Power Controller
24. Under some circumstances, the power module heatsink temperature
may rise above 50 degrees Celsius and it can take up to 15 minutes to
cool after the unit is shut down. If operators are likely to come into
contact with such heatsinks, adequate warnings and barriers must be
put in place in order to prevent injury.
25.To reach the thermal performance the gap between two Epack units
should be at minimum 10mm
26. Signal and power voltage wiring must be kept separate from one
another. Where this is impractical, shielded cables should be used for
the signal wiring.
27. To ensure that EPack comply with Electromagnetic Compatibility
requirements, ensure that the panel or DIN rail to which they are
attached is correctly grounded. The ground connection, designed to
ensure ground continuity, is not in any way a substitute for the
protective earth connection.
28. This product has been designed for environment A (Industrial). Use of
this product in environment B (domestic, commercial and light
industrial) may cause unwanted electromagnetic disturbances in which
cases the user may be required to take adequate mitigation measures.
SELV is defined (in IEC60947-1) as an electrical circuit in which the voltage
cannot exceed 'ELV' under normal conditions or under single fault
conditions, including earth faults in other circuits. The definition of ELV
is complex as it depends on environment, signal frequency, etc. See IEC
61140 for further details.
The I/O connector (5-way) & EPack supply (24V ac/dc) (2-way) are
compliant to the SELV requirements.
The alarm relay terminal block named ALR is compliant to the SELV
requirements; it can be connected to SELV or to voltage up to 230V
(Rated insulation voltage Ui : 230V)
ELECTRICAL INSTALLATION
N/L2
1 2 3 4 5
04 01 02
02
01
04
com
nc
no
10V
+
0V
DI1
DI2
1
1
0V
+
0V
DI1
DI2
0V
+
0V
DI1
DI2
Contact inputs
Voltage level inputs
Digital inputs
Analogue input
4.4 to 30V = high
-30V to +2.3V = low
2.3V to 4.4V = undefined
V/mA input (note 3)
0 to 10V
1 to 5V
2 to 10V
0 to 5V
0 to 20 mA
4 to 20 mA
Relay output
View on
lower face
500Ω to ∞ = open
0Ω to 150Ω = closed
150Ω to 500Ω = undefined
Switching characteristics
(resistive loads)
Vmax: 264V RMS
Vmin: 1V dc
Imax: 2A RMS
Imin: 1mA
Notes:
1. DI1 shown; DI2 similar
2. DI1 and DI2 can both be contact inputs or both be voltage inputs or be one of each.
3. Analogue input type (Volts or mA) is selected in I/O Analogue IP configuration. When
a mA range is selected, a suitable shunt resistor is automatically connected into circuit.
It is thus unnecessary for the user to fit external components.
4. Use 0.6 x 3.5 mm screwdriver for pluggable connectors
IO WIRING
SUPPLY WIRING
From Supply power for load
To load
Lift-up flap
Pull-down flap
Access to load
termination
screw head
Access to supply
termination screw
head
60mm minimum
Flat-bladed screw head
0.6 x 4.5 mm or 0.8 x 4.5mm
recommended
Screwdriver/Torque wrench screwdriver bit details for line and load termination
Auxiliary voltage alternatives
(as specified at time-of-order)
Neutral
reference
Safety earth con-
nection (M5 nut).
The earth con-
nection must be
made using a
Listed ring type
crimp.
View on
upper face
Insulated handle
COMMUNICATIONS WIRING
Supply cable sizes and torques
Terminals Terminal capacity Wire Type Torque
mm² AWG
Supply voltage (1/L1)
and
Load supply (2/T1)
1 mm²
to 16 mm²
AWG 20 to
AWG 6
Stranded
copper rated
90°C
1.7 Nm
(15 Lb.inch.)
Safety earth M5 ring-type crimp terminal
U.L. : Listed ring-type crimp
terminal must be used
2.5 N.m
(22 Lb.inch.)
Phase reference (N/L2) (2-way)
Supply (24V ac/dc) (2-way)
Supply (85V-550Vac)(3-way)
I/O connector (5-way)
Relay connector (3-way)
0.25 mm²
to 2.5 mm²
AWG 24 to
AWG 12
Stranded
copper rated
75°C
0.56 Nm
(5 lb. inch)
Centre pin
not connected
Warning: Connection of 2 conductors in the same terminal is not allowed.
SAFETY NOTES
DVD CONTENTS AND INSTALLATION
Product documentation.The documentation on this DVD is
in pdf format which requires the use of Adobe® Acrobat® 4.0 or
later to view it. The English language version of Adobe Acrobat
4.0 for Microsoft® Windows® may be installed from this DVD.
DOCUMENTATION
EPack Controller User Guide HA031414
1. Eurotherm shall not be held responsible for any damage, injury, losses or
expenses caused by inappropriate use of the product or failure to comply
with this manual
2. Accordingly the user is responsible for checking, before commissioning the
unit, that all the nominal characteristics correspond to the conditions under
which it is to be installed and used
3. If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment might be impaired.
4. The product must be commissioned and maintained by suitably qualified
personnel, authorized to work in an industrial low voltage environment.
5. BRANCH-CIRCUIT PROTECTION AND SAFETY OVERLOAD PROTECTION
This product does not contain any branch-circuit protection or internal
safety overload protection. It is the responsibility of the user to add branch-
circuit protection upstream of the unit. It is also the responsibility of the user
to provide external or remote safety overload protection to the end
installation. Such branch-circuit and safety overload protection must
comply with applicable local regulations.
UL: The above mentioned branch-circuit protection is necessary for
compliance with National Electric Code (NEC) requirements
6. If opening of the branch circuit protective or the supplemental fuses (high
speed fuse) the product (Epack) shall be examined and replaced if
damaged.
7. The product (Epack) is not suitable for isolation applications, within the
meaning of EN60947-1.
8. The instrument shall have one of the following as a disconnecting device,
fitted within easy reach of the operator, and labelled as the disconnecting
device.
a. A switch or circuit breaker which complies with the requirements of
IEC60947-1 and IEC60947-3
b. A separable coupler which can be disconnected without the use of a
tool.
9. EPack alarms protect thyristors and loads against abnormal operation, and
provide the user with valuable information regarding the type of fault.
Under no circumstances should these alarms be regarded as a replacement
for proper personnel protection. It is strongly recommended that the
installing authority include independent, system-safety mechanisms to
protect both personnel and equipment against injury or damage, and that
such safety mechanisms be regularly inspected and maintained. Consult
the EPack supplier for advice.
10. Units are designed to be installed in a cabinet connected to the protective
earth according to IEC60364-1 and IEC60364-5-54 or applicable national
standards.
11. The cabinet must be closed under normal operating conditions. Adequate
air conditioning/ filtering/ cooling equipment must be fitted to the cabinet
in order to prevent the ingress of conductive pollution, the formation of
condensation etc.
12. We recommend fitting fan-cooled cabinets with a fan failure detection
device or a thermal safety cut-out
13. Before any other connection is made, the protective earth terminal shall be
connected to a protective conductor. Wire conductor cross sections must
comply with table 9 of IEC60947-1 or NEC Article 310 Table 310-16. U.L.:
The earth connection must be made using a Listed ring type crimp. Used
cables must be rated 90°C stranded copper only
14. The earth connection should be tightened at the torque defined in table 2-
1. It is recommended to perform regular inspection of the earth tightening
15. Any interruption of the protective conductor inside or outside the
apparatus, or disconnection of the protective earth terminal is likely to make
the apparatus dangerous under some fault conditions. Intentional
interruption is prohibited.
Whenever it is likely that protection has been impaired, the unit shall be
made inoperative, and secured against accidental operation. The
manufacturers nearest service centre should be contacted for advice.
16. Before carrying out any wiring to the unit it must be ensured that all relevant
power and control cables, leads or harnesses are isolated from voltage
sources.
17. Power connections. Wire conductor cross sections must comply with table 9
of IEC60947-1 or NEC Article 310 Table 310-16. Used cables must be rated
90°C stranded copper only.
18. Power terminals should be tightened according to the torque values
defined in table 2-1. It is recommended to perform regular inspection of
the power terminals tightening.
19. The cable use to connect auxiliary supply should be correctly protected by
a branch-circuit protection. It is the responsibility of the user to add branch-
circuit protection. Such branch-circuit must comply with applicable local
regulations.
20. To comply with safety requirements, the 24V auxiliary supply must be
derived from a SELV or PELV circuit
21. The 85Vac to 550Vac auxiliary supply shall be protected by supplemental
fuse ATM2 rated 600Vac/dc, 2A by MERSEN/Ferraz Shawmut (E33925). The
maximum voltage between any pole of the power supply and terminals 1/
L1, N/L2 should be lower than 550Vac. The maximum voltage between any
pole of the power supply and earth should be lower than 550Vac (rated
insulation voltage 500V)
22. For safety reasons, opening the unit is strictly forbidden.
23. Units are designed to be mounted vertically. There must be no obstructions
(above or below) which could reduce or hamper airflow. If more than one
set of units is located in the same cabinet, they must be mounted in such a
way that air from one unit is not drawn into another.
HA031600ENG iss 4 June 2016 (CN34584)
1
8
1
8
Yellow
Green
Pin Signal
8
7
6
5
4
3
2
1
Not used
Not used
Rx-
Not used
Not used
Rx+
Tx-
Tx+
LEDs:
Green = Tx activity
Yellow = Connected
Eurotherm: International sales and support www.eurotherm.com
Contact Information
Eurotherm Head Office
Faraday Close,
Durrington,
Worthing, West Sussex,
BN13 3PL
Sales Enquiries
T +44 (01903) 695888
F 0845 130 9936
Worldwide Offices
www.eurotherm.com/worldwide
Scan for local
contacts
General Enquiries
T +44 (01903) 268500
F 0845 265982
© Copyright Eurotherm Limited 2016
Eurotherm by Schneider Electric, the Eurotherm logo, Chessell, EurothermSuite, Mini8, Eycon, Eyris, EPower, EPack, nano-
dac, piccolo, versadac, optivis, Foxboro and Wonderware are trademarks of Schneider Electric, its subsidiaries and affiliates.
All other brands may be trademarks of their respective owners.
All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any
means, nor may it be stored in a retrieval system other than for the purpose to act as an aid in operating the equip-ment to
which the document relates, without the prior written permission of Eurotherm Limited.
Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this docu-
ment may therefore be changed without notice. The information in this document is given in good faith, but is intended for
guidance only. Eurotherm Limited will accept no responsibility for any losses arising from errors in this document.
1 2 3 4 5
04 01 02
72mm (2.83 in)
46.7mm (1.84 in)
163.5mm (6.44 in)
129.2mm (5.09 in)
121mm (4.76 in)
158.2mm (6.23 in)
117mm (4.61 in)
147mm (4.79 in)
174mm (6.85 in)
24V
AC/DC
N/L2
1 2 3 4 5
04 01 02
51mm (2.01 in)
46.7mm (1.84 in)
136.2mm (5.36 in)
24V
AC/DC
N/L2
129.2mm (5.09 in)
121mm (4.76 in)
117mm (4.61 in)
147mm (4.79 in)
174mm (6.85 in)
163.5mm (6.44 in)
SPECIFICATION
MECHANICAL INSTALLATION
EPack (auxiliary) supply power
(low voltage option shown)
Phase reference
(neutral)
I/O connector
Load power output
Relay output
Safety earth connection (M5 nut).
The earth connection must be
made using a Listed ring type
crimp.
Load power input
EPack (auxiliary) supply power
(low voltage option shown)
Phase reference
(neutral)
I/O connector
Load power output
Relay output
Safety earth
connection
(M5 nut).
The earth
connection
must be
made using a
Listed ring
type crimp.
Load power input
View on
upper face
16A to 32A units 40A to 63A units
STANDARDS
EN60947-4-3:2000 + A1:2006 + A2 :2011 (Low-voltage switchgear and controlgear -Part 4-3:
Contactors and motor-starters - AC semiconductor controllers and contactors for non-motor loads
(identical to IEC60947-4-3:2014)
UL60947-4-1 CAN/CSA C22.2 NO.60947-4-1-14 Low-Voltage Switchgear and Controlgear - Part 4-1:
Contactors and Motor-Starters - Electromechanical Contactors and Motor-Starters
Russian Approvals: EAC approval and Pattern Approval
INSTALLATION CATEGORIES
General installation category details are summarised in the table below.
PHYSICAL
Dimensions and fixing centresSee figures below for details
Weight 16 to 32A units 800g + user connectors
40 to 63A units 950g + user connectors
EMC
EMC immunity tests EN60947-4-3:2000 + A1:2006 + A2 :2011 & EN60947-4-3:2014
EMC emission tests EN60947-4-3:2000 + A1:2006 + A2 :2011
This product has been designed for environment A (Industrial). Use of this
product in environment B (domestic, commercial and light industrial) may
cause unwanted electromagnetic disturbances in which case the user may
need to take adequate mitigation measures
POWER (at 45°C)
Voltage rangeLoad: 100 to 500V (+10% -15%)
Auxiliary: 24V ac/dc (+20% -20%) or 100 to 500V (+10% -15%)
Frequency range 47 to 63 Hz for load and ac auxiliary supplies)
Power requirement 24V dc supply: 12W
24V ac supply: 18VA
500V ac supply: 20VA
Installation category Rated impulse withstand
voltage (Uimp)
Rated insulation voltage
Communication II 0.5 kV 50V
Standard IO II 0.5 kV 50V
Relays III 4 kV 230V
Module power III 6 kV 500V
Installation category See adjacent table.
Nominal load current 16 to 63 Amps
Short circuit protection by external supplemental fuses (high speed fuse) see User
Manual
Rated short-circuit conditional current 100kA (co-ordination type 1)
Pollution degree Pollution degree 2
Utilization categories (Load types) AC51: Non-inductive or slightly inductive loads, resistance
furnaces
AC56a: Transformer Primary or MOSI (Molybenum Silicide)
Time temperature dependant loads (Silicon Carbide,
Carbon)
Duty cycle Uninterrupted duty / continuous operation
Load Types Single phase control of resistive loads (low/high temperature coefficient and non-
ageing/ageing types) and transformer primaries.
Overload conditions AC51: 1xle continuous
OPERATOR INTERFACE
Display 1.5” square TFTcolour display allowing viewing of selected parameter values in real time,
plus configuration of instrument parameters for users with adequate access permission.
Pushbuttons Four push buttons provide page and item entry and scroll facilities.
ENVIRONMENT
Temperature limits Operating: 0°C to 45°C at 1000m
0°C to 40°C at 2000m
Storage: -25°C to +70°C
Altitude 1000m maximum at 45°C
2000m maximum at 40°C
Humidity limits 5% to 95% RH (non-condensing)
Protection CE: IP10 (EN60529)
UL Open Type
Atmosphere Non-explosive, non-corrosive, non-conductive
External wiring General:Must comply with IEC60364-1 and IEC60364-5-54 and all applicable local
regulations. Cross sections must comply with table 9 of IEC60947-1
UL: Must comply with NEC and all applicable local regulations. Cross sections must
comply with NEC, Article 310 Table 310-16.
Temperature rating: Power conductors: 90°C; other wires: 75°C
Shock To (EN60068-2-27) and IEC60947-1 Annex Q
Vibration (EN60068-2-6) To (EN60068-2-6) and IEC60947-1 Annex Q
SYMBOLS USED IN THE INSTRUMENT LABELLING
One or more of the symbols below may appear as a part of the instrument labelling
RoSH
5Protective conductor terminal DRisk of electric shock
AC supply only OPrecautions against static electrical discharge
must be taken when handling this unit
LUnderwriters Laboratories listed
mark for Canada and the US WRefer to the manual for instructions
;Do not touch Heatsink Hot
Surface CDeclaration of conformity to European standard
For Bulkhead mounting, fit the upper
bracket ‘A’ to the rear of the unit by removing
screw ‘B’ and associated shakeproof washer,
offering the bracket up to the unit, and then
securing it using screw ‘B’ ensuring that the
bracket is correctly oriented (as shown) and
that the shakeproof washer is fitted between
the screw head and the bracket.
The relevant screwdriver should have a 3mm
AF hexagonal bit. The recommended
tightening torque is 1.5Nm (1.1 lb-ft).
A
B
View on
lower face
View on
upper face
View on
lower face
M5 Nut
WARNING
For 24V supplies: in order to comply with safety requirements,
the supply voltage must be derived from a SELV or PELV circuit.
M5 nut
M5 nut
BULKHEAD MOUNTING BRACKET
The data shown
here is related to
the China RoHS 2.0
Administrative
Measures for the
Restriction of
Hazardous
Substances in
Electric Appliances
and Electronic
Products released
January 21st 2016.

Other manuals for epack

2

Other Eurotherm Controllers manuals

Eurotherm P304c User manual

Eurotherm

Eurotherm P304c User manual

Eurotherm Invensys Mini8 Installation and operation manual

Eurotherm

Eurotherm Invensys Mini8 Installation and operation manual

Eurotherm Invensys 3216 User manual

Eurotherm

Eurotherm Invensys 3216 User manual

Eurotherm 2704 User manual

Eurotherm

Eurotherm 2704 User manual

Eurotherm SSD Drives 635 User manual

Eurotherm

Eurotherm SSD Drives 635 User manual

Eurotherm 7000 Series User manual

Eurotherm

Eurotherm 7000 Series User manual

Eurotherm 2216e User manual

Eurotherm

Eurotherm 2216e User manual

Eurotherm 2416 Owner's manual

Eurotherm

Eurotherm 2416 Owner's manual

Eurotherm P304c User manual

Eurotherm

Eurotherm P304c User manual

Eurotherm 2604 Owner's manual

Eurotherm

Eurotherm 2604 Owner's manual

Eurotherm Invensys 2408 User manual

Eurotherm

Eurotherm Invensys 2408 User manual

Eurotherm Invensys Mini8 Assembly instructions

Eurotherm

Eurotherm Invensys Mini8 Assembly instructions

Eurotherm EPower User manual

Eurotherm

Eurotherm EPower User manual

Eurotherm 2500 User manual

Eurotherm

Eurotherm 2500 User manual

Eurotherm 7000 Series User manual

Eurotherm

Eurotherm 7000 Series User manual

Eurotherm epack User manual

Eurotherm

Eurotherm epack User manual

Eurotherm 7000 Series User manual

Eurotherm

Eurotherm 7000 Series User manual

Eurotherm epack User manual

Eurotherm

Eurotherm epack User manual

Eurotherm 7000 Series User manual

Eurotherm

Eurotherm 7000 Series User manual

Eurotherm 902 Series User manual

Eurotherm

Eurotherm 902 Series User manual

Eurotherm 3508 User manual

Eurotherm

Eurotherm 3508 User manual

Eurotherm 690+ Series User manual

Eurotherm

Eurotherm 690+ Series User manual

Eurotherm Nanodac User manual

Eurotherm

Eurotherm Nanodac User manual

Eurotherm T940X Operating manual

Eurotherm

Eurotherm T940X Operating manual

Popular Controllers manuals by other brands

ComAp IG-NT reference guide

ComAp

ComAp IG-NT reference guide

Emerson Fisher 630 Series instruction manual

Emerson

Emerson Fisher 630 Series instruction manual

GCE MediVital E Instructions for use

GCE

GCE MediVital E Instructions for use

TRIAC THD S11 SERIES Installation & maintenance manual

TRIAC

TRIAC THD S11 SERIES Installation & maintenance manual

Illumra E3R-MBCFP-02 Starter Guide

Illumra

Illumra E3R-MBCFP-02 Starter Guide

Norac UC4+ Operator's manual

Norac

Norac UC4+ Operator's manual

Infineon NAC1080 user manual

Infineon

Infineon NAC1080 user manual

Gree CE55-24/F owner's manual

Gree

Gree CE55-24/F owner's manual

Siemens SIMATIC manual

Siemens

Siemens SIMATIC manual

I-Panda 40A Series manual

I-Panda

I-Panda 40A Series manual

Helios PA Series quick start guide

Helios

Helios PA Series quick start guide

Berker 9450 0200 operating instructions

Berker

Berker 9450 0200 operating instructions

Commodore A 2091-40 user guide

Commodore

Commodore A 2091-40 user guide

Rayrun N20 user manual

Rayrun

Rayrun N20 user manual

Qorvo PAC5526 user guide

Qorvo

Qorvo PAC5526 user guide

Schalk UMS 5 manual

Schalk

Schalk UMS 5 manual

ADB Safegate RELIANCE AGLAS-C user manual

ADB Safegate

ADB Safegate RELIANCE AGLAS-C user manual

NEC Renesas mPD71312 user manual

NEC

NEC Renesas mPD71312 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.