: Refer to the Swing Guard T installaon manual for Sensor Head mounng locaons, DIP switch
sengs, angle adjustments and roung of wire harnesses.
Wiring Bodyguard-T
The Bodyguard-T does not require a lockout relay for use with the iQ control box. The iQ control box generates the
data signals for door open, closing, and closed posions. Refer to Aachment 2, 3 , or 4, as applicable for wiring
connecons. Program the Bodyguard-T Relay Output to #1.
Wiring Superscan-T
Refer to Aachment 2, 3 , or 4 as applicable for wiring connecons.
Wiring Holding Beam
The Holding Beam input is used in applicaons when there is a rail-mounted holding beam. When the door is
closing and the beam is obstructed, the door will not open unl the door is completely closed and the header-
mounted sensor becomes acve. When the door is open and the beam is obstructed, the door will remain open.
Refer to Aachment 2, 3 , or 4 as applicable for wiring connecons.
Wiring Other Sensors
Refer to Aachment 2, 3, 4 or 5 as applicable for wiring connecons.

12 Document # 204143 REV 5 • www.stanleyaccess.com • 1.800.7.ACCESS
TUNE-IN INSTRUCTIONS
4
Tuning in the iQ Using the Controller Pushbuttons
1. To change the INDEX:
• Hold ENTER switch while pressing UP or DOWN to get to desired INDEX
2. To change a VALUE:
• Unlock the keypad by seng index 99 to value 00.
• Aer the desired INDEX is selected, release ENTER and within 2.5 seconds press UP or DOWN to
get the desired VALUE. (If the UP or DOWN buttons are not pressed within 2.5 seconds
of releasing the ENTER buon, the display will change from the VALUE back to the STATUS.)
3. To display STATUS CODE:
• A few seconds aer the VALUE is selected, the display indicates the STATUS CODE
4. To show the INDEX and VALUE
• To show the INDEX, hold ENTER. Once ENTER is released the display will show the VALUE of that
INDEX.
5. Read the descripons enrely before performing each step. Check the INDEX and VALUE aer each
step.
6. To store changes in permanent memory:
• Cycling door open one me will store changes.
7. To lock keypad:
• Lock keypad by seng index 99 to value 01 or by turning power OFF and then ON.
8. To access the door cycle counter funcon:
a. Ensure that the keypad is locked by seng index 99 to 01.
b. Ensure that the index is set to any index but 99.
c. Press the up or down key to access the door cycle counter.
d. The display will show “dc” followed by four pairs of digits, followed by “dc”. For example, if the
door count was 12345678 cycles the door will display “dc” “12” “34” “56” “78” “dc.”

iQ Control Box
10.18.2019
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204143 REV 5 13
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
Table 1. FIS Procedure Using Pushbuttons
Step Description
Display
Index Value Status
Code
1 Set Funcon switch to Closed.
2 Turn power on.
3 Unlock keypad. 99 0 00
4 Restart FIS. 96 1 A0
5 Select door type (Refer to Table 2). 0 Refer to Table 2 A0
6 Select Motor 1 Handing. 1 00 = Right hand
01 = Le hand
A0
7 Select Motor 2 Handing. 2 00 = Right hand
01 = Le hand
A0
8 Accept FIS. Display will show A1. 3 1 A1
9 Make changes: Safety Logic.
(NOTE: If there are no sensors
connected, leave value of 00).
11 Safety Logic. INDEX 11 - 00 to 15
00 = Sensor
01 = Sentrex
02 = Carpet
03 = Carpet 12 Sec.
04 = Non-Monitored Bi-Fold
05 = Monitored DM & OHP. ACT, STL
& SAF, both single & pair
06 = Monitored DM & OHP Dual
Egress. STL, ACT, STL & SAF
07 = Monitored OHP & Photobeam.
SAF & Photobeam
08 = Monitored DM ACT. ACT both
single & pair
09 = Monitored OHP Bi-Fold. SAF
10 = Monitored DM. ACT & STL both
single & pair
11 = Two OHP Monitored Bi-fold. SAF,
Bi-Fold/Swing
12 = Monitored Hub Based Sensors.
ACT & STL
13 = Swing-Guard T
14 = Monitored DM Stall & OHP both
single and pair. STL & SAF
15 = Monitored DM Stall & OHP Dual
Egress. STL & SAF
A1
10 Lock Keypad. 99 01 00
11 Final Tune in. -- -- --
ABBREVIATIONS
DM Door Mounted Sensors
OHP Overhead Presence Sensor
ACT Acvaon Side Presence Sensor
STL Stall Presence Sensor
SAF Safety Presence Sensor
Index Tables

iQ Control Box
14 Document # 204143 REV 5 • www.stanleyaccess.com • 1.800.7.ACCESS
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
10.18.2019
Table 2. iQ Mode Values
Code iQ Operational Mode
01 Dura-Glide door style—Single Motor
02 Dura-Glide door style—Dual Motor
03 Magic-Swing Door Style—Single Motor
04 Magic-Swing Door Style—Dual Motor
05 Magic-Force Door Style—Single Motor
06 Magic-Force Door Style—Dual Motor
07 Magic-Force Door Style—Single Motor Low Energy
08 Magic-Force Door Style—Dual Motor Low Energy
09 Fold door style--Single Motor
10 Fold door Style--Dual Motor
Description Index
iQ Mode Specic Door Operaonal Values - These depend upon the mode selected 00-89
Reserved 90-95
Command: Restart FIS. Entering 01 will cause FIS to restart. 96
Firmware: Entering 01 will display FE followed by two pairs of digits followed by FE.
For example, if the rmware is 0609, the controller will display FE 06 09 FE.
97
Command: Restart auto conguraon. Entering 01 sets the Control Box to A1, which keeps all
previous values and then the Control Box re-learns the encoder count.
98
Command: Lock. Entering 01 will lock all VALUE imports except this INDEX. This prevents
inadvertent changes to input values. VALUES may be unlocked by entering 00 in this INDEX.
99
Table 3. Index List

1.800.7.ACCESS • www.stanleyaccess.com • Document # 204143 REV 5 15
Table 4. Magic Force/Magic Swing Configuration Codes
Index Min.
Value
Max.
Value Description Motor
Defaults
Low
Energy
Full
Energy
0 1 125 Open Speed** M1 32 61
1 1 125 Open Check Speed** M1 6 6
3 0 99 Open Check Length M1 20 30
4 0 99 Magic Touch Sensivity
(01= max. Sensivity) M1 0 0
5 1 99 Magic Touch Hold Open Time
(25 sec. max. = 99%) M1 16 16
6 1 99 Hold Open Delay
(25 sec. max. = 99%) M1 22 6
7 0 99 Open Torque M1 35 60
8 0 99 Open Check Torque M1 35 60
9 0 99 Stall Torque M1 8 8
11 0 15 Safety Logic M1 0 0
12 0 1 2S Operaon M1 0 0
13 3 60 Open Obstrucon Time
(60 = 1.5 seconds) M1 20 20
14 0 40 Open Acceleraon M1 20 10
15 0 10 Open Braking M1 8 8
16 0 50 Operate Delay
(0.1 sec. increments: 5.0 sec. max.) M1 0 0
17 0 1 No Reverse on Obstrucon M1 0 0
18 0 50 Lock Delay M1 0 0
19 0 1 Manual Mode Sensor Override M1 0 0
20 1 125 Open Speed** M2 32 61
21 1 125 Open Check Speed** M2 6 6
23 0 99 Open Check Length M2 20 30
24 0 99 Magic Touch Sensivity
(01= max. Sensivity) M2 0 0
25 1 99 Magic Touch Hold Open Time
(25 sec. max. = 99%) M2 16 16
**Max value listed in table not accessible from keypad.
Table 4 Continued Next Page

16 Document # 204143 REV 5 • www.stanleyaccess.com • 1.800.7.ACCESS
Table 4. Magic Force/Magic Swing Configuration Codes (Continued)
Index Min.
Value
Max.
Value Description Motor
Defaults
Low En-
ergy
Full En-
ergy
26 1 99 Hold Open Delay
(25 sec. max. = 99%) M2 22 6
27 0 99 Open Torque M2 35 60
28 0 99 Open Check Torque M2 35 60
29 0 99 Stall Torque M2 8*** 8***
31 0 1 O Mode M1 0 0
32 0 1 Lock Logic M1 1 1
33 3 60 Open Obstrucon Time
(60 sec. = 1.5 seconds) M2 20 20
34 0 40 Open Acceleraon M2 20 10
35 0 10 Open Braking M2 8 8
36 0 50 Operate Delay
(0.1 sec. increments: 5.0 sec. max.) M2 0 0
37 1 99 Unlock Time
(99 = unlocked unl full closed) M1 10 10
38 0 4 Fire Alarm Mode M1 0 0
*Please refer to Features and Functions for more information on parameters.
**Max value listed in table not accessible from keypad.
***Default value is different for Magic-Swing.

iQ Control Box
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204143 REV 5 17
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
Table 5. Status Codes
Status Code Description Remedy/Cause
0 Normal
0b Obstrucon
20 Breakout
33 System Error
Door moves slowly on one cycle:
• Note it. No acon required.
Door moves slowly on several cycles.
Display shows 33 on slow cycles:
• Reset Power.
• If code does not clear, call Tech Support.
34 Internal Communicaon Error:
Type 1 (see Aachment 7)
Door moves slowly on one cycle:
• Note it. No acon required.
Door moves slowly on several cycles.
Display shows 34 on slow cycles:
• Reset Power.
• If code does not clear, call Tech Support.
35 Motor Drive Failure Replace Controller.
36 Internal Communicaon Error:
Type 2 (see Aachment 7)
Door moves slowly on one cycle:
• Note it. No acon required.
Door moves slowly on several cycles.
Display shows 36 on slow cycles:
• Reset Power.
• If code does not clear, call Tech Support.
55 Stall State
A0 Uncongured
A1 FIS in Progress
A2 FIS Learn Complete
b1 Encoder Error Cable failure.
b2 Encoder Mismatch Wrong Encoder/Magnet.
b3 Encoder Failure Wrong Encoder/Magnet or cable failure.
Ensure motor is aempng to move.
c1 Learn Error
dB Troubleshoong Mode
Continued next page.
Status Codes

iQ Control Box
18 Document # 204143 REV 5 • www.stanleyaccess.com • 1.800.7.ACCESS
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
10.18.2019
Door State Description
00 Door State is Closed.
02 Door State is Opening.
04 Door State is in Open Check.
06 Door State is Full Open.
09 Door State is in Close Check.
15 Door State is Open Stop.
16 Door State is Close Stop.
18 Door State is in Power Close.
19 Door State is in Lock Release.
21 Door State is in Power Assist.
22 Door State is in Power Close at Closed.
NOTES:
• If the current status code is “Normal operaon—All OK”, the iQ will show the current door state.
Otherwise, the iQ alternates between showing the current status code and the door state.
• d1 and d2 displayed when controlling more than one door.
Any state that follows d1 is referencing door #1.
• Any state that follows d2 is referencing door #2
Table 6. Door States
Door States
Table 5. Status Codes (continued)
Status Code Description Remedy/Cause
E2 / ho Door Held Open
Use best pracces to troubleshoot using
hand held device and provided
wiring diagrams.
E3 Door Length Error 1. Check mechanical issues, components.
2. Re-do First Installaon Sequence (FIS).
E5 Motor Drive Error
E6 Power Close Control Failure Verify Power Close Speed Module wiring.
F0 Stall Sensor Failure Verify sensor wiring and safety logic seng.
F1 Approach Sensor Failure Verify sensor wiring and safety logic seng.
F2 Hold Beam Sensor Failure Verify sensor wiring and safety logic seng.
F4 Safety 1 Sensor Failure Verify sensor wiring and safety logic seng.
F5 Safety 2 Sensor Failure Verify sensor wiring and safety logic seng.
FA Fire Alarm Acve

iQ Control Box
1.800.7.ACCESS • www.stanleyaccess.com • Document # 204143 REV 5 19
Copyright 2019, Stanley Access Technologies, LLC. All rights reserved. Reproduction
in whole or in part without the express written permission of Stanley is prohibited.
Final Tune-In Adjustments
• Refer to ANSI/BHMA A156.10, “American Naonal Standard for Power Operated Pedestrian Doors,” or
ANSI/BHMA A156.19, “American Naonal Standard for Power Assist and Low Energy Power Operated Doors,”
or the most current ANSI/BHMA standards.
• CYCLE and RECYCLE door several mes to verify proper speeds and forces, and PERFORM adjustments in the
following order:
a. ADJUST CK (Close Check) cam.
b. ADJUST Open Speed.
c. ADJUST Open Check Speed.
d. ADJUST CLS (Close Speed) rheostat.
e. ADJUST CK (Close Check Speed) rheostat.
NOTE: Adjustments to the CK (Close Check) rheostat also aect closing speed.
Closing speed must always be checked aer adjusng Close Check Speed.
f. ADJUST CLS (Close Speed) rheostat.
Caution: To prevent motor overheang and premature motor failure, Stall Torque must not be
set too high.
g. ADJUST Stall Torque.
h. ADJUST torque.
i. ADJUST me delay.
Warning: The Magic-Touch™ Hold Open Time must be a minimum of 3 seconds to ensure compliance
with ANSI/BHMA A156.19 “American Naonal Standard for Power Assist and Low Energy Power
Operated Doors,” or most current ANSI/BHMA standards.
j. ADJUST Magic-Touch™ Hold Open Time.
k. ADJUST breakout and breakout status cams.
l. ADJUST Power Close Speeds, Torques and Angles.
m. ENSURE all ANSI/BHMA, and UL compliance requirements are met.
n. POWER DOWN the door, POWER UP the door, and ENSURE that all sengs have been stored
in the controller.
o. Verify that the correct Safety Logic has been selected for Sensor Monitoring and that JP301 is installed.
p. Please refer to Aachment 11 for iQ Controller Fine Tuning for adjustment recommendaons.

20 Document # 204143 REV 5 • www.stanleyaccess.com • 1.800.7.ACCESS
3
4
5
6
7
8
9
10
N.C.
RED
GREEN
WHITE
1
2
3
4
5
6
7
8
WIRE HARNESS(CONNECTOR
SEEN FROM WIRESSIDE)
TWO-WIRE HARNESS TERMINATED BY TWO
COMM.MATE-N-LOCKRECEPTACLECONTACTS
COM.N.O.
TB3
AUX. SWITCH
N.C.
COM. N.O.
AUX. SWITCH
BREAKOUT STATUSWIRING--SINGLEDOOR
BREAKOUT STATUS WIRING--DUAL DOOR
N.C.
COM. N.O.
AUX. SWITCH
OPERATOR NO.1
OPERATOR NO.2
3
5
5
3
1
2
3
4
5
6
7
8
9
10
TB3
1
2
ATTACHMENTS
5
Attachment 1
Breakout Status Wiring for Magic-Swing Operators
(Sheet 1 of 1)
3
4
5
6
7
8
9
10
N.C.
RED
GREEN
WHITE
1
2
3
4
5
6
7
8
WIRE HARNESS(CONNECTOR
SEEN FROM WIRESSIDE)
TWO-WIRE HARNESS TERMINATED BY TWO
COMM.MATE-N-LOCKRECEPTACLECONTACTS
COM.N.O.
TB3
AUX. SWITCH
N.C.
COM. N.O.
AUX. SWITCH
BREAKOUT STATUSWIRING--SINGLEDOOR
BREAKOUT STATUS WIRING--DUAL DOOR
N.C.
COM. N.O.
AUX. SWITCH
OPERATOR NO.1
OPERATOR NO.2
3
5
5
3
1
2
3
4
5
6
7
8
9
10
TB3
1
2
Table of contents
Other Stanley Controllers manuals

Stanley
Stanley QB Expert User manual

Stanley
Stanley PSI-C Product manual

Stanley
Stanley JUMPiT J309E User manual

Stanley
Stanley Magic-Swing HDLE User manual

Stanley
Stanley EX5500 User manual

Stanley
Stanley PAC 520 User manual

Stanley
Stanley DE-MC521 User manual

Stanley
Stanley MC521 Pro User manual

Stanley
Stanley JUMP iT J5C09D User manual

Stanley
Stanley Theta Controller User manual
Popular Controllers manuals by other brands

REVENTON
REVENTON HMI SINGLE user guide

Linear
Linear LTC3828EUH quick start guide

Toho Electronics
Toho Electronics TTM-P4W Series instruction manual

Eliwell
Eliwell EWDR 981 manual

Allen-Bradley
Allen-Bradley PowerFlex 700S installation instructions

Circor
Circor Contromatics M6 Series Installation, operation and maintenance manual