manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ERMCO
  6. •
  7. Circuit Breaker
  8. •
  9. ERMCO AHT-1 Guide

ERMCO AHT-1 Guide

1
CIRCUIT BREAKER OPERATION & ADJUSTMENT (AHT‐1 & T‐12)
Preliminary factory adjustment of the breakers is expected to give
signal light contact connuity under the following four condions:
1. When the cocking lever is moved beyond the open posion.
2. When the cocking lever is moved beyond the closed posion.
3. When the trip bar is moved, but before the breaker contacts are
tripped.
4. When the breaker has tripped completely.
To achieve these condions, the posion of the two signal light
contacts and the calibrang screw are factory preset. To obtain light
indicaon from the reset posion, the cocking lever must be moved
toward the light tower when the contacts are open. To obtain light
indicaon from the closed posion, the cocking lever must be moved
toward the contacts when the contacts are closed. This allows the
light switch operaon to be checked outside the tank.
Following this preliminary adjustment, the breakers are calibrated
and packaged.
To obtain the same condions when the breaker is installed in a
transformer requires the correct amount of free travel at each end of
the operang handle moon.
Obtaining the correct free travel is oen a cut‐and‐try procedure due
to variaon in the handle locaon, breaker locaon and tank
dimensions. To facilitate this adjustment the following steps may
prove useful.
1. Bolt breaker to support, ghten screws firmly and back offthe
screw under the trip bar ½ turn.
2. Install the operang handle assembly in the tank and ghten
the clamping nut unl the gasket stop booms out. Further
ghtening is undesirable.
3. Posion the operang handle to align the yellow arrow with the
“R” on the bearing, allowing about ¼” clearance between the
handle stop and the bearing stop. Posion breaker in the
cocked posion with the contacts open.
4. Screw the connecng rod (link arm) in to the cocking lever unl
the holes in the rod and operang arm mate. Insert a coer pin
in the holes, hold coer pin in place and move the operang
handle to check for the following operaons:
a. Close and open the breaker.
b. Close breaker, trip light contact manually (avoid tripping
main breaker contacts). Reset light by moving operang
handles to the “L” posion.
c. Trip breaker contacts and try reseng the breaker. A
properly adjusted breaker will have approximately ¼” of
travel lebetween the handle and bearing stops. If
breaker fails to operate properly, adjust connecng rod
unl the above operang condions are obtained.
FOR MORE INFORMATION VISIT ermco‐eci.com
ERMCO COMPONENTS, INC | 1607 Industrial Road | Greeneville, TN 37745
5. Install coer pin permanently; avoid binding between rod and
lever.
6. Install signal light in tank wall; ghten clamping nut only enough
to compress the gasket. Avoid over‐ghtening.
7. Posion calibraon control mechanism (overload lever) on the
breaker at the “normal” posion. Insert the preformed end
control wire into the breaker overload lever and thread the
control cable (sheath) into the support on the breaker and lock
the connecon by pinching the support around the cable
sheath.
8. Posion the calibraon control mechanism (overload lever) on
the breaker in the “normal” posion. Hold the control assembly
lever on the operang handle bearing in the “normal” posion.
Thread the control cable through the hole in the cable support
and lock the connecon by pinching the support around the
cable sheath. Twist the control wire into and around the
emergency overload control lever as show below.
9. Connect signal light winding to terminal on the breaker.
10. Connect signal light winding to the signal light.
11. For breakers without emergency overload and signal light, the
following procedure is recommended to make the breaker
assembly adjustment in the transformer tank:
a. Place breaker in the cocked posion with the contacts
open.
b. Adjust threaded connecng rod (link arm) so that the
yellow arrow on the operang handle is aligned with the
“O” on the bearing.
c. Check breaker for proper reset and close operaons.
Adjust connecng rod (link arm) to achieve proper
operaon, if required.
ECI
A1‐15
11/04
A1‐16
10‐21
2
STANDARD OPERATING INSTRUCTION GUIDE FOR LOW‐VOLTATE BREAKER & SIGNAL LIGHT
WARNING : ON SINGLE PHASE & THREE PHASE TRANSFORMERS
WITH THE SECONDARY CIRCUIT BREAKER OPEN, THERE MAY BE
SUFFICIENT COUPLING TO THE WINDING SO THAT PERCEPTIBLE
SHOCK MIGHT BE OBTAINED FROM THE SECONDARY TERMINALS.
A circuit breaker when provided is mounted inside the tank, under
the liquid level. The funcon of this breaker is to open the low‐
voltage circuit and protect the transformer from faults or severe
overloads. A red signal light, when provided, gives the warning that
the load has reached a value near the tripping point of the breaker.
The signal light remains lighted unl reset (turned off) by means of
the breaker‐operang handle. Transformers should not be operated
under load condions that will cauase the red light to appear
frequently, since it indicates an overload on the transformers. When
such a condion exists, it is recommended that a larger transformer
be substuted to avoid impairing the life of the smaller unit.
The circuit breaker operang handle and posion indicator are
shown in Figure 1. Transformers are shipped with the circuit
breakers closed. To open the low voltage circuit manually, move the
handle so that the pointer moves from “C” (closed) to “O” (open), at
which point the circuit is open. Verify that the circuit breaker is
latched in the “open” posion.
To insure that the discharge of the stac charge, which is somemes
present in the low voltage winding due to capacitance, it is
recommended that the low voltage be grounded aer opening the
circuit breaker unl the high voltage is disconnected.
To close the breaker aer manual opening move the handle so the
arrow points towards “C”. If the breaker has been tripped it is
necessary to move the arrow towards “R” to reset the breaker
before closing the breaker by moving the arrow towards “C”.
If a fault exists or and excessive load exists at the me the breaker is
closed, the breaker will reopen even though the operang handle is
held in the “C” (closed) posion.
To reset the signal light, rotate the handle to the “L” (light), and then
return to “C” (close). If the light fails to go out, the transformer is sll
over heated.
Provision is made for checking the signal light bulb when the
transformers is in service, to do this, rotate the handle to “L” (light)
FOR MORE INFORMATION VISIT ermco‐eci.com
ERMCO COMPONENTS, INC | 1607 Industrial Road | Greeneville, TN 37745
and the light should come on. If it does not, the bulb should be
replaced. The bulb is a standard six‐volt, GE bulb No. 44, and is
replaceable from outside the transformer and by removing the signal
light lens. Aer checking return the operaon handle to “C”. Faulty
bulbs should be replaced, since operang the transformer with the
faulty bulb or without a bulb may result in radio noise.
Some circuit breakers are equipped with emergency overload
devices, which can be used to restore service following a circuit
breaker operaon due to overload. With the emergency lever in the
normal posion the breaker will trip at its normal sengs as
calibrated at the factory. Moving the lever in clockwise direcon (see
Figure 1) increases the seng so that a higher temperature is
required to trip the breaker. This emergency seng provides extra
load capacity and sll permits manual breaker operaon, and also
retains short circuit protecon of the transformer. It is important
that the emergency seng be used only when and as long as
absolutely necessary, because its use will result in a reducon of
transformer life.
A meter seal is provided on the emergency lever to prevent
tampering. It is recommended that a new seal be applied when it is
returned to the normal posion aer emergency operaon.
ECI
7‐7D
A1‐17
3/02
3
CIRCUIT BREAKER APPLICATION
ECI
7‐7D
A1‐12
02/05
4
CIRCUIT BREAKER APPLICATION
ECI
7‐7D
A1‐13
01/99
5
CIRCUIT BREAKER APPLICATION
ECI
7‐7D
A1‐14
11/01

This manual suits for next models

1

Popular Circuit Breaker manuals by other brands

Siemens 3WX3653-1J 00 Series operating instructions

Siemens

Siemens 3WX3653-1J 00 Series operating instructions

Eaton IZM quick start guide

Eaton

Eaton IZM quick start guide

Schrack BES3 Series operating instructions

Schrack

Schrack BES3 Series operating instructions

Siemens TSLN3M manual

Siemens

Siemens TSLN3M manual

Siemens Sentron WL operating instructions

Siemens

Siemens Sentron WL operating instructions

Eaton Magnum PXR user manual

Eaton

Eaton Magnum PXR user manual

Eaton NRX NF Technical data

Eaton

Eaton NRX NF Technical data

ABB EMAX E2.2 Series Circuit Diagram

ABB

ABB EMAX E2.2 Series Circuit Diagram

OEZ SE-BD Series Instructions for use

OEZ

OEZ SE-BD Series Instructions for use

Shihlin electric BW-2000 manual

Shihlin electric

Shihlin electric BW-2000 manual

Siemens 3VT9200-4TC00 operating instructions

Siemens

Siemens 3VT9200-4TC00 operating instructions

ABB eVD4 Installation and service instructions

ABB

ABB eVD4 Installation and service instructions

hager H400 manual

hager

hager H400 manual

Eaton VCP-W Series Instructions for installation/operation/maintenance/servicing

Eaton

Eaton VCP-W Series Instructions for installation/operation/maintenance/servicing

Siemens 3VT9.00-3MN.2 Series operating instructions

Siemens

Siemens 3VT9.00-3MN.2 Series operating instructions

ABB SACE Emax 2 manual

ABB

ABB SACE Emax 2 manual

bonitron M3675T Customer Reference Manual

bonitron

bonitron M3675T Customer Reference Manual

GE FK800 Installation instruction

GE

GE FK800 Installation instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.