EDS1311-001
Page 1 of 2
It is the responsibility of the person installing the electrical equipment to ensure that the installation meets the
requirements of the IET wiring regulations and is therefore ‘t for purpose’. Factors such as correct selection
of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior
to full testing and power-up. Any other regulations applicable to the equipment being installed such as the
Machinery Directive and current health and safety legislation must also be adhered to.
All connections (including factory made) must be checked for the correct tightness prior to commissioning of
the electrical installation.
All connections should be checked periodically to ensure correct tightness.
Important Safety Notice
DO NOT USE POWER TOOLS ON THESE PRODUCTS
SPD Specication
Technical Data: Safe Surge Unit | ECSS-102
TY6 30N
According the IEC61643-11 Type 2
Earthing System TT/TN
System Voltage Un 230/400V
Max. continous operation AC voltage Uc 275V
Norminal discharge current (8/20µs) In 15kA
Maximum discharge current (8/20µs) Imax 30kA
Voltage protection level Up 1.5kV
Maximum backup fuse 63A gL
Response time tA 25ns
Enviroment temperature Tu -40 C ~ 80 C
Status indicator non/red
Mounting 35mm Din Rail
Cross section of wire (min.) 4mm
Cross section of wire (max.) 16mm
Casing material Thermal plastic
UL94 - V0
Degree of protection IP20
Enclosure Dimensions
MCB Specication
Product Ranges EUC1P, EUC2P, EUC3P
Standard (s) IEC 60898, EN 60898
Certication KEMA
Characteristic Curves B, C & D
Rated Current (In) 1, 2, 4, 6, 10, 16, 20, 25, 32, 40, 50 & 63A
Rated Voltage (Ue) AC 230(240)/400(415)V
Rated Frequency 50/60Hz
Rated impulse withstand voltage (Uimp) 4kV
Energy Limiting Class 3
Number of poles 1, 2 & 3
Rated Short-Circuit Capacity (Icn) 10Ka
Operating Temperature -5 to 40 C*
Altitude Not exceeding 2000 metres
Humidity Not exceeding 50% at 40 C and 90% at 20 C
Pollution Degree 2
Overvoltage Category III
Terminal Protection IP20
Mounting 35mm DIN Rail
Terminal Type Tunnel
Terminal Capacity 1.0-25mm²
Recommended Terminal Torque 2.0Nm
* average not exceeding 35 C over 24 hour period
238
105
78
102
32 DIA.
181
55
6 DIA.