manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Eurotherm
  6. •
  7. Controllers
  8. •
  9. Eurotherm 3508 User manual

Eurotherm 3508 User manual

•mV range +40mV or +80mV
•High level range 0 – 10V
•High Impedance mid level range 0 – 2V. Used for zirconia probe oxygen input.
•A line resistance for voltage inputs may cause measurement errors
Built in Relay (AA)
•Relay shown in de-energised state
•Isolated 240Vac
•Relay rating: Max: 264Vac 2A resistive; min: 1V, 1mAdc to provide sufficient
whetting current.
-
+
V+
V-
Standard Connections
These are connections which are common to all instruments in the range.
PV Input (Measuring Input)
1. Run input wires separate from power cables
2. When shielded cable is used, it should be grounded at one point only
3. Any external components (such as zener barriers, etc) connected between sensor and input terminals
may cause errors in measurement due to excessive and/or un-balanced line resistance or possible
leakage currents
4. This input is not isolated from logic I/O A and logic I/O B
Thermocouple or Pyrometer Input
•Use the correct type of thermocouple compensating cable, preferably
shielded, to extend wiring
•It is not recommended to connect two or more instruments to one
thermocouple
•The resistance of the three wires must be the same
•The line resistance may cause errors if it is greater than 22Ω
Note 1: The RTD wiring is not the same as 2400 series instruments. It is the
same as 26/2700 series
Note 2: For 2-wire this is a local link
RTD Input
VI
V+
V-
Note 2
Linear Input V, mV and High Impedance V
+80mV
0 – 2V
0 – 10V
V+
V-
•For mA input connect the 2.49Ωresistor supplied across the input terminals
•The resistor supplied is 1% accuracy 50ppm temperature coefficient
•A resistor 0.1% accuracy 15ppm resistor can be ordered as a separate item.
Part No. SUB35/ACCESS/249R.1
Linear Input mA
0 – 20mA
4 – 20mA
V+
V-
Digital I/O
These terminals may be configured as logic inputs, contact inputs or logic outputs in any combination.
It is possible to have one input and one output on either channel.
!The Digital IO is not isolated from the PV input. The controller is designed to
operate normally if the input sensor is connected to 240Vac, but in this case these terminals will
be at this potential.
Logic Inputs
•Voltage level logic
inputs, 12V, 5-40mA
Active > 10.8V
Inactive < 7.3V
LA
LB
LC
Input 1
Input 2
Common
Contact Closure Inputs
•Contact open
>1200Ω
•Contact closed
<480Ω
LA
LB
LC
Input 1
Input 2
Common
LA
LB
LC
Output 1
Output 2
Common
Digital (Logic) Outputs
•The logic outputs are capable of driving SSR or thyristors up to 9mA,
18V. It is possible to parallel the two outputs to supply 18mA, 18V.
The fixed digital logic outputs may be used to power remote 2 wire transmitters. The fixed digital
I/O are, however, not isolated from the PV input circuit, so this does not allow the use of 3 or 4 wire
transmitters. An isolated module must be used for the 3 and 4 wire types.
Digital (Logic) Outputs used to power a remote 2 wire transmitter.
The parallel logic outputs supply >20mA, 18V.
Connect the supplied load resistor equal to 2.49Ωfor mA
input
Isolated Transmitter Option
module +24V >20mA
xA
xB
3 Wire
Transmitter
V+
V-
4- 20mA
2.49Ω
+
-
Digital (Logic) Output modules used to power remote 3 or 4 wire transmitters.
LA
LB
Output 1
Output 2
4
-
20mA
2 Wire
Transmitter
2.49Ω
V+
V
-
xA
xB
4 Wire
Transmitter
V+
V-
4- 20mA
2.49Ω
+
-
Isolated Transmitter Option
module +24V >20mA
AA
AB
AC
Plug in I/O modules can be fitted in three positions in the 3508 and six positions in 3504. The
positions are marked Module 1, 2, 3, 4, 5, 6. With the exception of the Analogue Input module, any
other module listed in this section, can be fitted in any of these positions. To find out which
modules are fitted check the ordering code printed on a label on the side of the instrument. If
modules have been added, removed or changed it is recommended that this is recorded on the
instrument code label.
•Hardware Code: R2 and RR
•Rating of relays: 2A, 264Vac max or 100mA, 12V
min to provide sufficient whetting current.
Plug in I/O Module Connections
Relay (2 pin) and Dual Relay Module
Change Over Relay
Voltage
supply
Contactor,
Relay, Panel
lamp etc
xC
xD
xA
xB
_
+
+
+
Common
-
+
Output A
Output B
Output C
SSR or
thyristor
unit xC
xD
xA
xB
Second triac
First triac
Voltage
supply
Motorised
valve
Raise
Lower
xC
xD
xA
xB
Voltage
supply
First relay
Second relay (dual relay only)
xA
xB
xC
xD
Contactor
Relay Panel
lamp etc
Contactor
Relay Panel
lamp etc
•Hardware Code: R4
•Relay Rating: 2A, 264Vac max or 100mA, 12V
min to provide sufficient whetting current.
Triple Logic and Isolated Single Logic Output
•Hardware Code: TP and LO
•Outputs Rating: (18Vdc at 8mA max.)
•No channel isolation.
•Single Logic Output connections: D – Common
A – Logic Output
Triac and Dual Triac
•Hardware Code: T2 and TT
•Combined Output Rating: 0.7A, 30 to 264Vac
•Dual relay modules may be used in place of dual triac.
•The combined current rating for the two triacs
must not exceed 0.7A
Dual DC Output (Slots 1, 2 and 4 only)
•Hardware Code: DO
•Output Rating: each channel can be 4-20mA
or 24Vdc power supply)
High Resolution DC Retransmission & Transmitter Power Supply (Slots 1, 2 and 4 only)
•Hardware Code: HR
•Output Rating: Channel 1 (15 bit 4-20mA).
Channel 2 (24Vdc)
Snubbers
Snubbers are used to prolong the life of relay contacts and to reduce interference when switching
inductive devices such as contactors or solenoid valves. The fixed relay (terminals AA/AB/AC) is
not fitted internally with a snubber and it is recommended that a snubber be fitted externally. If
the relay is used to switch a device with a high impedance input, no snubber is necessary.
All relay modules are fitted internally with a snubber since these are generally required to switch
inductive devices. However, snubbers pass 0.6mA at 110V and 1.2mA at 230Vac, which may be
sufficient to hold on high impedance loads. If this type of device is used it will be necessary to
remove the snubber from the circuit.
The snubber is removed from the relay module as follows:-
1. Unplug the controller from its sleeve
2. Remove the relay module
3. Use a screwdriver or similar tool to snap out the track.
The view shows the tracks in a Dual Relay Output module.
Break out
tracks as
required to
disconnect
the snubber
-
+
-
+
Output 1
Output 2
20V
–
30V
4-20mA
xA
xB
xD
xC
-
+
-
+
Output 1
Output 2
20V
–
30V
4
-
20mA
xA
xB
xD
xC
For module functionality see ‘Quick Code’.
The function of the connections varies depending on the type of module fitted in each position and
this is shown below.
Note: The order code and terminal number is pre-fixed by the module number (x). For example,
Module 1 is connected to terminals 1A, 1B, 1C, 1D; module 2 to 2A, 2B, 2C, 2D, etc.
•All modules are isolated 240Vac CATII.
Wiring
Wire Sizes
The screw terminals accept wire sizes from 0.5 to 1.5
mm (16 to 22AWG) and should be tightened to
0.4Nm (3.5lb in). Hinged covers prevent hands or
metal making accidental contact with live wires.
1. Cut out the panel to the size shown.
To Remove the Controller from its Sleeve
Ease the latching ears outwards and pull the controller forward.
When plugging back in ensure that the latching ears click into place to maintain the IP65 sealing
Installation
Panel cut out
3504 controller A x A
A 92mm (- 0.0 + 0.8)
3.62inch (-0.00,+0.03)
3508 controller A x B
B 45mm (- 0.0 + 0.6)
1.77inch (-0.00,+0.02)
2. Fit the IP65 sealing gasket behind the front bezel of the instrument
3. Insert the instrument in its sleeve through the cut-out.
4. Spring the panel retaining clips into place. Secure the instrument in position by holding it level
and pushing both retaining clips forward.
5. Peel off the protective cover from the display
If the panel retaining clips subsequently need removing, they can be unhooked from the side with
either your fingers or a screwdriver.
Parts Supplied and Dimensions
3508 and 3504 Process Controllers
This instrument is intended for permanent installation, for indoor use only, and to be enclosed in an
electrical panel.
Select a location where minimum vibrations are present and the ambient temperature is within 0 and
50oC (32 and 122oF).
The instrument can be mounted on a panel up to 15mm thick.
To assure IP65 and NEMA 4 front protection, use a panel with smooth surface texture.
Please read the safety information before proceeding and refer to the EMC Booklet part number
HA025464. For details not covered in this guide a 3500 Engineering Manual part no. HA027988 is
available. These documents may be downloaded from www.eurotherm.co.uk.
ENG
HA030143/1 CN25273 03/09
PV Input
Digital
Inputs/
Outputs
Live or 24V (2)
Neutral or 24V (2)
Ground
Logic I/O A
Logic I/O B
Logic I/O Com
Polarising Keys (1). One per module
COMMS MODULE H
COMMS MODULE J
MODULE 1
MODULE 2
MODULE 3
MODULE 4
MODULE 5
MODULE 6
Power
Supply
Fixed Relay
(form C)
PV Input
T/C RTD mV mA
3504 (1) Polarising keys are intended to prevent modules,
not supported by this controller, from being fitted.
Supported modules are defined by the order code -
the
arrow on the polarising key points in the upward
direction when these are fitted. An example of an
unsupported module is
an unisolated module (coloured
red) from a 2400 series controller. It is possible to fit
such a module but it is the users responsibility to
ensure that it is safe to install it in the particular
application. When this has been verified the polarising
key may be adjusted with a screwdriver to point in the
down direction.
A 96mm 3.78inch
B 48mm 1.89in
C 12.5mm 0.5in
D 150mm (5.91in)
A
Latching
ears Panel retaining
clips
Label
B A Controller sleeve
Terminal
block with
covers
D
C
2.49Ωresistors are
also supplied for
each mA input
(Not to scale)
C
D
A
A
B
Recommended
Minimum Spacing
C
10mm (0.4in)
D
38mm (1.5in)
35043508
Polarising Keys (1). One per module
Instrument Terminals
Live or 24V (2)
Neutral or 24V (2)
Ground
Logic I/O A
Logic I/O B
Logic I/O Com
MODULE 1
MODULE 2MODULE 3
Power
Supply
Digital
Inputs/
Outputs
Fixed Relay
(form C)
3508
T/C RTD mV mA
COMMS MODULE H
COMMS MODULE J
•Hardware Code: D4
•Output Rating: (10Vdc, 20mA max)
DC Control
DC Retransmission
•Hardware Code: D6
•Output Rating: (10Vdc, 20mA max)
Triple Logic Input
•Hardware Code: TL
•Input Ratings: Logic inputs <5V OFF >10.8V ON
Limits: -3V, +30V
Triple Contact Input
•Hardware Code: TK
•Input Ratings: Logic inputs >28KOFF <100ON
24V Transmitter Power Supply
•Hardware Code: MS
•Output Rating: 24Vdc 20mA
Potentiometer Input
•Hardware Code: VU
•Rating: 100Ωto 15KΩ
Plug in I/O Module Connections (continued)
Transducer Power Suppy
Transducer with Internal Calibration Resistor
Actuator
0-20mA
or
0-10Vdc
-
+
xA
xB
To other
controllers
0-20mA
or
0
-
10Vdc
-
+
xA
xB
Common
Input 1
Input 3
Input 2
xA
xB
xD
xC
Common
Input 1
Input 3
External
Switches
or Relays
xA
xB
xD
xC
Input 2
+0.5V
0V
xA
xB
xD
xC
•Hardware Code: G3
•Rating: Configurable 5V
or 10Vdc.
•Minimum load resistance
300Ω
+
-
Transmitter
xA
xB
B
10Vdc
power
supply
+
-
mV Input
V- V+
A
Internal
switch to
connect
Rcal
R
CAL
V+
V-
xA
xB
xC
xD
Transducer
Controller
Red
Black
Green
White
Red
30.1KΩ
Transducer
B
10Vdc
power
supply
+
-
mV Input
Controller
V- V+
A
Internal
switch to
connect
Rcal
Black
Green
White
xA
xB
xD
xC
V+
V-
Transducer with External Calibration Resistor
Input if an analogue input module is used in
the appropriate slot.
C
D
Switch On
If the Controller is new and has not previously
been configured it will start up showing the ‘Quick
Start’ codes. This is a built in tool which enables
you to configure the input type and range, the
output functions and alarms.
!Incorrect configuration can result in
damage to the process and/or personal injury
and must be carried out by a competent person
authorised to do so. It is the responsibility of
the person commissioning the instrument to
ensure the configuration is correct.
To Configure Parameters in Quick
Start Mode
With ‘QckStart’ selected, press to scroll
through a list of parameters.
Edit the parameters using Vor .
When the required choice is selected a brief blink
of the display indicates that it has been accepted .
The first parameter is ‘Units’.
This parameter is associated
with Loop 1 ‘LP1’ and resides
in the ‘PV Input’ list as shown.
Continue setting up the paras presented until the
‘Finished’ view is displayed.
If all parameters are set up as required press V
or to select ‘Yes’.
The loop(s) are set to Auto on exit from Quick
Start and the controller re-starts in operator level
2.
The ‘HOME’ display is shown - see ‘Normal
Operation’.
☺If you wish to edit parameters again do not
select ‘Yes’ but continue to press .
All available parameters are shown in the following
tables.
Quick Start Parameters - Fixed Build Parameters shown in bold are defaults.
Group Parameter Value Availability
LP1
PV Input
Units
Engineering units for the PV. (C, F, K
options change the displayed units)
C, F, K
V. mV, A, mA, pH, mmHg, psi, Bar, mBar, %RH, %, mmWG, inWG, inWW, Ohms,
PSIG, %O2, PPM, %CO2, %CP, %/sec, Vacuum, sec, min, hrs, None
Always
LP1
PV Input
Resolution
Decimal point position for the PV
XXXXX, XXXX.X, XXX.XX, XX.XXX, X.XXXX Always
LP1
PV Input
Range Type
To select the linearisation algorithm
required and the input sensor.
Thermocouple: J, K, L, R, B, N, T, S, PL2, C, CustC1(2&3)
RTD: Pt100
Linear: 0-50mV, 0-5V, 1-5V, 0-10V, 2-10V, 0-20mA, 4-20mA
Always
LP1
PV Input
IO Type
Only shown if custom curve is selected
Thermocpl, RTD, Pyrometer, mV40, mV80, mA, Volts, HIZVolts, Log10
LP1
PV Input
Range High/Low
Max /min. display range and SP limits
Depends on Range type selected. Default 1372/-200 Always
LP1
Loop
Loop 1 Channel 1, control type (normally
Heat)
PID, VPU, VPB, Off,
OnOff
Always
LP1
Loop
Loop 2 Channel 2, control type (normally
Cool)
PID, VPU, VPB, Off,
OnOff
VPU = Boundless valve position control. This does not
need a feedback potentiometer
VPB = Bounded valve position control. Requires a
feedback potentiometer
Always
LP2
PV Input
Source
Defines where the PV input is wired to
None, FixedPV, Module6 (Module6 is available only if an analogue input module
is fitted).
If a dual loop
controller
The LP1 parameters listed above are repeated for LP2 if the LP2 PV Input is configured.
Logic function (input or output)
To configure the function of Logic IO which
can be an output or an input.
Not Used, Lp1 Ch1, Lp1 Ch2, Lp2 Ch1, Lp2 Ch2,
Alarm1 to 8, AnyAlarm, NewAlarm, ProgEvnt1 to 8,
LP1SBrkOP, LP2SBrkOP*, LPsSBrk*, (outputs)
LP1 A-M, LP1 SPsel, LP2 A-M, LP2 SPsel, AlarmAck,
ProgRun, ProgReset, ProgHold (Inputs)
[Note 1] [Note 2]
* LP2 and LPs (both loops) only shown if
the second loop is configured.
Programmer options only available if the
controller is a programmer/controller.
Init
LgcIO LA
Min OnTime (if configured as a control OP) Auto, or 0.01 to 150.00 [Note 2] [Note 3]
The above two parameters are repeated for the LB Logic I/O (LgcIO LB)
Init
RlyOP AA
AA Relay output
function
This relay is always fitted.
Not Used, Lp1 Ch1, Lp1 Ch2, Lp2 Ch1, Lp2 Ch2, Alarm 1 to 8, Any
Alarm, New Alarm, ProgEvnt1 to 8, LP1SBrkOP, LP2SBrkOP*, LPsSBrk*.
Always if the instrument Is ordered as a
programmer/controller. [Note 4]
Init
RlyOP AA
AA Relay Min OnTime Auto, or 0.01 to 150.00 [Note 2] [Note 3]
Note 1) Parameters only appear if the function has been turned on, eg If ‘Control Channel 1’ = ‘Off’, ‘Chan 1’ does not appear in this list. When a control
channel is configured for valve positioning, LgcIO LA and LgcIO LB act as a complementary pair. If, for example, Chan 1 is connected to LgcIO LA
(valve raise) then LgcIO LB is automatically set to Chan 1 (valve lower). This ensures the valve is never raised and lowered simultaneously.
The same complementary behaviour also applies to dual output modules and channels A and C of triple output modules
Note 2) If any input function, for example Chan 1, is connected to another input it will not appear in this list
Note 3) Is available if the Control Channel is not On/Off and is allocated to the LA, LB or AA output as applicable
Note 4) For valve position control Chan 1 or Chan 2 will not appear in this list. Valve position outputs can only be dual outputs such as LA and LB or dual
relay/triac output modules
To Re-enter Quick Start Mode
If you have exited from Quick Start mode (by selecting ‘Yes’ to the ‘Finished’ parameter) and you need to make further changes, the Quick start mode can be entered again at any time.
1. Hold down then power up the controller. Keep this button pressed until the ‘Startup’ - ‘Goto QckStart’ screen is displayed.
2. Press to enter the quick start list. You will then be asked to enter a passcode.
3. Use Vor Wto enter the passcode – default 4. If an incorrect code is entered the display reverts to the ‘Quick Start’ view.
It is then possible to repeat the quick configuration as described previously.
Note: The Quick Start view contains two additional parameters - ‘Cancel’ and ‘Config’.
Select Cancel to revert to normal operating mode.
Config will allow full configuration mode to be entered (after entering the correct pass code). Configuration is described in the Engineering Manual HA027988.
Quick Start Parameters -Alarms Parameters shown in Bold are defaults.
Group Parameter Value Availability
None No alarm type configured
Abs High/Low Absolute high/low
Init
Alarm 1 to 8
Type
Dev High/ Low/ Band
Deviation high/ low/ band
Always
None Not connected
PV Input Connected to main process variable does not appear if Alarm Type = Deviation
LP1/2 PV Connected to Loop 1/2 process variable
Init
Alarm 1 to 8
Source
Module1 - Module6 Connected to an analogue input module and only of the Alarm Type is not a deviation alarm
Always if Type ≠None
PV Input and ModX Ip do not
appear if Type = Deviation
Init
Alarm 1 to 8
Setpoint To adjust the alarm threshold within the range of the source. Always if Type ≠None
None No latching
Auto Automatic
latching
The alarm continues to be active until both the alarm condition is removed AND the alarm is
acknowledged. The acknowledgement can occur BEFORE the condition causing the alarm is removed.
Manual Manual latching The alarm continues to be active until both the alarm condition is removed AND the alarm is
acknowledged. The acknowledgement can only occur AFTER the condition causing the alarm is removed.
Init
Alarm 1 to 8
Latch
Event Alarm beacon does not light but any output associated with the event will activate and a scrolling message will appear.
Always if Type ≠None
No Continue back around the quick configuration listFinished Exit
Yes Go to normal operation. The loop(s) are set to Auto on exit from quickstart mode and the controller re-starts in Level 2.
Quick Start Parameters - Plug in I/O Modules
The controller automatically displays parameters applicable to the module fitted - if no module is fitted in a slot then it does not appear in the list.
Each module can have up to three inputs or outputs. These are shown as A, B or C after the module number and this corresponds to the terminal numbers on the back of the instrument. If the I/O is single only A
appears. If it is dual A and C appears if it is triple A, B and C appear.
Note: If an incorrect module is fitted the message ‘Bad Ident’ will be displayed.
Module type Parameter Value Availability
Change over relay (R4)
2 pin relay (R2)
Triac output (T2)
Dual Relay (RR)
Dual triac output (TT)
Relay (Triac) function
Not Used
All parameters the same as RlyOP AA, including Min OnTime if the OP is a relay
Always (if the module is fitted)
Single Logic Output (LO)
Triple Logic Output (TP)
Logic Out function Not Used
All parameters the same as RlyOP AA
Always (if the module is fitted)
Not Used Module fitted but not configured
LP1/2 Ch1/2OP Loop 1/2 Channel 1/2 control output
LP1/2 SP Tx Loop 1/2 setpoint retransmission
LP1/2 PV Tx Loop 1/2 PV retransmission
LP1/2 ErrTx Loop 1/2 error retransmission
DC Output function
LP1/2 PwrTx Loop 1/2 output retransmission
Range Type 0–5V, 1-5V, 1–10V, 2–10V, 0-20mA, 4-20mA
DC Output (D4)
DC Retransmission (D6)
Display High/low 100.0/0
Always (if the module is fitted).
Note: If a Dual DC Output module is fitted, it cannot be
configured using the Quick Start Code. To configure this module
refer to the Engineering Manual part no. HA027988.
Not Used Module fitted but not configured
LP1/2 A-M Loop 1/2 Auto/manual
LP1/2 SPsel Loop 1/2 SP select
LP1/2 AltSP Loop 1/2 Alternative SP select
AlarmAck Alarm acknowledge
Triple Logic Input (TL)
Triple Contact Input (TK)
Logic In function
ProgRun/Reset/Hold
Programmer run/reset/hold
A function can only be allocated to one input. eg if AlarmAck is
configured on X*A it is not offered for the other inputs
* is the module number.
LP2 does not appear if loop 2 is not configured.
Not Used Module fitted but not configured
LP1/2 AltSP Loop 1/2 alternative setpoint
LP1/2 OPH/L Loop 1/2 remote OP power max/min
Analogue IP function
LP1/2 V1/2Pos To read valve position from the feedback potentiometer loop 1/2
LP1/2 V1Pos and LP1/2 V2Pos only appear if Loop 1 or 2 and the
control channel 1 or 2 is set to VPB.
Alt/SP does not appear if the programmer option is supplied.
LP2 does not appear if loop 2 is not configured.
Range Type Thermocouple: J, K, L, R, B, N, T, S, PL2, C. RTD: Pt100
Linear: 0-50mV, 0-5V, 1-5V, 0-10V, 2-10V, 0-20mA, 4-20mA Not shown if analogue IP function not used
Analogue Input (AM)
Display High/low 100.0/0.0 These parameters only appear for Linear Range
Not Used Module fitted but not configured
LP1/2 AltSP Loop 1/2 Alternative setpoint
LP1/2 OPH/L Loop 1/2 output power maximum/ minimum
Potentiometer Input (VU) Pot Input function
LP1/2 V1/2Pos To read valve position from the feedback potentiometer loop 1/2
LP1/2 V1Pos and LP1/2 V2Pos only appear if Loop 1 or 2 and the
control channel 1 or 2 is set to VPB.
Alt/SP does not appear if the programmer option is supplied.
LP2 does not appear if loop 2 is not configured.
Transducer Power Supply (G3) TdcrPSU function 5 Volts or 10 Volts Always (if the module is fitted)
Transmitter power supply (MS) No parameters. Used to show the ID of the module if fitted
Normal Operation
Switch on the controller. Following a brief self-test sequence, the controller will start up
in AUTO mode and show the ‘HOME’ display in Operator Level 2 (following Quick Start).
If the controller is configured as a dual loop instrument the start up view shows a
summary of the two loops.
Note: Views shown in this guide are for 3504 and represent typical examples.
Beacons
OP1 Illuminates when output 1 is ON (normally heating)
OP2 Illuminates when output 2 is ON (normally cooling or alarm)
MAN Illuminates when manual mode active. If the HOME display is showing the dual loop overview, MAN
illuminates if Loop 1 is in manual. If the Loop 1 or Loop 2 overviews are being displayed MAN applies to the
loop being displayed.
REM Illuminates when alternative setpoint is active
SPX Illuminates when setpoint 2 is active
ALM If an alarm occurs the red alarm beacon flashes together with a message showing the source of the alarm,
for example ‘AnAlm1 - Abs Hi’ (the latter can also be a customised message). When acknowledged the
alarm message disappears. If the alarm condition is still present the beacon lights continuously. For non-
latched alarms it will extinguish when the alarm is cleared.
RUN Illuminates when the programmer running – flashing indicates End
HLD Illuminates when the programmer is in Hold (frozen)
J Flashes when J Channel digital communications is active
H Flashes when H Channel digital communications is active
IR On when infra red communications is enabled and flashes when infra red communications is active
Operator Buttons
A/MAN
This button
can be
disabled
Toggles the selected loop between Auto and Manual operation.
In Manual the controller output power is adjusted by the user using W
Vbuttons. The input sensor is still connected and reading the PV but
the control loop is open. ‘MAN’ will be indicated.
In Auto the controller automatically adjusts the output to maintain
control, ie the loop is closed.
The controller will power up in the mode it was in when it was powered
down.
PROG To select the programmer summary page
RUN/
HOLD
This button
can be
disabled
Press once to select a program. Press again to run the selected program.
‘RUN’ will be indicated in the top banner of the display.
Press again to hold a program. ‘HLD’ will be indicated
Press and hold for at least two seconds to reset a program.
‘RUN’ will flash at the end of a program
‘HLD’ will flash during holdback
+
‘ACK’. Press these buttons together to acknowledge an alarm.
Press to select new PAGE headings
Press to select a new parameter in the page
W
Press to decrease an analogue value, or to
change the state of a digital value.
V
Press to increase an analogue value, or to
change the state of a digital value
(Any parameter value can
be changed if it is
preceded by v)
Shortcut Key Presses
Backpage Press followed by c. With held down continue to press cor d
to scroll page headers backwards or forwards.
Backscroll When in a list of parameters, press 4followed by c.With 4held down
continue to press cor dto scroll parameters backwards or forwards.
Jump to HOME
display Press + 4
To Set The Required Temperature (Setpoint)
In the view above, press Wor Vto lower or raise the setpoint value of Loop 1.
The new setpoint is accepted when Wor Vis released and is indicated by a brief flash of the setpoint value.
To change Loop 2 setpoint, press . Loop 2 SP value is preceded by v. Press Wor Vas above to
change the value.
A momentary press of either button will show the setpoint in use, e.g. SP1.
Process Variable (PV)
Loop 1
Current access level Lev1; Lev2; or Lev3 (3504 only)
Press to scroll through further parameters
including programmer status details
Beacons
Output Loop 1
Process Variable (PV) Loo
p 2
Setpo
int (SP)
Loop 1
Setpoint (SP) Loop 2
Output Loop 2
Auto/Manual Loop2
Units
(if configured)
If the controller is configured as a
dual loop the HOME displays will
vary as shown here:-
Loop 1
Loop 2
Operator buttons
Typical HOME Display
Ethernet (Modbus TCP)
The Ethernet module can only be fitted in the H slot - terminals HA to HF.
With this option a special cable assembly is also supplied. This cable must be used since the magnetic
coupling is contained within the RJ45 connector. It consists of an RJ45 connector (socket) and a
termination assembly which must be connected to terminals HA to HF.
View of cable which
may also be ordered
separately as Part No
SUB3500/COMMS/EA
Activity and transmit data
LED indicators
Cable connected to
terminals HA to HF
I/O Expander
An I/O expander (Model No 2000IO) can be used with 3500 series controllers to allow the number
of I/O points to be increased by up to a further 20 digital inputs and 20 digital outputs. Data
transfer is performed serially via a two wire interface module (order code EX) which is fitted in
digital communications slot J.
A description of the IO Expander is given in handbook HA026893 whivh can be downloaded from
www.eurotherm.co.uk.
20 Inputs
20 Outputs
IO Expander
Data
transfer


3500 Controller
E1
E2
JE
JF
•The inputs and outputs to and from the IO
Expander are isolated 240Vac.
Digital Communications modules can be fitted in both H and J positions. The connections being available on HA to HF and JA to JF depending on the position in which the module is fitted. The two positions could
be used, for example, to communicate with ‘iTools’ configuration package on one position, and to a PC running a supervisory package on the second position.
Communications protocols may be Modbus, EIBisynch, DeviceNet®, Profibus or Modbus TCP.
Note:- In order to reduce the effects of RF interference the transmission line should be grounded at both ends of the screened cable. However, if such a course is taken care must be taken to ensure that
differences in the earth potentials do not allow circulating currents to flow, as these can induce common mode signals in the data lines. Where doubt exists it is recommended that the Screen (shield) be grounded
at only one section of the network as shown in all of the following diagrams.
A further description of Modbus and EIBisynch communications is given in 2000 series Communications Handbook, Part No. HA026230, which can be downloaded from www.eurotherm.co.uk.
•
Digital communications modules isolated 240Vac CATII
Digital Communications Connections
= Twisted pairs
The KD485 communications converter is recommended for
interfacing to EIA 485. This unit is also used to buffer an EIA 485
network when it is required to communicate with more than 32
instruments on the same bus, and may also be used to bridge 2-
wire EIA485 to 4-wire EIA 422.
* The use of bootlace ferrules may be an aid to wiring where two
wires are to be connected to the same terminal
EIA485 3-Wire Connections
220Ωtermination
resistor
EIA232/EIA 485
communications converter
Com
RxA
RxB
TxA
TxB
Com
Tx
Rx
Com
Rx
Tx
Screen
Daisy Chain
to further
controllers *
220Ωtermination resistor
on last controller in the line
Local Ground
or JA
or JB
or JC
or JD Common
or JE
or JF
HF
HA
HB
HC
HD
HE
Modbus Slave (H or J Module) or EIBisynch
EIA232 Connections
Com
Tx
Rx
Local Ground
Screen
or JA
or JB
or JC
or JD Common
or JE Rx
or JF Tx
HF
HA
HB
HC
HD
HE
Com
Tx
Rx
EIA422/EIA485 5-Wire
Connections
EIA232/EIA422
communications
converter
TxA
TxB
Com
RxA
RxB
Com
Rx
Tx
Screen
220Ωtermination resistor
on last controller in the line
Local Ground
Daisy Chain
to further
controllers *
220
Ω
termination resistor
or JA
or JB
or JC
or JD Common
or JE
or JF
HF
HA
HB
HC
HD
HE
•Low voltage supply: 24Vac/dc, -
15%, +10%
1. For supply connections use 16SWG or larger wires rated for at least 75oC.
2. Use copper conductors only.
3. For 24V the polarity is not important.
4. The power supply input is not fuse protected. This should be provided externally.
Recommended external fuse ratings are as follows:-
For 24 V ac/dc, fuse type: T rated 4A 250V
For 100-240Vac, fuse type: T rated 1A 250V.
Controller Power Supply
Line
N
eutral
L
N
Fuse
24Vac or dc
24
24
Fuse
!
Ensure that you have the correct supply for your controller.
Before connecting the instrument to the power line, make sure that the
line voltage corresponds to the description on the identification label.
Safety requirements for permanently connected equipment state:
•A switch or circuit breaker shall be included in the building
installation
•It shall be in close proximity to the equipment and within easy reach
of the operator
•It shall be marked as the disconnecting device for the equipment.
Note: a single switch or circuit breaker can drive more than one
instrument.
•High voltage supply: 100 to
240Vac, -15%, +10%, 48 to 62
Hz +2Hz
Further information is available in the DeviceNet Communications Handbook Part No HA027506 which can be downloaded from www.eurotherm.co.uk.
This table shows standard cable connections.
Controller Terminal CAN Label Wire Colour Description
HA V+ Red
DeviceNet network power positive terminal. Connect the red wire of the DeviceNet cable here. If the DeviceNet network does not supply the power,
connect to the positive terminal of an external 24 Vdc power supply.
HB CAN_H White DeviceNet CAN_H data bus terminal. Connect the white wire of the DeviceNet cable here.
HC SHIELD None
Shield/Drain wire connection. Connect the DeviceNet cable shield here. To prevent ground loops, the DeviceNet network should be grounded in only
one location.
HD CAN_L Blue DeviceNet CAN_L data bus terminal. Connect the blue wire of the DeviceNet cable here.
HE V- Black
DeviceNet network power negative terminal. Connect the black wire of the DeviceNet cable here. If the DeviceNet network does not supply the
power, connect to the negative terminal of an external 24 Vdc power supply.
HF Connect to instrument earth
DeviceNet Wiring
A description of Profibus is given in the Profibus Communications Handbook Part No HA026290 which can be downloaded from www.eurotherm.co.uk.
Profibus
Single ground
Shielded twisted pair
cables
Rx (A)
Example Profibus Wiring
Controller
Terminals
HBShield
HC VP (+5V)
HD Tx (B)
HE Rx (A)
HF Dig Grnd
Profibus master
(9-way D-type pinout)
Devices should be daisy
chained one to the next
VP (+5Vdc)
Tx (B)
Digital ground
390Ω
220Ω
390Ω
Node
3500 slave 1
HF HE HD HC
Node
Terminating resistors on first
and last devices
VP (+5Vdc)
Digital ground
Tx (B)
R
x (
A
)
390Ω
220Ω
390Ω
Node
Node
3500 slave 1
HF HE HD HC
If options code PD is ordered a D Type Connector
for rear terminal mounting is supplied
Plastic
spacer
9 Pin
connector
assembly
Rear terminal
block
9 pin connections
Pin 1: Shield
Pin 3: Tx/Rx +ve
Pin 5: Ground
Pin 6: +5V
Pin 8 : Tx/Rx –ve
Pin 9: Spare
1
3
5
9
6
HA: Spare
HB: Shield
HC: +5V
HD: Tx/Rx -ve
HE: Tx/Rx +ve
HF: Ground
Analogue Input (T/C, RTD, V, mA, mV) Slots 1, 3, 4 & 6 only
•Hardware Code: AM
•Isolated output 240Vac CATII
Plug in I/O Module Connections (continued)
Analogue Input (Zirconia Probe)
•The temperature sensor of the zirconia probe can be connected to the Fixed PV input, terminals
V+ and V-, or to an Analogue Input module, terminals C & D. The voltage source is connected to
an Analogue Input module, terminals A & D.
Fixed PV (or an Analogue Input Module)
Zirconia Probe Construction
Outer Electrode
Inner Electrode
Ceramic Insulator
Zirconia
Sensor
Hot End
Screen
Zirc. mV
Thermocouple
-
+
-
+
Outer metallic shell of the probe
Zirconia Probe Screening Connections
The zirconia sensor wires should be screened and
connected to the outer shell of the probe if it is situated in
an area of high interference.
Thermocouple
-
+
xA
xB
xD
xC
3-wire RTD
For 2-wire
this is a
local link
xA
xB
xD
xC
-
Volt
source
Voltage
-3 to 10V or –1.4 to 2V
+
xA
xB
xD
xC
Current
0 to 20mA or 4 to 20mA
+
-
2.49Ω
resistor
supplied
Current
source
xA
xB
xD
xC
mV
(40mV or 80mV)
+
-
mVolt
source
xA
xB
xD
xC
Analogue Input Module
-
Zirconia
Volt
source
+
xA
xB
xD
xC
or xD
or xC
+
-
V
-
V+
-
Outer Electrode
Inner Electrode
Screen
Zirc. m
V
T.C.
-
+
-
+
-
+
+
Screened Cable
xA
xB
xD
xC
xA
xB
xD
xC
Safety and EMC Information
This instrument is intended for industrial temperature and process control applications within the requirements of the European Directives on Safety and EMC.
The information contained in this manual is subject to change without notice. While every effort has been made to ensure the accuracy of the information, your supplier shall not be held liable for errors contained
herein.
!
The safety and EMC protection can be seriously impaired if the unit is not used in the manner specified. The installer must ensure the safety and EMC of the installation.
Safety. This instrument complies with the European Low Voltage Directive 73/23/EEC, by the application of the safety standard EN 61010.
Unpacking and storage. If on receipt, the packaging or unit is damaged, do not install but contact your supplier. If being stored before use, protect from humidity and dust in an ambient temperature range of -
30oC to +75oC.
Electrostatic discharge precautions. Always observe all electrostatic precautions before handling the unit.
Service and repair. This instrument has no user serviceable parts. Contact your supplier for repair.
Cleaning. Isopropyl alcohol may be used to clean labels. Do not use water or water based products. A mild soap solution may be used to clean other exterior surfaces.
Electromagnetic compatibility. This instrument conforms with the essential protection requirements of the EMC Directive 89/336/EEC, by the application of a Technical Construction File. It satisfies the general
requirements of the industrial environment defined in EN 61326.
Caution: Charged capacitors. Before removing an instrument from its sleeve, disconnect the supply and wait at least two minutes to allow capacitors to discharge. Avoid touching the exposed electronics of an
instrument when withdrawing it from the sleeve.
Safety Symbols. Symbols used on the instrument have the following meaning:
!
Caution, refer to accompanying documents) Protective Conductor Terminal
Installation Category and Pollution Degree. This unit has been designed to conform to BSEN61010 installation category II and pollution degree 2, defined as follows:-
Installation Category II (CAT II). The rated impulse voltage for equipment on nominal 230V supply is 2500V.
Pollution Degree 2. Normally only non conductive pollution occurs. However, a temporary conductivity caused by condensation must be expected.
Personnel. Installation must only be carried out by suitably qualified personnel
Enclosure of Live Parts. To prevent hands or metal tools touching parts that may be electrically live, the controller must be installed in an enclosure.
Caution: Live sensors. The controller is designed to operate if the temperature sensor is connected directly to an electrical heating element. However, you must ensure that service personnel do not touch
connections to these inputs while they are live. With a live sensor, all cables, connectors and switches for connecting the sensor must be mains rated for use in 240Vac CATII.
Wiring. It is important to connect the unit in accordance with the data in this sheet ensuring that the protective earth connection is ALWAYS fitted first and disconnected last. Wiring must comply with all local
wiring regulations, i.e. UK, the latest IEE wiring regulations, (BS7671), and USA, NEC Class 1 wiring methods.
!
Do not connect AC supply to low voltage sensor input or low level inputs and outputs.
Voltage rating. The maximum continuous voltage applied between any of the following terminals must not exceed 240Vac:
•relay output to logic, dc or sensor connections;
•any connection to ground.
The controller must not be wired to a three phase supply with an unearthed star connection. Under fault conditions such a supply could rise above 240Vac with respect to ground and the product would not be safe.
Conductive pollution. Electrically conductive pollution i.e. carbon dust, MUST be excluded from the enclosure in which the controller is installed. To secure a suitable atmosphere in conditions of conductive
pollution, fit an air filter to the air intake of the enclosure. Where condensation is likely, include a thermostatically controlled heater in the enclosure.
Grounding of the temperature sensor shield. In some installations it is common practice to replace the temperature sensor while the controller is still powered up. Under these conditions, as additional
protection against electric shock, we recommend that the shield of the temperature sensor is grounded. Do not rely on grounding through the framework of the machine.
Manufacturing Address
U.K. Worthing
Eurotherm Ltd
T(+44) 1903 268500
Einfo.uk@eurotherm.com
www.eurotherm.co.uk
© Copyright Eurotherm LtdTM 2008
All rights are strictly reserved. No part of this document may be reproduced, modified or
transmitted in any form by any means, nor may it be stored in a retrieval system other than for the
purpose to act as an aid in operating the equipment to which the document relates, without the
prior written permission of Eurotherm.
Eurotherm pursues a policy of continuous development and product improvement. The
specification in this document may, therefore, change without notice. The information in this
document is given in good faith, but it is intended for guidance only. Eurotherm will accept no
responsibility for any loses arising from errors in this document.
Product group
3500
Table listing restricted substances
Chinese
产品
3500
铅
汞
镉
六价铬
多溴联苯
多溴二苯醚
印刷线路板组件
XOO O O O
附属物 OOO O O O
显示器 OOO O O O
模块 XOX O O O
O
X
English
Product
3500 Pb Hg Cd Cr(VI) PBB PBDE
PCBA X O O O O O
Enclosure O O O O O O
Display O O O O O O
Modules X O X O O O
O
X
Approval
Name:
Position:
Signature:
Date:
Martin Greenhalgh Quality Manager
IA029470U620 (CN23172) Iss ue 1 Feb 07
Restriction of Hazardous Substances (RoHS)
限制使用材料一览表
有毒有害物质或元素
表示该有毒有害物质在该部件所有均质材料中的含量均在
SJ/T11363-2006
标准规定的限量要求以下。
Indicates that this toxic or hazardous substance contained in at least one of the homogeneous
materials used for this part is above the limit requirement in SJ/T11363-2006.
表示该有毒有害物质至少在该部件的某一均质材料中的含量超出
SJ/T11363-2006
标准规定的限量要求。
Toxic and h azardous substan ces and elem ents
Indicates that this toxic or hazardous substance contained in all of the homo geneous materials for
this part is below the limit requ irement in SJ/T11363-2006.
Restricted Materials Table
E
UR
O
T
H
E
R
M
®
®
Over Temperature Protection.
To prevent overheating of the process under fault conditions, a separate over-temperature protection unit should be fitted which will isolate the heating circuit. This must have an independent temperature
sensor.
Note: Alarm relays within the unit will not give protection under all failure conditions.
Installation Requirements for EMC. To comply with European EMC directive certain installation precautions are necessary:-
•General guidance. Refer to EMC Installation Guide, Part no. HA025464.
•Relay outputs. It may be necessary to fit a suitable filter to suppress conducted emissions. Filter requirements depend on the type of load. Typical applications may use Schaffner FN321 or FN612.
•Table top installation. If using a standard power socket, compliance with commercial and light industrial emissions standard is usually required. To comply with conducted emissions standard, a suitable mains
filter must be installed, such as Schaffner FN321 or FN612.
Summary Pages
If configured these are shown in the lower alpha-numeric message centre. They list typical operating parameters for different features of the controller as shown in the Navigation Diagram below:
To Select Manual Operation
Press (A/MAN) button.
If two loops are enabled and the dual loop overview is being displayed,
pressing the A/MAN button will toggle loop 1 between Auto and Manual.
The beacon ‘MAN’ will light and the indication of output power is preceded
by v.
Press and hold Wor Vto decrease or increase the output power.
The MAN
beacon
illuminates
The SP line
changes to
show output
demand.
To switch loop 2 between Auto and
Manual, press to scroll into
the loop 2 section, then press
A/MAN.
If loop 1 overview is being displayed,
press the A/MAN button to toggle
loop 1 between Auto and Manual
If loop 2 overview is being displayed, press the A/MAN button to toggle loop
2 between Auto and Manual.
If any other overview is being displayed, the first press of the A/MAN button
will select the dual loop overview and the action is as described above.
Loop1/Loop2
Status of a running program
To set up or edit a program
Status of Alarms
To set alarm setpoints
Control Summary
Transducer
Calibration
Program number
Segment number
Segment time left
Delayed start
Program status
Channel 1 profile SP value
Channel 2 profile SP value
Fast run
User value when in reset
Channel 1 target SP
Channel 2 target SP
Segment duration or
Rate of change
Current segment type
Number of cycles left
Event output states
Program time remaining
Go back cycles remaining
Program number
Segments used
Channel 1/2 holdback value
Program repeat cycles
Segment number
Segment type
Target setpoint
Ramp rate
Holdback type
PV event
Time event
User value
PID set
To set event outputs
Duration of a segment
Guranteed Soak type
End type
Wait for
PV wait
Go back to segment
Go back cycles
Call program
Call cycles
The output power changes continuously when Wor Vis pressed

New alarm
Any alarm
Acknowledge all?
Analogue alarm 1 to 8
Analogue alarm 1 to 8 ack
Digital alarm 1 to 8 status
Digital alarm 1 to 8 ack
1: High Alarm
2: Low Alarm
3: Deviation High
4: Deviation Low
5: Deviation Band
(Up to 8 if configured).
Setpoint select SP1 or SP2
SP1 value
SP2 value
Setpoint rate
To start autotune
Proportional band value
Integral time
Derivative time
Relative cool gain
Cut back high
Cut back low
Control output high limit
Control output low limit
Channel 1 hysteresis
Channel 2 hysteresis
Channel 2 deadband
Ch1 motor travel time
Ch2 motor travel time
Safe output
Start tare
Start calibration
Start high calibration
Calibration status
Clear current calibration
Scale high
Scale low
Input high
Input low
For a description of these parameters refer to
the Engineering Manual HA0278988.
Further customised pages may be shown if
they have been configured

Example: To Create or Edit a Program
This example shows how the operator buttons are used to set up a program.
The principle is the same for all features.
A program can only be edited when it is in Reset or Hold.
Select a program Press to select the ‘Program Edit’ page
Press Vor Wto select the program
number
Set up a holdback value
* Press to select ‘Ch1/2HldBkVal’
Press Vor Wto set the value
Set up the number of
times a program repeats
*
Press again to select ‘Cycles’
Press Vor Wto choose the number of
cycles
Set up or edit a segment Press to select ‘Segment’
Press Vor Wto choose the segment
number
Set up the segment type
Press to select ‘Segment Type’
Press Vor Wto choose the segment type
The parameters which follow depend on the segment type chosen.
Set up the value of SP
required at the end of
the segment
Press to select ‘Target SP’ for Ch1 and Ch2.
Press Vor Wto choose the value
Set up the segment time Press to select ‘Duration’.
Press Vor Wto choose the value
Set up ‘Holdback Type’ * Press to select Ch1/2HldBck Type’.
Press Vor Wto choose the value
Set up which events
operate in the segment *
Press to select ‘Event Outs’.
Press Vor Wto turn the event on or off.
* These parameters are only shown if the feature has been configured. See the
Engineering manual HA0278988 for further information.
Repeat the above procedure for further segments required in the program. The
final segment should be configured as ‘End’ You can then set up the action
required at the end of the program. This may be ‘Dwell’, ‘Reset’ or ‘SafeOP’.
Example: To Select and Run a Program
This example assumes the program has been entered as described.
Press
Select a program Press Vor Wto choose the program number to
be run
Run the selected
program Press again
Hold a program
Press
Reset a program
Press and hold for at least 3 seconds
Alternatively, run, hold or reset a program by scrolling to ‘Program Status’ using
and select ‘Run’, ‘Hold’ or ‘Reset’ using Vor W.
The button (3504 only) provides a short cut to the Program Status page
from any view.
To inspect/change the status of a running program, press to select the
‘Program Status’ list and to select parameters.
Access Levels
Parameters are available in deeper levels of access protected by different levels
of security. 3200i
Lev1 and Lev2 are intended for day to day operation. It is possible to configure
a limited number of parameters in either level.
Lev3 provides a much greater access to parameters. Typically these are
parameters used when commissioning a system.
Config. To change the fundamental characteristics of the instrument.
Each level (except 1) is protected by a security code. The security codes can be
changed in Configuration level as described in the Engineering Handbook
HA027988.
To Select an Access Level
Press and hold until the display shows ‘Access’.
Press Vor Wto ‘Goto’ the required access level
Press Vor Wto enter a security code. For level 2 the default is 2.
When the correct pass code has been entered ‘Pass’ is displayed momentarily
and the controller returns to the HOME display in the level of operation selected.
It is not necessary to enter a pass code when going from a higher level to a
lower level.
Holdback freezes the program if the
process value (PV) does not track the
setpoint (SP) by more than a user
defined amount. The instrument will
remain in HOLDBACK until the PV
returns to within the requested
deviation from setpoint. The display
will flash the HOLD beacon.
Holdback Type may be selected
from:-
Off No holdback
Band Deviation high & low
High Deviation high
Low Deviation low
The following choices are available,
depending on programmer type. For
example SyncAll offers Wait, Time and
End only:-
Rate Rate of change of setpoint
Time Time to target
Dwell Soak at constant setpoint
Step Step change to new setpoint
Wait Wait for pre-determined
condition
GoBack Repeat previous segments
Call Insert a new program
End Final segment

Other manuals for 3508

2

This manual suits for next models

1

Other Eurotherm Controllers manuals

Eurotherm P304c User manual

Eurotherm

Eurotherm P304c User manual

Eurotherm Invensys Mini8 Assembly instructions

Eurotherm

Eurotherm Invensys Mini8 Assembly instructions

Eurotherm SSD Drives 635 User manual

Eurotherm

Eurotherm SSD Drives 635 User manual

Eurotherm P304c User manual

Eurotherm

Eurotherm P304c User manual

Eurotherm 2100 User manual

Eurotherm

Eurotherm 2100 User manual

Eurotherm TE300 Series User manual

Eurotherm

Eurotherm TE300 Series User manual

Eurotherm EPower User manual

Eurotherm

Eurotherm EPower User manual

Eurotherm 7000 Series User manual

Eurotherm

Eurotherm 7000 Series User manual

Eurotherm TE200A User manual

Eurotherm

Eurotherm TE200A User manual

Eurotherm 2216e User manual

Eurotherm

Eurotherm 2216e User manual

Eurotherm 2132 User manual

Eurotherm

Eurotherm 2132 User manual

Eurotherm epack User manual

Eurotherm

Eurotherm epack User manual

Eurotherm 7000 Series User manual

Eurotherm

Eurotherm 7000 Series User manual

Eurotherm Invensys 3216 User manual

Eurotherm

Eurotherm Invensys 3216 User manual

Eurotherm 3500 series User manual

Eurotherm

Eurotherm 3500 series User manual

Eurotherm Invensys 2408 User manual

Eurotherm

Eurotherm Invensys 2408 User manual

Eurotherm 7000 Series User manual

Eurotherm

Eurotherm 7000 Series User manual

Eurotherm 7000 Series User manual

Eurotherm

Eurotherm 7000 Series User manual

Eurotherm 808 User manual

Eurotherm

Eurotherm 808 User manual

Eurotherm Invensys Mini8 User manual

Eurotherm

Eurotherm Invensys Mini8 User manual

Eurotherm Invensys 3216 User manual

Eurotherm

Eurotherm Invensys 3216 User manual

Eurotherm 2416 Owner's manual

Eurotherm

Eurotherm 2416 Owner's manual

Eurotherm Nanodac User manual

Eurotherm

Eurotherm Nanodac User manual

Eurotherm 2604 Owner's manual

Eurotherm

Eurotherm 2604 Owner's manual

Popular Controllers manuals by other brands

Evco Vcolor 679 Installer manual

Evco

Evco Vcolor 679 Installer manual

McCain 2070LX user manual

McCain

McCain 2070LX user manual

Glass Ware Janus user guide

Glass Ware

Glass Ware Janus user guide

Dimplex RXPW4 quick start guide

Dimplex

Dimplex RXPW4 quick start guide

SpeedFun Ribelle instructions

SpeedFun

SpeedFun Ribelle instructions

Ascon tecnologic Y39 operating instructions

Ascon tecnologic

Ascon tecnologic Y39 operating instructions

Cypress CapSense CY8CMBR2044 Design guide

Cypress

Cypress CapSense CY8CMBR2044 Design guide

Infineon XDPP1100 user manual

Infineon

Infineon XDPP1100 user manual

Gardena 1892 Operator's manual

Gardena

Gardena 1892 Operator's manual

Honeywell HC900 reference guide

Honeywell

Honeywell HC900 reference guide

Sunricher SR-2830RGB manual

Sunricher

Sunricher SR-2830RGB manual

EDS BL 9228 quick start guide

EDS

EDS BL 9228 quick start guide

SMC Networks LEKFS G Series instruction manual

SMC Networks

SMC Networks LEKFS G Series instruction manual

Generac Power Systems PWRmanager owner's manual

Generac Power Systems

Generac Power Systems PWRmanager owner's manual

Danfoss ECL Comfort 310 installation guide

Danfoss

Danfoss ECL Comfort 310 installation guide

Full Gauge Controls AHC-80 plus quick start guide

Full Gauge Controls

Full Gauge Controls AHC-80 plus quick start guide

SMC Networks EX230-SDN1 Installation and maintenance manual

SMC Networks

SMC Networks EX230-SDN1 Installation and maintenance manual

Emerson Dixell XR40CX Installing and operating instructions

Emerson

Emerson Dixell XR40CX Installing and operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.