Lumel RE70 User manual

1
TEMPERATURE CONTROLLER
48 x 48 mm
RE70 TYPE
USER’S MANUAL

RE70-09 User's Manual 2
Contents:
1. Application........................................................................................................................ 3
2. Controller set.................................................................................................................... 3
3. Basic requirements, operational safety.......................................................................... 3
4. Installation......................................................................................................................... 4
4.1. Controller installation................................................................................................... 4
4.2. Electrical connections.................................................................................................. 4
4.3. Recommendations for installation ............................................................................... 5
5. Starting work..................................................................................................................... 6
6. Service............................................................................................................................... 7
6.1. Programming Controller Parameters........................................................................... 7
6.2. Programming matrix.................................................................................................... 8
6.3. Setting Change............................................................................................................ 8
6.4. Parameters description ............................................................................................... 8
7. Inputs and outputs of the controller............................................................................. 10
7.1. Inputs ........................................................................................................................ 10
7.1. Output ....................................................................................................................... 11
8. Control............................................................................................................................. 11
7.1. ON-OFF algorithm..................................................................................................... 11
7.2. Innovative SMART PID algorithm.............................................................................. 12
9. Alarms ............................................................................................................................. 14
10. Additional functions..................................................................................................... 14
10.1. Displaying the control signal.................................................................................... 14
10.2. Manual mode........................................................................................................... 14
10.3. Defaults Settings..................................................................................................... 15
11. RS-485 interface with MODBUS protocol................................................................... 15
11.1. Introduction.............................................................................................................. 15
11.2. Error codes.............................................................................................................. 15
11.3. Register map........................................................................................................... 15
12. Error signaling.............................................................................................................. 17
13. Technical data............................................................................................................... 18
14. Controller ordering code.............................................................................................. 19

RE70-09 User's Manual 3
1. Application
The RE70 controller is destined for the temperature control. Controller works directly with
the resistance sensors or thermoelectric sensors.
The controller is equipped with one output that allows for dual-point control and alert
signalization. Dual-point control is based on the PID or ON/OFF algorithm. Relay output is
equipped with a switchable contact and allows for indirect control of the low-power objects.
The innovative SMART PID algorithm has been implemented in the controller.
2. Controller set
1
1234
OUTST
SP
5
RE70
2
3
4
Complete set of the controller includes:
1. controller................................................ 1 pc
2. plug with 6 screw terminals.................... 1 pc
3. plug with 8 screw terminals.................... 1 pc
4. holders to fix the meter in the panel....... 4 pcs
5. seal........................................................ 1 pc
6. user’s manual ........................................ 1 pc
7. guarantee card....................................... 1 pc
3. Basic requirements, operational safety
In terms of operational safety the controller meets the requirements of the EN 61010-1
standard.
Comments concerning safety:
•Assembly and installation of the electrical connections should conducted only by
people authorised to perform assembly of electric devices.
•Always check the state of connections before turning the controller on.
•Prior to taking the controller housing off, always turn the supply off and disconnect
measuring circuits.
•Removal of the controller housing during the warranty period voids the warranty.
•The device is designed to installation and usage in the industrial electromagnetic
environment.
•The installation should have a switch or a circuit-breaker installed. This switch should
be located near the device, easy accessible by the operator and suitably marked.

RE70-09 User's Manual 4
4. Installation
4.1. Controller installation
Fix the controller to the board with four screw brackets as shown in the fig. 1. A slot in
the panel must have the dimensions 45
+0,6
x 45
+0,6
mm. The thickness of the panel material
cannot exceed 15 mm.
1
2
Fig. 1. Controller installation.
Dimensions of the controller are presented on the fig. 2.
70
8
max. 93
max.15
48
48
Fig. 2. Controller dimensions.
4.2. Electrical connections
The controller has two separate connectors with screw terminals. One strip enables the
connection of the supply and outputs by a wire of 2,5 mm
2
, the second strip enables input
signal connections by a wire of 1,5 mm
2
.

RE70-09 User's Manual 5
Fig. 3. View of the controller's connection strips.
5
4
3
Pt100
5
4
3
Pt100
5
4
3
Pt1000
2
1
+
-
thermoresistor Pt100
in 2-wire system thermoresistor Pt100
in 3-wire system thermoresistor
Pt1000 thermocouple
Fig. 4. Input signals
supply
13
14
Fig. 5. Supply
supply
9
11
10
load
Fig. 6. Control/Alarm output
A(+)
B(-)
8
7
Fig. 7. RS-485 interface (only for configuration)
4.3. Recommendations for installation
To achieve full electromagnetic resistance of the controller, it is necessary to follow the
rules described below:
do not supply the controller from the network in the proximity of devices generating
high pulse noises and do not apply common earthing circuits,
apply network filters,
wires leading measuring signals should be twisted in pairs, and for resistance
sensors in 3-wire connection, twisted of wires of the same length, cross-section and
resistance, and led in a shield,
all shields should be one-side earthed or connected to the protection wire, the
nearest possible to the controller,

RE70-09 User's Manual 6
as a rule of thumb, wires transmitting different signals should be spaced as far as it
is possible (at least 30 cm) and should be crossed only at the right angle of 90°.
5. Starting work
Controller description
self-tune indicator
display for
measured value,
set point, menu
active output
indicator
manual mode indicator
keys
display set point
indicator
Fig. 8. Overview of the controller's front panel.
Switching a supply on
After powering on, the controller performs the display test, displays re70
re70re70
re70 text, software
version and the measured value.
Display may also show an error message (see table 11).
The ON-OFF control algorithm with hysteresis given in the table 2 is set by the defaults.
Change of the set point
Set point is displayed after
?
or
>
buttons are pressed, this is accompanied by SP
diode switching on. To change the set point, press
?
or
>
buttons again (fig. 9). The
beginning of the change is signaled by pulsing dot symbol on the display. New set point must
be accepted with a
@
button within 30 seconds after the
?
or
>
button have been
pressed, otherwise regulator will display set point with previously set point.
to change set-point press and hold one of the button
accept new
set-point
set-point
change
indicator
measured
value
or
Fig. 9. Change value of the set point.

RE70-09 User's Manual 7
6. Service
The controller service is presented on the fig. 10.
to change press
to cancel press
or
press and hold
to increase
the value
press and hold
to decrease
the value
to accept press
3sec.
2 sec.
correct
code?
N
Y
N
Y
active
access code
display control
signal
locking of change
normal working mode
change set point
mode
+
measured
value
h _ _ _
t u n e
set point
c o d e
err
manual
mode
self-tune mode
parameter
programming
mode
2sec.
2sec.
+
+
+
Fig. 10. Menu of controller service
6.1. Programming Controller Parameters
Pressing and holding down during ca 2 seconds the button
@
causes the entry to the
programming matrix. The programming matrix can be protected by an access code. In case
when giving a wrong value of the code, it is only possible to see settings through - without
possibility of changes.
Fig. 11 presents the transition matrix in the programming mode. The transition between
levels is carrying out by using the buttons
?
or
>
and the level selection by using the
button
@
. After selecting the level, the transition between parameters is carried out by
using the buttons
?
or
>
. In order to change the parameter setting proceed acc. to the
section 6.3. In order to exit from the selected level, transit between parameters until appears
the symbol [. . .] and press the button
@
. In order to exit from the programming matrix to
the normal working mode, transit between levels until appears the symbol [. . .] and press the
button
@
.
Some controller parameters can be invisible – it depends on the current configuration.
The description of parameters shows the table 1. The return to the normal working mode
follows automatically after 30 seconds since the last button pressure.

RE70-09 User's Manual 8
6.2. Programming matrix
inp
unit
iNty
t
-
li
sHif
dp
. . .
Input
parameters Unit Input type Type of line Shift of measured
value Position of decimal
point
Transition to
the higher level
outp
out
. . .
Output
parameters Output
configuration
Transition to
the higher level
ctrl
alg
type
Hy
s lo
s Hi
. . .
Control
parameters Control algorithm Type of control Hysteresis Lower threshold for
self-tuning Upper threshold for
self-tuning
Transition to
the higher level
pid
pb
t
i
td
y0
to
. . .
PID Parameters Proportional band Integral time
constant Derivative time
constant
Correction of
control signal, for P
or PD control Pulse period
Transition to
the higher level
alar
aLsp
aLdu
aLHy
. . .
Alarms
parameters Set point for the
absolute alarm
Deviation from the
set point of the
relative alarm Alarm hysteresis
Transition to
the higher level
spp
spl
spH
. . .
Set point
parameters
lower limitation of
the set point
setting
upper limitation of
the set point
setting
Transition to
the higher level
seru
seCU
s fn
. . .
Service
parameters Access code Self-tuning function
Transition to
the higher level
. . .
Exit from the
menu
Fig. 11. Programming matrix
6.3. Setting Change
The change of parameter setting begins after pressing the button
@
during the display
of the parameter name. The setting selection is carried out through the buttons
?
and
>
and accepted by the button
@
. The change cancellation follows after the simultaneous
pressure of the buttons
?
and
>
or after 30 seconds since the last button pressure. The
way to change the setting is shown on the fig. 12.
1234
to change
press cancel
increment
value
decrement
value
accept new
value
+
oNof
to change
press cancel
next text
value
previous
text value
accept new
value
+
Fig. 12. Setting change of number and text parameters.
6.4. Parameters description
The list of parameters is presented in the table 1.

RE70-09 User's Manual 9
List of configuration parameters Table 1
Symbol
of
parameter
Parameter description Default setting
Range of parameter change
inp – Input parameters
unit
Unit qC
qC
: degrees Celsius
qf
: degrees Fahrenheit
iNty
Input type pt1
pt1: Pt100
pt10: Pt1000
t-,: J type thermocouple
t-t: T type thermocouple
t-k: K type thermocouple
t-s: S type thermocouple
t-r: R type thermocouple
t-b: B type thermocouple
t-n: N type thermocouple
t-li
Line type for the sensor Pt100 2-p 2-p: 2-wire
3-p: 3-wire
dp
Position of the decimal point 1-dp
0_dp
: without a decimal place
1_dp: 1 decimal place
shif
Shift of measured value 0.0
°C
(
0.0
°F)
-100.0
…
100.0 °C
(-180.0
…
180.0 )
outp – Output parameters
out
Output configuration y
off: control off
Y: control signal
AHi: upper absolute alarm
Alo: lower absolute alarm
dwHi: upper relative alarm
dwlo: lower relative alarm
dwin: internal relative alarm
dwou: external relative alarm
ctrl – Control parameters
1)
alg
Control algorithm oNof oNof: ON-OFF control algorithm
pid: PID control algorithm
type
Type of control inu dir: direct control (cooling)
inu: reverse control (heating)
Hy
Hysteresis
4)
2.0
°C
(
3.6
°F)
0.2
…
100.0 °C
(0.2
…
180.0 °F)
s lo
Lower threshold for self-tuning 0.0
°C
(
32.0
°F)
MIN…MAX
6)
s Hi
Upper threshold for self-tuning 800.0
°C
(
1,472.0
°F)
MIN…MAX
6)
pid – PID parameters
2)
pb
Proportional band 30.0
°C
(54
0.0
°F)
0.1
…
550.0 °C
(0.1
…
990.0 °F)

RE70-09 User's Manual 10
Symbol
of
parameter
Parameter description Default setting
Range of parameter change
ti
Integral time constant 300 0
…
9999 s
td
Derivative time constant 60.0 0.0
…
2500 s
y0
Correction of control signal,
for P or PD control
0.0 0
…
100.0 %
to
Pulse period 20.0 0.5
…
99.9 s
alar – Alarms parameters
3)
aLsp
Set point for the absolute alarm 0.0
°C
(
32.0
°F)
MIN…MAX
6)
aLdu
Deviation from the set point of
the relative alarm 0.0
°C
(
0.0
°F)
-200,0
…
200,0 °C
(-360.0
…
360.0 °F)
aLHy
Hysteresis for the alarm 2.0
°C
(
3.6
°F)
0.2
…
100.0 °C
(0.2
…
180.0 °F)
spp – Set point parameters
spl
Lower limitation of the set point
setting -200.0
°C
(-3,28
0.0
°F)
MIN…MAX
6)
spH
Upper limitation of the set point
setting 1,767.0
°C
(3,212
.6
°F)
MIN…MAX
6)
serp – Service parameters
seCU
Access code
5)
0 0…9999
s fn
Self-tuning function on off: locked
on: available
1)
Group of parameters visible only when setting the output on the control signal.
2)
Group of parameters visible only when setting the control algorithm on PID.
3)
Group of parameters visible only when setting the output on one of the alarm.
4)
Parameter visible only when setting the control algorithm on ON-OFF.
5)
Parameter hidden in the monitoring mode of parameters only for readout.
6)
See table 2.
Range limits for inputs table 2
Input / sensor MIN MAX
°C
°F
°C
°F
Thermoresistor Pt100 -200 °C -328 °F 850 °C 1,562 °F
Thermoresistor Pt1000 -200 °C -328 °F 850 °C 1,562 °F
J type thermocouple -50 °C -58 °F 1,200 °C 2,192 °F
T type thermocouple -50 °C -58 °F 400 °C 752 °F
K type thermocouple -50 °C -58 °F 1,372 °C 2,501.6 °F
S type thermocouple 0 °C 32 °F 1,767 °C 3,212.6 °F
R type thermocouple 0 °C 32 °F 1,767 °C 3,212.6 °F
B type thermocouple 0 °C 32 °F 1,767 °C 3,212.6 °F
N type thermocouple -50 °C -58 °F 1,300 °C 2,372 °F
7. Inputs and outputs of the controller
7.1. Inputs
Input is the source of the measured value used for control or for alarms. The input is
universal and the sensors Pt100, Pt1000 or thermocouples can be connected to it.

RE70-09 User's Manual 11
Start by using a unit
unitunit
unit
parameter to set the temperature display unit. Unit change
resets the value to the factory settings, with a different value ranges for Celsius and
Fahrenheit scale.
Input signal is selected with a iNty
iNtyiNty
iNty
parameter.
For the Pt100 thermoresistor, choose the t
tt
t-
--
-li
lili
li connection type - 2-wire or 3-wire. In
the 3-wire Pt100 connection, resistance compensation is automatic.
For thermocouples, a cold terminal compensation is automatic.
Position of the decimal point is a additional parameter that determines display format of
measured value and set point; it is set by the dp
dpdp
dp parameter. Correction of the indicated
measured value is determined by the shif
shifshif
shif parameter.
7.1. Output
The controller has one output. It is possible to choose the following output options: on-off
control, proportional control (PID) or alert. It is necessary to set the pulse period for the
proportional control.
Pulse period is a time between two subsequent input engagements during proportional
control. Pulse period length should be adjusted for the dynamic properties of the object and
characteristics of the output device. It is recommended to use SSR transmitter for quick
processes. Relay output is used for a contactor control in the slow-changing processes.
Long pulse periods for quick-change processes may cause unnecessary oscillation. In
theory, the shorter pulse period is, the better the control, however for the relay output a
period should be as large, as possible to optimize lifespan of the relay.
Pulse period setting recommendations Table 3
Output Pulse period is Load
electromagnetic transmitter recommended >20s
min. 10 s 5 A/230 VAC
or a contactor
min. 5 s 2 A/230 VAC
8. Control
7.1. ON-OFF algorithm
When high accuracy of a temperature control is not required, especially for the high
time constant and small delay, it is possible to use ON-OFF control with hysteresis.
Disadvantage of this method is the occurrence of oscillations, even at small hysteresis
values.
Fig. 13. Operation way of the heating type output for the ON-OFF control.
on
off
setpoint
value
measured
value
hysteresis
output

RE70-09 User's Manual 12
7.2. Innovative SMART PID algorithm
When high precision of the temperature control is necessary, it is recommended to use
PID algorithm. Innovative SMART PID algorithm ensures increased precision in the
extended range of the control object classes.
Tuning of the controller to object is achieved by automatically selected PID parameters
using the self-tuning function or manual setting the value of the proportional element, integral
element and derivative element.
7.2.1. Self-tuning
The controller has the function to select PID settings. In most cases these settings
ensure an optimal control.
To begin the self-tuning, transit to the tune
tunetune
tune message (acc. to the fig. 10) and hold down
the button
@
during at least 2 sec. If the control algorithm is set on ON-OFF or the self-
tuning function is locked, then the tune message tune
tunetune
tune is hidden.
For a correct realization of the self-tuning function, it is required to set the parameters
s lo
s los lo
s lo and s Hi
s His Hi
s Hi. The parameter s lo
s los lo
s lo should be set on the value corresponding to the
measured value at the switched off control. For object temperature control, you can set 0ºC.
The parameter s Hi
s His Hi
s Hi should be set on the value corresponding to the maximum measured
value when the control is switched on the full power.
The flickering AT symbol informs about the activity of the self-tuning function. The
duration of self-tuning depends on dynamic object properties and can last maximally 10
hours. During self-tuning or directly after it, over-regulations can occur and because of this,
one must set a smaller set point if possible.
The self-tuning is composed of following stages:
self-tuning process
- calculation of PID settings and stored
them in the non-volatile memory
- start control with new PID settings
- enter to manual mode
- the error code is on the display until
confirmation
self-tuning
ended
with success
YES
NO
The self-tuning process will be stopped without counting PID settings, if a supply
decay occurs or the button
@
will be pressed.
In this case, the control with current PID
settings will be started.
If the self-tuning experiment does not end with success, then an error code will be displayed,
acc. to the table 4.

RE70-09 User's Manual 13
Error codes for self-tuning function Table 4
Error code
Reason Procedure
eS01 P or PD control was selected. One must choose PI, PID control, i.e. the TI unit
must be higher than zero.
eS02 The set point is incorrect. Change temperature set point or the
parameters s lo, s Hi.
eS03 The button @ was pressed.
eS04 The maximal self-tuning duration time has
been exceeded. Check, if the temperature sensor is correctly
situated, if the set point value is not set too
higher for the given object.
eS05 The waiting time of switching has been
exceeded.
eS06 The input range limit has been exceeded. Take note of the way to connect the sensor. Do
not allow that the overflow results in exceeding
of the input range limit.
eS20 Very non-linear object, enabling to obtain
correct values of PID parameters, or an
interference has occurred.
Carry out the self-tuning again. If that does not
help, choose PID parameters manually.
7.2.2. Proceeding in case of a unsatisfactory PID control
It is recommended to choose PID parameters, changing the value in a twice higher or
twice less. During the change, one must respect following principles.
a) Free jump response:
−decrease the proportional band,
−decrease the integral and derivative time.
b) Over-regulations
−increase the proportional band,
−increase the derivative time,
c) Oscillations
−increase the proportional band,
−increase integral time,
−decrease the derivative time,
d) Instability
−increase the integral time.

RE70-09 User's Manual 14
9. Alarms
The controller output can be configured as an alarm output. For this, set the parameter out
as one of alarms. Available types of alarms are given on the figure 14.
aLsp
absolute high
(out
outout
out = AHi
AHiAHi
AHi)
aLsp
absolute lower
(out
outout
out = Alo
AloAlo
Alo)
SP
aLdu
(+)
relative high
(out
outout
out = dwHi
dwHidwHi
dwHi)
SP
a L d u
(-)
relative high
(out
outout
out = dwHi
dwHidwHi
dwHi)
SP
aLdu
(+)
relative lower
(out
outout
out = dwlo
dwlodwlo
dwlo)
SP
a L d u
(-)
relative lower
(out
outout
out = dwlo
dwlodwlo
dwlo)
SP
aLdu
aLdu
relative internal
(out
outout
out = dwin
dwindwin
dwin)
SP
aLdu
aLdu
relative external
(out
outout
out = dwou
dwoudwou
dwou)
Fig.14. Types of alarms
The set point for absolute alarms is the value defined by the parameter aLsp
aLspaLsp
aLsp, and for
relative alarms, it is the deviation from the set point - the parameter aLdu
aLduaLdu
aLdu. Alarm
hysteresis, the zone around the set point in which the input state is not changed is defined
by the aLHy
aLHyaLHy
aLHy
parameter.
10. Additional functions
10.1. Displaying the control signal
After pressing the button
@
the value of the control signal (0…100%) is displayed
on the display. On the first digit the h mark is displayed. Control signal can be displayed
when the out parameter is set on y.
10.2. Manual mode
The manual mode gives the possibility to identify, test the object, or control it after a
sensor damage.
The entry to the manual mode follows after holding down the button
@
during the
control signal is display. The manual mode is signaled by the pulsation of the diode with the
symbol . The controller interrupts the automatic control and begins the manual mode of the
output. The control signal value is on the display, preceded by the symbol h.
For the ON-OFF control – the control signal can be set up by the buttons
?
and
>
at 0%
or 100%.
For the PID control – the control signal can be set up by the buttons
?
and
>
at any
optional value from the 0.0…100% range.
The exit to the normal work mode follows after pressing simultaneously the buttons
?
and
>
.

RE70-09 User's Manual 15
10.3. Defaults Settings
Defaults settings can be restored during the supply connection by holding down the
buttons
?
and
>
till the moment when the inscription fabr
fabrfabr
fabr appears on the display.
11. RS-485 interface with MODBUS protocol
11.1. Introduction
RE70 controller is equipped with RS-485 serial interface with implemented MODBUS
asynchronous communication protocol. The interface is designed for controller configuration
prior to using it.
Summary of the RE70 controller serial interface:
−device address: 1,
−baud rate: 9600 bit/s,
−operation modes: RTU,
−information unit: 8N2,
−data format: integer (16 bits)
−maximum response time: 500 ms,
−maximum number of registers read/written in one command: 32.
RE70 controller uses following protocol functions:
Table 5
Code Meaning
03 n-registers read
06 1 register write
16 n-registers write
17 slave device identification
11.2. Error codes
If the controller receives query with the transmission error or checksum error, then such
query will be ignored. When a query with correct syntax and invalid values is found, the
controller returns an error code.
Table 6 shows error codes and their meaning.
Error codes Table 6
code meaning reason
01 illegal function function is not handled by the controller
02 illegal data address register address out of range
03 illegal data value
register value out of range or register is readout
only
11.3. Register map
In the controller, data are placed in 16-bit registers. The list of registers for write and
readout is presented in the table 7. Operation "R-" – means the possibility of readout, and
the operation "RW" means the possibility for readout and write.

RE70-09 User's Manual 16
Map of the registers from address 4000 Table 7
register
address marking
operati
on parameter range description
4000 -W 1 Command register
1 – revert to defaults settings (except for interface
settings and defined programs)
4001 R- 100…999 Program version number [x100]
4002 R- 1301…9999 Older 4 digits of the serial number
4003 R- 1…9999 Younger 4 digits of the serial number
4004 R- 0…0xFFFF Controller status – description in the table
8
4005 R- 0…0xFFFF Error status – description in the table
9
4006 R- acc. to the table
10
Measured value PV
4007 R- acc. to the table
10
Current set point SP
4008 R- 0…1000 Control signal [% x10]
4009 UNIT RW
0…1 Unit
0 – degrees Celsius
1 – degrees Fahrenheit
4010 INPT RW
0…8
Type of main input:
0 – thermoresistor Pt100
1 – thermoresistor Pt1000
2 – J type thermocouple
3 – T type thermocouple
4 – K type thermocouple
5 – S type thermocouple
6 – R type thermocouple
7 – B type thermocouple
8 – N type thermocouple
4011 T-LI RW
0…1 Type of line
0 – 2-wire
1 – 3-wire
4012 DP RW
0…1 Position of the decimal point of the main input
0 – without a decimal place
1 – 1 decimal place
4013 SHIF RW
-1000…1000 [x10
°
C]
-1800…1800 [x10
°
F]
Shift of the measured value of the main input
4014 OUT RW
0…7
Output function
0 – no function
1 – control signal
2 – upper absolute alarm
3 – lower absolute alarm
4 – upper relative alarm
5 – lower relative alarm
6 – internal relative alarm
7 – external relative alarm
4015 ALG RW
0…1 Control algorithm
0 – ON-OFF
1 – PID
4016 TYPE
RW
0…1 Type of control
0 – direct control – cooling
1 – reverse control – heating
4017 HY RW
2…1000 [x10
°
C]
2…1800 [x10
°
F] Hysteresis HY
4018 STLO
RW
acc. to the table
10
Lower threshold for self-tuning
4019 STHI RW
acc. to the table
10
Upper threshold for self-tuning
4020 PB RW
1…5500 [x10
°
C]
1…9900 [x10
°
F] Proportional band PB
4021 TI RW
0…9999 Integral time constant TI [s]
4022 TD RW
0…25000 Derivative time constant TD [s x10]
4023 Y0 RW
0…1000 Correction of control signal Y0 (for P or PD control)
[% x10]
4024 TO RW
5…999 Pulse period of output [s x10]
4025 ALSP
RW
acc. to the table
10
Set point for the absolute alarm [x10]

RE70-09 User's Manual 17
register
address marking
operati
on parameter range description
4026 ALDV
RW
-1800…1800 [x10
°
C]
-3600…3600 [x10
°
F]
Deviation from the set point of the relative alarm
4027 ALHY
RW
2…1000 [x10
°
C]
2…1800 [x10
°
F] Hysteresis for the alarm
4028 SPL RW
acc. to the table
10
Lower limitation of the fast set point change
4029 SPH RW
acc. to the table
10
Upper limitation of the fast set point change
4030 SECU
RW
0…9999 Access code to the menu
4031 STFN
RW
0…1 Self-tuning function
0 – locked
1 – unlocked
Register 4002 – controller status Table 8
bit description
0-11 Reserved
12 Automatic/Manual mode: 0 – automatic, 1 – manual
13 State of alarm: 0 – active, 1 – inactive
14 Measured value beyond the range limits
15 Controller error – check the error register
Register 4003 – error register Table 9
bit description
0-14 Reserved
15 Input discalibrated
Input range limits Table 10
sensor type
range
UNIT = °C [x10]
UNIT = °F [x10]
Pt100 -2000…8500 -3280…
……
…15620
Pt1000 -2000…
……
…8500 -3280…
……
…15620
Fe-CuNi (J) -500…
……
…12000 -580…
……
…21920
Cu-CuNi (T) -500…
……
…4000 -580…
……
…7520
NiCr-NiAl (K) -500…
……
…13720 -580…
……
…25016
PtRh10-Pt (S) 0…
……
…17670 320…
……
…32126
PtRh13-Pt (R) 0…
……
…17670 320…
……
…32126
PtRh30-PtRh6 (B) 0…
……
…17670 320…
……
…32126
NiCrSi-NiSi (N) -500…
……
…13000 -580…
……
…23720
12. Error signaling
Character messages signaling the incorrect controller operation. Table 11
Error code
Reason Procedure
____
________
____
Down overflow of the range
limit or lack of RTD
Check, if input signal values are situated in the appropriate
range – if yes, check if check if there is no short circuit in the
thermoresistor or the thermocouple is connected inversely.
::::
::::::::
::::
Upper overflow of the range
limit or break in the sensor
circuit
Check, if input signal values are situated in the appropriate
range – if yes, check if there is no break in the sensor circuit.
eRad
eRadeRad
eRad
Input discalibrated Connect the controller supply again and if that is not effective,
contact the nearest service shop.
eRee
eReeeRee
eRee
Configuration parameters
checksum error Connect the controller supply again and if that is not effective,
contact the nearest service shop.

RE70-09 User's Manual 18
13. Technical data
Input signals acc. to the table 12
Input signals and range limits for inputs Table 12
Sensor type Standard Designation Range
Pt100 EN 60751+A2:1997 Pt100 -200
…
850 °C -328
…
1,562 °F
Pt1000 EN 60751+A2:1997 Pt1000 -200
…
850 °C -328
…
1,562 °F
Fe-CuNi EN 60584-1:1997 J -50
…
1200 °C -58
…
2,192 °F
Cu-CuNi EN 60584-1:1997 T -50
…
400 °C -58
…
752 °F
NiCr-NiAl EN 60584-1:1997 K -50
…
1372 °C -58
…
2,501.6 °F
PtRh10-Pt EN 60584-1:1997 S 0
…
1767 °C 32
…
3,212.6 °F
PtRh13-Pt EN 60584-1:1997 R 0
…
1767 °C 32
…
3,212.6 °F
PtRh30-PtRh6 EN 60584-1:1997 B 0
…
1767 °C
1)
32
…
3212,6 °F
1)
NiCrSi-NiSi EN 60584-1:1997 N -50
…
1300 °C -58
…
2,372 °F
1)
Intrinsic error is related to the range limits 200…1,767 °C (392…3,212.6 °F)
*)
Sensor line resistance <10
Ω
/wire; the connection must use wires of identical diameter and length
Basic error of real value measurement
0.3% for thermoresistance inputs
0.3% for thermoelectric inputs (0.5% – for B, R, S);
Measurement time 0.33 s
Detection of error in the measurement circuit:
- thermocouple, Pt100 range limit exceeded
Types of outputs:
- relay output type SPDT (form C), max load: 5 A/230 V AC, max.
200,000 cycles for 5 A/230 V AC (resistive)
Way of output operation:
- reverse for heating
- direct for cooling
Rated operating conditions:
- supply voltage 230 VAC
±
10%
- supply voltage frequency 50/60 Hz
- ambient temperature 0…23…50 °C
- storage temperature -20…+70 °C
- relative air humidity < 85% (no condensation)
- preheating time 30 min
- operating position any
Power input < 4 VA
Weight < 0.25 kg
Protection grade ensured by the housing acc. to EN 60529
- from the frontal plate IP65
- from the terminal side IP20
Additional errors in rated operating conditions caused by:
- compensation of reference junction temperature
changes
≤
2
°
C
- resistance change of thermoresistance
sensor line
≤
50% intrinsic error value
- ambient temperature change
≤
100% intrinsic error value /10 K
Safety requirements acc. to EN 61010-1
1)
- circuit-to-circuit insulation basic
- installation category III
- pollution grade 2
- maximum phase-to-earth operating voltage:

RE70-09 User's Manual 19
- for supply circuit, output 300 V
- for input circuits 50 V
- altitude a.s.l. below 2000 m
Electromagnetic compatibility:
- noise immunity, acc. to standard EN 61000-6-2
- noise emission, acc. to standard EN 61000-6-4
14. Controller ordering code
The way of coding is given in the table 13.
Versions and ordering Table 13
RE70 controller –
XX
X X
Version standard 00
custom-made
*
XX
Language Polish
P
version English
E
other
*
X
acceptance without extra quality requirements
0
tests with quality inspection certificate
1
according to buyer's specification
*
X
*
after agreeing with the manufacturer

92
RE70-09
LUMEL S.A.
ul. Słubicka 1, 65-127 Zielona Góra, Poland
Tel.: (48-68) 45 75 100
Fax: (48-68) 45 75 508
e-mail:[email protected]
http://www.lumel.com.pl
Export Department:
Tel.: (48-68) 45 75 302
Fax: (48-68) 32 54 091
Other manuals for RE70
2
Table of contents
Other Lumel Temperature Controllers manuals