ETI ENA3D User manual

1 / 9 ETI d.d., Obrezija 5, SI-1411 Izlake
http://www.etigroup.eu/products-services
3PH - ENERGY METER
TECHNICAL MANUAL OF INSTALLATION
ENA3D ENA3
INDEX
1 - BUTTONS AND INDICATION LEDs: ................................................................................2
2 - ELECTRICAL DIAGRAM FOR INSTALLATION:...............................................................2
3 - SET-UP MENU:...................................................................................................................3
4 - ENTER THE ALARMS MENU:...........................................................................................5
5 - MEASUREMENTS FUNCTIONS:.......................................................................................6
6 - TECHNICAL DATA: ............................................................................................................7
7 - TERMINAL CONNECTIONS: .............................................................................................8
8-DIMENSIONS:.....................................................................................................................9
REGISTERS MODBUS-RTU TABLE ON REQUEST
!!! IMPORTANT !!! READ THE INSTALLATION MANUAL BEFORE USE.
THE SAFETY OF THE PRODUCT IS STRICTLY RELATED TO ITS USE THAT HAS TO BE
DONE AS SPECIFIED BY THE MANIFACTURER.

2 / 9 ETI d.d., Obrezija 5, SI-1411 Izlake
http://www.etigroup.eu/products-services
1 - BUTTONS AND INDICATION LEDs:
1.1 Buttons:
- Measurements Menu
- Value Decrease
- Value Increase
- Confirm selection
1.2 Indication LEDs
V
- Voltage (True RMS)
A
- Current
Hz
- Frequency
Cos
- Cos
W
- True Power
VAr
- Volt-Amp Reactive
VA
- Volt-Amp Apparent
V% THD
- Total Harmonic Distortion Voltage %
A% THD
- Total Harmonic Distortion Current %
Wh
- Watt-hours
VArh
- Volt-Amp Reactive hours
IND
- Inductive Load
CAP
- Capacitive Load
TEMP
- Temperature (internal temperature sensor)
1-2-3
- Alarm Relay status
k
- Multiplier measure x1000
M
- Multiplier measure x1000000
2 - ELECTRICAL DIAGRAM FOR INSTALLATION:

3 / 9 ETI d.d., Obrezija 5, SI-1411 Izlake
http://www.etigroup.eu/products-services
144x144 - Wiring Diagram:
9 MOD - Wiring Diagram:
Q1 - The installer has to provide an external disconnection device; this breaker has to be easily reachable and identified as:
"disconnection device".
() -Without transformer . = 1
For higher supply voltage than the supported range, insert one transformer each Phase and set . with transformer ratio.
3 - SET-UP MENU:
3.1 ENTER THE BASIC SET-UP MENU:

4 / 9 ETI d.d., Obrezija 5, SI-1411 Izlake
http://www.etigroup.eu/products-services
a) Press button for 5 seconds.
b) The display will show
c) Press button to show the parameters value .
d) Press button to enter and change the parameter value.
e) Press button to increase or button to decrease value.
f) When the value is OK press button to return at Basic parameters.
g) Press or button to scroll the programmable parameters.
h) Proceed and program all parameters until the last .
i) After last parameter press again button to save all data, display will shows and exit the Basic set-up Menu.
All LEDs will light for a few seconds.
l) If the display shows , an error has happened and was not possible to save the data.
Therefore it will be necessary to program again all the parameters on the Basic set-up menu.
Basic Set-up Menu:
PAR.
NAME
DESCRIPTION
RANGE
DEFAULT
.
..
Current transformer ratio.
5 … 50000
5
.
. .
Voltage transformer ratio (ex. VLINE / VSET = 500 / 400 = 1.25)
0.40 … 100
1.00
. (1)
.
Power Reading Interval.
60s … 360s
90s
. (2)
.
Average time filter Value.
1 … 20
4
(1) - Parameter . adjusts the time window width for the integration of current and power maximum demand.
(2) - Parameter . allows to modify the stabilising effect that the Average function applies to all readings.
3.2 ENTER THE ADVANCED MENU:
a) Press the button for 5 seconds.
b) The display will show
c) Press both buttons for 2 seconds until the display shows
d) Press button to show .
e) Press button to enter and change the parameter value.
f) Press button to increase or button to decrease value.
g) When the value is OK press button to return at Advanced parameters.
h) Press or to scroll the programmable parameters.
i) Press button to increase or button to decrease the value.
l) Proceed and program all parameters until the last .
m) After last parameter press again button to save all data, display will shows and exit the Advance Menu.
All LEDs will flash for a few seconds.
n) If the display shows , an error has happened and was not possible to save the data.
Therefore it will be necessary to program again all the parameters on the Advance Menu.
Advance Set-up Menu:
PAR.
NAME
DESCRIPTION
RANGE
DEFAULT

5 / 9 ETI d.d., Obrezija 5, SI-1411 Izlake
http://www.etigroup.eu/products-services
.
-
Mains Connection
0 = Three-Phase
1 = Single-Phase
0 … 1
0
.
.
Voltage Reference for Measures (steps of 5)
L/L - Three-Phase
L/N - Single-Phase
220 … 440
400
.
..
Sense of CT current
1 = CT on L1 Direct
2 = CT on L1 Inverse
1 … 2
1
..
1 = CT on L2 Direct
2 = CT on L2 Inverse
..
1 = CT on L3 Direct
2 = CT on L3 Inverse
.
-
Frequency
1 = 50 HZ
2 = 60 HZ
1 … 2
1
.
.
Serial interface TTL
0 = Disable
1 … 99 = Enable
0 … 99
1*
.
-
Temperature scale
0 = °C
1 = °F
0 … 1
0
.
-
List of settable Alarms (view details on the next Alarms Menu)
.
-
Serial
Protocol
Type
0
Proprietary
9600 Bds
EVEN
1 Bit Stop
0 … 18
0
1
Modbus
19200 Bds
EVEN
1 Bit Stop
2
Modbus
9600 Bds
EVEN
1 Bit Stop
3
Modbus
4800 Bds
EVEN
1 Bit Stop
4
Modbus
2400 Bds
EVEN
1 Bit Stop
5
Modbus
1200 Bds
EVEN
1 Bit Stop
6
Modbus
19200 Bds
ODD
1 Bit Stop
7
Modbus
9600 Bds
ODD
1 Bit Stop
8
Modbus
4800 Bds
ODD
1 Bit Stop
9
Modbus
2400 Bds
ODD
1 Bit Stop
10
Modbus
1200 Bds
ODD
1 Bit Stop
11
Modbus
19200 Bds
NONE
1 Bit Stop
12
Modbus
9600 Bds
NONE
1 Bit Stop
13
Modbus
4800 Bds
NONE
1 Bit Stop
14
Modbus
2400 Bds
NONE
1 Bit Stop
15
Modbus
1200 Bds
NONE
1 Bit Stop
16
Proprietary
9600 Bds
NONE
1 Bit Stop
17
Proprietary
4800 Bds
NONE
1 Bit Stop
18
Proprietary
9600 Bds
ODD
1 Bit Stop
*The values 1 to 99 indicate the device number when the units are connect on a serial interface.
3.3 TO SET DEFAULT PARAMETERS:
- In parameter, press all buttons together for 5 seconds, on display will shows
Now the device will restart.
ATTENTION: All settings made on the device will be lost and all steps will be restored to default setting.
4 - ENTER THE ALARMS MENU:
a) Press button for 5 seconds.
b) The display will show
c) Press both buttons for 2 seconds until the display shows
d) Press button several time until the display shows .
e) Press button to enter in list of settable Alarms, display shows .
f) Press or buttons to scroll Alarms that can be set: . >. >. > . >. >. >.
g) Press button to display the values set for the selected Alarm.
h) The display shows .
i) Press or buttons to scroll Alarm values that can be set: . >. .>. . >. > (only for .)
l) Press button to enter and change the desired Alarm values.

6 / 9 ETI d.d., Obrezija 5, SI-1411 Izlake
http://www.etigroup.eu/products-services
m) Press button to increase or button to decrease value.
n) When the value is OK press button to save value and return at Alarm values.
o) After setting all the desired Alarm values press button to return at list of settable Alarms.
p) After setting all the desired settable Alarms press button to return at Advanced parameters.
q) Press button to get another Advanced parameter.
r) After last parameter press again button to save all data, display will shows and exit the Advance Menu.
All LEDs will flash for a few seconds.
s) If the display shows , an error has happened and was not possible to save the data.
Therefore it will be necessary to program again all the parameters on the Advance Menu.
Alarms Set-up:
PAR.
Description
Range Enable
. (default)
Delay Time
. .(default)
Value time
. .(default)
Alarm Relay Set
.(default)
Select Phase
(default)
.
Too High Voltage
0 = disable
110 ... 150 (110)
1 ... 240 (10)
Min / Sec
(Sec)
0 = disable
1-2-3 (1)
-
.
Too Low Voltage
0 = disable
80 ... 95 (95)
1 … 240 (10)
Min / Sec
(Sec)
0 = disable
1-2-3 (1)
-
.
Too High Current
50 ... 500000
(100)
1 … 240 (10)
Min / Sec
(Sec)
0 = disable
1-2-3 (1)
0 = ALL (0)
1 = L1
2 = L2
3 = L3
.
Over Temperature
0 = disable
30° ... 60° (60°)
1 … 240 (10)
Min / Sec
(Sec)
0 = disable
1-2-3 (1)
-
.
THD % I
0 = disable
5 ... 200 (120)
1 … 240 (10)
Min / Sec
(Sec)
0 = disable
1-2-3 (1)
-
.
Low Cos
0 = disable
0.5 ... 0.95 (0.90)
1 … 240 (10)
Min / Sec
(Sec)
0 = disable
1-2-3 (1)
-
.
Discard Freq. Hz
0 = disable
±1 ... ±5 (5)
1 … 240 (10)
Min / Sec
(Sec)
0 = disable
1-2-3 (1)
-
Alarms Fixed:
Display Code
Description
Intervention Parameter
.
Set-up parameters error
The set-up parameters read by the EEPROM aren’t correct.
To restore is necessary the re-set made by the user.
.
Adjustment/setting
parameters error
The setting parameters read by the EEPROM aren't correct.
The device operates with the default parameters.
There could be error in the calculated measures.
The user can’t do the setting.
It is necessary to return the unit to the manufacturer.
.
Parameters error
The setting parameters read by the EEPROM aren’t correct
(set Cos, sensitivity, operation mode).
To reset is necessary to contact the manufacturer.
.
Cancellation
EPROM error
Only in the testing phase you can see if the EEPROM doesn’t operates correctly.
Is necessary to contact the manufacturer.
Pressing the button the visual alarm can temporarily be cancelled, and the readings can be shown to verify the causes
of the alarms.
5 - MEASUREMENTS FUNCTIONS:
a) If the load are inductive IND or capacitive CAP.

7 / 9 ETI d.d., Obrezija 5, SI-1411 Izlake
http://www.etigroup.eu/products-services
On Cosvalue indication, if the decimal point on last digit (from left) is flashing, this is because the system working as
Generator or the sense of current is inverted (verify correct CT connection or modify parameter .).
b) Press button to scroll on available measurements indicated by the related LED.
c) If a kis on the value must be multiplied x1000, instead If a Mis on the value must be multiplied x1000000.
d) Press both buttons to scroll measure automatically every 3s, press button for stop scroll.
e) While viewing one of these measures: V- A - Cos- W- VAr - VA - %THDV - %THDI if press button for 1s, all
displays and shows the average value measured.
f) While viewing one of these measures: V- A- %THDV - %THDI - TEMP if press both buttons for 1s, flashes
the relative Led and display shows the maximum value measured.
g) While select Wh measure, the display shows the value for each Phases if . set in Three-Phase mode or one Phase if
. set in Single-Phase mode, press it shows the total Wh for 5s.
Press both buttons for 15s to reset all Wh values.
h) While select VArh measure, the display shows the value for each Phases if . set in Three-Phase mode or one Phase
if . set in Single-Phase mode, press it shows the total VArh for 5s.
Press both buttons for 15s to reset all VArh values.
i) Only if . set in Three-Phase mode, while select Vmeasure, the display shows the value for each Phase, press
it shows the phase voltages.
Press for more than 5s to switch from to and set this as default measure value and vice versa.
l) While select TEMP measure, the display shows the current working temperature, press and hold it shows the total
device worked hours.
5.1 MEASURE DETAILS:
MAX VALUE:
The data recording happens every 2 seconds, then after 32
seconds, the micro calculates the average of the 16 different
recording and, if above the stored max value, this goes to
overwrite it and becomes effectively the new max value.
This is to avoid that a single abnormal pike can false the real
situation recording an extraordinary and occasional max value.
For the max Temperature the data is related to the single
reading not to the average.
AVERAGE VALUE:
The data capture occurs every 2 seconds, for example if
.=10 the average value is calculated on 20 seconds.
After power on, during the first 15 minutes, the recording of the max values is disabled.
6 - TECHNICAL DATA:
Supply Circuit
144x144
9 Modules
Measuring Type:
True RMS
Cos(L/L)
-
0.00 to 1.00 ±1%
Voltage (N/Lx)
VA
100 to 280 ±1%
Voltage (L/L)
VA
180 to 490 ±1%
Current (CT)
A
0.05 to 5.5 ±0.5%
Active Power (Lx)
W
Class 1
Reactive Power (Lx)
VAr
Class 1
Apparent Power (Lx)
VA
Class 1
THD of Volt or Current
%
0 to 255
Work Hours
H
0 to 9999 (with multiplier)
Ambient Temperature
°C
0/+60°C (or °F)

8 / 9 ETI d.d., Obrezija 5, SI-1411 Izlake
http://www.etigroup.eu/products-services
Supply Voltage
3x400V+N
230VL/N
Operating Limits
-10% … +10% Ue
Rated Frequency
50 or 60Hz
Power Consumption L/N - 230V
4 VA
4VA
Immunity time for Microbreakings
< 50ms
Measurement/Overvoltage Category
Class II
Current Input
Rated Current
5A
Operating Limits
0.050 … 5.5A
Overload Capacity
1.1Ie
Overload Peak
10Ie for 500mS
Measurement/Overvoltage Category
Class II
Reading and Control Range
Voltage Reading Limits
195...460 V
2 … 480 V
Current Reading Limits
0.050....5A
Type of Current and Voltage Readings
TRMS
FFT - Harmonic Spectrum
THD% - 64st
Relay Outputs
Number of Outputs
3
Contact Arrangement
1NO
Contacts Capacity
8A –250V(AC1)
Maximum Capacity the Common Contacts
8A (C1) - 10A (C2)
8A
Insulating Category/Rated Voltage VDE0110
C/250 - B/400
Maximum Switching Voltage
250V
Electrical Contact Life
20 x 1006ops
Mechanical Contact Life
100 x 103ops
Enclosure and Connections
Cable Type for connection
Only 90°C - 1.5/2.5mm2- 16/14 AWG
Working Temperature
-20 / +60 °C
Storage temperature
-30 / +70 °C
Operating Altitude
Up to 2000m
Pollution Degree
2
Electrical Insulation –Mains/Contact
4 kV
Protection Degree
IP41 Front - IP20 Terminals
Relative Humidity w/o Condensation
95 RH%
144x144
9 Modules
Enclosure Version
Flush Mount
DIN Rail
Dimensions
149 x 149 x 60mm
157 x 89 x 60mm
Weight
650g
480g
Serial Interface
TTL
Standard
Communication Protocol
Proprietary / MODBUS RTU
Connector Type
RJ11
EC Directives: - 2006/95/EC - Low Voltage
- 2004/108/EC - EMC
Norms Compliance: CE marking
- IEC EN 55022 - IEC EN 61000-4-2 - IEC EN 61000-4-3 - IEC EN 61000-4-4 - IEC EN 61000-4-5
- IEC EN 61000-4-6 - IEC EN 61000-4-11 - IEC EN 61000-6-2 - IEC EN 61000-6-4 - IEC EN 61010-1
- IEC EN 61010-2-030
7 - TERMINAL CONNECTIONS:

9 / 9 ETI d.d., Obrezija 5, SI-1411 Izlake
http://www.etigroup.eu/products-services
8-DIMENSIONS:
144x144 - MODEL
FRONT VIEW SIDE VIEW PANEL HOLE
9 MODULE - MODEL
FRONT VIEW SIDE VIEW
CLEANING OF THE UNIT:
If necessary clean the device with a soft cloth dampened with water.
This operation must be done with the instrument switched off and disconnected from any power source.
This manual suits for next models
3
Table of contents
Other ETI Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Hitachi
Hitachi L44LA instruction manual

Black & Decker
Black & Decker TLD100 instruction manual

Vega
Vega VEGACAL 62 operating instructions

Keller-druck
Keller-druck ECO1 quick start guide

PCB Piezotronics
PCB Piezotronics IMI Sensors M603C00 Installation and operating manual

SUTO
SUTO S 120 Instruction and operation manual