EST SIGA-CRR Assembly instructions

SIGA-CRR Polarity Reversal Relay Module
Installation Sheet
Description
The SIGA-CRR Polarity Reversal Relay Module is an
addressable device that is used to power and activate the
audible sounder in Signature audible detector bases.
The module can support a 2 A load of bases. Upon command
from the loop controller, the SIGA-CRR module relay transfers,
reversing the polarity of its 24 VDC output.
The module requires one address on the signaling line circuit
(SLC). Addresses are assigned electronically. There are no
address switches.
Diagnostic LEDs provide visible indication of the state of the
module through the cover plate:
• Normal: Green LED flashes
• Alarm/active: Red LED flashes
Personality code
The module requires the loop controller to download the
personality code that determines how the module operates.
Use the personality codes described below to configure the
SIGA-CRR. See Table 1 for listing information.
Personality code 8: Signal - dry contact output. Configures
the module as a dry relay contact to control external
appliances (door closers, fans, dampers) or equipment
shutdown.
Table 1: Personality code listing information
Code Description UL 864 CAN/ULC-
S527 EN 54-18
8 Signal - dry contact output Yes Yes Yes
Installation
Notes
• The module is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should not
be disassembled.
• This module does not operate without electrical power. As
fires frequently cause power interruption, discuss further
safeguards with the local fire protection specialist.
Install in accordance with all applicable local codes and
standards and the local authority having jurisdiction.
To install the module:
1. Wire in accordance with “Wiring” on page 2.
2. Write the address assigned to the module on the label
provided, and then apply the label to the module. Remove
the serial number label from the module, and then attach it
to the project documentation.
3. Using the screw provided, mount the wall plate on the
module. See Figure 1 for mounting details.
4. Using the screws provided, mount the wall plate (with the
module attached) on one of the compatible electrical
boxes listed in “Specifications” on page 3.
© 2012 UTC Fire & Security. All rights reserved. 1 / 4 P/N 387336P-EN • REV 6.0 • ISS 29FEB12

Figure 1: Mounting the CRR module
(
1
)
(2) (3)
(4)
(4)
(5)
(1) Compatible electrical box
(2) Module
(3) Wall plate, white (single-gang)
(4) #6-32 × 5/8 machine screw
(5) #4 × 1/2 self-tapping screw
Wiring
Wire in accordance with applicable requirements of the latest
editions of the local codes and standards and the local
authority having jurisdiction.
Note: When stripping wire ends, exposing more wire may
cause a ground fault or circuit malfunction on unsupervised
wiring; exposing less wire may result in a faulty connection.
Strip 1/4 in. (about 6 mm) from the ends of all wires that
connect to the terminal block of the module.
Notes
• Refer to the Signature loop controller installation sheet for
SLC wiring specifications.
• Each terminal on the module is limited to a single
conductor.
To wire the module:
1. Verify that all field wiring is free of opens, shorts, and
ground faults.
2. Make all wiring connections as shown in Figure 2.
Figure 2: Wiring diagram
+
++
+
(1) (2)
(3)(4)
(6)
(
5
)
(1) Auxiliary riser in (from power-limited, regulated power supply
listed for fire protective signaling)
(2) Auxiliary riser out (to next sounder base). Polarity reverses when
activated.
(3) Signaling line circuit (SLC) to next device
(4) Signaling line circuit (SLC) from previous device
(5) Power-limited and supervised
(6) Internal connections
Typical application
Figure 3 shows a typical application. Here, each detector
operates its sounder base. The SIGA-CRR is used to activate
all sounders, according to system programming rules. The CR
control relay is optional, and is used to disable or silence the
sounders.
2 / 4 P/N 387336P-EN • REV 6.0 • ISS 29FEB12

Figure 3: Typical application
AB4GAB4G
+
+
(3)
(1)
(5)
(2) (4)
(1) Signaling line circuit (SLC) from previous device
(2) SIGA-CR module
(3) Auxiliary riser in (24 VDC from regulated power supply listed for fire protective signaling)
(4) SIGA-CRR module
(5) Riser monitor module or equivalent supervisory circuit
Specifications
Operating voltage 15.20 to 19.95 VDC
Current
Standby
Activated
75 µA
75 µA
Ground fault impedance 10 kΩ
Contact rating (pilot duty) 24 VDC at 2 A
Circuit designation
Signaling line circuit
Class A, Style 6 or Class B, Style 4
Compatible bases SIGA-AB4, SIGA-AB4G
LPCB/CPD electrical box
Requirements
Minimum W × H × D
Plastic box with cover plate, no
gaps or unused holes
2.4 × 3.5 × 1.5 in. (60 × 85 ×
38 mm)
Compatible electrical boxes 2-1/2 in. (64 mm) deep single-gang
box;
4 in. square box, 1-1/2 in. (38 mm)
deep, with single-gang cover
Wire size 12 to 18 AWG (0.75 to 2.5 mm²)
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93%, noncondensing
Storage temperature range −4 to 140°F (−20 to 60°C)
Regulatory Information
Manufacturer Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
Year of manufacture The first two digits of the DATE MFG number
(located on the product identification label) are
the year of manufacture.
FCC compliance This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause
harmful interference, and (2) this device must
accept any interference received, including
interference that may cause undesired
operation.
North American
standards
CAN/ULC-S527, UL 864
European standards EN 54-18: 2005 Input/output devices
P/N 387336P-EN • REV 6.0 • ISS 29FEB12 3 / 4

Certification
CPD certificates 0832-CPD-1018
2002/96/EC (WEEE directive): Products
marked with this symbol cannot be disposed of
as unsorted municipal waste in the European
Union. For proper recycling, return this product
to your local supplier upon the purchase of
equivalent new equipment, or dispose of it at
designated collection points. For more
information, see: www.recyclethis.info.
Contact information
For contact information, see www.utcfireandsecurity.com.
4 / 4 P/N 387336P-EN • REV 6.0 • ISS 29FEB12
Other EST Control Unit manuals
Popular Control Unit manuals by other brands

Wilo
Wilo Stratos Smart IF module Installation and operating instructions

Penny + Giles
Penny + Giles EICT Installation and setup guide

barfield
barfield DC400 User instruction

Quectel
Quectel LTE Standard MMS Application note

Sun Microsystems
Sun Microsystems SFP+ installation guide

Monacor
Monacor PA-1120DMT Installation and operating instructions