janitza Prophi 6R User manual

Doc. no. 2.020.016.1.a 6.0.E - 11/2019
Janitza electronics GmbH
Vor dem Polstück 6
D-35633 Lahnau
Telefonischer Support: +49 6441 9642-22
E-Mail: [email protected]
www.janitza.com
www.janitza.com
Power Factor Controller
Prophi®6R
Manual
Version 6.0 E - 11/2019
Power Factor Controller
Prophi 6R
Manual
123456
Power Factor Controller
Blindleistungsregler
Auto
Program
Manual
Service
Enter
OK
Prophi
®
®

Prophi®6R
2
CONTENTS
Section 1 General / type series and accessories 3
Section 2 Installation of the controller / connection diagram 5
2.1 Current measurement 6
2.2 Programming of phase-correction
2.3 Alarm output / error messages 7
Section 3 Operating modes 7
Section 4 Automatic operation / display functions 8
Section 5 Programming 9
5.1 Automatic initialization 9
5.2 Manual programming 10
5.3 Programming lock 12
Section 6 Manual operation / Programming of fixed stages 13
Section 7 Service menu, Test run 14
Section 8 Expert mode 15
8.1 Expert mode 1
8.2 Expert mode 2 17
Section 9 Control principle 18
Section 10 Interface 19
Section 11 Initial operation 19
Section 12 Maintenance and warranty 19
Section 13 Troubleshooting 20
Section 14 Technical data 21
Annex: Annex 1 Table of control series 22
Description of control-series editor
Annex 2 Default settings 23
Operating diagram (fast programming) 25
- 2 -

Prophi®6R
3
!
CAUTIONS:
1. High voltage !
2. The device may only be used indoor !
3. Make sure that the discharge time set in controller
matches capacitor discharge time !
Section1 General
The power factor controller Prophi-6R is a modern control device of innovative design with
a variety of functions.
It is designed for a measuring voltage of 30...525V (L-N) or (L-L) and a supply voltage of
110...230VAC (+/- 15%)
It features a user interface with a menu-driven display in plain text for maximum ease of
operation. Straightforward symbols and alphanumeric displays in the language of the
country of use (ten languages) combine maximum ease of handling with convenient
presentation of results.
Display of various grid parameters, storage of various values and a test run option make it
easy to analyse errors and monitor the system.
An automatic initialization is available which will reduce the commissioning to a minimum.
Main features:
R6 switching outputs, 1 alarm relay
RTwenty pre-programmed control series with a self-optimized intelligent control
response
RControl-series editor for user-defined control series
RComplete menu-guided operation and display
RIlluminated graphic display with 2 x 16 characters
RFour-quadrant operation
RAutomatic initialization
RDisplay of various line parameters (V, I, F, Q, P, S...)
RDisplay of voltage and current harmonics
RDisplay and monitoring of temperature
RMonitoring of the individual capacitor power values
RStorage of maximum line-parameter and switching-operation values as well as
of the turn-on times of individual capacitor contactors
RManual / automatic operation
RProgramming of fixed stages and the option of skipping individual outputs
RNo-voltage turn-off
RError detection for various states and interference-message output
RTest run of PFC system with error analysis
RSwitchboard-integrated housing 144 x 144 x 55 mm

Prophi®6R
4
Fig. 2 Rear view
The controller is supplied as standard for an operating voltage of 110...230 VAC (+-15%),
a measuring voltage of 30...525 VAC (L-N) or (L-L), 50/60Hz and a measuring current of
5A or 1A. A voltage converter is required for different measuring voltages.
Caution!
Voltages which exceed the specified voltage range can damage the
device !
- 4 -
Fig.1 Front view
Operating mode
- Automatic
- Programming
- Manual operation
- Service
- Expert mode
Enter / OK
Confirm and
store values
Increase
selected
parameter
Reduce
selected
parameter
!
123456
Power Factor Controller
Blindleistungsregler
Auto
Program
Manual
Service
Enter
OK
Prophi
®
Blindleistungsregler
Power factor regulator
Type: Prophi 6R
Meas.voltage: 30-525VAC (L-N) /(L-L)
Power supply: 110 - 230VAC 50/60Hz
Ser.No.: 0815 / 2019
L1 ( R)
L2 ( S)
L3 ( T)
meas.current
Im ( 5A /1A)
1. ca p aci t or-
br a n ch
su p p ly-
vo l t age
Ub
me a s .
voltage
Um k l
P1
1 2 3 4 5 6
capacitor-
contactor 1-6
ala r m-
re l a y
Po wer Fa ctor C o n tro l l er
Pr o phi 6R
T 6, 3A
T 2A
T 2A
PE
K1
a b
Ub Um Im
L N L N k l
(L) (N) (L1)
L3
(N)
L2
k l a b P1 K1 K2 K3 K4 K5 K6
supply-
voltage
110...230V
meas-
voltage
meas.
current
alarm-
relay

Prophi®6R
5
Section 2 Installation and connection of the controller
The controller is designed to be incorporated into the front panel of a PFC-cabinet. It
requires a switchboard section of 138 x 138 mm to DIN 43700/ IEC 61554. The controller
is inserted from the front and is attached by means of the appended clamps. It may
be inserted only by qualified technicians and must be operated in accordance with the
specified safety regulations.
Before the Prophi-6R is connected up, all leads and cables must be checked to ensure that
no current is flowing through them and the current converter must be short-circuited.
Care should be taken to ensure that the measuring voltage and current are in the correct
phase position. The measuring-current circuit must be wired with copper leads of
2
2.5mm . The connection should be set up as shown in Fig. 3. The specified safety
regulations must be observed.
The measuring voltage may lie in the range from 30 - 525 VAC and can be connected
between L - N ( default ) or between L - L (programming of phase correction needed)
The supply voltage is 110...230 VAC +/- 15% and can be connected between L - N or
L -L (depending of the grid).
The coil voltage for the capacitor contactors and the measuring voltage
must be drawn from the same phase conductor, as only the measuring
voltage is monitored. (Protection against direct reconnection of the
capacitor contactors in the event of momentary single-phase power
failure)
Fig. 3: Connection plan
- 5 -
L1 (R)
L2 (S)
L3 (T)
N
meas.current
Im (5A/1A)
1. capacitor
branc
h
supply
voltage
Vb
meas.
voltage
Vm k l
P1
1 2 3 4 5 6
capacitor
co ntactor s 1-6
alarm
relay
power factor controller
Prophi-6R
T 6,3 A
T 2A
T 2A
PE
K1
a b
Ub Um Im
(L) (N) L1 N k l
(L3) (L2)
Power feed Load side
!

Prophi®6R
6
2.1 Current measurement
When installing the current converter, care should be taken to ensure that the load
current flows through it. The outputs of the compensation network must be installed
behind the current converter (in the direction of current flow). If the device is connected
up via sum-current converters, the overall conversion ratio is entered.
2.2 Programming of phase-correction - e.g. connection directly L-L (400V)
Adjustment of phase-correction between voltage and current in the meas. system is done
in expert mode 1 (page 17)
Example :
Meas.current: L1
Meas. Voltage L3-L2
Phase U/I [ 90°]
- 6 -
L1 (R)
L2 (S)
L3 (T)
N
Meas.current
supply-
voltage
Vb
meas. -
voltage
L2-L3 k l
T 2A
T 2A
PE
Ub Um Im
(L) (N) L3 L2 k l
using meas. current meas. voltage phase-angle
Preset: L1 L1 - N 0°
L1 L1 - L2 30°
L1 (k<->l) L2 - N 60°
s. example L1 L3 - L2 90°
L1 L3 - N 120°
L1 L3 - L1 150°
L1 (k<->l) L1 - N 180°
L1 (k<->l) L1 - L2 210°
L1 L2 - N 240°
L1 L2 - L3 270°
L1 (k<->l) L3 - N 300°
L1 (k<->l) L3 - L1 330°
kK k K
lL l L
Feed 1 Feed 2
K L K L
Measurement via sum current converter
Current
measurement
Prophi-6R
k l
k l
Example:
C.converter 1: 1000/5A
C.converter 2: 1000/5A
Sum-current converter: 5A+5A/5A
C.converter ratio is: 2000/5A

Prophi®6R
7
cos 0.76 IND F
j
cos 1.00 IND
cos 1.00 IND
300 kvar 50%
j
j
2.3 Alarm output / error messages
The alarm contact is closed in normal operation and opens in the event of a fault. The
relevant fault is simultaneously shown on the display in plain text (alternating with the
standard display in automatic operation)
UNDER-COMPENSATED Display and relay output
missing reactive power
OVER-COMPENSATED Display and relay output
OVERCURRENT Display and relay output
MEASURING VOLTAGE ? Display and relay output
OVERTEMPERATURE Display and relay output
OVERVOLTAGE Display and relay output
UNDERVOLTAGE Display and relay output
Section 3 Operating modes
When the operating voltage is switched on, the device briefly displays its designation and
software version, then changes to its normal operating status (automatic operation). The
active cos-phi value is always displayed in the upper line and the currently connected
capacitors are shown as symbols in the lower line (operating display).
HARMONICS Display and relay output
Additionally several messages for different operation states are generated. An individual
adjustment resp. suppression of particular messages is possible in expert mode 2. During
suppression, the indication of the message in the display, a possible release via alarm-
relays and effects on the controlling process will be prevented.
- 7 -
The power values of the individual capacitors are monitored constantly. If a capacitor is
defective or if the deviation from the rated power is excessive, the
corresponding capacitor is displayed inversely.
Display of active power-line cos phi Display of “Fan”-option
Active capacitor
branches
Control direction
(here connected-in)
Supply display (for
4-quadrant operation)
The control direction is symbolized
by a closed arrow
The connecting-in arrow is always
located after the maximum possible
number of stages (end stop)
An open arrow indicates that the
required blocking time (discharge
time) is running before an impending
switching step
A double arrow symbolizes fast
switching of several branches
Connecting-in
Connecting-out
By pressing the cursor
buttons, the display of
capacitor stages can be
changed:
Display of activated
stages in kvar and in
percent of total output
of PFC system
Display of activated
stages as bar-graph
display in percent of
total output of PFC-
system

Prophi®6R
8
Section 4 Automatic operation - display of grid parameters
The device is set to automatic operation as standard (not AUTO-INIT). Capacitor stages
are then automatically connected in or out in order to reach the target power factor. This
happens when the required reactive power exceeds the value of the smallest capacitor
stage.
In automatic operation, various network parameters can be displayed by repeatedly
pressing the "ENTER” key:
Action Display
ENTER 1 LINE VOLTAGE in V /%
ENTER 2 APPARENT CURRENT in A /%
ENTER 3 REACTIVE POWER in kvar /%
ENTER 4 ACTIVE POWER in kW /%
ENTER 5 APPARENT POWER in kVA /%
ENTER 6 DIFF. kVAR TO TARGET COS
ENTER 7 FREQUENCY in Hz
ENTER 8 TEMPERATURE in °C / °F
ENTER 9 HARMONICS (3.-19) V / %, I / %
Selection via arrow-keys
ENTER 10 THD-V, THD-I in %
ENTER 12 ENERGY in kWh, kvarh, (+/-)
reset in: Service / max.value reset
ENTER Software version
ENTER Return to: 1
The power value specifies the total power (3-phase) assuming symmetrical load. If no
key is pressed for 60 seconds, the display automatically returns to the operating status!
Automatic oper.
to display operation to programming to manual operation to value buffer to special functions
Programming Manual operation Service Expert mode
Repeated pressing of the "Operating Mode” key takes the user to the various menus in
sequence: Automatic operation - Programming - Manual (manual operation)-
Service - Expert mode and back.
- 8 -
1 LINE VOLTAGE
230.1 V

Prophi®6R
9
Section 5 Programming
Pressing the "Operating mode” key once takes the user from automatic operation to
Programming mode. Parameter 1 ( I-CONVERTER) is reached by pressing "ENTER”.
The upper display always shows the parameter and the lower one the set value. The
values are changed by pressing the é / ê keys. Subsequent pressing of the "ENTER” key
stores the value and takes the user to the next parameter.
Description of the parameters: See the next page
To quit programming mode in any step, press the "Operating mode” key.
é
é / ê” buttons,confirmation with ENTER)
the automatic test-run is performed.
3 test-runs will be performed during which all stages are being switched on and off. All
necessary parameters are collected, evaluated and stored. Under certain circumstances
3 additional test-runs may be required for a proper initialization.
After successful finalization of AUTO-INIT the controller will switch into normal operation.
In case of recognition of any discrepancies (plausibility) or of inaccurate connection, the
detected error will be displayed in plain text after finalization of AUTO-INIT and can be
eliminated. (see possible error messages at the end of the manual). AUTO-INIT may be
repeated then.
NOTE: If the Prophi-6R has been put into operation successfully by AUTO-INIT with all
values unknown, some values will be shown as “????” and this can not be changed. If a
new programming is required, a reset is needed before: Programming/Basic settings
[YES]
5.1. Automatic initialization (not usable in case of external voltage converter)
With the automatic initialization the device will automatically recognize the parameters of
the PFC-system. It also serves as plausibility check and storage of these parameters - the
user only has to make very little or even no adjustments.
Start of the initialization process is done from the menu point “PROGRAMMING” by
pressing the button “ ”
AUTO-INIT [YES] to be confirmed with pressing the ENTER button.
If the values of the current transformer OR the value of the first stage of the PFC-system
are known, they should be entered here. This later enables a display of all values of the
net in the correct electrical term. If no value is programmed (selection: unknown), values
of current and output can later only be indicated as percent.
After entering of the a.m. values (selection via “
- 9 -
1 AUTO - INIT
[ YES ]
1 CURRENT TRANS.
[UNKNOWN]
TEST 3 76 kvarTEST 1 69 kvar

Prophi®6R
10
5.2. Manual programming (program menu)
LANGUAGE SELECTION: This selects the language of the operating menu
(German, English, Spanish, Portuguese, French, RU, Cz, NL, PL, TR)
1 I-CONVERTER PRIM: [ 5...13000]A
This selects the primary current of the current converter. Adjustment is
via the é / ê keys. Save and continue with ENTER
2 I-CONVERTER SEC: [ 5 or 1]A
This sets the secondary current of the current converter
Selection via é / ê. Save and continue with ENTER
3 END STOPP: [ 6/7 ] switching to 7.stage in expert-mode 2
By setting the end stopp, the number of active capacitor branches is
matched to the respective capacitor bank. This is done via the é / ê
keys. The visible symbols of the capacitors correspond to the connected
outputs. The maximum possible number of capacitor branches is pre-
set at the works (6 branches). Save and continue with ENTER
4 CONTROL SERIES: [ 1...20 + E ]
The ratio of the capacitor branch power determines the control series,
the power of the first capacitor always being assigned the value 1. The
control series required for the compensation network is again selected
via the é/ê keys. If the required control series should exceptionally not
be present (Annex 1), the user may define a special one (control series
"E”).More on this point in the control-series editor in Annex 1.
5 CONTROL PRINCIPLE: The control preference may be selected here:
SEQUENTIAL connection
LOOP connection
INTELLIGENT loop connection (default setting)
COMBINED CHOKE
See Section 9 for an explanation of the various control modes.
Selection with é / ê keys. Save and continue with ENTER
6 POWER 1. STAGE: [ 0.01 ... 255.99 ] kvar
To determine the controller's response sensitivity, the dimensions of
the network's smallest capacitor (stage 1) must be known. They are
entered in two steps in kvar. The integral kvar values (before the
comma) are initially selected via the é / ê keys and saved with
ENTER. The positions after the comma are then selected, again via the
é / ê keys. If the response sensitivity is being undercut, a warning will
occur ( indication of “!” in the display )
Save and continue with ENTER
7 TARGET COS PHI: [ 0.1 ind ... 0.1 cap ]
By setting the target cos phi, the power factor to be attained via the PF
correction is defined. It is also set via the é / ê keys.
- 10 -

Prophi®6R
11
- 11 -
8 MEASURING VOLTAGE [ 30 ... 525]V
Programming the measuring voltage of the system.
The values programmed here always refer to the voltage at the clamps !
The voltage is selected via the é /ê keys. Save and continue with ENTER.
9 V - CONVERTER RATIO [ NO / 230V ... 380kV ]
When a measuring-voltage converter (e.g. for HV- measurement) is used, its
conversion ratio should be programmed here.
(Input of prim.voltage is here, sec. voltage is automatically from item 8)
Selection via the é /ê keys. Save and continue with ENTER.
10 CONNECTING TIME
This refers to the time between connecting the capacitors to increase the
momentary network capacitance. It should be noted that in practical operation the
real connection time is affected by the discharge time (locking time).
Setting range: 1 sec. ... 20 min. (long time for HV- networks)
Default setting: 40 sec.
Selection is performed via the é /ê keys. Continue with ENTER
11 DISCONNECTING TIME
This refers to the time between disconnecting the capacitors to reduce the
momentary network capacitance.
Setting range: 1 sec. ... 20 min. (long time for HV- networks)
Default setting: 40 sec.
Selection is performed via the é /ê keys. Continue with ENTER
12 DISCHARGE TIME
This is the time for which an individual output is blocked between connecting and
disconnecting. This blocking time has priority over connecting and disconnecting
times. It depends on the capacitor discharge rating and thus is specified by the
compensation network. The discharge time of a conventional network without
additional fast-discharge resistors or chokes should be set to no less than 40
seconds.
Setting range: 1 sec ...20 min. Default setting: 60 sec.
Selection is performed via the é /ê keys. Continue with ENTER
L1 (R) L1 (R)
L2 (S) L2 (S)
L3 (T) L3 ( T)
N
Meas. Current
Im (X/1A)
Operating
voltage
Ub
Meas.
Voltage
Um
T 2A
T 2A
PE
Ub UmIm
High voltage Low voltage
20 kV / 400 V
20000
100

Prophi®6R
12
13 ALARM TEMP [ 50...85]°C
The alarm temperature programmed here is the temperature at which the
capacitor stages are disconnected in steps. The controller’s alarm relay
responds after ten minutes. At the same time the display shows the cause of the
alarm (over-temperature). If the temperature drops again, the required
branches are automatically re-connected in steps.
The selection is performed with the é /ê keys. Save and continue with ENTER.
14 MESSAGE RELAY
this item appears if in ExpertMode2 the „alarm-relay“ is set as „message-relay“
The message relay can be programmed for one of the following options as
required:
"Fan”: Relay switches the external cabinet fan.
(Default) The switching threshold can be programmed under point 15.
Display: "F”
"Supply": Message when active power is supplied. Display: "S”
"Undercurrent” This message appears whenever the measuring current is not
reached. Display: "U” The signal is generated when the value drops
below the response sensitivity of the controller.
"Harmonics”: This message appears when the limit of the total harmonic distortion
THD-V is exceeded. This value can be set under "27 Harmonics” in%
15 FAN TEMP* [15...70]°C
Input of the switching threshold for the fan.
BASIC SETTING: [ NO ] ( YES / NO )
When the selection is made with YES and confirmed with ENTER, all parameters
are reset to the basic setting made by the PFC-system manufacturer.
(Optimal network values when the controller was supplied with a complete PFC-
system). If the controller is supplied from the works, this point corresponds to
the default setting. CAUTION: All user settings are lost!
5.3 Programming lock (active / inactive / automatic after 24 h)
The device is equipped with a programming lock to ensure protection from unauthorized
or inadvertent changes to the system parameters. The lock can be activated in expert
mode. If the lock is active, all parameters can be checked but not changed.
* Only active if option 'Fan' is selected
27 HARMONICS (harmonic limit) [7]% (0.5 ... 25,5)%
A limit for the total harmonic distortion THD-V (in%) can be entered here. When
this threshold is exceeded, a message is given. THD-V is the ratio of the
geometric sum of the uneven harmonics to the fundamental. A warning is
always shown in the display; an output via message relay only takes place
when this was selected in point 14.
- 12 -

Prophi®6R
13
Section 6 Manual operation (initial operation, maintenance, service)
Programming of fixed stages
In manual operation, capacitor branches can be connected/disconnected in the set
control series and switching time - irrespective of prevailing power-line conditions.
The starting condition is STOPP (no stages connected). Connections are made by
pressing the é key. Pressing ê initially leads back to STOPP mode. Repeated pressing of
ê leads to the disconnection of stages. The active operating status and active power
factor are always shown on the display (self-explanatory).
Pressing ENTER takes the user to the menu point "Programming of fixed stages”.
In the normal case, all stages are programmed for automatic operation (default setting).
In special cases, all controller outputs (C1-C6) may be permanently defined in succession
(continued switching via ENTER) for the following statuses:
AUTO: Automatic (normal) operation
The relevant output is marked by a capacitor symbol.
FIXED: The output is continuously connected, e.g. for fixed PFC. The output is
marked by an underlined capacitor symbol.
OFF: The output is continuously disconnected - e.g. for temporarily disconnecting a
defective capacitor. The capacitor symbol for this output is faded out. Underlining
appears.
The active stage is blinking. The required status is set via é /ê. By pressing ENTER, the
user saves this step and moves to the next stage.
The programmed statuses for the outputs also remain visible on the display in automatic
operation.
After the required settings have been made, pressing the "Operating Mode” key takes the
user to the next menu ("Service”) or further to "Automatic Operation”.
AUTO OFF FIX (Currently selected stage blinks)
Setting of fixed stages
Manual operation
- 13 -
STOP 0.99 CAPCAP ON 0.97 IND
C 6 - [FIXED]

Prophi®6R
14
- 14 -
Section 7 Service menu
The service menu is reached by the operating-mode key.
The stored maximum values of the network parameters can be displayed here as well as
the number of switching operations of the individual capacitors and their operating time.
The desired stages [in square brackets] can be selected via the arrow keys.
In addition, a fault memory is available, in which the last fault states of the system are
stored with fault code and in plain text. (This allows, for example, capturing short lived
events of overtemperature or overvoltage)
Action Display
ENTER 1 min/max. VOLTAGE in V
ENTER 2 max. REACTIVE POWER in kvar
ENTER 3 max. ACTIVE POWER in kW
ENTER 4 max. APPARENT POWER in kVA
ENTER 5 max. TEMPERATURE in °C / °F
ENTER 6 max. THD - V / THD - I in %
ENTER 7 RESET the maximum and energy values
ENTER 8 SWITCHING OPERATIONS C [1] - ...
+/- to C [6]
ENTER 9 OPERATING TIME C [1] - ... in h
+/- to C [6]
ENTER ERROR MEMORY E [1] - .... in plaintext
ENTER ERROR MEMORY RESET
ENTER TEST RUN
ENTER C-POWER (only after a test-run or AUTO-INIT)
ENTER Back to 1
TEST-RUN
This menu point allows the user to check the settings of the PFC controller. After activation
of the test run, the controller switches each stage on and off successively and calculates
the output of the capacitors connected (this procedure is done three times to eliminate
possible errors). The values calculated are stored and can be retrieved in the following
menu item (C-POWER). At the same time, a plausibility check is conducted with the values
programmed.
Any discrepancies found are evaluated and displayed in plain text. The following errors
can be displayed:
- No measuring voltage present
- Measuring voltage too high - check programming
- Measuring voltage too low - check programming
- No measuring current? - Short circuit link in current transformer?
- Phase angle current transformer? k/l or phase transposed ?
- Current
transformer ratio / 1. Step power wrong ?
- Control series? - check programming
- End stop? - check programming
- Capacitor defect or wrong power input
Note: The results displayed are messages intended to help the user trace the cause of the
error. Final evaluation remains the responsibility of the user. Under complicated (high load
fluctuations) grid conditions, 100% error recognition cannot be guaranteed.

Prophi®6R
15
- 15 -
Section 8 Expert mode 1 and 2
The expert mode is meant for the adjustment of values which normally should not be
changed. As a protection against mal-operation this level has an access code branching
out in Expert mode 1 or 2.
Password: Expert mode 1: “ 6343” Expert mode 2: “2244”
8.1. Expert mode 1
2 BASIC SETTING NEW [NO] (available: NO/YES)
Storage of active programming as a new basic setting (usually performed by the
PFC-system manufacturer). Caution: The original values are overwritten in the
process!
3 SWITCHING OPERATIONS RESET [NO] (available: NO/YES)
The stored switching operations of all capacitor stages are reset to zero. Caution: No
information is then available about the switching frequency of the stages and thus
the status of the network. (Reset of individual stages in Expert-mode 2 )
4 OPERATING TIME RESET [NO] (available: NO/YES)
The stored operating times of all outputs are set to zero.
(Reset of individual stages in Expert-mode 2 )
5 INTEGRATION TIME [1] s (1...255 sec.)
The integration time (the time required to form the average values of a
measurement) can be changed for special applications here.
6 SWITCHING POWER max [100] kvar (multiples of the smallest stage)
This factor specifies the maximum power which may be switched in one switching
step. It can be used to control the intelligent control system, which switches several
stages as a function of the power-factor requirement.
7 SWITCH.TRIGGER [66]% (30...100%)
Threshold for switching on of next stage. It should not be changed in the normal case!
8 OPERATING LOCK [NO] (NO / YES / 24H)
24H means, that it will be locked automatically after 24 hours
9 SWITCHING OPERATIONS WARNING [50000] (1000 ... 255000)
After an output has performed this number of switching operations, a warning
message is displayed. ( Abrasion of capacitor contactors and capacitors)
10 FAST DISCHARGE [NO] (NO or X for the desired stages)
If only some stages of a network are equipped with fast discharge equipment, those
stages can here be indicated with X. In this case, the desired discharge time for these
stages can be specified in the next menu point. Otherwise, menu point 11 is omitted.
11 DISCHARGE TIME [1] s (1s ..programmed normal discharge time)
Only available when fast discharge is programmed. The specified discharge time is
then also included in the normal display.

Prophi®6R
16
12 PHASE I [ 0°]
[L1] - L1 - N ] Adjustment of current phase position
13 PHASE V [ 0°]
L1 - [L1 - N ] Adjustment of voltage phase position
Phase correction between voltage and current in the measuring system. (refer p.6)
14 C-TEST [YES] ( YES / NO)
The power of the particular capacitor stage is calculated during each switching
operation and compared with the stage output of the capacitor. If the result varies
from the nominal value, an error message is generated. This test can be stopped
here.
15 C-FAULT [40] % (10...75 %)
The deviation from the rated value of the capacitor, for which a fault message is
generated, can be specified here (see point 14)
16 TEST ATTEMPTS [5] ( 1...9)
When at least this number of successive measurements has resulted in a fault in the
capacitor power, a C-fault message is output.
17 OUTPUT 1. STEP [0...255] (0...2550)
The range for entering the stage output can be increased to [0...2550] here, (e.g. for
medium voltage measurement)
18 CONTROL [3] PHASE ( 3 / 1 )
The measuring system of the controller is generally based on single-phase
measurement. For all standard settings (three-phase), the measurement is
converted and all outputs displayed as three-phase values (symmetry in grid
assumed). In the single-phase setting, display and control apply only to the single-
phase value measured (application: single-phase correction in asymmetrical grids)
19 DISPLAY cos
j / tan j
Switched over between cosinus or tangens
j in the display
- 16 -

Prophi®6R
17
- 17 -
8.2. Expert mode 2 ( Password: 2244)
The additional 2nd expert mode includes all messages for operation, warning and error
which are displayed by the controller. Here they may be deactivated separately. When
deactivated, the indication of the message in the display as well as possible activation of
the relay or effects on the control behavior are suppressed (detailed list of all messages s.
menu plan last page).
Also, the alarm relay may be programmed here as 7.stage or as message relay.
Switching operations/operation time of the capacitors can be set back separately.
EXPERT MODE 2 ENTER
2 ALARM RELAY (ERROR) (Error / 7. stage / Message relay)
Selection whether the alarm relay should be used for error message or as
additional 7th stage or as message relay for the standard controller.
Activation of particular operation, warning and error messages (s. above)
Example
3 ALARM DELAY TIME [10] min. (1...255min.)
Time after which the alarm relay will respond
4 UNDERVOLTAGE [50] % (20 ...100 %)
meas. voltage below this threshold will switch OFF all
stages at the same time
5 OVERVOLTAGE [115] % (105 ...140 %)
meas. voltage above this threshold will switch OFF
the stages step by step
If measure voltage returns to the permissible range, stages
will stepwise switch ON again.
6 FREQUENCY [40...80 Hz] (50Hz / 60Hz)
Measurement by the controller is done automatically in grids of 40 … 80 Hz.
In grids with extremely poor voltage quality it is recommend to select a fix
frequency (50 or 60 Hz) to avoid measuring errors due to voltage sags.
7 SWITCH. OPERATIONS C 1 RESET [NO] (YES/NO)
to
C 6 RESET [NO] (YES/NO)
Reset of switching operations of particular capacitors possible,
e.g. after replacement of particular capacitors or contactors
8 OPERATION TIME C 1 RESET [NO] (YES/NO)
to
C 6 RESET [NO] (YES/NO)
Reset of operation time of particular capacitors possible,
e.g. after replacement of particular capacitors
OVER-COMPENSATED
DISPLAY [YES]

Prophi®6R
18
- 18 -
Section 9 Control principle
The control response of the Prophi-6R can be selected in programming mode. In principle,
the controller has four different control modes:
1. Sequential connection
In sequential connection, the required capacitor stages are successively connected
and disconnected in stages (last in - first out). The ranking of each step always
corresponds to the power of the smallest stage.
Advantage: Exact definition of the next capacitor to be connected in each case
Disadvantage: Long settling time, high switching frequency of the small stages
In order to shorten the settling time, the BR6000 switches several stages
simultaneously for a large power-factor requirement. This applies to all
control types. The maximum dimensions of the simultaneously switching
branches can be changed in expert mode. If the value of the smallest stage
is pre-selected, the conventional sequential connection is obtained.
2. Loop connection
In this variant, the controller operates in loop mode (first in - first out) which
minimizes the wear on the capacitor bank, i.e. where stages are of equivalent
dimensions, the stage which was disconnected for the longest period of time is
always connected next.
Advantage: Balanced utilization of equivalent stages and thus an increased
operating life of the capacitor bank.
Disadvantage: This mode can only be used in control series with groups of the same
stage power and long settling time, as every switching step corresponds to the value
of the smallest stage.
3. Intelligent loop connection (default setting )
The intelligent control principle combines the advantages of the network-sparing
loop connection (first in - first out) with a much faster settling time, even for large
load skips, and reaches this goal with the fewest possible switching operations of the
capacitor stages. The optimized time response is achieved by the simultaneous
switching of several or larger capacitor groups as a function of the missing power
factor in the power line. Both the number of real switching frequencies of the
capacitors as well as the turn-on times of the branches are considered.
Advantage: Reaches the target cos phi in a fast-optimized settling time with a low
switching frequency of the capacitors.
4. Combined de-tuning (special case for combined de-tuned banks)
Within a combined de-tuned application, 2 adjoining equal steps are switched with
just one joint choke. This pairwise de-tuning requires an appropriate closed control
series (i.e. 1:1:1:1..., 1:1:2:2..., 1:1:2:2:4:4... or similar)
The condition for the switching behavior is defined in such a way that the number of
activated odd steps is always greater than or equal to the number of activated even
steps. The controller complies with the requirements of the control regime while
largely conforming to the intelligent switching behavior.

Prophi®6R
19
- 19 -
Section 10 Interface (not applicable)
Section 11 Initial operation
The controller must have been installed before being set up and operated.
All network-specific parameters are fully programmed as described in section 5
(Programming) by being entered in sequence and stored. The controller is then set to
automatic operation with the operating mode key. It is now ready for operation.
Section 12 Maintenance and warranty
The controller should need no maintenance if the operating conditions are observed.
However, it is recommended that a functional check of the controller be performed in
conjunction with the regular checking of the capacitor bank. In the event of any
interventions in the controller during the warranty period, all warranty claims lapse.

Prophi®6R
20
- 20 -
Fault
At target cos phi=1 and inductive load,
switch-off or connection of capacitor in
the corrected line
Supply / Drawing mismatched
Wrong line cos phi is displayed
Display:"UNDER CURRENT”
Display: "OVERCURRENT”
Alarm relay: after 10 min.
Display: "UNDERCOMPENSATED”
Alarm relay: after 10 min.
Display: "OVERCOMPENSATED”
Alarm relay: after 10 min.
Display: "MEASUREMENT VOLTAGE ???”
Alarm relay: after 10 min.
Display: "OVERTEMPERATURE”
Alarm relay: after 10 min.
Stages are disconnected for an inductive
line or connected for a capacitive line
The controller does not connect all
stages, or cos phi does not change at the
last stages
In automatic operation, individual stages
are not connected or disconnected
In strongly asymmetrically loaded lines,
differences may occur between control
response and power-factor
measurement, as the power factor is
measured in single phase.
No operating voltage
Check / Solution
Check terminals of the measuring voltage and
current (l and k)!
Check phase position
See above
Current in measuring range?
Line interruption?
Wrong current-converter factor?
Current transformer short-circuited?
Check current-converter ratio
Go through measuring current range
Check connection and phase position!
All stages connected - target cos phi not
reached: compensation network sufficiently
dimensioned?
Check connection and phase position!
Capacitive grid, although all stages
disconnected
No measurement voltage!
Cabinet temperature too high: Outputs are
switched off in stages irrespective of power-line
conditions
If a target cos phi is set which deviates from 1
despite an inductive line load, the display <
(disconnect stages) may light up. The arrows
indicate the control direction and not the line
conditions.
Check END STOPP !
Check whether individual stages are
programmed as fixed stages or OFF in the
"Manual operation / Fixed stages” menu!
Line measurements allow the most favorable
phase for measuring the power factor to be
determined. The current converter is set
accordingly for the measuring current.
Note: No display, alarm relay is activated
(open)
Section 13 Troubleshooting
Table of contents
Other janitza Controllers manuals
Popular Controllers manuals by other brands

Eaton
Eaton Cutler-Hammer S801TR Quick setup guide

Festo
Festo DFPD-Series operating instructions

Chauvet
Chauvet DMX-2X user guide

Honeywell
Honeywell ScanDome HTX-5000 instruction manual

Novus
Novus Villa NVE-MV107WIFI installation manual

Grundfos
Grundfos LC 232 Safety instructions and other important information

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-R Series user manual

ENERVEX
ENERVEX ADC150 Product information

Jung
Jung FA 10 EB operating instructions

Lumia
Lumia Max-E Series user manual

Böker
Böker Druck PV624 instruction manual

MAGUIRE
MAGUIRE Weigh Scale Blender 4088 Installation operation & maintenance