Cumberland Integra EXPERT 64EU User manual

EXPERT 64EU
Temperature Controller
USER’S MANUAL


FOR CUSTOMER USE
Enter the serial number located on the side of
the controller below for future reference.
Model number:
Serial number:
EXPERT 64EU

4EXPERT 64EU rev.03
TABLE OF CONTENTS
1. INTRODUCTION ........................................................................................... 6
1.1 Precautions ...................................................................................................................... 6
1.2 Symbols of the Manual ..................................................................................................... 7
1.3 Controller’s Overview ........................................................................................................7
2. MOUNTING INSTRUCTIONS ........................................................................ 10
2.1 Installing the Controller on the Wall ................................................................................... 10
2.2 Connections ..................................................................................................................10
2.2.1 Controller’s Main Wiring ...................................................................................................... 10
2.2.2 Probe Inputs ....................................................................................................................... 10
2.2.3 Alarm Connection ............................................................................................................... 11
2.2.4 0-10V Output Connection .................................................................................................... 11
3. USER INTERFACE....................................................................................... 12
3.1 Location of the Controls .................................................................................................. 12
3.2 How to Select & Modify the Parameters ............................................................................. 14
3.3 Status Leds ................................................................................................................... 15
4. CONTROLLER SETUP .................................................................................. 16
4.1 Setting the Time & Date .................................................................................................. 16
4.1.1 Day / Night Times ............................................................................................................... 16
4.2 Password ...................................................................................................................... 17
4.3 Controller Programs ........................................................................................................ 18
4.3.1 Selecting a Program ............................................................................................................ 18
4.3.2 Copying / Pasting a Program Configuration .............................................................................. 19
4.4 Installation Setup ............................................................................................................ 20
4.5 Output Setup .................................................................................................................23
4.6 Relay Assignment ........................................................................................................... 26
4.6.1 Principle of Operation .......................................................................................................... 26
4.6.2 Making the Assignment ....................................................................................................... 27
4.7 Assignment of Variable Outputs ....................................................................................... 28
4.7.1 Principle of Operation .......................................................................................................... 28
4.7.2 Making the Assignment ........................................................................................................ 28
4.8 Temperature Probe Assignment ........................................................................................ 29
4.9 Clean Mode & Empty Zones ............................................................................................. 31
4.9.1 Principle of Operation .......................................................................................................... 31
4.9.2 Settings ............................................................................................................................. 32
4.10 Test Mode ..................................................................................................................... 33
4.11 Version .........................................................................................................................33
5. TEMPERATURE SETTINGS ............................................................................ 34
5.1 Set Points ..................................................................................................................... 34
5.1.1 Adjusting the Set Points ....................................................................................................... 35
5.1.2 Set Point Curve .................................................................................................................. 36
6 VENTILATION SETTINGS............................................................................. 38
6.1 Minimum Ventilation ....................................................................................................... 38
6.1.1 Minimum Ventilation Timer ..................................................................................................38
6.1.2 Minimum Ventilation Curves ................................................................................................... 38
6.1.3 Minimum Ventilation Using Variable Fans ............................................................................... 39
6.1.4 Minimum Ventilation Using On/Off Fans ................................................................................. 39
6.1.5 Minimum Ventilation Settings ...............................................................................................40
6.1.5.1 Main Options ............................................................................................................................................. 40
6.1.5.2 Minimum Ventilation Timer Settings ............................................................................................................... 41
6.1.5.3 Minimum Ventilation Relay Selection .............................................................................................................. 42
6.1.5.4 Curve Settings ........................................................................................................................................... 44
6.2 Fan Stages .................................................................................................................... 46
6.2.1 Principle of Operation .......................................................................................................... 46
6.2.1.1 Main Operation of the Fan Stages ................................................................................................................. 46
6.2.1.2 Operation of Variable Outputs ....................................................................................................................... 47
6.2.1.3 Outside Temperature Compensation .............................................................................................................. 48
6.2.1.4 Operation of 0-10V Outputs used for Ventilation .............................................................................................. 49

5
EXPERT 64EU rev.03
EXPERT 64EU
6.2.2 Settings ............................................................................................................................. 50
6.2.2.1 Setting the Fan Stages ................................................................................................................................ 50
6.2.2.2 Setting the 0-10V Outputs (Used for Ventilation) .............................................................................................. 51
51
6.3 Tunnel Curtain ...............................................................................................................52
6.3.1 Principle of Operation .......................................................................................................... 52
6.3.2 Curtain Settings .................................................................................................................. 55
6.4 Inlets & Chimney Dampers ............................................................................................... 57
6.4.1 Principle of Operation .......................................................................................................... 57
6.4.1.1 Inlets and Chimney Dampers’ Operation .......................................................................................................... 57
6.4.1.2 Inlets’ Specific Functions ............................................................................................................................. 58
6.4.2 Settings ............................................................................................................................. 60
6.4.2.1 Chimney Damper Settings ............................................................................................................................ 60
6.4.2.2 Inlet Settings: Probe Assignment ................................................................................................................... 60
6.4.2.3 Inlet Settings: Openings ............................................................................................................................... 61
6.4.2.4 Inlet Settings: Temperature Compensation ...................................................................................................... 62
6.4.2.5 Inlet Settings: Static Pressure Compensation .................................................................................................... 62
6.5 Cooling Outputs ............................................................................................................. 63
6.5.1 Principle of Operation .......................................................................................................... 63
6.5.2 Settings ............................................................................................................................. 64
7. HEATING ..................................................................................................... 65
7.1 Heating Stages ...............................................................................................................65
7.1.1 Principle of Operation .......................................................................................................... 65
7.1.2 Settings ............................................................................................................................. 66
7.2 0-10V Heating Outputs ................................................................................................... 67
7.2.1 Principle of Operation .......................................................................................................... 67
7.2.2 Settings ............................................................................................................................. 67
8. LIGHTS ...................................................................................................... 68
8.1 Principle of Operation ...................................................................................................... 68
8.2 Settings ........................................................................................................................ 69
9. CLOCK OUTPUTS ....................................................................................... 71
10. RELATIVE HUMIDITY (RH) CONTROL ........................................................... 72
10.1 Principle of Operation ...................................................................................................... 72
10.1.1 RH Compensation on the Minimum Ventilation Speed ............................................................... 72
10.1.2 RH Compensation with Heating Outputs ................................................................................. 72
10.1.3 RH Compensation with Cooling Outputs ................................................................................. 73
10.2 Setting the RH Compensation Parameters ........................................................................... 74
11. ALARMS ................................................................................................... 76
11.1 Alarm Log ..................................................................................................................... 76
11.2 Alarm Conditions ............................................................................................................ 76
11.3 Setting the Alarm Limits .................................................................................................. 78
12. MONITORING FUNCTIONS .......................................................................... 79
12.1 Current Conditions .......................................................................................................... 79
12.2 Individual Temperature Probe Readings .............................................................................. 79
12.3 History .........................................................................................................................79
12.4 Monitoring the Animal Age & Number ............................................................................... 81
12.4.1 Entering the Age, Mortalities & Culled ; Starting a Batch .......................................................... 81
13. TECHNICAL SPECIFICATIONS ..................................................................... 83
14. MEMORY CARD ......................................................................................... 84
14.1 Transfer Error ................................................................................................................. 85
15. INSTALLATION REPORT.............................................................................. 86
16. INDEX ...................................................................................................... 98

6EXPERT 64EU rev.03
1. INTRODUCTION
1.1 Precautions
We strongly recommend installing supplementary natural ventila-
tion as well as a backup thermostat on at least one cooling stage
(refer to the wiring diagram enclosed with this user's manual to
connect the thermostat).
Although fuses at the input and outputs of the controller protect
its circuits in case of an overload or overvoltage, we recommend
installing an additional protection device on the controller's supply
circuit.
The room temperature where the controller is located MUST
ALWAYS REMAIN BETWEEN 32°F AND 104°F (0°C TO 40°C).
To avoid exposing the controller to harmful gases or excessive
humidity, it is preferable to install it in a corridor.
DO NOT SPRAY WATER ON THE CONTROLLER
Caution. Carefully read the following text for it contains impor-
tant information which, if ignored, may cause the controller to
operate improperly.
Pay attention. The following text contains very useful informa-
tion.
:$51,1*
The function/parameter is common to all of the controller pro-
grams.

7
EXPERT 64EU rev.03
EXPERT 64EU
1.2 Symbols of the Manual
1.3 Controller’s Overview
The EXPERT 64EU is an electronic device used for environmental control in livestock
buildings. It allows the user to maintain a specified target temperature by controlling
the operation of ventilation and heating equipment. The following inputs & outputs
can be controlled:
OUTPUTS :
- 64 On/Off relays to operate:
8 heating stages (and a possibility to simulate up to 16 heating stages);
15 fan stages;
3 cooling outputs;
24 clock outputs;
1 tunnel curtain output;
- 2 Variable outputs;
- 12 Inlet outputs;
- 4 0-10V outputs to operate:
- heating devices;
- lights;
- additional variable fans;
- chimney dampers.
INPUTS:
- 8 inside temperature probes;
- 1 outside temperature probe;
- 1 indoor humidity sensor;
- 1 outdoor humidity sensor;
- 1 static pressure sensor;
- 1 water meter;
Refer to the wiring diagram enclosed at the end of this manual
to connect the various devices on the controller’s inputs & outputs.
:$51,1*

8EXPERT 64EU rev.03
EXPERT 64EU
MAIN FEATURES OF THE CONTROLLER:
VERY LARGE LCD DISPLAY
A large LCD screen provides an efficient interface for displaying, monitoring and
adjusting the parameters.
3 CONTROLLER PROGRAMS
The controller allows to set 3 different programs to control the room temperature. It is
thus possible to activate a specific program, that uses particular temperature settings,
in accordance with the animal age for instance.
STATUS LEDS
Pilot lights that indicate the status of the controller outputs, allowing the user to
monitor the system’s operation without having to enter the building.
REMOVABLE CONNECTORS
Inputs’ connection is now made easier by removing the connector from the main board.
MINIMUM VENTILATION CYCLE
When ventilation is not required to reduce the room temperature, the fan outputs can
run either continuously or intermittently to reduce the humidity level and supply
oxygen to the room.
SET POINT AND MINIMUM VENTILATION CURVES
The controller can automatically change the room set point and the minimum ventilation
fans’ speed, over a given period of time, in accordance with the animals’ requirements.
PROBE READINGS RECORDED FOR PAST DAYS
Minimum and maximum readings of the static pressure and humidity probes are re-
corded for the current day and for the past 75 days. The minimum and maximum
readings of each individual temperature probe is recorded for the current day and for
the past 7 days.
WATER MONITORING
A pulse input is provided to monitor the water consumption. The daily water con-
sumption is displayed for the current day and for the past 75 days.
ALARM MANAGEMENT
Alarms are provided for high-low temperatures, defective probes and other system
functions.
HUMIDITY COMPENSATION
The minimum ventilation fans’ speed can be automatically adjusted depending on the
humidity level in the room. Mist units can be activated whenever the humidity level in

9
EXPERT 64EU rev.03
EXPERT 64EU
the house is too low or can be shut off when it is too high. Finally, the heating
outputs can be activated to compensate for high humidity levels.
EIGHT INDEPENDENT PROBE TEMPERATURE INPUTS
Up to eight inside temperature probes can be connected to the controller in order to
obtain a more accurate reading of the average house temperature and a faster reac-
tion time.
STATIC PRESSURE CONTROL
A static pressure input is provided to control static pressure level by opening and
closing the air inlets.
OUTSIDE TEMPERATURE COMPENSATION
Fan stages are automatically adjusted according to the outside temperature. It en-
sures a better stability in the room temperature.
0-10V OUTPUTS
Four 0-10V outputs can be activated to control additional variable ventilation stage,
heating devices, lights, or chimney dampers.
CONTROL OF THE AIR INLET MOVEMENT
If the controller is used in combination with one or more air inlet modules, the move-
ment of air inlets can be coordinated with the operation of the fans using a potenti-
ometer located on the panel drive. This allows the air inlets to be adjusted correctly,
without the influence of uncontrollable factors such as wind or air from adjoining
rooms
PASSWORD PROTECTION
A password feature is used to restrict access to some of the controller setup functions.
BACKUP BATTERY
A backup battery allows the unit to keep time in case of a power failure.
OVERLOAD AND OVERVOLTAGE PROTECTION
Resettable fuses are provided at low-voltage inputs and outputs of the controller to
protect its circuitry in the case of an overload or overvoltage.
COMPUTER CONTROL
The controller can be connected to a computer, thus making it possible to centralize
the management of information and diversify control strategies.
TEST MODE
This mode allows you to simulate temperature changes and verify the performances
of your controller.

10 EXPERT 64EU rev.03
2. MOUNTING INSTRUCTIONS
2.1 Installing the Controller on the Wall
Fasten the four metal brackets on the mounting holes located behind the controller
using the four screws included with the controller. Mount the enclosure on the wall
using four other screws. Be sure the electrical knockouts are at the bottom of the
enclosure in order to prevent water from entering the controller. The enclosure must
be mounted in a location that will allow the cover to be completely opened right up
against the wall.
2.2 Connections
Note that the input connectors are now removable. This
makes it easier to connect the different elements to the
terminals.
2.2.1 Controller’s Main Wiring
Refer to the wiring diagram enclosed with this user's manual to connect the control-
ler. Use the electrical knockouts provided at the bottom of the enclosure. Do not
make additional holes in the enclosure, particularly on the side of the enclosure when
using a computer communication module.
ALL WIRING MUST BE DONE BY AN AUTHORIZED ELECTRICIAN
AND MUST COMPLY WITH APPLICABLE CODES, LAWS AND
REGULATIONS. MAKE SURE POWER IS OFF BEFORE DOING ANY
WIRING TO AVOID ELECTRICAL SHOCKS AND EQUIPMENT DAM-
AGE.
2.2.2 Probe Inputs
Probes operate at low voltage and are isolated from the supply. Make sure that probe
cables remain isolated from all high voltage sources. In particular, do not route the
probe cables through the same electrical knockout as other cables. Do not connect
the shield from the probe cable to a terminal or a ground.
:$51,1*

11
EXPERT 64EU rev.03
EXPERT 64EU
EXTENDING A PROBE:
Each probe can be extended up to 500 feet (150 meters).
To extend a probe:
Use a shielded cable of outside diameter between 0.245 and 0.260 in (6.22 and 6.60
mm) (the cable dimensions should not be under 18 AWG) to ensure the cable entry is
liquid tight. Do not ground the shielding.
It is preferable to solder the cable joint to ensure a proper contact between the two
cables.
Do not run probe cables next to other power cables.
When crossing over other cables, cross at 90°.
DEFECTIVE TEMPERATURE PROBES:
An alarm is generated when a defective probe is detected. The defective temperature
probes are identified in the "11. Alarm Log" menu. Refer to chapter 11 for further
information on the alarms.
2.2.3 Alarm Connection
There are two types of alarms on the market. One type activates when
current is cut off at its input, whereas the other activates when current
is supplied at its input. For an alarm of the first type, use the NC
terminal as shown on the wiring diagram. For an alarm of the second
type, use the NO terminal.
2.2.4 0-10V Output Connection
It is recommended to use a 18 to 22 AWG wire to connect the devices to the 0-10V
outputs. This type of output can be used to connect various devices such as heaters,
lights, fans, chimney dampers, etc.
:$51,1*

12 EXPERT 64EU rev.03
3. USER INTERFACE
3.1 Location of the Controls
LCD DISPLAY
LED DISPLAY
ARROW KEYS
STATUS LEDS

13
EXPERT 64EU rev.03
EXPERT 64EU
LARGE LCD DISPLAY:
LCD Screen & Screen Contrast: The large LCD display
shows the various readings and parameters. The screen
contrast can be modified using the potentiometer located
behind the screen: open the controller’s front panel to
access the potentiometer then use a screwdriver to adjust
the contrast.
The
Current Conditions
menu is automatically selected
after 4 minutes of inactivity.
LED DISPLAY:
This display shows the current average room temperature
and/or the static pressure level. The message “CLn” is dis-
played while the controller is in clean mode.
STATUS LEDS:
The status pilot lights indicate the current state of the different stages and outputs.
Refer to section 3.3 for further information about the status leds.
ARROW KEYS:
The arrow keys are used to navigate within the controller’s menus. The up and down-
arrow keys are also used to adjust a parameter value when it is flashing on the
display.
ENTER / MODIFY BUTTON:
- To enter in a menu:
Pressing this key allows to access the selected menu.
- To modify a parameter:
Pressing this key when a parameter is selected allows to enter the edition mode,
e.g. the parameter flashes on the display, which means that it can now be
modified by using the up and down-arrow keys. Refer to section 3.2 for detailed
steps showing how to modify a parameter.
BACK BUTTON:
This key is used to return to the previous menu.
LCD CONTRAST
POTENTIOMETER

14 EXPERT 64EU rev.03
EXPERT 64EU
These arrows indicate which
menu is currently selected.
These arrow indicate the pres-
ence of additional menus be-
yond the displayed menus. Use
the arrow keys to scroll the
display.
Use the arrow keys to select
the desired item.
Press the “BACK” button to
return to the previous menu.
Press the “MODIFY/ENTER” button to access the selected menu.
Press the “MODIFY/ENTER” button to edit a parameter (see below).
PARAMETER ADJUSTMENT:
• Use the arrow keys to select the
desired parameter. When a param-
eter is selected, the message
“Change : Press Modify” is shown
at the bottom of the display. This
means the selected parameter can
be edited.
• Press the "Enter / Modify" button to
access the edition mode. The param-
eter then flashes on the display. It is
now possible to modify its value.
• Use the up and down-arrow keys to set the parameter to the desired value.
• Press the "Enter / Modify" button once again to validate the new value and to exit
the edition mode. The parameter stops flashing.
(
&
6
3.2 How to Select & Modify the Parameters

15
EXPERT 64EU rev.03
EXPERT 64EU
3.3 Status Leds
MEANING
TURNS ON WHEN AN ALARM CONDITION IS DETECTED.
FLASHES WHEN AN ALARM CONDITION OCCURED AND HAS BEEN
RE-ESTABLISHED BY ITSELF.
TURNS ON WHEN A CLOCK OUTPUT IS OPERATING.
TURNS ON WHEN A LIGHT OUTP UT IS ACTIVE .
TURNS ON WHEN THE SELECTED 0-10V OUTPUT 1-4 IS OPERATING.
OPEN TURNS ON WHEN A TUNNEL CURTAIN IS OPENING
CLOSE TURNS ON WHEN A TUNNEL CURTAIN IS CLOSING
TURNS ON WHEN A COOLING OUTPUT IS ACTIVE.
TURNS ON WHEN THE SELECTED FAN STAGE IS ENABLED
FAN STAGE 1 LED FLASHES IN MINIMUM VENTILATION
FLASHES WHEN ONE STEP OF THE HEATING OUTPUT IS
OPERATING (REGULAR OR HIGH FIRE STEP);
TURNS ON WHEN BOTH STEPS OF THE HEATING OUTPUT ARE
OPERATING (REGULAR AND HIGH FIRE STEPS).
0-10V OUTPUT
LED
ALARM
CLOCK
LIGHT
COOLING
FAN 1-15
HEATER 1-8
TUNNEL

16 EXPERT 64EU rev.03
4. CONTROLLER SETUP
4.1 Setting the Time & Date
Select
9. Advanced Settings
1. Time and Date
• Press the
Enter / Modify
button then
use the up and down-arrow keys to set
the current day of the week.
• Press the
Enter / Modify
button to step
to the next item then use the up and
down-arrow keys to set the selected
item.
• Proceed in similar fashion to set the
whole time and date.
4.1.1 Day / Night Times
If night functions are used, the user must specify the time at which the day and night
start and the transition time between both. The transition time is the interval of time
over which the controller gradually switches from daytime to night time settings.
The following menu is only accessible if
the night set point has been enabled
(s. 4.4).
Select
9. Advanced Settings
4. Night Set Point Settings
2. Day/Night Time
• Set the day and night’s start times
and the transition time between the
day and night.
Main Menu
9. Advanced Settings
10. Select Program
11. Alarm Log
12. Controller Setup
Submenu: Press Enter
Press to Select an tem
Advanced Settings
1. Time and Date
2. Set Point Curve
3. Relative Humidity Compensation
4. Night Set Point Settings
Exit: Press Back Submenu: Press Enter
Press to Select an tem
Time and Date
Wed Aug 27 2003
7 : 07 : 07 PM
Exit: Press Back Change: Press Modify
Press to Select an tem
Main Menu
9. Advanced Settings
10. Select Program
11. Alarm Log
12. Controller Setup
Submenu: Press Enter
Press to Select an tem
Advanced Settings
3. Relative Humidity Compensation
4. Night Set Point Settings
Exit: Press Back Submenu: Press Enter
Press to Select an tem
Night Set Point Settings
1. Night Set Point Curve
2. Day / Night Time
Exit: Press Back Submenu: Press Enter
Press to Select an tem
Day / Night Time
Day Starts At 7:30 A
NightStarts At 8:00 P
Transition Time 30 min
Exit: Press Back Change: Press Modify
Press to Select an tem

17
EXPERT 64EU rev.03
EXPERT 64EU
4.2 Password
This function allows to identify 2 different user types. It is used to restrict access to
certain functions of the controller. The password is made up of 4 digits. When a correct
password is entered, the current user is identified.
Installer Password:
The installer mode gives full access to all the
controller functions. The installer password can
be modified as explained below.
User Password:
The user mode gives access to the basic functions
of the controller. The controller automatically re-
turns to the user mode after 15 minutes of inac-
tivity. The user passwords cannot be modified.
Select
12. Controller Setup
4. Password
ENTERING A PASSWORD:
• Press the
Enter / Modify
button then
use the up and down-arrow keys to
enter the first digit of the password.
Press the
Enter / Modify
button once
again to step to the next digit.
• Enter the 4 digits of the password then
press the
Enter / Modify
button once
again to validate. The user is then iden-
tified. The message “Invalid password”
is displayed if a wrong password is en-
tered.
CHANGING THE INSTALLER PASSWORD:
The installer password must first be entered as shown above to be modified.
The message “Change Password” is displayed when the current user is identi-
fied as the Installer. The new installer password can then be entered.
• Confirm the new installer password:
Once the new installer password is entered, the message “Confirm Password”
is displayed. Enter the new password once again to confirm the password.
Press the
Enter / Modify
button at the end to validate.
Main Menu
11. Alarm Log
12. Controller Setup
Controller Setup
4. Password
5. Relay Assignment
Password
Current User nstaller
Change User * * * *
Change Password * * * *
Confirm Password * * * *
Exit: Press Back Change: Press Modify
Press to Select an tem
Default installer password
0 - 6 - 1 - 0
User 1 Password
1 - 1 - 1 - 1
User 2 Password
2 - 2 - 2 - 2

18 EXPERT 64EU rev.03
EXPERT 64EU
4.3 Controller Programs
The controller allows to use up to 3 separate programs to control the room tempera-
ture. It is thus possible to activate a specific program, that uses particular settings, in
accordance with the age of the animals for instance. Most parameters of the control-
ler must be set separately for each program.
MAKE SURE THE PROPER PROGRAM IS SELECTED BEFORE
CHANGING ANY PARAMETER OF THE CONTROLLER!
4.3.1 Selecting a Program
Select
10. Select Program
• Select the desired program then press the
Enter/Modify
key to validate. The se-
lected program settings are now used by
the controller.
:$51,1*
Main Menu
10. Select Program
11. Alarm Log
12. Controller Setup
Submenu: Press Enter
Press to Select an tem
Select Program
Running program Program 1
Clean Mode Status Off
Detect Lo Temperature? No
Exit: Press Back Change: Press Modify
Press to Select an tem

19
EXPERT 64EU rev.03
EXPERT 64EU
4.3.2 Copying / Pasting a Program Configuration
It is possible to duplicate a whole program configuration by copying it and pasting it
on another program. This avoids repeating the same programming sequence several
times. The following steps can only be performed from the installer mode (s. 4.2).
Select
12. Controller Setup
3. Copy/Paste Programs*
* Only accessible from the installer mode (s. 4.2).
• Select the program as follows:
Copy From Program:
This is the source program. The one
that will be duplicated.
Copy to Program:
This is the target program. The one
on which the copied program will
be pasted.
• Once the source and the target programs have both been defined, the message
"Confirm?" appears on the display. Select “Yes” to confirm the program’s
duplication. The message " Copy in progress.... please wait.. " is displayed.
Wait until the duplication process is over.
Main Menu
11. Alarm Log
12. Controller Setup
Controller Setup
3. Copy / Paste Program
4. Password
Copy / Paste Program
Copy From Program: 1
Copy to Program: 3
Confirm? Yes
Copy n Progress...Please Wait...
Exit: Press Back Change: Press Modify
Press to Select an tem

20 EXPERT 64EU rev.03
EXPERT 64EU
4.4 Installation Setup
The following section shows how to customize the controller for your particular
application. It shows how to enable the controller’s inputs, to select the desired
measuring units and to set other basic functions of your controller. Normally, this
setup needs to be done only once for each program.
Pay attention. Some of the Installation Setup parameters are common to all
programs. Templates are available at the end of this manual to write down
the specific settings of each program.
Select
12. Controller Setup
1. Installation*
* Only accessible from the installer mode (s. 4.2).
• Set the appropriate parameters
amongst the following:
• Number of Programs:
Select the number of controller pro-
grams. Ranges from 1 to 3 programs.
Common to all programs.
• Time Display:
Select AM/PM or 24 hours.
Common to all programs.
• # of Temperature Probes:
Select the number of indoor
temperature probes connected to the
controller, excluding the outside tem-
perature probe. Adjustable from 1 to 8
probes.
Common to all programs.
• Outside temperature probe:
Enable / disable the outside T° probe input.
Common to all programs.
• Room Relative Humidity (RH) Probe:
Enable / disable the room humidity probe input.
Common to all programs.
Main Menu
11. Alarm Log
12. Controller Setup
Controller Setup
1. nstallation
2. Output Setup
3. Copy / Paste Program
4. Password
5. Relay Assignment
6. Variable Output Assignment
7. Probe Assignment
8. Version
9. Test Mode
Submenu: Press Enter
Press to Select an tem
nstallation
Number of Programs 3
Time of day format AM/PM
Number of T° Probes 8
Use Outside T° Probe? Yes
Use Room RH Probe? Yes
Use Outside RH Probe? Yes
Use Static Pressure? Yes
Use Water Meter? Yes
Temperature Units °F
Static Pressure Units WC
Water Meter Units gal
Water Meter Calibration 1 gal/p
RH influence on min vent? Yes
RH influence on Heating? Yes
Use Mist Shutoff? Yes
Use Mist on Low R.Humidity Yes
Out T influence bandwidth Yes
Summer Temperature 59.0°F
Winter Temperature 41.0°F
Use Night Set Point? No
Show on Digit Display T°
Exit: Press BackChange: Press Modify
Press to Select an tem
Table of contents
Other Cumberland Temperature Controllers manuals