E+E Elektronik EE23 series User manual

BA_EE23_B2_e // v1.0 // technical data are subject to change // 194768
Operation Manual
EE23
Humidity/Temperature Sensor

E+E Elektronik Ges.m.b.H. doesn’t accept warranty and liability claims neither upon this publication nor in case of
improper treatment of the described products.
The document may contain technical inaccuracies and typographical errors. The content will be revised on a
regular basis. These changes will be implemented in later versions. The described products can be improved and
changed at any time without prior notice.
© Copyright E+E Elektronik Ges.m.b.H.
All rights reserved.
EMC note USA (FCC):
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15
of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
EMC note Canada (ICES-003):
CAN ICES-3 (A) / NMB-3 (A)

CONTENT
1 General .................................................................................................................................................4
1.1 Explanation of Symbols.................................................................................................................................4
1.2 Safety Instructions.........................................................................................................................................4
1.2.1 General Safety Instructions..................................................................................................................................4
1.2.2 Safety Instructions for the Alarm Output Module with Voltage >50V....................................................................4
1.2.3 Safety Instructions for the Integrated Power Supply (Option AM3)......................................................................4
1.3 Environmental Aspects..................................................................................................................................5
2 Scope of Supply ..................................................................................................................................5
3 Operating Components ......................................................................................................................6
3.1 Electronics Board for Model T1, T2, T4 and T6.............................................................................................6
3.2 Display for Model T1, T2, T4 and T6 .............................................................................................................7
3.3 Electronic Board for Model T5.......................................................................................................................8
3.4 Display for Model T5 .....................................................................................................................................9
4 Intallation ...........................................................................................................................................10
4.1 Mounting the Enclosure...............................................................................................................................10
4.2 Mounting the Sensing Probe .......................................................................................................................11
4.3 Electrical Connection...................................................................................................................................12
4.4 Connection Versions ...................................................................................................................................12
5 Calibration / Adjustment ...................................................................................................................14
5.1 Denitions....................................................................................................................................................14
5.2 Adjustment of EE23 Model T1, T2, T4 and T6 via Push Buttons on the Electronics Board........................14
5.2.1 2-Point RH Adjustment Procedure / T Adjustment Procedure............................................................................ 14
5.2.2 1-Point RH Adjustment Procedure / T Adjustment Procedure ........................................................................... 15
5.2.3 Return to Factory Calibration .............................................................................................................................15
5.3 Adjustment of the EE23 Model T5 via the USB Service Interface...............................................................16
6 Maintenance.......................................................................................................................................16
7 Troubleshooting ................................................................................................................................16
7.1 Fuse Replacement for Option AM3 .............................................................................................................16
8 Accessories and Spare Parts ..........................................................................................................17
9 Technical Data ...................................................................................................................................18
9.1 Operating Range Humidity Sensor..............................................................................................................19

4
Operating manual EE23 humidity / temperature sensor
1 General
This operation manual is part of the scope of supply and serves for ensuring proper handling and opti-
mal functioning of the device.
The operation manual shall be read before commissioning the equipment and it shall be provided to all
staff involved in transport, installation, operation, maintenance and repair.
The operation manual may not be used for the purposes of competition without the written consent of
E+E Elektronik® and may not be forwarded to third parties. Copies may be made for internal purposes.
All information, technical data and diagrams included in these instructions are based on the information
available at the time of writing.
1.1 Explanation of Symbols
This symbol indicates safety information.
It is essential that all safety information is strictly observed. Failure to comply with this information can
lead to personal injuries or damage to property. E+E Elektronik® assumes no liability if this happens.
This symbol indicates instructions.
The instructions shall be observed in order to reach optimal performance of the device.
1.2 Safety Instructions
1.2.1 General Safety Instructions
• Avoid any unnecessary mechanical stress and inappropriate use.
• Replacetheltercapwithutmostcare,sothattheltercapdoesnottouchthesensingelementsof
the sensing head at any time.
• Do never touch the sensing elements.
• Forsensorcleaningandltercapreplacementpleasesee“Cleaninginstructions”atwww.epluse.com.
• Installation,electricalconnection,maintenanceandcommissioningshallbeperformedbyqualied
personnel only.
1.2.2 Safety Instructions for the Alarm Output Module with Voltage >50V
(not available for model T5 with remote probe up to 180 °C (356 °F))
• The alarm output module must be separated from the screw terminals
by the partition plate (see picture).
• The enclosure must be properly closed before power on.
• Power off the device before opening the enclosure.
1.2.3 Safety Instructions for the Integrated Power Supply (Option AM3)
• The back cover and the middle (active) part of the EE23 with
metal enclosure must be grounded during operation.
• The E23 enclosure must be properly closed before power on.
• Power off the device before opening the enclosure.

5
Operating manual EE23 humidity / temperature sensor
1.3 Environmental Aspects
Products from E+E Elektronik® are developed and manufactured observing of all relevant requirements
with respect to environment protection. Please observe local regulations for the device disposal.
For disposal, the individual components of the device must be separated according to local recycling
regulations. The electronics shall be disposed of correctly as electronics waste.
2 Scope of Supply
Included in
all versions
According to ordering
guide
EE23 according to ordering guide x
Operation manual in English x
InspectioncerticateaccordingtoDINEN10204–3.1 x
Allen key 3.0 only for metal enclosure
Mating cable connector for integrated power supply AM3
Mating cable connector RSC 5/7 AM3 / E4
M16 cable gland except AM3, E4

6
Operating manual EE23 humidity / temperature sensor
3 Operating Components
3.1 Electronics Board for Model T1, T2, T4 and T6
Fig. 1 Electronics board model T1, T2, T4 and T6
1. Jumpers:
Selection of the output signal and output range
voltage output current output
2. Display:
Connectors for the optional display
3. Status LEDs
D1 (red) - continuously on during the calibration routine
-oneshortashconrmsresettofactorycalibration
D2(green) -ashesduringnormaloperation
- continuously on indicates sensor damage
4. Push-Buttons
The S1 and S2 push buttons are used for the EE23 adjustment as well as for returning to the factory
calibration (see Calibration / Adjustment).
5. Level / Hysteresis
Potentiometers for setting the threshold / hysteresis (available with alarm module only)

7
Operating manual EE23 humidity / temperature sensor
3.2 Display for Model T1, T2, T4 and T6
The display is plugged into the connectors on the electronics board and it can easily be replaced. For
upgradinganEE23originallywithoutdisplaypleasesee“Replacementparts/accessories”.
1 2 3 4
5
6
Fig. 2 Display description T1, T2, T4 and T6
1. CAL
Indicates that the device in calibration/adjustment mode
2. > <
>: indicates measured value above the alarm threshold (with alarm module only).
visual feedback when depressing the S1 push button (Fig. 1)
<: indicates measured value below the alarm threshold (with alarm module only).
visual feedback when depressing the S2 push button (Fig. 1)
3. SET
Indication for EE23 with optional alarm output
4. Td / Tf
Dew point temperature / frost point temperature
5. °C / °F
Unit for temperature (T) and dew point temperature (Td) and frost point temperature (Tf)
6. %RH
Unit for relative humidity (RH)

8
Operating manual EE23 humidity / temperature sensor
3.3 Electronic Board for Model T5
T5 = remote probe up to 180 °C (356 °F)
1. Display
2. Status LEDs
3. Interface
Fig. 3 Electronics board model T5
1. Display:
Connectors for the optional display
2. Status LEDs:
Green LED
ashing-->Supplyvoltageapplied/Microprocessorisactive
Red LED
constantly lit --> Error category 1 = non-critical error, can be solved by the user
ashing-->Errorcategory2=criticalerror,returnthedeviceforservice
Blue LED
constantly lit --> analogue output is set to voltage.
Orange LED
constantly lit --> analogue output is set to current.
3. Interface:
USB-Interface for service use

9
Operating manual EE23 humidity / temperature sensor
3.4 Display for Model T5
Fig. 4 Display description T5
1. Measurand 2. Units 3. Mesurand selection
SI US
RH Relative humidity % %
Press the ∆or ∇ button
to select the measurand
to be displayed.
T Temperature °C °F
h Enthalpy kJ/kg ftlbf/lb
r Mixture ratio g/kg gr/lb
dv Absolute humidity g/m³ gr/ft
Tw Wet-bulb temperature °C °F
Td Dew-point temperature °C °F
e Water vapour partial pressure mbar psi
Tab. 1 Mesurand selection
Error description Error code
(display)
Error
category Recommended action
Short circuit - on voltage output 11)
ERROR: 01
1
Check wiring of outputsShort circuit - on voltage output 21)
Short circuit - on both voltage outputs*
Current loop open - output 1
ERROR: 02 Check wiring of outputsCurrent loop open - output 2
Current loop open - both outputs
RH sensor dirty ERROR: 03 Clean the sensor2)
Hardware error
ERROR: 05
2Return the faulty unit for
service
ERROR: 06
ERROR: 08
Temperature measurement failure ERROR: 07
Humidity measurement failure ERROR: 09
ERROR: 10
1) not available with 0 - 1 V output
2)see“CleaningInstructions”atwww.epluse.com/ee23
Tab. 2 Description of error messages on the display

10
Operating manual EE23 humidity / temperature sensor
4 Intallation
4.1 Mounting the Enclosure
1. Only for model T2 (duct mounting). Drill the hole for inserting the probe into the duct wall,Fig. 7 on
page 11. The relevant position of top left mounting screw of the back cover with respect to the probe
center:
2. FixthebackcoverofEE23ontothewall/panelusing4screws(diametermax.4.2mm(0.2”);not
included in the scope of supply).
The device shall be mounted with the cable glands pointing downwards or horizontal.
3. Wiretheterminalsinsidethebackcoveraccordingto„Fig.10Connectiondiagram“onPage12.
4. Insert the middle (active) part into the back cover. By this the connection pins of the middle part will
plug into the terminals of the back cover and thus realize the electrical connection.
5. Place the front cover onto the middle part and close tight the enclosure using the four screws included
in the scope of supply.
Drilling for round holes:
Drilling for long holes:
Fig. 5 Mounting of metal enclosure
116 (4.5“)
50.8 (2“)
Fig. 6 Mounting of polycarbonat enclosure
Metal enclosure: x=28.5mm(1.1”) y=37.5mm(1.5”)
Polycarbonate enclosure: x=20.5mm(0.8”) y=25.4mm(1”)

11
Operating manual EE23 humidity / temperature sensor
For the wall mount model the probe must point downwards.
For the duct mount model the probe must point either horizontally or downwards.
Ø12 (0.5“)
Ø12
(0.5“)
Ø14 (0.6“)
X
Y
Fig. 7 T1 Wall mount T2 Duct mount
Mounting onto DIN rails
EE23 with polycarbonate enclosure can be mounted also on DIN rails with the bracket HA010203 (not
includedinthescopeofsupply,see“spareparts/accessories”).
4.2 Mounting the Sensing Probe
Whenever possible place the entire probe inside the space to be monitored.
In case of mounting the probe into a partition wall, it is of paramount importance for accurate mea-
surement to avoid T gradients along the probe. In case of large T difference between the two sides of
the wall, it is highly recommended to insert the probe completely (up to the cable outlet) into the wall.
Should this not be possible, place a thermal isolation layer on the part of the probe outside the wall (on
the cable side).
ForprobemountingintoapartitionwallusethemountingangesHA010201forprobediameter12mm
andHA010208forprobediameter5mm.NeitherthemountingangesnortheEE23probesarepres-
sure rated and as such they are not appropriate for pressure tight mounting. For pressure tight require-
ments please see www.epluse.com for appropriate products such as EE310.
Ø46 (1.8“)
Ø
12 (0.5“)
Ø
13
(0.51“)
37 (1.5“)
Fig. 8 Mounting ange HA010201 Mounting ange HA010208

12
Operating manual EE23 humidity / temperature sensor
For applications where condensation is likely to happen, certain ways of mounting are required.
• For probe hanging onto its cable from the ceiling, use the drip water protection HA010503 (not inclu-
dedinthescopeofsupply,see“spareparts/accessories”).Thisprotectstheprobeandthesensing
head against water dripping along the cable.
• For horizontal mounted probe, a drip water point should be made just before the probe.
13 (0.51“)
85 (3.3“)
34
(1.3“)
horizontal hanging onto the probe cable
stainless steel
mounting flange
drip water loop
drip water
protection
Fig. 9 Mounting the sensing probe
4.3 Electrical Connection
Power supply and outputs Alarm output
output and supply alarm output
Relais status for
RH < threshold
Power supply
Fig. 10 Connection diagram
4.4 Connection Versions
standard option E4 option AM3
1) Two M16x1.5 cable glands (one of them mounted onto the enclosure)
2) Power supply + analogue outputs: cable connector, 5-poles, straight M12 (Lumberg RKC 5/7)
3) Analogue output: cable connector, 5-poles, straight M12 (Lumberg RKC 5/7)
4)ACpowersupply:cableconnector,3-poles,straight(7/8ʺ-16UN)

13
Operating manual EE23 humidity / temperature sensor
Pin assignment for option E4 (with supply 8...35V DC / 12...30V AC)
plug for supply and
analogue output
(front view) 12
3
4
5
Description: Pins:
V+ 5
GND 4
GND 3
OUT1 2
OUT2 1
Pin assignment for option AM3 (integrated supply unit for 100...240V AC)
plug for
analogue outputs
(front view) 12
3
4
5
Description: Pins:
GND 3
OUT1 2
OUT1 1
plug for 100-240 V
metal enclosure
(front view)
Description: Pins:
grounding (PE) 1
phase (L1) 2
neutral wire (N) 3
plug for 100-240 V
polycarbonate enclosure
(front view)
Description: Pins:
phase (L1) 1
neutral wire (N) 3
Externaldiameterofsupplycable:10-12mm(0.39-0.47”)
Maximum wire cross section for connecting cable: 1.5mm² (AWG 16)
The protection of the supply cable against excess current and short-circuit must be designated
to a wire cross section of 0.8mm² (AWG 18) (6A fuse).
The back cover and the middle part of the metal enclosure must be grounded during operation!

14
Operating manual EE23 humidity / temperature sensor
5 Calibration / Adjustment
5.1 Denitions
Calibration
The calibration documents the accuracy of a measurement device. The device under test
(specimen)iscomparedwiththereferenceandthedeviationsaredocumentedinacalibrationcerti-
cate. During the calibration, the specimen is not changed or improved in any way.
Adjustment
The adjustment improves the measurement accuracy of a device. The specimen is compared with the
reference and brought in line with it. An adjustment can be followed by a calibration which documents
the accuracy of the adjusted specimen.
For general calibration / adjustment guidelines and for the choice of humidity reference devices please
see“CalibrationInstructions”at www.epluse.com/ee23
The 2-point adjustment is recommended for best accuracy over a wide RH and / or T range.
Always start the 2-point adjustment with the lower adjustment point RH_low / T_low, followed by the
higher adjustment point RH_high / T_high.
The span between the two adjustment points must be:
|RH_high–RH_low| >30%RH
|T_high–T_low| >30°C(54°F)
The 1-point adjustment should be used only when the RH and/or T range of interest is rather narrow.
The RH resp. T adjustment point should be ideally in the middle of the range of interest.
Example:
In a climate controlled environment with 40% < RH < 60% and 15 °C < T < 25 °C (59 °F < T < 77 °F),
1-point adjustment shall be performed at 50 % RH and 20 °C (68 °F).
1-point adjustment leads to very good accuracy within the range of main interest at the cost of the
accuracy beyond this range.
5.2 Adjustment of EE23 Model T1, T2, T4 and T6
via Push Buttons on the Electronics Board
5.2.1 2-Point RH Adjustment Procedure / T Adjustment Procedure
1. For a RH humidity adjustment set the jumper to CAL RH / for a temperature adjustment set the
jumper to CAL T.
First point adjustment
2. Allow for the probe to stabilize at RH_low / T_low for min. 30 minutes.
3. Press BUTTON S2formin.3secondstostarttheadjustmentprocedurefortherstpoint.TheLED
„D1“illuminatesand„CAL<“appearsontheLCdisplay.
4. Press BUTTON S1 (up) and S2 (down) to adjust the measured value in steps of 0.1% / 0.1 °C up
or down to match the reference value. The change is indicated on the display (if available) or can be
measured at the analogue output.
5. Press BUTTON S1formin.3secondstostoreadjustedvalueandendtherstpointadjustment.
or

15
Operating manual EE23 humidity / temperature sensor
Press BUTTON S2 for min. 3 seconds to exit adjustment procedure without storing the adjusted
value.
InbothcasestheLED„D1“andthesymbol„CAL<“ontheLCdisplayaredeactivated.
Second point adjustment
6. Allow for the probe to stabilize at the desired RH_high / T_high for min. 30 minutes.
7. Press BUTTON S1 for min. 3 seconds to start the adjustment procedure for the second point. The
LED„D1“illuminatesand„CAL>“appearsontheLCdisplay.
8. Press BUTTON S1 (up) and S2 (down) to adjust the measured value in steps of 0.1% / 0.1 degC up
or down to match the reference value. The change is indicated on the display (if available) or can be
measured at the analogue output.
9. Press BUTTON S1formin.3secondstostoreadjustedvalueandendtherstpointadjustment.
or
Press BUTTON S2 for min. 3 seconds to exit adjustment procedure without storing the adjusted
value.
In both cases the LED„D1“andthesymbol„CAL>“ontheLCdisplayaredeactivated.
5.2.2 1-Point RH Adjustment Procedure / T Adjustment Procedure
1. For a RH humidity adjustment set the jumper to CAL RH / for a temperature adjustment set the
jumper to CAL T.
2. Allow for the probe to stabilize at the desired RH / T for min. 30 minutes.
3. For adjustment point > 50% RH / in the upper half of the T output scale): press BUTTON S1 for min.
3secondstostarttheprocedure.TheLED„D1“illuminatesand„CAL<“appearsontheLCdisplay.
or
For adjustment point < 50% RH / in the lower half of the T output scale): press BUTTON S2 for min.
3secondstostarttheprocedure.TheLED„D1“illuminatesand„CAL>“appearsontheLCdisplay.
4. Press BUTTON S1 (up) and S2 (down) to adjust the measured value in steps of 0.1% / 0.1 °C up or
down to match the reference value. The change is indicated on the display (if available) or can be
measured at the analogue output.
5. Press BUTTON S1formin.3secondstostoreadjustedvalueandendtherstpointadjustment.
or
Press BUTTON S2 for min. 3 seconds to exit adjustment procedure without storing the adjusted
value.
InbothcasestheLED„D1“andthesymbol„CAL“ontheLCdisplayaredeactivated.
5.2.3 Return to Factory Calibration
ToreturntoRHorTfactorycalibrationsetrstthejumpertoRHortoTrespectively.
During normal measuring mode (i.e. not during the adjustment procedure. LED D1 shall be off, the
displayshallnotshow“CAL”)pressingBUTTON S1andS2togetherformin5seconds.Thereturnto
factorycalibrationisconrmedbyashortashoftheLED„D1“.

16
Operating manual EE23 humidity / temperature sensor
5.3 Adjustment of the EE23 Model T5 via the USB Service Interface
1. DownloadandinstalltheEE-PCSProductCongurationSoftwarefromwww.epluse.com/congurator
2. Connect the USB service interface of EE23-T5 to the PC.
3. Start the EE-PCS software.
4. Select the desired adjustment mode and follow the instructions of the EE-PCS.
6 Maintenance
When employed in dusty, polluted environment:
• TheltercapshallbereplacedasneededwithanE+Eoriginalone.Apollutedltercapcauses
longer response time of the device.
• Forcleaningofthesensingheadpleasesee“CleaningInstructions”atwww.epluse.com/ee23.
7 Troubleshooting
SeestatusLEDsat„3OperatingComponents“onPage6 and error messages on the display at „3.4
DisplayforModelT5“onPage9.
7.1 Fuse Replacement for Option AM3
IfthegreenLEDonthePCBisnotashingwiththesupplyvoltageswitchedoncheckthefuseand
replace if required.
Fuse secondary: 250mA / T UL248-14
Recommended replacement types:
Series: MSTU 250 Manufacturer: Schurter Order No.: 0034.7109
Series: 374 Manufacturer: Littelfuse Order No.: 374 0250
Fig. 11 Fuse replacement

17
Operating manual EE23 humidity / temperature sensor
8 Accessories and Spare Parts
Description Order Code
- Filter caps HA0101xx
- External power supply unit V03
- Display + housing cover in metal
for T1, T2, T4 and T6 D03M-EE23
for T5 D05M-EE23T5
- Display + housing cover in polycarbonate
for T1, T2, T4 and T6 D03P-EE23
for T5 D05P-EE23T5
-Mountingangeforprobediameter12mm HA010201
-Mountingange5mm(formodelT6only) HA010208
- Bracket for plastic enclosure - for installation onto mounting rails HA010203
- Drip water protection HA010503
- Calibration set (seedatasheet„CalibrationKit“) HA0104xx
- Radiation shield HA010502

18
Operating manual EE23 humidity / temperature sensor
9 Technical Data
Measurands
Relative Humidity
Working range 0...100% RH
Accuracy1(including hysteresis, non-linearity and repeatability, traceable to intern. standards, administrated by NIST, PTB, BEV...)
EE23-T1/T2/T4/T5 EE23-T6
-15...40°C (5...104°F) ≤90% RH ± (1.3 + 0.3%*mv) % RH ± (1.8 + 0,3%*mv) % RH
-15...40°C (5...104°F) >90% RH ± 2.3% RH ± 2.8% RH
-25...70°C (-13...158°F) ± (1.4 + 1%*mv) % RH ± (1.9 + 1%*mv) % RH
-40...180°C (-40...356°F) ± (1.5 + 1.5%*mv) % RH -
Temperature dependence electronics typ. ± 0.015% RH/°C
Response time t90 with metal grid filter at 20 °C (68 °F) < 15 sec.
Temperature
Probe working range EE23-T1 -40...60°C (-40...140°F)
EE23-T2/T6 -40...80°C (-40...176°F)
EE23-T4 -40...120°C (-40...248°F)
EE23-T5 -40...180°C (-40...356°F)
Accuracy
Temperature dependence of electronics typ. 0.002°C/°C
Output Scale Span
from up to units
EE23-T1 EE23-T2/T6 EE23-T4 EE23-T5
Humidity RH 0100 100 100 100 % RH
Temperature T -40 (-40) 60 (140) 80 (176) 120 (248) 180 (356) °C (°F)
Dew point temperature Td -40 (-40) 60 (140) 80 (176) 100 (212) 100 (212) °C (°F)
Frost point temperature Tf -40 (-40) 0(32) 0(32) 0(32) 0(32) °C (°F)
Outputs 0 - 1 V -0.5 mA < IL < 0.5 mA
0 - 5 / 0 - 10 V -1 mA < IL < 1 mA
0 - 20mA / 4 - 20 mA RL< 470 Ohm
General
Supply voltage
for 0 -1 V / 0 - 5 V outputs 10.5 - 35V DC or 12 - 28V AC
for 0 - 10 V / 0 - 20 mA / 4-20 mA outputs 15.0 - 35V DC or 15 - 28V AC
100...240V AC, 50/60Hz supply module (optional)
Current consumption for voltage output
for DC supply ≤25 mA (with alarm module ≤35 mA)
for AC supply ≤45 mAeff (with alarm module ≤70 mAeff)
Current consumption for current output
for DC supply ≤55 mA (with alarm module ≤65 mA)
for AC supply ≤100 mAeff (with alarm module ≤120 mAeff)
Enclosure/protectionclass PCorAlSi9Cu3/IP65;NEMA4
Cablegland M16x1.5 cableØ4.5-10mm(0.18-0.39”)
Electrical connection screw terminals max. 1.5 mm² (AWG 16)
Working temperature range of electronics -40...60°C (-40...140°F)
Working temperature range with display -30...60°C (-22...140°F)
Storage temperature range -40...60°C (-40...140°F)
CE compatibility according EN61326-1 EN61326-2-3 ICES-003 ClassB
Industrial Environment FCC Part15 ClassB
Alarm Module2)
Output SPDT-Switch max. 250V AC/8A or 28V DC/8A
threshold hysteresis
Setting range 10...95% RH 3...15% RH
Setting accuracy ± 3% RH
1) The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-times standard deviation). The accuracy was calculated in
accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
2) only for models T1, T2, T4 and T6.
EE23-T1/T2/T4/T5 EE23-T6
°C°C
∆°C∆°C

19
Operating manual EE23 humidity / temperature sensor
9.1 Operating Range Humidity Sensor
Relative humidity [%RH]
Temperature [degC]
The gray area shows the allowed measurement range for the humidity sensor.
Operationbeyondthisrangedoesnotdestroythesensingelement,butthespeciedmeasurement
accuracy cannot be guaranteed.

HEADQUARTERS
E+E Elektronik Ges.m.b.H.
Langwiesen 7
A-4209 Engerwitzdorf
Austria
Tel: +43 7235 605 0
Fax: +43 7235 605 8
www.epluse.com
SUBSIDIARIES
E+E Elektronik Germany
Office Bad Homburg
Tel: +49 6172 13881-0
Office Hamburg
Tel: +49 160 9050 6460
Office Stuttgart
Tel: +49 151 538 37 500
E+E Elektronik Italy
Tel: +39 02 2707 86 36
E+E Elektronik France
Tel: +33 4 74 72 35 82
E+E Elektronik USA
Office Boston
Tel: +1 508 530 3068
Office Chicago
Tel: +1 847 490 7813
E+E Elektronik Korea
Tel: +82 31 732 6050
E+E Elektronik China
Office Beijing
Tel: +86 10 8499 2361
Office Shanghai
Tel: +86 21 6117 6129
Office Guangzhou
Tel: +86 20 3898 7052
Other manuals for EE23 series
2
Table of contents
Other E+E Elektronik Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Ringder
Ringder RC-113M user manual

domat
domat HYGRASGARD RFF Series Operating Instructions, Mounting & Installation

Milesight
Milesight TS101 quick start guide

Hoval
Hoval RS-T operating instructions

Danfoss
Danfoss ECL Comfort 100M User's guide and installation instructions

GE
GE GE-VCPL Series instruction manual

Minco
Minco Heaterstat CT398 Technical user guide

PCB Piezotronics
PCB Piezotronics IMI SENSORS TO642A31 Installation and operating manual

Busch-Jaeger
Busch-Jaeger 1094 operating instructions

Domotec
Domotec Therm-Control DHB 370 C Installation notes

Bosch
Bosch CRC200 Installation instructions for contractors

Omron
Omron E5EX-H manual