4.3. DESCRIPTION OF THE PARAMETERS.
Code: Units:
Default:Description:
F11 °C/°F
0.0Temperature setting value. Range of changes is limited by the F14 and F13 parameters.
F12 °C/°F
1.0Hysteresis (temperature control accuracy).
Range:
F14...F13
0.1...20.0
Group:
Adjustment
F13 °C/°F
302.0Maximum temperature value possible to set by the user.
F14 °C/°F
-58.0Minimum temperature value possible to set by the user. -58.0...302.0
-58.0...302.0
F18 °C/°F
0.0Evaporator sensor calibration. This is the value of rescaling the evaporator sensor in relation to actually measured temperature. -20.0...+20.0
F19 °C/°F
0.0Temperature sensor calibration. This is the value of rescaling the temperature sensor in relation to actually measured temperature. -20.0...+20.0
F21 Minutes
3.0
Minimum compressor stoppage time. It also means the delay time of switching the compressor after giving power supply.
Parameter protects the compressor against too frequent switching in case of power failure.
F22 %
0The factor of compressor operation time when chamber sensor failure.
0.0...10.0
0...100
Compressor
F23 Minutes
60Work/stoppage mode of the compressor after chamber sensor failure.
Operation and stoppage time of the compressor after chamber sensor failure is determined
on the basis of these two parameters.
Operation time: ton = F22xF23 ; Stoppage time: toff = F23-ton
Example: F22=20%; F23=60min then ton = 12min ; toff = 48min
F29 -
COOL
Main output operation mode. COOL = cooling ; HEAT = heating 5...999
COOL/HEAT
F31 Hours
12.0Interval between defrosting cycles. 0.1...99.9
F32 °C/°F
15.0Ending of the defrosting temperature.
F33 Minutes
30Maximum defrosting cycles duration. 0.0...100.0
1...99
F34 Minutes
5Dripping time of the evaporator after defrosting cycle. It is also the delay time of switching the compressor on after defrosting.
F35 -
OFF
Defrosting cycles control form. OFF - defrosting off, 1 - automatically, from time to time equals toF31,
2 - automatically, when the total operation time of the compressor reaches a value of F31, 3 - automatically, according to the real-time
0...99
OFF,1, 2, 3
F36 -
1End of defrosting: 0 - after lapse of time F33; 1 - if the evaporator reaches the temperature of F32 or after lapse of time F33
F37 -
0Type of defrosting. 0 - electrical, 1 - with hot gas (compressor turned on when defrosting) 0, 1
0, 1 -
F38 OFFFan operation when defrosting. OFF - off, ON - on. (Recommended F38=ON when natural defrosting). OFF/ON
Defrosting
F41
-
1
Fan operation. There are 7 fan operation modes available: OFF - fan turned off.
1 - fan runs parallel to the compressor, is switched on after running the compressor with F42 delay and turned off after its stoppage with F43 delay.
2 - fan runs parallel to the compressor, is switched on before the running of the compressor with F42 lead and turned off after its stoppage with F43 delay.
3 - fan operates according to the evaporator temperature sensor, is activated when the value drops below the temperature F44 and turned off when
the evaporator sensor temperature rises above the value: F44+F45
4 - fan operates according to the evaporator temperature sensor, is activated when the value rises above temperature F44 and turned off,
when the evaporator sensor temperature drops below the value: F44-F45
5 - fan runs with the compressor. During the stoppage of the compressor, fan operates periodically: turned on for F46 time, turned off for F47 time.
Attention! During defrosting, the fan operation is specified by F38 parameter.
OFF,1...6
F42 Seconds
30Lead/delay time of the fan run before/after the compressor run. Parameter is considered, when F41=1 and 2.
F43 Seconds
0Delay time of the fan stoppage after stopping the compressor. Parameter is considered, when F41=1 and 2. 0...999
0...999
F44 °C/°F
-10.0Fan switching temperature. Parameter is considered, when F41=3 and 4. -58.0...302.0
F45 °C/°F
5.0Evaporator sensor temperature hysteresis. Parameter is considered, when F41=3 and 4.
F46 Minutes
10Fan operation time during the stoppage of the compressor, when F41=5 0.1...50.0
0...999
F47 Minutes
10Fan stoppage time during the stoppage of the compressor, when F41=5 0...999
F50
-
0
Bistate input D1: 0 - unused; 1 - alarm when short-circuit; 2 - alarm when short-circuit with maintaince of alarm signalling;
3 - alarm when opened; 4 - alarm when opened with maintance of alarm signalling
F80 -
OFFPassword to access the configuration menu. OFF - password protection inactive. F80 = 0000 - no password
0...4
0000...9999
F81 -
°CTemperature unit °C/°F.
F98 -
-Reserved.
°C/°F
-
F99 -
-Controller test. Disconnect output device to make the test! Otherwise the system can crash. -
Fan
End Exit.
F59 YESEvaporator sensor: YES - active, NO - inactive YES/NO
F61 -
Six following defrosting runs during the day.
OFF - no defrosting 00:00...23:59
OFF
F60
Hour:min
-
Real-time clock setting (RTC). 00:00...23:59
F66
F85 Hours
-Timer current time. -
F86 -
NOTimer zeroing.
F87 Hours
OFF
Timer time setting.After lapse of the time, controller turns off all outputs, turns on the beeper and the display indicates A99 code.
You can check the current time of the timer in F85 parameter or reset counting with F86 parameter. OFF - timer function inactive.
YES/NO
0000...9999
OFF
Inputs
RTCOthers
Hour:min
-
4