Euramco Safety UB20 Series Manual

SM-EFATEX EV A
Portable Ventilators for
Hazardous Locations
Rated:
The Portable Ventilators described here in are intended for use in
Explosive Atmospheres in accordance with the limitations of the
rating. It is the user’s responsibility to determine the suitability of
equipment for the intended purpose.
II 2 G Ex d e IIB T6
TECHNICAL INFORMATION & INSTALLATION INSTRUCTIONS
Applicable Models:
UB20xx EFi120xx
EFi75xx EFi85xx
EFi150xx
UB20xx
EFi120xx
EFi150xx
EFi75xx
EFi85xx
SM-EFATEX Rev C

WARNING!
These units are intended for Explosive Atmospheres use in accordance
with ATEX Directive 94/9/EC. It is the user’s responsibility to determine
the suitability of this equipment for the intended purpose
CAUTION! THESE FANS ARE NOT INTENDED FOR USE IN MINES
SUSCEPTIBLE TO FIREDAMP.
Explosion Proof Fan Rated: Ex d e IIB T6
Euramco Safety hereby declares that the equipment listed in this
manual conforms to the relevant Essential Health and Safety
Requirements of the European Machinery Directive and standards listed
below.
Council of European Communities Directives:
89/392/EEC as amended by 91/368/EEC and 93/44/EEC.
Also EC Directives 93/68/EECI, 94/9/EC, and 76/117/EEC.
Standards to which conformity is declared:
See Declaration of Conformity (last page).
Category, Group and Zone Classifications
* According to ATEX Directive (94/9/EC)
T6 Temperature Classification
* According to EN 60079-0:2006
85°C T6
To ensure that there is no risk of ignition due to hot surfaces, the
equipment is classified with regard to the maximum surface
temperature of any part of the equipment while in operation based on
the ambient temperature of 40°C. Equipment must be selected with a
suitable temperature classification for the gases and vapors present
where the equipment is to be installed. Ensure that the maximum
surface temperature of any parts of the equipment are below the
ignition temperature of the explosive atmosphere concerned.
This equipment is intended for use in ambient temperatures ranging
between -20°C and +40°C.
Classification: Ex de
*According to EN 60079-1:2004
Flame Proof Enclosures with Increased Safety Components.
Description of Apparatus
The Portable Ventilator assemblies represented herein consist of an
Approved Explosion Proof Electric Motor Rated: Ex d IIB by Bluffton
Motor Works (Formerly Franklin Electric) as listed below and are
covered by Certificate No. DEMKO 03 ATEX134885U.
EURAMCO SAFETY VENTILATOR BLUFFTON MOTOR
MODEL #
INPUT VOLTAGE
EURAMCO PART #
BLUFFTON PART #
IMPELLER
UB20xx
115VAC, 60Hz
EF7002XX
1933007415
PLASTIC
UB20xx
230VAC, 50/60Hz
EF8002XX
1933007419
PLASTIC
EFi75xx
115/230VAC, 50/60Hz
EB7201XX
EB7201XX-230
1133007405
METAL
EFi85xx
115/230VAC, 50Hz
EB8201XX
EB8201XX-110
1223007401
METAL
EFi120xx
115/230VAC, 50Hz
EA8120XX
EA8120XX-110
1223007401
METAL
EFi150xx
115/230VAC, 50/60Hz
EG8200XX
EG8200XX-230
1133007417
METAL
The Flame Proof Electric Motor
Power Requirements: See chart above.
Ambient Temperature Range: -20°C<Tamb< +40°C
Ingress Protection to IEC 529: IP55
Marked: (“Bluffton Motor Works”) Electric Motor for Hazardous
Locations
Flame Proof Enclosure:Ex d IIB
The electric motor consists of one flameproof enclosure, which contains
less than 6% magnesium by weight. The on/off switch is housed within
the motor enclosure, and is operated by a shaft, extending out from the
rear end bell to a lever. The lever is accessible via an attached push
rod.
Motor connections are made through a non-detachable cable, secured
to the motor with an approved Flame Proof cable gland from the
company Hawke, Model 501/421/0/M20 and complies with International
Standards EN 60079-0:2006, EN 60079-1:2004, EN 60079-7:2007.
The electric motor drives an aluminum or plastic fan blade containing
less than 6% Magnesium by weight which is enclosed in a plastic,
statically conductive housing with a conductivity rating of <1 giga-
ohmes. Connection to the motor is facilitated by a Terminal Block
mounted in an Increased Safety/Flame Proof Enclosure rated II 2 G Ex
e II T6, from the company Rose Industries, Part No. 05080806, and
covered under the certificate No. PTB 00ATEX1063. This box was
designed to conform to International Standards EN 60079-0:2006, EN
60079-1:2004, EN 60079-7:2006, EN 61241-0:2004 and EN 61241-
1:2004. The enclosure features stainless steel grounding lugs, with a
high heat silicon gasket.
The Flame Proof enclosure has attached, approved, explosion proof
cable glands Rated:IIGD Ex e II
Type: Polyamide Ex metric conforms to International Standards EN
60079-0:2006, EN 60079-7:2006, EN 61241-0:2006 and EN 61241-
1:2004.
Material: Polyamide
Color: Black/Blue
Grommet: NBR
Protection classification: IP68
Temperature range: -4°F to +212°F
Approval: PTB 00 ATEX 1063
The power cable from each blower is terminated with either a yellow
120VAC or a Blue 240VAC Explosion-proof plug to match the operating
voltage of the motor. The plugs are made by Appleton and complies
with International Standards: EN 60079-0:2006, EN 60079-1:2004, EN
61241-0:2004, EN 61241-1:2004 & EN 60079-7:2006.
The fans are assembled with both Inlet and Outlet Safety Guards that
conform to the safety standards to prevent danger zones being reached
by upper limbs in the BS EN 294:1992
Guards Standard.
II 2 G Ex d e IIB T6
CE 0539
Demko 09ATEX 0926969
TECHNICAL INFORMATION & INSTALLATION INSTRUCTIONS
SM-EFATEX Rev C

INSTALLATION & START-UP
During the installation and start-up of the Euramco Safety blowers in
areas where there is a risk of explosion:
▪Design of the electrical installations must be in accordance with
EN 60079-14.
▪Ensure power source is providing an electrical ground.
▪Blowers must be integrated into a system in a way to support
accessibility for regular maintenance.
▪Perform careful inspection of each blower system to ensure
ducting is securely attached to blower. All components of the
blower system are made of electrically conductive material. It is
very important to properly and securely attach each piece to
maintain a ground path.
▪Ensure set-up, installation, operation, and maintenance are
performed only by properly trained personnel.
▪Operation after a faulty installation or maintenance shall be
considered as unintended use.
Before STARTING the FIRST Time
DO not start operation if there are signs of shipping damage to blade,
guards, or housing. STOP, call your dealer. USE Ex-Rated receptacles
for this equipment. IT IS NOT recommended to use extension cords for
high amperage load. (See power rating label on limit.)
OPERATION
Always ensure the switch is in the OFF position prior to connecting a
ventilator to a power source.
Stop the blower if mechanical noise, vibration, or other abnormal
conditions occur. Any noise other than turbine-type pitch is not normal.
To protect the user, this unit is equipped with thermal overload
protection with automatic reset. Motor will restart without warning after
protector trips. If motor thermal protection trips, disconnect unit and
determine cause.
Conductive RAMFAN Portable Ventilators are made with statically
conductive materials. When ducting is required to remote the ventilator
from the point of application in a potentially explosive environment, the
ducting must be statically conductive and properly secured to ventilator
to minimize the potential fan static electricity build up.
MAINTENANCE
Disconnect power before disassembly or cleaning. Never immerse or
directly spray motor with liquids.
Clean ventilator with commercially available biodegradable cleaning
solutions. Do not use solvents containing hydrocarbons (i.e. MEK,
Acetone).
Clean fan periodically to remove accumulated dust or debris.
There are no user serviceable parts. Contact factory for replacement
part applicability.
Do not change make or model number of motor for any reason!
CAUTIONS
Do not move ventilator while fan is in operation. Use good lifting
practices when moving ventilator to prevent bodily injury.
Blower should be operated and repaired by trained personnel only.
Do not operate if there is any physical damage to cord, plug or
receptacle.
Keep fingers and hands clear of fan blade. Keep fan guard securely in
place. Do not operate with damaged or missing fan guards.
Use properly grounded power receptacle in potentially explosive
atmospheres, and for operation safety. Ensure continuity to the earth.
Fatal electrical shock may result if motor frame and adjacent metal are
not grounded in compliance with electrical code.
Keep area clear of rock and debris.
Keep away from children.
WARRANTY
Positive Pressure Ventilators and Turbo Ventilators, excluding engine
and wear items, are warranted for one year from date of original
purchase, to be free of defects in material and workmanship. Electric
motors are warranted by their respective manufacturers. Wear items
include feet, fasteners, handles, wheels, and paint, and are not covered
under the warranty. Fan impellers and shrouds are warranted to be free
of defects in material and workmanship for five years. Components
exposed to salt water service are warranted for a period of one year
from date of original purchase.*
Portable Blowers:
Portable Blowers are warranted against defects in material and
workmanship for a period of one year from the date of original purchase.
Duct is not warranted due to its intended use.
*Authorization for warranty repairs must be obtained from the
factory. There are no other warranties expressed or implied.
SM-EFATEX Rev C
INSTRUCTION & CARE

2746 Via Orange Way Spring Valley, CA 91978 Ph +1 (619) 670-9590 Fx +1 (619) 670-7345 www.EuramcoSafety.com
Feet
Screw
SM-EFATEX Rev C

DECLARATION OF CONFORMITY
In respect of the following Directives:
Council of European Communities Directives
89/392/EEC as amended by 91/368/EEC, 93/44/EEC and 93/68/EEC (Machinery Directive)
Also the following European Directives for our Electric Fans
73/23/EEC (Low Voltage Directive)
89/336/EEC (EMC Directive)
94/9/EC (ATEX Directive)
Standard(s) to which conformity is declared:
EN 294 (Safety of Machinery – Safety Distances to Prevent Danger Zones Being Reached by the
Upper Limbs)
EN 953 (Safety of Machinery –Guards – General Requirements for the Design and Construction
of Fixed and Movable Guards)
EN 50081-2 (Electromagnetic Compatibility Generic Emission - Industrial)
EN 61000-6-2 (Electromagnetic Compatibility – Immunity for Industrial Environments)
EN 60079-0:2006 (Electrical Apparatus for Potentially Explosive Atmospheres – General Requirements)
EN 60079-1:2004 (Electrical Apparatus for Potentially Explosive Atmospheres – Flameproof Enclosures ‘d’)
EN 60079-7:2007 (Electrical Apparatus for Potentially Explosive Atmospheres Increased Safety ‘e’)
Manufacturer’s Name: Euramco Safety, Inc.
Manufacturer’s Address: 2746 Via Orange Way
Spring Valley, CA 91978
USA
Type of Equipment: Flame Proof - Increased Safety / Exhausters
Model No: UB20xx EFi120xx
EFi75xx EFi150xx
EFi85xx
Euramco Safety Inc. hereby declares that above equipment conforms to the relevant Essential Health and
Safety Requirements of the European Machinery Directive (89/392 EEC as amended by 91/368 EEC,
93/44 EEC and 93/68 EEC), and the additional Directives and Standards listed above.
Jack Simmons Date 09/08/2011
Engineering and Quality Control Manager
9/11
Other manuals for UB20 Series
2
This manual suits for next models
4
Table of contents
Other Euramco Safety Fan manuals
Popular Fan manuals by other brands

Westinghouse
Westinghouse ETL-ES-GW-Alloy LED-WH16 owner's manual

Salda
Salda AKU 500x250 EKO Technical manual

Broan
Broan HRV650 Installation, operation and maintenance instructions

Haier
Haier FSM016M - 10-04 user manual

Luminance Brands
Luminance Brands kathy ireland HOME Batalie Breeze CF621VNB00 owner's manual

Emerson
Emerson ACF765BS owner's manual