manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Leviton
  6. •
  7. Surge Protector
  8. •
  9. Leviton 52412-DS3 User manual

Leviton 52412-DS3 User manual

PK-92964-10-02-0A
Multi-Phase Transient Voltage Surge Suppressor
Cat. No. 52000 Series
For main distribution and branch circuit panels
INSTALLATION INSTRUCTIONS
Limiteur de surtensions transitoires polyphasé
Gamme 52000
Pour panneaux de branchement ou de dérivation
DIRECTIVES
Dispositivos Protectores de Sobrecargas
Nos. de Cat. Serie 52000
Para paneles de distribución de circuitos principales o derivados
INSTRUCCIONES DE INSTALACION
DANGER
HIGH VOLTAGE
HauteTension
PK-92964-10-02-0A
LIMITED TEN YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else
that this product at the time of its sale by Leviton is free of defects in materials and
workmanship under normal and proper use for ten years from the purchase date. Leviton’s
only obligation is to correct such defects by repair or replacement, at its option, if within
such ten year period the product is returned prepaid, with proof of purchase date, and a
description of the problem to Leviton Manufacturing Co., Inc., Att: Power Quality
Customer Support, 860 Harold Place, Chula Vista, CA 91914, U.S.A. This warranty
excludes and there is disclaimed liability for labor for removal of this product or reinstallation.
This warranty is void if this product is installed improperly or in an improper environment,
overloaded, misused, opened, abused, or altered in any manner, or is not used under
normal operating conditions or not in accordance with any labels or instructions. There are
no other or implied warranties of any kind, including merchantability and fitness for a
particular purpose, but if any implied warranty is required by the applicable jurisdiction, the
duration of any such implied warranty, including merchantability and fitness for a particular
purpose, is limited to ten years. Leviton is not liable for incidental, indirect, special, or
consequential damages, including without limitation, damage to, or loss of use of, any
equipment, lost sales or profits or delay or failure to perform this warranty obligation. The
remedies provided herein are the exclusive remedies under this warranty, whether based
on contract, tort or otherwise.
For Technical Assistance Call:
1-800-648-3332 (U.S.A. Only)
www.leviton.com
PK-92964-10-02-0A 10/23/02, 11:11 AM1
ENGLISH
Table of Contents
SECTION PAGE
DESCRIPTION ...................................................................................................... 1
FEATURES ........................................................................................................... 1
TO INSTALL .......................................................................................................... 1
SERVICING INSTRUCTIONS ............................................................................. 7
FRANÇAIS............................................................................................................ 9
ESPAÑOL ........................................................................................................... 20
Page 33
NOTES
PK-92964-10-02-0A 10/23/02, 11:11 AM2
DESCRIPTION
The 52000 TVSS Panel Protection System is a high-performance Transient Voltage Surge Suppressor
designed for use on main distribution and branch circuit panels.
FEATURES
•Replaceable plug-in modules, which facilitate maintenance.
•Hybrid component suppression design.
•TVSS protection on all phases.
•Common Mode TVSS protection for WYE Systems.
•Diagnostic monitoring of each phase module.
•Acoustic as well as visual failure indicators.
•Provisions for operation with an optional Remote Supervisor Panel, allowing monitoring of TVSS
status from distant locations.
•UL Listed (except 52347-M3) and CSA Certified design.
•48-62 Hz operation.
•Location per IEC std: Class III.
•One port.
•Optional surge counter with front panel LCD display.
TO INSTALL
WARNING: TO BE INSTALLED AND/OR USED IN ACCORDANCE WITH APPROPRIATE
ELECTRICAL CODES AND REGULATIONS (INCLUDING NEC/CEC, AS APPLICABLE).
WARNING: IF YOU ARE NOT SURE ABOUT ANY PART OF THESE INSTRUCTIONS, CONSULT
A QUALIFIED ELECTRICIAN.
WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER
OR FUSE AND TEST THAT THE POWER IS OFF BEFORE WIRING!
WARNING: THIS DEVICE IS NOT A LIGHTNING ARRESTOR. IT WILL NOT SURVIVE
LIGHTNING STRIKES IN CLOSE PROXIMITY TO THE PREMISES OR SUSTAINED
OVERVOLTAGES.
WARNING: ELECTROCUTION AND FATAL OR SERIOUS INJURY AND PROPERTY DAMAGE
CAN RESULT FROM FAULTY INSTALLATION.
CAUTION: USE THIS DEVICE ONLY WITH COPPER OR COPPER CLAD WIRE. WITH
ALUMINUM WIRE USE ONLY DEVICES MARKED CO/ALR OR CU/AL.
NOTE: DO NOT OPERATE AT ALTITUDES EXCEEDING 2000 METERS.
NOTE: OPERATE INDOORS BETWEEN 30-90% RELATIVE HUMIDITY.
NOTE: IT IS RECOMMENDED THAT THE 52000 TVSS PANEL PROTECTION SYSTEM BE
INSTALLED BY A QUALIFIED ELECTRICIAN.
1. Identify the device or load to be protected:
The 52000 Panel should be located as close as
possible to the electrical panel serving the load to be protected in order to minimize connection
lead length resistance and inductance.
Page 1Page 32
NOTES
PK-92964-10-02-0A 10/23/02, 11:11 AM3
Page 2
2. Identify the electrical system in use (Delta or WYE system voltage): Matching TVSS module and
line voltages is critical! Identify the system in use by measuring L-N and L-L voltages.
CAUTION: VOLTAGE MEASUREMENTS CAN BE DANGEROUS TO LIFE AND/OR
PROPERTY! CONFIRM THAT THE MAXIMUM MEASURED VOLTAGES DO NOT EXCEED THE
AC RMS VOLTAGE RATING SPECIFIED ON THE 52000 REPLACEABLE MODULES, OR
DAMAGE MAY OCCUR TO THE MODULES. SEE FIGS. 1-6.
3.
Cutting Access Holes: Cut holes for conduit in panel using approved metal cutting tools. Prevent
any metallic filings from remaining inside the panel. If any metallic filings enter panel, care must be
exercised to remove them using a vacuum device or other tools, as required.
Mount securely: Refer to the
"Panel Mounting"
Instruction Sheet (enclosed).
Conduit Installation:
Conduit should be installed with lock nut and bushing. Lock nut should be
adjusted so that bushing secures properly, and conduit and bushing extend as little as possible into
enclosure.
4.
Connections: With the line POWER OFF, remove Terminal Block Cover and connect leads using
the largest stranded wire size possible (#10 to #3 AWG, stranded) as illustrated in the wiring
diagrams. Screw terminal torque requirements: #10 AWG (35 in.-lbs.), #8 AWG (40 in.-lbs.),
#3-#6 AWG (45 in.-lbs.).
Connecting wire lengths from the circuit breaker panel to the 52000’s terminal block should be
minimal (less than 18" if possible). Power leads may be connected to L1, L2, and L3 without
regard to phase A, B, or C, except for the Three Phase High Leg Delta connection. In this
connection, either of the two power leads may be connected to L2 and L3 without regard to phase,
but the High Leg power lead must be connected to L1 (Fig. 6). Figs. 7 and 8 illustrate two
methods for connection lead attachment.
In Method 1, Fig. 7, the TVSS Panel provides a feed through connection between the circuit
breaker panel and a load.
NOTE: Maximum wire size is #3 AWG stranded.
This feed through hookup provides the best connection with regard to surge protection for the
dedicated load. This type of connection is desirable when the branch feeds sensitive loads that
need to be protected, such as a computer room or an area of electronic instrumentation.
G L1N
TVSS
Module1
Common
Mode Module
G
N
V(L-N)
L1
Fig. 1 – Single Phase with Grounded Neutral
Page 31
NOTES
PK-92964-10-02-0A 10/23/02, 11:11 AM4
Page 3
NOTE: Protection components are in parallel with loads.
The Leviton 52000 TVSS Panel should be mounted as close as possible to the circuit breaker
panel to provide maximum surge protection to other branches fed by other circuit breakers within
the circuit breaker panel. It should be noted that during installation or maintenance of the 52000
TVSS Panel, the circuit breakers which feed the 52000 must be opened, therefore power to the
load will be momentarily disconnected.
NOTE: The load current is limited to wire size in use, but must not exceed 100 Amps,
maximum continuous current.
In Fig. 3, Cat. Nos. 52120-7M3 and 52277-7M3 should only be used for the 3 Phase, 4 wire with
Ground, Wye configuration. DO NOT use with a Delta configuration.
In Method 2, Fig. 8, the TVSS Panel is connected through dedicated circuit breakers of 30 amps.
For maximum surge protection the TVSS Panel should be mounted as close as possible (no more
than 18 inches) from the circuit breaker panel. Use wire size #10 to #3 AWG, stranded. In a
G L1N L2
TVSS
Module 1
Common
Mode Module
G
N
V(L-L)
L1
L2 V(L-N)
V(L-N)
Module 2
Fig. 2 – Single (Split) Phase 3-Wire with Ground
GARANTIA LEVITON POR DIEZ AÑOS LIMITADA
Leviton garantiza al consumidor original de sus productos y no para beneficio de nadie más que
este producto en el momento de su venta por Leviton está libre de defectos en materiales o
fabricación por un período de diez años desde la fecha de la compra original. La única obligación
de Leviton es corregir tales defectos ya sea con reparación o reemplazo, como opción, si dentro
de tal período de diez años el producto pagado se devuelve, con la prueba de compra fechada y
la descripción del problema a Leviton Manufacturing Co., Inc., Att: Power Quality
Customer Support, 860 Harold Place, Chula Vista, CA 91914, U.S.A. Esta garantía
excluye y renuncia toda responsabilidad de mano de obra por remover o reinstalar este producto.
Esta garantía es inválida si este producto es instalado inapropiadamente o en un ambiente
inadecuado, sobrecargado, mal usado, abierto, abusado o alterado en cualquier manera o no es
usado bajo condiciones de operación normal, o no conforme con las etiquetas o instrucciones.
No hay otras garantías implicadas de cualquier otro tipo, incluyendo mercadotecnia y propiedad
para un propósito en particular pero si alguna garantía implicada se requiere por la jurisdicción
pertinente, la duración de cualquiera garantía implicada, incluyendo mercadotecnia y propiedad
para un propósito en particular, es limitada a diez años. Leviton no es responsable por daños
incidentales, indirectos, especiales o consecuentes, incluyendo sin limitación, daños a, o pérdida
de uso de, cualquier equipo, pérdida de ventas o ganancias o retraso o falla para llevar a cabo la
obligación de esta garantía. Los remedios provistos aquí son remedios exclusivos para esta garantía,
ya sea basado en contrato, agravio o de otra manera.
Para Asistancia Técnica llame al:
1-800-648-3332 (Sólo en E.U.A.)
www.leviton.com
Page 30
G L3L1N L2
TVSS
Module 3
Common
Mode Module
G
V(L-L)
L1
L3
NV(L-N)
V(L-N)
Module 2
Module 1
L2
V(L-N)
Fig. 3 – Three Phase, 4 Wire with Ground, WYE
*NOTE: Six (6) fuses are used for
Cat. Nos. 52120-7M3 & 52277-7M3
*
PK-92964-10-02-0A 10/23/02, 11:11 AM5
Page 4 Page 29
Modo DEL Tono Remoto DELS DEL Botón DEL Botón DEL Botón
Falla Audible Módulo Estado Desactivar Desactivar Desactivar Desactivar acción
(Rojo) (Verde) de Pila (Amarillo) momentánéa
Normal APAG APAG APAG ENC APAG FUERA APAG FUERA APAG FUERA
APAG APAG APAG ENC APAG DENTRO ENC FUERA APAG FUERA
Falla de ENC ENC ENC APAG FUERA APAG FUERA APAG FUERA
Módulo ENC APAG ENC APAG APAG DENTRO ENC FUERA APAG FUERA
Pila ENC ENC ENC ENC ENC FUERA APAG FUERA APAG FUERA
Baja APAG APAG APAG ENC ENC FUERA APAG DENTRO ENC FUERA
No ENC ENC ENC APAG APAG FUERA APAG FUERA APAG FUERA
Energía ENC APAG ENC APAG APAG DENTRO APAG FUERA APAG FUERA
APAG APAG ENC APAG APAG FUERA APAG DENTRO APAG FUERA
Auto ENC ENC ENC ENC ENC FUERA APAG FUERA APAG DENTRO
Prueba
uno o más
Auto Prueba
("Test")
Desactivar Pila
("Low Battery")
Tono Audible
("Audio Alarm")
Tabla 1 - Funciones del Indicator de Diagnostico:
Lista de las funciones de diagnóstico de los paneles
en serie 52000.
variation of this connection, the panel circuit breakers can also feed a load by connecting the
TVSS panel to the circuit within an approved connection enclosure. In this case, the circuit
breakers must be rated for this load. The TVSS panel should be connected to these breakers
through a 30-amp rated (minimum), 3-pole disconnect switch. This facilitates TVSS disconnection
for installation or maintenance without interrupting power to the load.
5. Conduit attachment: A 2-inch hole in the enclosure is recommended to be used for In-Out
conduit connection.
CAUTION: THE ENCLOSURE MUST BE PROPERLY GROUNDED BY USE OF #10 AWG
MINIMUM SIZE COPPER WIRE ROUTED TO THE “G” TERMINAL LUG.
6. Attaching the connection leads - TVSS to power lines:
CAUTION: THE FOLLOWING INSTALLATION SHOULD BE PERFORMED WITH THE POWER
OFF! ALWAYS TURN OFF POWER BEFORE WORKING ON THE TVSS PANEL, SUCH AS
WHEN CHANGING FUSES AND INSERTING OR REMOVING REPLACEABLE MODULES.
Fig. 5 – Three Phase, 3 Wire with Ground,
Delta (Corner Leg Grounded)
Fig. 4 – Three Phase, 3 Wire, Delta (Non-Grounded)
G L3L1N L2
TVSS
Module 3
G
V(L-L)
L1
L3 V(L-L)
Module 2
Module 1
L2 V(L-L)
G L3L1N L2
TVSS
Module 3
G
V(L-L)
L1
L3 V(L-L)
Module 2
Module 1
L2 V(L-L)
SÓLO PARA MÉXICO (For use in Mexico Only)
POLIZA DE GARANTIA: LEVITON, S.A. DE C.V., RFC LEV-920526651, ARISTA 54-A, MEXICO 11270 D.F., MEXICO
Tel. 5386 00 73.
Garantiza este producto por el término de un año en todas sus partes y mano de
obra contra cualquier defecto de fabricación y funcionamiento a partir de la fecha
de entrega o instalación del producto bajo las siguientes CONDICIONES:
1. Para hacer efectiva esta garantía, no podrán exigirse mayores requisitos que la
presentación de esta póliza junto con el producto en el lugar donde fue adquirido
en cualquiera de los centros de servicio que se indican a continuación.
2. La empresa se compromete a reemplazar o cambiar el producto defectuoso sin
ningún cargo para el consumidor, los gastos de transportación que se deriven
de su cumplimiento serán cubiertos por: LEVITON, S.A. DE C.V.
3. El tiempo de reemplazo en ningún caso será mayor a 30 días contados a partir
de la recepción del producto en cualquiera de los sitios en donde pueda hacerse
efectiva la garantía.
4. Cuando se requiera hacer efectiva la garantía mediante el reemplazo del
producto, esto se podrá llevar a cabo en: LEVITON, S.A. DE C.V.
5. Esta garantía no es válida en los siguientes casos: A) Cuando el producto ha
sido utilizado en condiciones distintas a las normales. B) Cuando el producto no
ha sido operado de acuerdo con el instructivo de uso en idioma español
proporcionado. C) Cuando el producto ha sido alterado o reparado por personas
no autorizadas por LEVITON, S.A. DE C.V.
6. El consumidor podrá solicitar que se haga efectiva la garantía ante la propia
casa comercial donde adquirió el producto.
7. En caso de que la presente garantía se extraviara el consumidor puede recurrir
a su proveedor para que se le expida otra póliza de garantía previa presentación de la nota de compra o factura respectiva.
DATOS DEL USUARIO
NOMBRE: DIRECCION:
COL: C.P.
CIUDAD:
ESTADO:
TELEFONO:
DATOS DE LA TIENDA O VENDEDOR
RAZON SOCIAL: PRODUCTO:
MARCA: MODELO:
NO DE SERIE:
NO. DEL DISTRIBUIDOR:
DIRECCION:
COL: C.P.
CIUDAD:
ESTADO:
TELEFONO:
FECHA DE VENTA:
FECHA DE ENTREGA O INSTALACION:
SÓLO PARA MEXICO
PK-92964-10-02-0A 10/23/02, 11:11 AM6
Page 28 Page 5
Interruptor para Desactivar el Sonido: Cuando se indica una falla y es notada por el personal
autorizado, desactive el sonido de alarma momentáneamente presionando el interruptor para
desconectar la alarma. El LED Rojo de alarma continuará oscilando. Cuando se reemplace el
fusible o módulo malogrado, presione otra vez el interruptor para reinstalar el tono de alarma.
Funciones de la Batería: En el caso que más de un fusible se queme, una batería alcalina es
utilizada para dar energía al circuito de diagnóstico para alertar al usuario que hay un problema.
Cuando esto ocurre, el LED Rojo de alarma oscila, la alarma y el transmisor remoto se activan.
Cuando los múltiples LEDs Verdes del módulo están APAGADOS, es probable que la unidad de
diagnóstico del circuito está cargada por la batería. Para conservar la vida de la batería, es
recomendable que el usuario presione el interruptor para desconectar la alarma. Después que los
fusibles y módulos son reemplazados, el LED Rojo se APAGA. Presione el interruptor para
desconectar la alarma y reactivar el tono de alarma.
Batería Malograda: En el paquete de envío, la unidad va con el interruptor para desconectar la
batería en la posición de desconexión, de tal manera que la batería no se descargue durante la
ausencia de energía CA. Cuando la corriente CA se aplica por primera vez el LED Rojo de batería
desconectada y el LED Amarillo de batería baja se encenderán. Presione momentáneamente el
interruptor de desconexión de batería para activar la batería. Si los LEDs se apagan indicará que la
batería está desconectada o baja.
Indicación de Batería Baja: El LED Amarillo encendido indica una condición anormal en la batería.
Esto se debe a voltaje bajo en la batería o que no hay batería. Cuando esto sucede el LED Rojo de
alarma oscila, se escucha un sonido y el indicador remoto se activa. Cuando el usuario es alertado
con el LED amarillo encendido y todos los LEDs verdes del Módulo encendidos, quiere decir que
hay falla en la batería y que NO hay falla en el fusible o energía del módulo PSTT. Presione el
interruptor de desconexión de batería para apagar el sonido de alarma, el LED oscilante y la señal
del remoto de mal funcionamiento de batería. El LED Amarillo se mantendrá encendido para
recordar que se tiene que reemplazar la batería. Esta función rehabilita la función de alarma para
continuar el monitoreo de la falla del PSTT. Cuando cambie batería, presione momentáneamente el
interruptor de desconexión de batería. Una batería nueva puede causar que el LED Amarillo se
APAGUE y rehabilitará la función de alarma de batería baja después de presionar el botón para
desconectar la batería.
Reemplazo de Batería: Presione el sujetador de las baterías y deslice las baterías afuera.
Asegúrese de seguir la polaridad marcada en el compartimiento.
Interruptor de Prueba: Un “Interruptor de Prueba” capacita al usuario probar todas las funciones
descritas arriba, para un buen funcionamiento. Cuando se presiona el interruptor de prueba
ocurrirán las siguientes funciones:
•El LED Amarillo de batería baja se ilumina
•El LED Rojo de advertencia de alarma oscila
•El sonido de alarma suena
•El indicador de alarma del Panel Supervisor Remoto (accesorio opcional) si está cableado, se
activará, además probará el Panel Supervisor Remoto.
The ground terminal within the TVSS Panel is connected to the metal enclosure. For isolated
ground systems, the isolated ground wire should not be connected to the In-Out ground terminals.
However, as indicated in step 5, the enclosure must be grounded via a ground conductor to the
ground terminal. With the power OFF, connect phase leads to L1, L2, and L3 as indicated in step
4. Connect the neutral, for WYE systems, to the neutral terminal. Connect ground to ground
terminal. Figs. 7 and 8 illustrate alternate connection systems which use circuit breakers (either
dedicated or load sharing), or a disconnect switch. Connection leads should be cut to length and
wrapped. Avoid sharp bends. Lead wire insulation should not be cut or damaged except to
expose ends for connection.
7. Remote connection:
•Relay status circuit and contacts rated at 5 Amps. The voltage rating is 250VAC or 30VDC.
Contacts accommodate 20-12 AWG wire secured to terminals using 3.5 in.-lbs. of torque. Wiring
must be rated 600 VAC, dressed and secured away from live parts and protected from sharp
edges and door entrapment. Hole must be cut in enclosure for conduit connection. If surge
protection fails, continuity will be between the "NO" and "C" contacts.
NOTE: If surge suppression failure has occurred, a transient surge has exceeded the
rating of the module and it should be replaced immediately.
•A7/8 inch hole cut on the hinged side of the enclosure is recommended for the Remote
Supervisor Panel connections. See Remote Supervisor Panel Instructions for its connection
method.
8. Battery Installation: A 9-Volt alkaline battery is included in the shipping carton. The purpose of
the 9-Volt battery is to power the diagnostic warning circuitry in the event of a power failure or
multiple fuse failures. Remove the battery holder from the diagnostic assembly. Insert the 9-Volt
battery (be sure to follow the polarity markings on the battery compartment), and slide the battery
holder back in.
9.Secure modules and replace terminal block cover. Be certain all TVSS Modules are tightly in
place and remove any extra materials. Close and secure enclosure cover door before applying
power.
Fig. 6 – Three Phase, High Leg Delta (Cat. No. 52412-DS3)
G L3L1N L2
TVSS
Module 3
G
V(L-L)
L1
L3
Module 2
Module 1
L2 V(L-L)
V(L-N) V(L-N)
240 v
120 v 120 v
(High Leg)
PK-92964-10-02-0A 10/23/02, 11:11 AM7
Page 6 Page 27
de 9-voltios (asegúrese de seguir las marcas de polaridad en el compartimiento de la batería) y
deslice el sujetador en su lugar.
9.Asegure los módulos y coloque la cubierta del bloque terminal. Asegure que todos los módulos
PSTT estén bien seguros en su lugar y quite cualquier material extra. Cierre y asegure la puerta
del recinto antes de conectar la energía.
10. Active el sistema ENCENDIENDO la energía CA: La luces Verdes de Estado del Módulo se
deben iluminar y estar visibles a través de las entradas de la puerta del recinto y todas las
demás luces deben estar APAGADAS. Si encuentra problemas que no se pueden resolver
usando el Procedimiento de Problemas Aislados, impreso en el interior de la puerta del recinto,
contacte con el Departamento Técnico de Leviton: 1-800-648-3332.
11. Examen de Diagnóstico: Presione y sostenga el botón de prueba. El indicador Rojo de alarma
debe oscilar, la alarma debe sonar, la luz amarilla de batería baja se debe iluminar y el indicador
de alarma del Panel Supervisor Remoto se debe activar, si está cableado. Suelte el botón.
12. Prueba del Contador de Sobretensión: Si el Panel 52000 tiene un contador LCD se
sobretensión en la parte del frente, presione el botón “Reset”(reinicio), luego el botón de “Test”
(Prueba). La pantalla debe registrar y contar las sobretensiónes cada vez que presione el botón
“Test”. Presione el botón “Reset” cada vez que la pantalla LCD esté al máximo (el LED Rojo de
la unidad LCD se iluminará). Presione el botón “Reset” cada vez que quiera aclarar la pantalla.
INSTRUCCIONES DE MANTENIMIENTO
Procedimiento e Instrucciones de mantenimiento de la Serie 52000 PSTT:Lea cuidadosamente
estas instrucciones así como las instrucciones de Reemplazo del Módulo y Fusible. Procedimiento
antes de hacer mantenimiento.
PRECAUCION: ANTES DE ABRIR LA CUBIERTA DEL RECINTO SPTT DESCONECTE LA
ENERGIA. ELECTROCUCION Y SERIOS DAÑOS PERSONALES Y/O A LA PROPIEDAD
PUEDEN RESULTAR DE UN MAL MANTENIMIENTO. SE RECOMIENDA QUE EL
MANTENIMIENTO DEL PANEL PROTECTOR DEL SISTEMA SE REALICE POR UN
ELECTRICISTA CALIFICADO.
Indicador del Diagnóstico de Funciones: La Tabla 1 muestra el diagnóstico de funciones de los
paneles de la serie 52000.
Diagnósticos del Módulo: Cada módulo contiene un LED Verde por cada modo. Cuando están
iluminados indican que el módulo está instalado correctamente, que la energía para esa fase está
presente y el fusible de protección para este modo está intacto. Reemplace los módulos lo más
rápido posible después de una falla (LED Verde apagado). Si los LEDs no están iluminados indica
pérdida de energía o que un fusible voló debido a sobretenciones, tales como tormentas eléctricas.
Cuando esto suceda, vea la Tabla correspondiente a los fusibles de los LEDs del Módulo (ubicados
en el interior de la puerta del panel) para la lista de indicadores LED Verdes y sus fusibles
designados.
Indicación de Falla: La oscilación del LED Rojo de Alarma y un sonido audible indica pérdida de
energía en los módulos. Esto puede ser debido a la ausencia de energía en la fase principal o
debido a un fusible quemado, causado por la falla del módulo debido a una sobretensión
momentánea (condición que causa indicación de falla). También transmite lo que sucede al
indicador remoto (accesorio opcional) a través de un par de cables ópticos aislados Clase II.
NOTA (Sólo para paneles Delta): Sólo cuando una fase de voltaje está afuera (sin fusible o
módulo de falla) los Paneles Delta revierten a una fase sencilla, los LEDs Verdes permanecen
ENCENDIDOS y el diagnóstico de alarma se mantiene inactivo.
10. Activate the system by turning AC power ON: The Green Module Status lights should be
illuminated and visible through the ports in the enclosure door, and all other lights should be OFF.
If problems are encountered that can not be resolved using the Problem Isolation Procedure
printed on the inside of the enclosure door, contact Leviton Technical Support: 1-800-648-3332.
11. Diagnostic Test: Press and hold down the test button. The Red warning indicator should blink,
the audible tone signal should beep, the Yellow low battery light should illuminate, and the
Remote Supervisor Panel warning indicator, if wired in, will be activated. Release the test button.
Fig. 7 – TVSS Feed Through Connection
G L3L1N L2
TVSS
G
L1
L3
L2
N
Conduit
TVSS
will accept
up to
#3 AWG
stranded
wire
To
loads
up to
100
Amps
G
N
Circuit Breaker Panel
Wye system illustrated —
Delta system would not include neutral line
Fig. 8 – TVSS Shunt Connection
G L3L1N L2
TVSS
G
L1
L3
L2
N
Conduit
To
loads
G
N
Circuit Breaker Panel
Wye system illustrated —
Delta system would not include neutral line
30 Amp
Disconnect
Switch
Connection Enclosure
PK-92964-10-02-0A 10/23/02, 11:11 AM8
Page 26 Page 7
•Para las conexiones del Panel Supervisor Remoto se recomienda cortar un hueco de 0.47 cm
en el lado de la bisagra. Vea las instrucciones del Panel Supervisor Remoto para esta método
de conexión.
8.Instalación de Batería: Se incluye una batería alcalina de 9 Voltios en el cartón de envío. La
batería de 9 voltios es para dar energía al circuito de alarma en el caso de apagón o falla de
varios fusibles. Quite el sujetador de la batería del ensamble de diagnóstico. Coloque la batería
G L3L1N L2
TVSS
G
L1
L3
L2
N
Conduit
El PSTT acepta
cable hasta
#3 AWG
G
N
Panel Interruptor de Circuitos
Sistema estrella ilustrado -
El sistema Delta no incluye línea Neutro
Para
cargas
hasta
100
Amps
Fig. 7 – Alimentación del PPST a través de Conexión
12. Surge Counter Test: If the 52000 Panel has a LCD surge counter on it's front panel, press it's
"Reset" switch, then the "Test" switch. The display should register surge counts each time the
"Test" switch is depressed. The "Reset" switch should be depressed whenever the LCD display is
at a maximum (the LCD unit's red LED will be illuminated). "Reset" may be depressed anytime to
clear the display.
SERVICING INSTRUCTIONS
Leviton Series 52000 TVSS Servicing Instruction Procedure: Carefully read these instructions as well
as the Module and Fuse Replacement Instruction Procedure before attempting service.
CAUTION: BEFORE OPENING TVSS ENCLOSURE COVER, POWER MUST BE TURNED OFF.
ELECTROCUTION AND FATAL OR SERIOUS INJURY AND PROPERTY DAMAGE CAN RESULT
FROM FAULTY SERVICING. IT IS RECOMMENDED THAT THE 52000 TVSS PANEL
PROTECTION SYSTEM BE SERVICED BY A QUALIFIED ELECTRICIAN.
Diagnostic Indicator Functions: Table 1 lists the diagnostic functions of the 52000 series panels.
Module Diagnostics: Each module contains a Green LED for each mode. When illuminated, they
indicate that the module is properly seated, power for that phase is present, and the protection fuse
for that mode is intact. Modules should be replaced as soon as possible, after a failure is noted (unlit
Green LED). Absence of illuminated LEDs indicates either a loss of power or a blown fuse due to
excessive transients, such as due to a direct lightning strike. When this occurs, see the Module LED/
Fuse Correspondence Chart (located on the inside panel door) for the list of the Green LED
indicators and their designated fuses.
Fault Indication: A flashing Red warning LED, in addition to an audible beep tone, indicates loss of
power to the modules. This can be due to the absence of main phase power, or a blown fuse caused
by module failure due to transient over-stress (a condition which causes the Fault Indication). It also
transmits the occurrence to a remote indicator (an accessory item) via an optically isolated Class II
wire pair.
NOTE (For Delta panels only): When only one phase voltage is out (with no fuse or module
failure) Delta panels revert to single phase, the Green LEDs stay ON and the diagnostic warning
remains inactive.
Beep Disable Switch: When a fault has been indicated and noted by authorized personnel, the
audible beep tone may be disabled by momentarily pressing the beep disable switch. The Red
warning LED will continue to flash. When the malfunctioning fuse and module have been replaced,
the beep disable switch should be pressed again in order to re-enable the audible beep tone.
Battery Function: In the unlikely event that more than one fuse has blown, a 9-volt alkaline battery
is utilized to power the diagnostic circuitry so as to alert the user that there is a problem. When this
occurs, the flashing Red warning LED, audible beep tone, and remote transmitter are activated.
When multiple Green module LEDs are OFF, it is probable that the unit’s diagnostic circuitry is being
powered from the battery. In order to conserve battery life, it is recommended that the user press the
beep disable switch to turn OFF the audible beep. After the fuses and modules are replaced, the
Red flashing LED will turn OFF. Press the beep disable switch in order to reactivate the audible
warning tone.
Battery Disable: The unit is shipped with the battery disable switch in the disable position so the
battery will not continually discharge in the absence of AC power. When AC power is first applied,
the Red battery-disable LED and Yellow low-battery LED will be lit. The battery disable switch
should be pressed momentarily to enable the battery. This will be indicated by both the battery
disable and low battery LEDs turning OFF.
Fig. 8 – Conexión Shunt del PSTT
G L3L1N L2
TVSS
G
L1
L3
L2
N
Conduit
Para
cargas
G
N
Panel Interruptor de Circuitos
Sistema estrella ilustrado -
El sistema Delta no incluye línea Neutro
Interruptor de
desconexión
Shunt de 30 Amp
Conexión de Caja
PK-92964-10-02-0A 10/23/02, 11:11 AM9
Page 8 Page 25
Mode Fault Beeper Remote Module Battery Disable Disable Disable Disable Momentary
LED LEDs Status Button LED Button LED Action
(Red) (Green) LED Button
(Yellow)
Normal OFF OFF OFF ON OFF OUT OFF OUT OFF OUT
OFF OFF OFF ON OFF IN ON OUT OFF OUT
Module ON ON ON OFF OUT OFF OUT OFF OUT
Fault ON OFF ON OFF OFF IN ON OUT OFF OUT
Low ON ON ON ON ON OUT OFF OUT OFF OUT
Battery OFF OFF OFF ON ON OUT OFF IN ON OUT
No AC ON ON ON OFF OFF OUT OFF OUT OFF OUT
Power ON OFF ON OFF OFF IN OFF OUT OFF OUT
OFF OFF ON OFF OFF OUT OFF IN OFF OUT
Self ON ON ON ON ON OUT OFF OUT OFF IN
Test
one or more
Self Test
("Test")
Battery Disable
("Low Battery")
Beeper
("Audio Alarm")
Table 1 - Diagnostic Indicator Functions:
List of the diagnostic functions of the 52000
series panels.
Low Battery Indication: An illuminated Yellow LED indicates an abnormally low battery condition.
This may be due to low battery voltage or a missing battery. When this happens the Red warning
LED will flash, the audible beep will sound, and the remote indicator will be enabled. When the user
is alerted to the warning status, the illuminated condition of the Yellow LED and the lighted condition
of all the Green module LEDs denotes a battery fault and not a TVSS module power or fuse fault.
The Disable Battery switch should then be pressed to silence the audible alarm beep, flashing LED,
and remote warning for the battery malfunction. The Yellow LED may remain illuminated as a
reminder that the battery needs replacing. This action re-enables the warning function to continue to
monitor TVSS faults. When the battery is replaced, the Disable Battery switch should be
momentarily pressed. A fresh battery, when the disable battery switch is pressed, will cause the
Yellow LED to turn OFF and will re-enable the Low Battery warning function after pressing the
battery disable switch.
Battery Replacement: Press battery holder and slide battery out. Be sure to follow the battery
polarity marking on the battery compartment.
Test Switch: A “Press to Test Switch” enables the user to test for proper operation of all the
functions described above. When the test switch is held down, the following functions will occur:
• The Yellow low battery LED will illuminate.
•The Red warning LED will flash.
•The audible tone beeper will sound.
•The Remote Supervisor Panel warning indicator (an accessory item), if wired in, will be activated, thus
also testing the Remote Supervisor Panel.
5.Conexión del Conducto: Se recomienda hacer un orificio de 5 cm en el recinto para hacer la
conexión de Entrada y Salida del conducto.
PRECAUCION: EL RECINTO DEBE ESTAR CONECTADO A TIERRA APROPIADAMENTE
USANDO UN ALAMBRE PEQUEÑO DE COBRE #10 AWG DIRIGIDO A LAALETA TERMINAL “G”.
6
.
Conexión de los Conductores - PSTT a la Línea de Energía:
PRECAUCION:
LA SIGUIENTE INSTALACION SE DEBE HACER CON ¡LA ENERGIA
DESCONECTADA! DESCONECTE SIEMPRE LA ENERGIA ANTES DE TRABAJAR CON EL
PANEL PSTT, ASI COMO CUANDO CAMBIA FUSIBLES, O CUANDO INSERTA O CAMBIA
MODULOS REMPLAZABLES.
La terminal a tierra dentro del Panel PSTT se conecta al recinto de metal. Para sistemas a tierra
aislados, el alambre a tierra aislado no se debe conectar a las terminales a tierra de Entrada y
Salida. Sin embargo, como se indica en el paso 5, el recinto se debe conectar a tierra con el
conductor a tierra a la terminal a tierra. Con la energía DESCONECTADA, conecte los
conductores de Fase a L1, L2 y L3 como se indica en el paso 4. Conecte el Neutro a la terminal
neutro, en los sistemas estrella. Conecte el conductor a tierra a la terminal a tierra. Las Fig. 7 y 8
muestran sistemas de conexión alternos que usan interruptor de circuitos (tanto dedicados o que
comparten cargas) o interruptor para desconectar. Los conductores de conexión se deben cortar
del largo y envolver. Evite dobleces puntiagudas. No corte o dañe el aislante del conductor,
excepto las puntas para la conexión.
7.Conexión Remota:
•El circuito de estado del relevador y contactos están capacitados para 5 Amp. La capacidad de
voltaje es 250VCA o 30 VCD. Los contactos acomodan cables de 12 a 20 AWG que se
aseguran a las terminales usando una presión de 3.5 in.-lbs. La capacidad del cableado debe
ser de 600 VCA, protegido y seguro alejado de partes vivas y protegido de filos agudos y el
cierre de la puerta. Corte el agujero del recinto para conexión del conducto. Si la protección de
sobretensión falla, habrá continuidad entre los contactos «NO» y «C».
NOTA: Si ocurre una falla de protección de sobretensión, una sobretensión ha excedido
la capacidad del módulo y debe ser reemplazado inmediatamente.
Fig. 6 – Tres Fases, Ramal Alto Delta (No. de Cat. 52412-DS3)
G L3L1N L2
TVSS
Módulo 3
G
V(L-L)
L1
L3
Módulo 2
Módulo 1
L2 V(L-L)
V(L-N) V(L-N)
240 v
120 v 120 v
(High Leg)
PK-92964-10-02-0A 10/23/02, 11:11 AM10
Page 24 Page 9
FRANÇAIS
Table des matières
SECTION PAGE
DESCRIPTION....................................................................................................10
CARACTÉRISTIQUES........................................................................................ 10
INSTALLATION ................................................................................................... 10
MAINTENANCE .................................................................................................. 16
ENGLISH ..............................................................................................................1
ESPAÑOL ........................................................................................................... 20
NOTA: La corriente de la carga es limitada de acuerdo al tamaño del cable en uso, pero no
puede exceder de 100 Amps. de corriente sostenida máxima.
En la Fig. 3, los Nos. de Cat. 52120-7M3 y 522770-7M3 sólo se deben usar para la configuración
Wye, Trifásica, 4 alambres con tierra. NO lo use con configuración Delta.
En el método 2, Fig. 8, el Panel PSTT está conectado a través de un interruptor de circuitos
dedicado de 30 amps. Para máxima protección de sobretensión, monte el Panel PSTT lo más
cerca posible del panel interruptor de circuitos (no más de 45 cm.). Use cable entrelazado #3 a
#10 AWG. En una variación de esta conexión, el panel interruptor de circuitos también puede
alimentar a la carga conectando el panel PSTT al circuito en una conexión aprobada dentro del
recinto. En este caso, el interruptor de circuitos debe estar capacitado para esta carga. El panel
PSTT debe estar conectado a estos interruptores a través de un interruptor de 30 Amps (mínimo),
3-polos. Esto facilita la desconexión del PSTT para instalación o mantenimiento sin interrumpir la
energía a la carga.
Fig. 4 – Tres Fases, 3-Alambres, Delta (No tierra)
G L3L1N L2
TVSS
Módulo 3
G
V(L-L)
L1
L3 V(L-L)
Módulo 2
Módulo 1
L2 V(L-L)
Fig. 5 – Tres Fases, 3-Alambres con Tierra,
Delta (Ramal de la esquina a tierra)
G L3L1N L2
TVSS
Módulo 3
G
V(L-L)
L1
L3 V(L-L)
Módulo 2
Módulo 1
L2 V(L-L)
PK-92964-10-02-0A 10/23/02, 11:11 AM11
Page 10 Page 23
DESCRIPTION
Le système de protection de panneau 52000 de Leviton est un efficace dispositif limiteur de
surtensions transitoires (DLST) conçu pour les panneaux de distribution et de dérivation.
CARACTÉRISTIQUES
•Modules amovibles enfichables qui en facilitent l’entretien.
•Conception à circuits hybrides.
•Protection contre les surtensions sur toutes les phases.
•Protection en mode commun pour les systèmes en étoile.
•Surveillance diagnostique de chaque module de phase.
•Indicateurs de panne visuels et sonores.
•Raccords prévus pour une unité de télésurveillance optionnelle, permettant le contrôle à distance
de l’état de la protection.
•Conception homologuée UL (sauf le 52347-M3) et certifiée CSA.
•Fonctionnement de 48 à 62 Hz.
•Emplacement conforme aux normes de la CEI (classe III).
•Un point de connexion.
•Compteur de surtensions optionnel avec affichage à cristaux liquides à l’avant du panneau.
INSTALLATION
AVERTISSEMENT : INSTALLER OU UTILISER CONFORMÉMENT AUX CODES DE
L’ÉLECTRICITÉ EN VIGUEUR (INCLUANT LE NEC AMÉRICAIN ET LE CCÉ, LE CAS ÉCHÉANT).
AVERTISSEMENT : À DÉFAUT DE BIEN COMPRENDRE LES PRÉSENTES DIRECTIVES, EN
TOUT OU EN PARTIE, ON DOIT FAIRE APPEL À UN ÉLECTRICIEN QUALIFIÉ.
AVERTISSEMENT : POUR ÉVITER LES RISQUES D’INCENDIE, DE CHOC ÉLECTRIQUE OU
D’ÉLECTROCUTION, COUPER LE COURANT AU FUSIBLE OU AU DISJONCTEUR; S’ASSURER
QUE LE COURANT SOIT BIEN COUPÉ AVANT DE PROCÉDER À L’INSTALLATION.
AVERTISSEMENT : CE DISPOSITIF N’EST PAS UN PARAFOUDRE; IL N’EST PAS CONÇU
POUR RÉSISTER AUX DÉCHARGES ÉLECTRIQUES À PROXIMITÉ IMMÉDIATE OU AUX
SURTENSIONS PROLONGÉES.
AVERTISSEMENT : LE FAIT DE MAL INSTALLER CE DISPOSITIF POURRAIT SE TRADUIRE
PAR DES BLESSURES GRAVES OU MORTELLES OU PAR DES DOMMAGES À L’ÉQUIPEMENT
RACCORDÉ.
MISE EN GARDE : N’UTILISER CE DISPOSITIF QU’AVEC DU FIL DE CUIVRE; EN PRÉSENCE
DE FIL D’ALUMINIUM, UTILISER SEULEMENT LES DISPOSITIFS PORTANT LA MARQUE CO/ALR
OU CU/AL.
REMARQUE : NE PAS UTILISER CE DISPOSITIF À DES ALTITUDES SUPÉRIEURES À
2000 MÈTRES.
REMARQUE : CE DISPOSITIF EST CONÇU POUR FONCTIONNER À L’INTÉRIEUR, À UN TAUX
D’HUMIDITÉ RELATIVE SE SITUANT ENTRE 30 ET 90 %.
REMARQUE : ON RECOMMANDE QUE LES DISPOSITIFS DE LA GAMME 52000 SOIENT
INSTALLÉS PAR UN ÉLECTRICIEN QUALIFIÉ.
NOTA: Tamaño máximo del cable entrelazado #3 AWG.
Esta interconexión de alimentación provee la mejor conexión con relación a la protección de
sobretensión de la carga dedicada. Este tipo de conexión es conveniente cuando los circuitos
derivados alimentan cargas sensitivas que necesitan ser protegidas, tales como sala de
computadoras o un área de instrumentos de electrónica.
NOTA: La protección de los componentes están en paralelo con las cargas.
Monte el Panel PSTT 52000 lo más cerca posible del panel interruptor de circuitos para proveer
máxima protección a los otros circuitos derivados alimentados por otro interruptor de circuitos
dentro del panel interruptor de circuitos. Note que durante la instalación o mantenimiento del
Panel PSTT, el interruptor de circuitos que alimenta al Panel 52000 debe estar abierto, por lo
tanto la energía a la carga estará momentáneamente desconectada.
G L1N L2
TVSS
Módulo 1 Módulo de
Modo Común
G
N
V(L-L)
L1
L2 V(L-N)
V(L-N)
Módulo 2
Fig. 2 – Fase Sencilla (Dividida) 3-Alambres con Tierra
G L3L1N L2
TVSS
Módulo 3
Módulo de
Modo Común
G
V(L-L)
L1
L3
NV(L-N)
V(L-N)
Módulo 2
Módulo 1
L2
V(L-N)
Fig. 3 – Tres Fases, 4-Alambres con Tierra, ESTRELLA
*NOTA: Se usan Seis (6) Fusibles para los
Nos. de Cat. 52120-7M3 y 52277-7M3 Módulo1
*
PK-92964-10-02-0A 10/23/02, 11:11 AM12
Page 22 Page 11
1.Déterminer le dispositif ou la charge à protéger : Le 52000 doit être installé le plus près
possible du panneau électrique qui alimente les charges à protéger, de manière à réduire la
résistance et l’inductance du parcours.
2.Déterminer le type de système électrique – en triangle (Delta) ou en étoile (WYE) : Il est
absolument essentiel que les tensions nominales des modules et des lignes d’alimentation soient
les mêmes. On peut déterminer le type de système en présence en mesurant les tensions simple
(L-N) et composée (L-L).
MISE EN GARDE : CES MESURES PEUVENT ÊTRE DANGEREUSES POUR LES
PERSONNES ET LE MATÉRIEL! S’ASSURER QUE LES TENSIONS MAXIMALES MESURÉES
NE DÉPASSENT PAS LES TENSIONS EFFICACES INDIQUÉES SUR CHAQUE MODULE
AMOVIBLE, À DÉFAUT DE QUOI, CEUX-CI POURRAIENT ÊTRE ENDOMMAGÉS. SE
REPORTER AUX FIGURES 1 À 6.
3.Découper les trous d’accès : Tailler des orifices dans le panneau pour les conduits au moyen
des outils à métaux appropriés. Faire en sorte qu’aucune pièce métallique n’entre à l’intérieur du
panneau; le cas échéant, se servir d’un aspirateur ou d’autres instruments pour les en retirer.
Fixer solidement le dispositif : Se reporter aux directives «
Installation dans le panneau
» ci-
incluses.
Installer le conduit : Le conduit doit être fixé au moyen d’une bague et d’un contre-écrou. Ce
dernier doit être ajusté de manière à ce que la bague soit bien assujettie et que cette dernière,
ainsi que le conduit, pénètre le moins possible dans l’enceinte.
4.Raccorder les fils : En s’assurant que L’ALIMENTATION soit bien COUPÉE, retirer le couvercle
du bornier et raccorder les fils (toronnés, du calibre le plus élevé possible – entre 10 et 3 AWG) tel
qu’illustré au schéma de câblage approprié.
Appliquer le couple approprié au moment de visser les bornes : 35 po-lb (pour les fils de
calibre 10 AWG), 40 po-lb (8 AWG) ou 45 po-lb (6 à 3 AWG).
Le parcours des fils du panneau à disjoncteurs au bornier du 52000 devrait être le plus court
possible (moins de 45 cm [18 po], dans la mesure du possible). Les fils d’alimentation peuvent
être raccordés aux bornes L1, L2 ou L3, sans égard à la phase (A, B ou C), sauf dans le cas d’un
T L3L1N L2
TVSS
Module1
Module en
mode commun
T
N
V(L-N)
L1
Figure 1 – Système monophasé avec neutre mis à la terre
G L1N
TVSS
Módulo1
Módulo de
Modo Común
G
N
V(L-N)
L1
Fig. 1 – Fase Sencilla con Neutro a Tierra
2.Identifique el sistema eléctrico en uso (sistema de voltaje Delta o WYE): Es importante que el
módulo PSTT y los voltaje de línea coordinen. Identifique el sistema en uso midiendo los voltajes
de L-N y L-L.
PRECAUCION: ¡MEDIR EL VOLTAJE PUEDE SER PELIGROSO PARA LA VIDA Y/O
PROPIEDAD!Confirme que los voltaje MAXIMOS NO excedan la capacidad de voltaje RMS de CA
especificada en los módulos reemplazables, porque pueden dañar los módulos. Vea Fig. 1-6.
3.Corte de los huecos de acceso: Corte los huecos para el conducto en el panel usando las
herramientas de metal aprobadas para cortar. Prevenga que filamentos de metal queden dentro
del panel. Si algunos filamentos de metal entran al panel, tenga mucho cuidado para sacarlos,
use una aspiradora o cualquier otra herramienta que sea necesaria.
Montaje Seguro: Vea la hoja de instrucciones
de “Montaje de Panel”
(incluida).
Instalación del Conducto: Instale el conducto con un buje y tuerca de seguridad. La tuerca de
seguridad se debe ajustar de manera que el buje este asegurado apropiadamente y el conducto y
el buje se extiendan lo menos posible dentro del recinto.
4.Conexiones: Con la ENERGÍA DESCONECTADA, quite la cubierta del Bloque Terminal y
conecte los conductores usando el cable entrelazado más grueso posible (#3 a #10 AWG
entrelazado) como se muestra en los diagramas de cableado.
Requerimientos de presión para los tornillos terminales: #10 AWG (35 in.-lbs.), #8 AWG
(40 in.-lbs.), #3-#6 AWG (45 in.-lbs.).
El grueso de los conductores de conexión entre el panel interruptor de circuitos y el bloque
terminal 52000 debe ser mínimo (si es posible menos 45 cm). Los conductores de energía se
deben conectar a L1, L2, L3 sin considerar la Fase A, B o C, excepto por la conexión Delta del
Ramal Alto de Tres Fases. En esta conexión, cualquiera de los conductores de energía pueden
estar conectados a L2 o L3 sin considerar la fase, pero, el conductor del Ramal Alto debe estar
conectado a L1 (Fig. 6). Las Figs. 7 y 8 muestran dos métodos para la conexión del conductor.
En el método 1, Fig. 7, el panel PSTT provee alimentación a través de la una conexión entre el
panel interruptor de circuitos y una carga.
PK-92964-10-02-0A 10/23/02, 11:11 AM13
Page 12 Page 21
système triphasé en triangle de type « High Leg », où le fil d’alimentation de la dérivation
supérieure doit être raccordé à L1, et les deux autres, à L2 ou L3, sans égard à la phase. Les
figures 7 et 8 illustrent ces deux modes de connexion.
Méthode 1 (figure 7) : le panneau à DLST procure un raccord en passage continu entre le
panneau à disjoncteurs et la charge.
REMARQUE : fils toronnés d’un calibre maximal de 3 AWG.
Ce type de raccordement constitue la meilleure connexion en ce qui a trait à la protection de la
charge raccordée. On le recommande dans le cas de dérivation alimentant des appareils délicats
qui requièrent une protection accrue, comme les ordinateurs et les instruments électroniques.
REMARQUE : les dispositifs de protection sont raccordés en parallèle avec les charges.
Le panneau à DLST de Leviton doit être installé le plus près possible du panneau à disjoncteurs
de manière à assurer une protection maximale aux dérivations raccordées aux autres disjoncteurs
du panneau. Il est à noter que lorsqu’on procède à l’installation ou à l’entretien du 52000, les
T L3L1N L2
TVSS
Module 1 Module en
mode commun
T
N
V(L-L)
L1
L2 V(L-N)
V(L-N)
Module 2
Figure 2 – Système monophasé
(phase distincte) trifilaire avec MALT
DESCRIPCION
El Panel de Protección del sistema PSTT 52000, es un Protector de Sobretensión de Voltaje
Transitorio diseñado para ser usado en paneles principales de distribución y circuitos derivados.
CARACTERISTICAS
•Módulos enchufables reemplazables, que facilitan el mantenimiento.
•Diseño de supresión con componente híbrido.
•Protección PSTT en todas las fases.
•Protección PSTT en el modo común para sistemas estrella.
•Monitoreo de diagnóstico en cada fase del módulo.
•Indicadores de falla tanto acústicos como visuales.
•Provisto para operar con un Panel Supervisor Remoto opcional que le permite el monitoreo del
estado del PSTT desde ubicaciones distantes.
•Listado por UL (excepto el No. 52347-M3) y diseño Certificado por CSA.
•Operación de 48-62 Hz.
•Ubicación IEC std: Clase III.
•Una entrada.
•Contador de sobretensión opcional con pantalla frontal LCD.
PARA INSTALAR
ADVERTENCIA: PARA INSTALARSE Y/O USARSE DE ACUERDO CON LOS CODIGOS
ELECTRICOS Y NORMAS APROPIADOS (INCLUYENDO NEC/CEC, SI ES APLICABLE).
ADVERTENCIA: SI USTED NO ESTA SEGURO ACERCA DE ALGUNA DE LAS PARTES DE
ESTAS INSTRUCCIONES, CONSULTE A UN ELECTRICISTA CALIFICADO.
ADVERTENCIA: PARA EVITAR DESCARGA ELECTRICA, FUEGO, O MUERTE, INTERRUMPA
EL PASO DE ENERGIA MEDIANTE EL INTERRUPTOR DE CIRCUITO O FUSIBLE. ¡ASEGURESE
DE QUE EL CIRCUITO NO ESTE ENERGIZADO ANTES DE INICIAR LA INSTALACION!
ADVERTENCIA: ESTE PRODUCTO NO ES UN PARARRAYOS. NO SOBREVIVE GOLPES DE
RAYOS CERCA AL LUGAR O NO SOPORTA SOBREVOLTAJES SOSTENIDOS.
ADVERTENCIA: LA INSTALACION INCORRECTA PUEDE CAUSAR ELECTROCUCION,
HERIDAS PERSONALES Y/O DAÑO A LA PROPIEDAD O EQUIPO.
PRECAUCION: USE ESTE PRODUCTO SOLO CON CABLE DE COBRE O REVESTIDO DE
COBRE. PARA CABLE DE ALUMINIO USE SOLO PRODUCTOS MARCADOS CON EL SIMBOLO
CO/ALR O CU/AL.
NOTA: NO OPERA EN ALTURAS QUE SUPERAN LOS 2000 METROS
NOTA: OPERA EN INTERIORES ENTRE 30-90% DE HUMEDAD RELATIVA.
NOTA: SE RECOMIENDA QUE EL PANEL PROTECTOR DEL SISTEMA PSTT 52000 SEA
INSTALADO POR UN ELECTRICISTA CALIFICADO.
1.Identifique el producto o la carga que se va a proteger: Ubique el panel lo más cerca posible
del panel eléctrico que sirve a la carga que va a proteger, para minimizar la resistencia e
inducción en la longitud de los conductores de conexión.
T L3L1N L2
TVSS
Module 3
Module en
mode commun
T
V(L-L)
L1
L3
NV(L-N)
V(L-N)
Module 2
Module 1
L2
V(L-N)
Figure 3 – Système en étoile triphasé
quadrifilaire avec MALT
*
*REMARQUE:six (6) fusibles sont utilisés
pour les modèles 52120-7M3 et 52277-7M3
PK-92964-10-02-0A 10/23/02, 11:11 AM14
Page 20 Page 13
disjoncteurs lui étant raccordés doivent être ouverts, ce qui coupe temporairement le courant à
leur charge.
REMARQUE : l’intensité du courant dépend du calibre des fils utilisés, mais ici, ne doit pas
dépasser 100 A en service continu.
Dans la figure 3, les modèles 52120-7M3 et 52277-7M3 ne peuvent être utilisés qu’en présence
d’une configuration en étoile triphasée quadrifilaire (avec MALT); NE PAS s’en servir dans une
installation en triangle.
Méthode 2 (figure 8) : le panneau à DLST est raccordé à des disjoncteurs de 30 A désignés.
Pour assurer la meilleure protection, le disjoncteur doit être installé à 45 cm (18 po) ou moins du
panneau à disjoncteurs, par l’entremise de fils toronnés de calibre 10 à 3 AWG. Dans une variante
de ce mode de connexion, les disjoncteurs du panneau peuvent également alimenter une charge
si on raccorde le panneau à DLST au circuit, en le mettant dans un boîtier de connexion approuvé;
T L3L1N L2
TVSS
Module 3
T
V(L-L)
L1
L3 V(L-L)
Module 2
Module 1
L2 V(L-L)
Figure 4 – Système en triangle triphasé
trifilaire (sans MALT)
ESPAÑOL
Tabla de Contenido
SECCION PAGINA
DESCRIPCION ...................................................................................................21
CARACTERISTICAS ..........................................................................................21
INSTALACION .................................................................................................... 21
INSTRUCCIONES DE SERVICIO ...................................................................... 27
FRANÇAIS............................................................................................................ 9
ENGLISH ..............................................................................................................1
Figure 5 – Système en triangle triphasé
trifilaire avec MALT (
Corner Leg
)
T L3L1N L2
TVSS
Module 3
T
V(L-L)
L1
L3 V(L-L)
Module 2
Module 1
L2 V(L-L)
PK-92964-10-02-0A 10/23/02, 11:11 AM15
Page 14 Page 19
dans de telles installations, les valeurs nominales des disjoncteurs doivent correspondre à ceux
de la charge raccordée. Le panneau à DLST doit être relié aux disjoncteurs par l’entremise d’un
sectionneur tripolaire d’au moins 30 A, qui permettra la déconnexion de l’unité sans avoir à couper
l’alimentation de la charge en cas d’entretien ou de nouvelle installation.
5.Fixer les conduits : On recommande de pratiquer un orifice de 5 cm (2 po) pour raccorder les
conduits d’entrée/de sortie.
MISE EN GARDE : L’ENCEINTE DOIT ÊTRE CORRECTEMENT MISE À LA TERRE PAR
L’ENTREMISE D’UN FIL DE CUIVRE D’UN CALIBRE MINIMAL DE 10 AWG RACCORDÉ À LA
BORNE DE MALT (« G »).
6.Raccorder les fils de sortie du DLST à ceux de l’alimentation.
MISE EN GARDE : LES ÉTAPES SUIVANTES DOIVENT ÊTRE EFFECTUÉES SUR UN
CIRCUIT DONT L’ALIMENTATION A ÉTÉ COUPÉE! ON DOIT TOUJOURS COUPER
L’ALIMENTATION AVANT D’EFFECTUER QUELQUES TRAVAUX QUE CE SOIT SUR UN DLST
(REMPLACEMENT DE FUSIBLE, AJOUT OU RETRAIT DE MODULES, ETC.)
La borne de terre du panneau à DLST est raccordée à l’enceinte métallique. Dans le cas de
systèmes à MALT isolée, le fil de terre ne doit pas être raccordé aux bornes d’entrée/de sortie de
terre. Toutefois, tel qu’indiqué en 5, l’enceinte doit être correctement mise à la terre par l’entremise
d’un fil de terre raccordé à la borne de MALT. En s’assurant que le courant soit bien coupé,
raccorder les fils de sortie de phase aux bornes L1, L2 ou L3, conformément aux directives de
l’étape 4. Raccorder le neutre, dans le cas de systèmes en étoile, à la borne de neutre, et le fil de
terre à celle de MALT. Les figures 7 et 8 illustrent les divers modes de connexion par disjoncteurs
(à charges désignées ou réparties) ou par sectionneur. Les fils de sortie doivent être coupés à la
longueur désirée et enroulés. Éviter les courbes trop prononcées. L’isolant des fils ne doit être ni
coupé ni endommagé, sauf aux extrémités dénudées.
Figure 6 – Système en triangle triphasé
«
High Leg
» (modèle 52412-DS3)
T L3L1N L2
TVSS
Module 3
T
V(L-L)
L1
L3
Module 2
Module 1
L2 V(L-L)
V(L-N) V(L-N)
240 v
120 v 120 v
(High Leg)
EXCLUSIONS ET GARANTIE LIMITÉE DE 10 ANS
Leviton garantit au premier acheteur, et uniquement au crédit du dit acheteur, que ce produit
ne présente ni défauts de fabrication ni défauts de matériaux au moment de sa vente par
Leviton, et n’en présentera pas tant qu’il est utilisé de façon normale et adéquate, pendant
une période de dix ans suivant la date d’achat. La seule obligation de Leviton sera de corriger
les dits défauts en réparant ou en remplaçant le produit défectueux si ce dernier est retourné
port payé, accompagné d’une preuve de la date d’achat, avant la fin de la dite période de dix
ans, à la Manufacture Leviton du Canada Limitée, au soin du service de l’Assurance
Qualité, 165 boul. Hymus, Pointe-Claire, (Québec), Canada H9R 1E9. Par cette garantie,
Leviton exclut et décline toute responsabilité envers les frais de main d’oeuvre encourus pour
retirer et réinstaller le produit. Cette garantie sera nulle et non avenue si le produit est installé
incorrectement ou dans un environnement inadéquat, s’il a été surchargé, incorrectement
utilisé, ouvert, employé de façon abusive ou modifié de quelle que manière que ce soit, ou s’il
n’a été utilisé ni dans des conditions normales ni conformément aux directives ou étiquettes
qui l’accompagnent. Aucune autre garantie, explicite ou implicite, y compris celle de qualité
marchande et de conformité au besoin, n’est donnée, mais si une garantie implicite est requise
en vertu de lois applicables, la dite garantie implicite, y compris la garantie de qualité marchande
et de conformité au besoin, est limitée à une durée de dix ans. Leviton décline toute
responsabilité envers les dommages indirects, particuliers ou consécutifs, incluant, sans
restriction, la perte d’usage d’équipement, la perte de ventes ou les manques à gagner, et
tout dommage-intérêt découlant du délai ou du défaut de l’exécution des obligations de cette
garantie. Seuls les recours stipulés dans les présentes, qu’ils soient d’ordre contractuel,
délictuel ou autre, sont offerts en vertu de cette garantie.
Pour toute aide technique, composer le :
1 800 405-5320 (Canada seulement)
www.leviton.com
PK-92964-10-02-0A 10/23/02, 11:11 AM16
Page 18 Page 15
Mode Témoin de Tonalité Télé- Témoins Témoin Bouton Témoin Bouton Témoin Bouton à
défaillance avertisseur de d’état de de de de de action
(Rouge) module la pile désactivation désactivation désactivation désactivation momentané
(Vert) (Jaune)
Normal ÉTEINT(S) ÉTEINT(S) ÉTEINT(S) ALLUMÉ(S) ÉTEINT(S) RESSORTI ÉTEINT(S) RESSORTI ÉTEINT(S) RESSORTI
ÉTEINT(S) ÉTEINT(S) ÉTEINT(S) ALLUMÉ(S) ÉTEINT(S) ENFONCÉ ALLUMÉ(S) RESSORTI ÉTEINT(S) RESSORTI
Défaillance ALLUMÉ(S) ALLUMÉ(S) ALLUMÉ(S) ÉTEINT(S) RESSORTI ÉTEINT(S) RESSORTI ÉTEINT(S) RESSORTI
de module ALLUMÉ(S) ÉTEINT(S) ALLUMÉ(S) ÉTEINT(S) ÉTEINT(S) ENFONCÉ ALLUMÉ(S) RESSORTI ÉTEINT(S) RESSORTI
Pile faible ALLUMÉ(S) ALLUMÉ(S) ALLUMÉ(S) ALLUMÉ(S) ALLUMÉ(S) RESSORTI ÉTEINT(S) RESSORTI ÉTEINT(S) RESSORTI
ÉTEINT(S) ÉTEINT(S) ÉTEINT(S) ALLUMÉ(S) ALLUMÉ(S) RESSORTI ÉTEINT(S) ENFONCÉ ALLUMÉ(S) RESSORTI
Pas ALLUMÉ(S) ALLUMÉ(S) ALLUMÉ(S) ÉTEINT(S) ÉTEINT(S) RESSORTI ÉTEINT(S) RESSORTI ÉTEINT(S) RESSORTI
d’limentation ALLUMÉ(S) ÉTEINT(S) ALLUMÉ(S) ÉTEINT(S) ÉTEINT(S) ENFONCÉ ÉTEINT(S) RESSORTI ÉTEINT(S) RESSORTI
ÉTEINT(S) ÉTEINT(S) ALLUMÉ(S) ÉTEINT(S) ÉTEINT(S) RESSORTI ÉTEINT(S) ENFONCÉ ÉTEINT(S) RESSORTI
Auto- ALLUMÉ(S) ALLUMÉ(S) ALLUMÉ(S) ALLUMÉ(S) ALLUMÉ(S) RESSORTI ÉTEINT(S) RESSORTI ÉTEINT(S) ENFONCÉ
vérification
un ou plus
Auto-
vérification
(“Test”)
Pile désactivée
(“Low Battery”
Tonalité
(“Audio Alarm”)
Tableau 1 - Diverses fonctions diagnostiques :
Fonctions diagnostiques de la gamme 52000.
Figure 7 – Raccordement en passage continu
T L3L1N L2
TVSS
T
L1
L3
L2
N
Conduit
Les DLST
acceptent les
fils toronnés
d'un calibre
pouvant
atteindre
3 AWG
Vers
des
charges
pouvant
atteindre 100 A
T
N
Panneau à disjoncteurs
Système en étoile -
Les systèmes en triangle ne
comprennent pas de ligne neutre
Figure 8 – Raccordement en dérivation
T L3L1N L2
TVSS
T
L1
L3
L2
N
Conduit
Vers les
charges
T
N
Panneau à disjoncteurs
Système en étoile -
Les systèmes en triangle ne
comprennent pas de ligne neutre
Sectionneur
de 30 A
Boîtier de connexion
Retrait de la pile : Appuyer sur le porte-pile et en retirer cette dernière. Lorsqu’on insère une
nouvelle pile, on doit s’assurer de respecter la polarité indiquée sur le compartiment.
Bouton de vérification : Un bouton de vérification permet à l’utilisateur de s’assurer du bon état de
marche de toutes les fonctions décrites ci-dessus. Si on maintient ce bouton enfoncé, les choses
suivantes devraient se produire :
•le témoin jaune d’usure de la pile s’allume;
•le témoin rouge d’avertissement clignote;
•la tonalité se fait entendre;
•l’unité de télésurveillance (téléavertisseur optionnel) s’active, ce qui permet du même coup d’en
vérifier le fonctionnement.
PK-92964-10-02-0A 10/23/02, 11:11 AM17
Fonctions diagnostiques : Le tableau 1 énumère les diverses fonctions diagnostiques des
panneaux de la gamme 52000.
Diagnostic des modules : Chaque module est doté d’un témoin vert pour chaque mode qui,
allumé, indique que le dispositif est bien ancré, que la phase qui l’alimente est sous tension et que le
fusible qui le protège est intact. À la suite d’une panne (témoin vert éteint), on doit remplacer les
modules le plus rapidement possible. En s’éteignant, les témoins indiquent une perte de puissance
ou un fusible grillé suivant une surtension transitoire excessive, comme un coup de foudre direct.
Dans de tels cas, se reporter au tableau de correspondance situé à l’intérieur du couvercle du
panneau pour connaître l’emplacement du fusible correspondant au témoin affecté.
Indication de panne : Les pannes d’alimentation sont indiquées par le clignotement d’un témoin
rouge et l’émission d’une tonalité. Ces pannes peuvent être attribuables à l’absence de courant sur
la phase principale ou au grillage d’un fusible des suites d’un bris de module causé par une
surtension excessive. Le cas échéant, la panne est transmise à un téléavertisseur optionnel par
l’entremise d’une paire de fils à isolation optique de classe II.
REMARQUE (NE S’APPLIQUANT QU’AUX SYSTÈMES EN TRIANGLE) : lorsque le courant est
coupé à une seule des phases (et qu’il n’y a pas de panne au niveau des fusibles ou des
modules), les panneaux d’un système en triangle reviennent en mode monophasé, les
témoins verts restent allumés et l’avertissement diagnostique, désactivé.
Bouton d’arrêt de la tonalité : Lorsqu’une panne a été indiquée et notée par du personnel autorisé,
on peut arrêter la tonalité en appuyant momentanément sur ce bouton. Le témoin rouge
d’avertissement continue alors de clignoter, mais la tonalité s’arrête. Une fois le fusible ou le module
défectueux remplacés, on doit à nouveau appuyer sur le bouton afin de réarmer la tonalité.
Fonction de la pile : La pile alcaline de 9 V sert à alimenter les circuits de diagnostic dans
l’éventualité, fort peu probable, d’une panne au niveau de plusieurs fusibles à la fois. Dans de tels
cas, le témoin rouge d’avertissement se met à clignoter, la tonalité se fait entendre et le
téléavertisseur (le cas échéant) est activé. Si les témoins verts de plusieurs modules sont éteints, il
se peut que les circuits de diagnostic soient alimentés par la pile. Afin de prolonger la durée utile de
cette dernière, on recommande en cas de panne d’appuyer aussitôt que possible sur le bouton
d’arrêt de la tonalité. Une fois les fusibles et les modules remplacés, le témoin rouge devrait
s’éteindre (on doit de nouveau appuyer sur le bouton d’arrêt de tonalité afin de réarmer cette
dernière).
Mise hors circuit de la pile : Le bouton de commande de la pile est réglé en usine à la position
«hors circuit» de manière à ce qu’elle ne se décharge pas continuellement en l’absence de courant.
Lorsqu’on alimente le dispositif pour la première fois, le témoin rouge de mise hors circuit et le jaune
d’usure de la pile devraient s’allumer; on doit alors appuyer sur le bouton de commande pour activer
la pile (les deux témoins devraient s’éteindre).
Indication d’usure de la pile : Si le témoin jaune de la pile s’allume, c’est qu’aucun courant n’est
perçu de cette dernière (elle est trop usée ou n’a pas été installée). Dans de tels cas, le témoin
d’avertissement rouge devrait se mettre à clignoter, la tonalité, se faire entendre, et le
téléavertisseur (le cas échéant), s’activer pour signaler le problème à l’utilisateur. Quand le témoin
jaune et les témoins verts de tous les modules sont allumés, il s’agit d’une panne de pile, non de
module ou de fusible. On doit alors appuyer sur le bouton de mise hors circuit de la pile afin d’arrêter
les mécanismes d’avertissement (le témoin jaune reste cependant allumé afin de rappeler à
l’utilisateur que la pile doit être remplacée); ce geste réarme les fonctions diagnostiques du système
de protection lui-même. Une fois la pile remplacée, on doit également appuyer momentanément sur
le bouton de mise hors circuit de la pile. Une fois cette démarche effectuée, le témoin jaune devrait
s’éteindre et la fonction d’avertissement d’usure de la pile, être rétablie.
Page 16 Page 17
7.Raccorder une unité de télésurveillance :
•Les valeurs nominales des contacts et du circuit de relais d’état sont de 250 V c.a. ou de
30 V c.c., à une intensité de 5 ampères. Les contacts conviennent aux fils d’un calibre de 20 à
12 AWG, lesquels sont raccordés aux bornes en appliquant un couple de 3,5 po-lb. Le câblage
doit pouvoir supporter une tension de 600 V c.a., et être paré, gardé à l’écart des pièces sous
tension et protégé des aspérités et des fermetures de porte. Un trou doit être pratiqué dans
l’enceinte pour le passage d’un conduit. En cas de panne de protection, la continuité est
maintenue entre les contacts «NO» (normalement ouvert) et «C» (fermé).
REMARQUE : si une panne de limitation survient, c’est qu’une surtension transitoire a
dépassé les valeurs nominales du module, lequel doit aussitôt être remplacé.
•On recommande de pratiquer un trou de 2,2 cm (7/8 po) du côté articulé de l’enceinte pour
permettre le raccordement de l’unité de télésurveillance. Se reporter aux directives concernant
l’installation de cette dernière.
8.Installer la pile : Une pile alcaline de 9 V est comprise dans le carton d’expédition. Cette pile sert
à alimenter les circuits d’avertissement dans le cas de pannes d’alimentation ou de plusieurs
fusibles en même temps. Retirer le porte-pile du mécanisme de diagnostic. Insérer la pile de 9 V
(en s’assurant de respecter la polarité inscrite dans le compartiment) et remettre le porte-pile en
place.
9.Fixer les modules et remettre le couvercle du bornier. S’assurer que les modules soient bien
ancrés et retirer toute matière étrangère de l’enceinte. Fermer solidement la porte de cette
dernière avant de rétablir le courant.
10. Activer le système en rétablissant le courant : Les indicateurs d’état verts des modules
devraient s’allumer et être visibles à travers les orifices de la porte de l’enceinte; tous les autres
témoins devraient être éteints. En cas de problèmes impossibles à régler suivant la Procédure
de diagnostic des anomalies inscrite sur la porte de l’enceinte, on peut composer le numéro
d’assistance technique de Leviton, soit le 1 800 405-5320 (au Canada seulement).
11. Effectuer une vérification diagnostique : Appuyer sur le bouton de vérification en le
maintenant enfoncé. Le témoin rouge d’avertissement devrait clignoter et la tonalité, se faire
entendre. Le témoin jaune d’usure de la pile devrait lui aussi s’allumer, et l’indicateur de l’unité
de télésurveillance, le cas échéant, devrait s’activer. Relâcher le bouton de vérification.
12. Vérifier le fonctionnement du compteur de surtensions : Si le panneau utilisé est doté d’un
compteur de surtensions à l’avant, appuyer sur le bouton de réinitialisation («
Reset
») du
compteur, puis sur le bouton de vérification («
Test
»); l’affichage devrait indiquer une surtension
chaque fois que ce dernier est enfoncé. On doit également utiliser le bouton de réinitialisation
lorsque le nombre maximal de surtensions est affiché (le témoin rouge est allumé); ce bouton
permet en outre d’effacer l’affichage en tout temps.
DIRECTIVES DE MAINTENANCE
Procédure d’entretien relative au DLST 52000 de Leviton : On doit lire attentivement les
directives suivantes, de même que celles relatives au remplacement des fusibles ou des modules,
avant de procéder à l’entretien ou à la réparation du DLST.
MISE EN GARDE : ON DOIT COUPER LE COURANT AU FUSIBLE OU AU DISJONCTEUR
AVANT D’OUVRIR LA PORTE DE L’ENCEINTE DU DLST. LE NON-RESPECT DES PROCÉDURES
DE MAINTENANCE POURRAIT ENGENDRER DES DOMMAGES MATÉRIELS ET DES
BLESSURES GRAVES OU MORTELLES; ON RECOMMANDE QUE LE SYSTÈME DE LIMITATION
52000 SOIT TOUJOURS ENTRETENU ET RÉPARÉ PAR UN ÉLECTRICIEN QUALIFIÉ.
PK-92964-10-02-0A 10/23/02, 11:11 AM18

Other Leviton Surge Protector manuals

Leviton 37120-7 User manual

Leviton

Leviton 37120-7 User manual

Leviton 51240-WM User manual

Leviton

Leviton 51240-WM User manual

Leviton 51020-WMT User manual

Leviton

Leviton 51020-WMT User manual

Leviton 47120-7 User manual

Leviton

Leviton 47120-7 User manual

Leviton 51110-PTC User manual

Leviton

Leviton 51110-PTC User manual

Leviton 51005-WM User manual

Leviton

Leviton 51005-WM User manual

Leviton 5480 User manual

Leviton

Leviton 5480 User manual

Leviton 57000-M3S User manual

Leviton

Leviton 57000-M3S User manual

Leviton 51005-WM User manual

Leviton

Leviton 51005-WM User manual

Leviton 37120-7 User manual

Leviton

Leviton 37120-7 User manual

Leviton 5480-IG User manual

Leviton

Leviton 5480-IG User manual

Leviton 3862-CON User manual

Leviton

Leviton 3862-CON User manual

Leviton 57000 Series User manual

Leviton

Leviton 57000 Series User manual

Leviton 51120-1 User manual

Leviton

Leviton 51120-1 User manual

Leviton R Series User manual

Leviton

Leviton R Series User manual

Leviton 32120-DY3 User manual

Leviton

Leviton 32120-DY3 User manual

Leviton 51015-WM User manual

Leviton

Leviton 51015-WM User manual

Leviton 55240-ASA User manual

Leviton

Leviton 55240-ASA User manual

Leviton 3803-MOD User manual

Leviton

Leviton 3803-MOD User manual

Leviton 37120-7 User manual

Leviton

Leviton 37120-7 User manual

Leviton SmartlockPro GSIA2 User manual

Leviton

Leviton SmartlockPro GSIA2 User manual

Leviton 3880-DIN User manual

Leviton

Leviton 3880-DIN User manual

Leviton 51120-3R User manual

Leviton

Leviton 51120-3R User manual

Leviton 3812 User manual

Leviton

Leviton 3812 User manual

Popular Surge Protector manuals by other brands

CPT PSC1 Series installation instructions

CPT

CPT PSC1 Series installation instructions

North Shore Safety LineGard PGFS-13105 INSTALLATION AND TESTING PROCEDURE

North Shore Safety

North Shore Safety LineGard PGFS-13105 INSTALLATION AND TESTING PROCEDURE

M-system MD7PM instruction manual

M-system

M-system MD7PM instruction manual

Total Protection Solutions LoadTrack TK-LTL120P-30A Installation, operation and maintenance manual

Total Protection Solutions

Total Protection Solutions LoadTrack TK-LTL120P-30A Installation, operation and maintenance manual

Intermatic IG1240RC user manual

Intermatic

Intermatic IG1240RC user manual

Delta LA302R Installation

Delta

Delta LA302R Installation

Tripp Lite TLP602 Specifications

Tripp Lite

Tripp Lite TLP602 Specifications

Black Box SP070A quick start guide

Black Box

Black Box SP070A quick start guide

Tripp Lite VR1208R owner's manual

Tripp Lite

Tripp Lite VR1208R owner's manual

watt box WB-600-FP owner's manual

watt box

watt box WB-600-FP owner's manual

Tripp Lite SPS415HGULTRA owner's manual

Tripp Lite

Tripp Lite SPS415HGULTRA owner's manual

Tripp Lite B110-SP-CAT quick start guide

Tripp Lite

Tripp Lite B110-SP-CAT quick start guide

Tripp Lite MT-6PLUS Specification sheet

Tripp Lite

Tripp Lite MT-6PLUS Specification sheet

watt box WB-11-LIGHT Manual instructions

watt box

watt box WB-11-LIGHT Manual instructions

Tripp Lite TLP808TEL Specifications

Tripp Lite

Tripp Lite TLP808TEL Specifications

Tripp Lite Data Shield DB25-ALL Specifications

Tripp Lite

Tripp Lite Data Shield DB25-ALL Specifications

Tripp Lite TR-6 Specifications

Tripp Lite

Tripp Lite TR-6 Specifications

Rocket Fish RF-PCS7ES13 Guide d'installation rapide

Rocket Fish

Rocket Fish RF-PCS7ES13 Guide d'installation rapide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.