Eurotherm 2208e Owner's manual

Installation and operation
handbook
2208e
2204e
TEMPERATURE
CONTROLLERS
ENG


Installation and Operation Handbook Contents
2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03 a-1
MODELS 2208e and 2204e
TEMPERATURE CONTROLLERS
INSTALLATION AND OPERATION HANDBOOK
1 Chapter 1 OPERATION Page
1.1 FRONT PANEL LAYOUT................................................................1-2
1.2 GETTING STARTED.......................................................................1-4
1.2.1 Viewing The Process Value and Setpoint............................................1-4
1.2.2 To Adjust The Setpoint........................................................................1-4
1.2.3 Viewing The Display Units...................................................................1-5
1.2.4 Use Of The “SCROLL” Button .......................................................1-5
1.2.5 Use Of The ‘PAGE’ Button .............................................................1-6
PARAMETER LISTS.................................................................................1-7
1.4 MANUAL OR AUTOMATIC CONTROL..........................................1-8
1.4.1 Selecting Auto/Manual Operation........................................................1-8
1.4.2 How To Manually Adjust Output Power ...............................................1-9
1.5 SUMMARY.......................................................................................1-9
1.6 Selecting SETPOINT 1 OR SETPOINT 2.....................................1-10
1.7 RAMP DWELL FUNCTION ...........................................................1-11
1.7.1 To Set up a Ramp/Time Program......................................................1-11
1.7.2 To Run the Program..........................................................................1-12
1.7.3 Power Failure During Program Run...................................................1-12
1.8 LOCATION OF PARAMETERS - BLOCK DIAGRAM ..................1-13
1.9 NAVIGATION DIAGRAM (Part A) .................................................1-14
NAViGATION Diagram (Part B)..............................................................1-15
1.10 parameter tables............................................................................1-16
1.10.2 Alarm List.......................................................................................1-17
1.10.3 Autotune List..................................................................................1-17
1.10.4 PID List...........................................................................................1-18
1.10.5 Setpoint List...................................................................................1-19
1.10.6 Input List ........................................................................................1-20
1.10.7 On/Off List......................................................................................1-20
1.10.8 Output List......................................................................................1-21
1.10.9 Communications List......................................................................1-21
1.10.10 Access List.....................................................................................1-21
1.11 ALARMS.....................................................................................1-22
1.11.1 Types of Alarm Used in the 2200...................................................1-22
1.12 ALARM RELAY OUTPUT ..........................................................1-23
1.12.1 SETTING ALARM LEVELS............................................................1-24
1.12.2 ALARM INDICATION AND ACKNOWLEDGEMENT .....................1-25
1.12.3 DIAGNOSTIC ALARMS .................................................................1-26

Contents Installation and Operation Handbook
a-2 2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03
2 Chapter 2 INSTALLATION 2-1
2.2 INSTRUMENT LAYOUTS ...............................................................2-2
2.2.2 Outline Dimensions Model 2208e........................................................2-3
2.2.3 Outline Dimensions Model 2204e........................................................2-3
2.3 INTRODUCTION .............................................................................2-4
2.3.2 Controller labels ..................................................................................2-4
2.4 MECHANICAL INSTALLATION......................................................2-4
2.4.2 Unplugging and plugging-in the controller...........................................2-4
2.5 WIRING............................................................................................2-5
2.5.2 Wire Sizes...........................................................................................2-6
2.5.3 Wiring connections..............................................................................2-6
2.5.4 Sensor input connections....................................................................2-7
2.5.5 Outputs 1 and 2 connections...............................................................2-7
2.6 PDS MODES....................................................................................2-8
2.7 SNUBBERS.....................................................................................2-8
Typical single loop wiring diagram........................................................2-9
2.9 RS 232/485/422 Communication connections...........................2-10
2.9.2 Wiring of EIA-485 serial communication links...................................2-11
2.10 DEVICENET WIRING TO SERIES 2200E CONTROLLERS.....2-12
2.10.2 DeviceNet Terminal Functions.......................................................2-12
2.10.3 Wiring Interconnections for DeviceNet Communications...............2-13
3 Chapter 3 ACCESS LEVELS 3-1
3.2 THE DIFFERENT ACCESS LEVELS..............................................3-2
3.3 SELECTING AN ACCESS LEVEL..................................................3-3
3.3.2 Returning to Operator Level................................................................3-5
3.4 EDIT LEVEL ....................................................................................3-5
3.4.2 Hiding or revealing a complete list ......................................................3-6
3.4.3 Promoting a parameter........................................................................3-6

Installation and Operation Handbook Contents
2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03 a-3
4. Chapter 4 TUNING ..............................................................................4-1
4.1. WHAT IS TUNING?.........................................................................4-2
4.2. AUTOMATIC TUNING.....................................................................4-3
4.2.1. Heating and Cooling Output Cycle Times............................................4-3
4.3. HOW TO TUNE................................................................................4-4
4.3.1. Typical automatic tuning cycle.............................................................4-5
4.3.2. Calculation of the cutback values........................................................4-5
4.4. MANUAL TUNING...........................................................................4-6
4.4.1. Setting the cutback values...................................................................4-7
4.4.2. Integrating action and manual reset....................................................4-8
4.4.3. Automatic droop compensation (Adc) .................................................4-8
5. Chapter 5 CONFIGURATION 5-1
5.1 SELECTING CONFIGURATION LEVEL 5-2
5.2 SELECTING A CONFIGURATION PARAMETER 5-3
5.3 LEAVING CONFIGURATION LEVEL 5-3
5.4 STEPS INVOLVED IN CONFIGURING A CONTROLLER 5-3
5.5 NAVIGATION DIAGRAM (PART A) 5-4
5.6NAVIGATION DIAGRAM (PART B) 5-5
5.7 CONFIGURATION PARAMETER TABLES 5-7
5.8 CONFIGURATION OF DIGITAL COMMUNICATIONS …………5-16
5.8.1. To Configure the Function and Baud Rate…………………………… 5-16
5.8.2. To Set Instrument Address…………………………………………… 5-17
5.9 DEVICENET…………………………………………………………… 5-17
5.9.1. The EDS File…………………………………………………………… 5-17
5.9.2. ODVA Compliance…………………………………………………… 5-17
6 Chapter 6 USER CALIBRATION..........................................................6-1
6.8 WHAT IS THE PURPOSE OF USER CALIBRATION? ..................6-2
6.9 USER CALIBRATION ENABLE......................................................6-3
6.10 SINGLE POINT CALIBRATION...................................................6-4
6.11 TWO POINT CALIBRATION........................................................6-5
6.12 CALIBRATION POINTS AND CALIBRATION OFFSETS...........6-6

Contents Installation and Operation Handbook
a-4 2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03
7 Chapter 7 ALARM CONFIGURATION.................................................7-1
7.1 DEFINITION OF ALARMS AND EVENTS ......................................7-2
7.1.1 Types Of Alarms..................................................................................7-2
7.2 DIGITAL OUTPUT FUNCTIONS.....................................................7-4
7.3 STEP1 - CONFIGURING THE FOUR ‘SOFT’ ALARMS ................7-5
7.4 STEP 2 - ATTACHING AN ALARM TO A PHYSICAL OUTPUT....7-6
7.5 STEP 3 - GROUPING ALARMS ON A SINGLE OUTPUT .............7-7
7.6 STEP 4 - REMOVING ALARMS FROM AN OUTPUT....................7-7
8. Chapter 8 MOTORISED VALVE CONTROL .....................................8-1
8.1. PARAMETERS FOR MOTORISED VALVE CONTROL.................8-2
8.2. COMMISSIONING THE MOTORISED VALVE CONTROLLER.....8-2
8.2.1. Adjusting the minimum on-time ‘Ont.H............................................8-2
8.3. MOTORISED VALVE APPLICATIONS...........................................8-3
8.3.1. Auto Tuning.........................................................................................8-3
8.3.2. 2200e Valve Positioner Set-up Table..................................................8-3
9 Chapter 9 LOAD CURRENT MONITORING AND DIAGNOSTICS 9-1
9.1 LOAD CURRENT MONITORING AND DIAGNOSTICS ...............9-2
9.2 EXAMPLE WIRING DIAGRAM (FOR MODE 1 & 2 OPERATION)9-3
Example Wiring Diagram (for mode 5 operation)..............................9-4
9.4 OPERATION..................................................................................9-5
To Read Load Current (modes 2 and 5 only) .................................................9-5
9.1.2 To Display Load Current Continuously in the Lower Readout (modes 2
and 5 only) .......................................................................................9-5
9.1.3 Display Modes..................................................................................9-5
9.1.4 How Heater Alarms Are Displayed...................................................9-6
9.5 TO SET THE ALARM TRIP LEVELS............................................9-7
9.6 Relay Outputs...............................................................................9-7
9.7 TO CONFIGURE PDS LOAD CURRENT DIAGNOSTICS ...........9-8
9.1.5 To configure the Logic Module for PDS modes 1 or 2 .....................9-8
9.1.6 To configure logic input a for pds (Mode 5 only)..............................9-9
To Configure Low and High Current Trip Alarms............................9-10
9.9 TO ATTACH SOFT ALARMS TO A RELAY OUTPUT...............9-11
9.10 THE SCALING FACTOR.........................................................9-12
9.1.7 To adjust the scaling factor............................................................9-12

Installation and Operation Handbook Contents
2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03 a-5
10 Chapter 10 RETRANSMISSION...................................................10-1
10.1 WHAT IS RETRANSMISSION.................................................10-2
10.2 TO CONFIGURE RETRANSMISSION....................................10-3
10.3 SCALING RETRANSMITTED OUTPUT SIGNALS.................10-4
10.1.1 To Range Retransmitted Output OP .........................................10-4
10.1.2 To Range Retransmitted Setpoint SP or Process Variable PV10-5
10.1.3 To Range Retransmitted Error Err..........................................10-5
Appendix A UNDERSTANDING THE ORDERING CODE
.
....... A-1
Appendix B SAFETY & EMC INFORMATION
.
....................... B-1
TECHNICAL SPECIFICATION
.
......................... B-6
This product is covered by one or more of the following US Patents:
5,484,206 and 5,793,754; Additional patents pending.
PDSIO
is a registered trademark of Eurotherm.
INSTANT ACCURACY™, SSRx Load Doctor™ and SSRx Enhanced Load Doctor ™
are trademarks of Eurotherm.”

Contents Installation and Operation Handbook
a-6 2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03
Symbols in Use In This Handbook
Useful information
Button Operation
Caution, (refer to the
accompanying documents) Functional earth
(ground) terminal
!
i
!

Installation and Operation Handbook Operation
2208e and 2204e Controller 1-1
Chapter 1 OPERATION
1.1 FRONT PANEL LAYOUT .................................................................2
1.2 GETTING STARTED.........................................................................4
1.2.1 Viewing The Process Value and Setpoint.............................................4
1.2.2 To Adjust The Setpoint..........................................................................4
1.2.3 Viewing The Display Units.....................................................................5
1.2.4 Use Of The “SCROLL” Button .........................................................5
1.2.5 Use Of The ‘PAGE’ Button ..............................................................6
PARAMETER LISTS ..................................................................................7
1.4 manual or automatic control..........................................................8
1.4.1 Selecting Auto/Manual Operation .........................................................8
1.4.2 How To Manually Adjust Output Power.................................................9
1.5 SUMMARY........................................................................................9
1.6 Selecting SETPOINT 1 OR SETPOINT 2......................................10
1.7 RAMP DWELL FUNCTION.............................................................11
1.7.1 To Set up a Ramp/Time Program .......................................................11
1.7.2 To Run the Program............................................................................12
1.7.3 Power Failure During Program Run....................................................12
1.8 Location of Parameters - Block Diagram....................................13
1.9 NAVIGATION DIAGRAM (Part A)...................................................14
NAViGATION Diagram (Part B)...............................................................15
1.10 parameter tables.........................................................................16
1.10.1 HOME Display.................................................................................16
1.10.2 Alarm List.........................................................................................17
1.10.3 Autotune List....................................................................................18
1.10.4 PID List............................................................................................18
1.10.5 Setpoint List.....................................................................................19
1.10.6 Input List..........................................................................................20
1.10.7 On/Off List .......................................................................................20
1.10.8 Output List.......................................................................................21
1.10.9 Communications List.......................................................................21
1.10.10 Access List ......................................................................................21
1.11 alarms..........................................................................................22
1.11.1 Types of Alarm Used in the 2200 ....................................................22
1.12 Alarm relay output......................................................................23
1.12.1 SETTING ALARM LEVELS .............................................................24
1.12.2 ALARM INDICATION AND ACKNOWLEDGEMENT.......................25
1.12.3 DIAGNOSTIC ALARMS...................................................................26

Operation Installation and Operation Handbook
1-2 2208e and 2204e Controller
1.1 FRONT PANEL LAYOUT
Figure 1-1 Model 2208e front panel layout
Figure 1-2 Model 2204e front panel layout
Page
Button
Scroll
Button
Down
Button
Up
B
utton
Manual mode
S
etpoint 2 active PDS Remote Setpoint
S
etpoint rate limit active
20.0.0
20.0.0
OP1
OP2
SP2 REM
2208e
Output 1 Output 2
Upper readout
Lower readout
Down
Button
Manual mode
Page
Button
Scroll
Button
Up
B
utton
Remote Setpoint
Output 2
U
pper readout
Lower readout
Output 1
S
etpoint 2
active
Setpoint rate
l
imit active
20.00
20.00
OP1
OP2
2204e
SP2 REM

Installation and Operation Handbook Operation
2208e and 2204e Controller 1-3
Button or
indicator Name Explanation
OP1 Output 1
When lit, it indicates that heating output is on.
OP2 Output 2
When lit, it indicates that cooling output is on.
SP2 Setpoint 2
When lit, this indicates that Setpoint 2 has been
selected.
REM Remote Setpoint
When lit, this indicates that the PDS remote
Setpoint input has been selected. ‘REM’ is also
used to indicate that user comms is active.
MAN Manual light
When lit, it indicates that manual mode has been
selected
RUN Run light
When lit, it indicates that Setpoint rate limit is
active.
Page button Press to select a new list of parameters.
Scroll button Press to select a new parameter in a list.
Down button Press to decrease a value in the lower readout.
Up button Press to increase a value in lower readout.
Figure 1.3 Controller buttons and indicators
For Valve Positioning, please refer to Appendix D ‘Motorised Valve Control
i

Operation Installation and Operation Handbook
1-4 2208e and 2204e Controller
1.2 GETTING STARTED
Thank you for selecting the 2208e/2204e controller.
This section shows the principle of operation.
1.2.1 Viewing The Process Value and Setpoint
Install and wire up the controller in accordance with Chapter 2 and switch on. Following a 3
second self-test sequence, this is the display you will see,
Figure 1.4 The “Home Display”
The display may flash an alarm message. Refer to the Parameter Tables later in this
chapter for a complete list and meaning of the messages.
1.2.2 To Adjust The Setpoint
Figure 1.5 The lower readout shows the setpoint
After 2 seconds the lower readout will ‘blink’ indicating that the new value has been accepted.
For everyday use you may not need to do anymore than this.
Output 1
A
ctual Temperature (Process Value)
Output 2
Required Temperature (Setpoint)
20.0
23.0
O
P1
O
P2
!
"
Press and hold to
increase temperature
Press and hold to
decrease temperature
20.0
140.0
O
P1
O
P2

Installation and Operation Handbook Operation
2208e and 2204e Controller 1-5
1.2.3 Viewing The Display Units
Figure 1.6 Pressing or will flash the display units for 0.5 secs
If you get lost, pressing and together will return you to the Home display
1.2.4 Use Of The “SCROLL” Button
Pressing the scroll button will display the output power level. Continued pressing will
display further parameters in the operator scroll list.
Figure 1.6 Upper readout is parameter name. Lower is value
Keep pressing to
r
eturn to the
Home display or select further
parameters (if available)
2nd press
3rd press
Output
A
ctual output level %
OP
OPOP
OP
100.0
100.0100.0
100.0
Manual/Auto
A
ctual state
m
mm
m-
--
-A
AA
A
Auto
AutoAuto
Auto
Display Units
C
CC
CDegrees Centigrade
F
FF
FDegrees Farenheit
K
KK
KDegrees Kelvin
No units - Linear inputs
M
omentarily
press either
button
!
!
0.5 sec.
23.0
C
20.0
20.020.0
20.0
140.0
140.0140.0
140.0
i

Operation Installation and Operation Handbook
1-6 2208e and 2204e Controller
1.2.5 Use Of The ‘PAGE’ Button
The “PAGE” button accesses parameter LISTS.
Parameters are settings in the instrument which, generally, can be changed by the user to suit
the process. Examples are: Alarms, Self Tune, etc. They are found under headings called
LISTS and a full set is given later in this chapter.
Figure 1.7 Press to choose a parameter list
The actual list headings may be longer or shorter than indicated above and you can
customise this for the operator’s convenience in EDIT level, Chapter 3.
Keep pressing to
select more list headings
1st press
0.2 sec.
23.0
23.023.0
23.0
C
CC
C
20.0
20.020.0
20.0
1400
14001400
1400
3rd press
2nd press
AL
ALAL
AL
LiSt
LiStLiSt
LiSt atun
atunatun
atun
LiSt
LiStLiSt
LiSt
2
22
20.0
0.00.0
0.0
14.00
14.0014.00
14.00
i

Installation and Operation Handbook Operation
2208e and 2204e Controller 1-7
1.3 PARAMETER LISTS
Press to choose a LIST - “ALARMS” is a good one. This list allows you to set the alarm
trip levels. The parameters which appear in the list will vary according to the configuration of
your controller.
Figure 1.8 Choose a list. Press to select a parameter
If, at any time, no key is pressed within 45 seconds, the display will always return to
the “HOME” display.
A complete description of the parameter lists is given on page 1-14.
or to
change trip level
or to
change trip level
1st press
!
2nd press
0.2 sec.
23.0
23.023.0
23.0
C
CC
C
20.0
140.0
There are 4 alarms in
the controller. The first
character is the alarm
number. The following
three letters indicate
alarm type as follows:
-
--
-FSL
FSLFSL
FSL Full Scale Low
-
--
-FSH
FSHFSH
FSH Full Scale High
-
--
-d
dd
dHi
HiHi
Hi Deviation High
-
--
-dLo
dLodLo
dLo Deviation Low
-
--
-dEv
dEvdEv
dEv Deviation Band
-
--
-Lcr
LcrLcr
Lcr Low current
-
--
-Hcr
HcrHcr
Hcr High current
Disabled alarms will not
be displayed.
Chapter 7 gives a full
description of alarms.
A
larm
List
A
larm 1
Now press
t
he SCROLL
b
utton
2nd press
AL
ALAL
AL
LiSt
LiStLiSt
LiSt
1
11
1-
--
---
----
--
50.0
50.050.0
50.0
2
22
2---
------
---
200 0
200 0200 0
200 0
Keep pressing
1. to scroll through further parameters
2. to return to list header
A
larm 2
i

Operation Installation and Operation Handbook
1-8 2208e and 2204e Controller
1.4 MANUAL OR AUTOMATIC CONTROL
The controller can be used in two modes:
Automatic mode - in which the output power is automatically adjusted to hold the
temperature at the required value. The controller normally operates in this mode.
Manual mode - in which the output is manually adjusted by the Operator. In this mode the
‘MAN’ light will be on.
One other mode is available:
Remote setpoint - The setpoint is generated as an input signal from a master 2000 series
controller. In this mode the REM light is on.
1.4.1 Selecting Auto/Manual Operation
Figure 1.9 Auto/Manual select
or to select
2 sec.
23.0
23.023.0
23.0
C
CC
C
20.0
20.020.0
20.0
1st press
Output
A
ctual output level %
Manual/Auto
Auto
AutoAuto
Auto automatic mode
Man
ManMan
Man
manual mode
2nd press
3rd press
OP
OPOP
OP
100.0
100.0100.0
100.0
m
mm
m-
--
-A
AA
A
mAn
mAnmAn
mAn
Keep pressing
to return to “HOME”
display

Installation and Operation Handbook Operation
2208e and 2204e Controller 1-9
1.4.2 How To Manually Adjust Output Power
Figure 1.10 The “Home Display” in manual mode
1.5 SUMMARY
To step through list headers press the Page button until the required header is obtained
To step through parameters within a particular list press the Scroll button until the
required parameter is obtained
To change the value (or state) of a parameter press the Raise button or the
Lower button
The remainder of this chapter provides a complete list of all parameters available.
A
ctual Temperature (Process Value)
20.0
20.020.0
20.0
50.0
50.050.0
50.0
O
P1
O
P2
Output Power Demand
Manual Indicator on
!
"
Press and hold to
increase power
Press and hold to
decrease power
Manual mode is generally used for test and commissioning purposes, take
care not to leave the controller in this mode since damage or personal injury
could occur.
i

Operation Installation and Operation Handbook
1-10 2208e and 2204e Controller
1.6 SELECTING SETPOINT 1 OR SETPOINT 2
The instrument has the facility to select two setpoints. This may be useful, for example, where
it is required to switch control between two different setpoints or to control in a standby
condition, thus avoiding the necessity to change the setpoint manually each time.
To Select Setpoint 1 orSetpoint 2
This may be done in two ways:-
1. By an external switch or relay contact wired to a digital input
2. Through the front panel using the SP list
Figure 1-11 To Select Setpoint 1 or 2
Press to
select SP list
20.0
140.0
Setpoint
List
Press scroll
button to
SSEL
SP
SPSP
SP
LiSt
LiStLiSt
LiSt
SSEL
SSELSSEL
SSEL
SP 1
SP 1SP 1
SP 1 Press or to
change between SP 1 and
SP 2
When setpoint 2 is
selected the SP2 beacon
i
lluminates.

Installation and Operation Handbook Operation
2208e and 2204e Controller 1-11
1.7 RAMP DWELL FUNCTION
The ramp dwell function is selected by turning the setpoint rate limit parameter SPrr to a
value. It can be set to RUN in two ways:-
1. Through the front panel using the SP list
2. By an external switch or relay contact wired to a digital input configured for reset
(rset). When closed the program will reset. When open the program will run. To run
the program from the initial reset state, it is necessary to first close the switch then open
it.
The controller will then ramp from setpoint 1 to setpoint 2 at a rate set by the SPrr
parameter.
When the controller reaches setpoint 2 it can remain at this level for a timed period, using the
dwel parameter.
At the end of the dwell period the action of the controller is determined by the End Type
parameter End.t.
1.7.1 To Set up a Ramp/Time Program
Set setpoint 1 to the value at which to start the ramp. Set setpoint 2 to the value which you
wish to ramp to. This is described in the previous section.
Now press until SPrr is displayed
Figure 1-12 Ramp/Dwell Program
In Run mode the controller will ramp
from SP 1 to SP 2 at 20.0 units per
minute
Press scroll button to dwEl
SPrr
SPrrSPrr
SPrr
20.0
20.020.0
20.0
dwel
dweldwel
dwel
60.0
60.060.0
60.0
Press or to set the
SP ramp rate in units per minute
Press or to set the
dwell time in minutes
I
n Run mode the controller will dwell at
SP 2 for 60 minutes
Press scroll button to End.t
End.t
End.tEnd.t
End.t
rSEt
rSEtrSEt
rSEt
Press or to choose
the action required at the end of
the dwell time
In Run mode the controller will reset at the
end of the dwell time.
Other choices are:-
HoLd The program will go into Hold
StbY The program will go into
standby
dwel The program will dwell for an
unlimited period

Operation Installation and Operation Handbook
1-12 2208e and 2204e Controller
1.7.2 To Run the Program
In Full access level the Status of the program can be read as follows:-
A program may also be reset or run using an external switch contact if a digital input has been
configured. See Configuration section.
Figure 1-13 To Run the Ramp/Dwell Program
1.7.3 Power Failure During Program Run
1. During Ramp. After return of power, the working setpoint will servo to the current PV
value, and the ramp continues to SP2 followed by the timed dwell.
2. During Dwell. After return of power the working setpoint will servo to PV, the ramp
continues to SP2 followed by full programmed dwell. In effect this causes the program to
restart.
Use the Hide, Reveal and Promote features to customise the display for a programmer.
See Chapter 3.
From the previous view,
press scroll button to ProG
Prog
ProgProg
Prog
run
runrun
run
Press or to
choose run To reset the controller to start conditions, select
rSEt
i
From the previous view,
press scroll button to StAt
StAt
StAtStAt
StAt
rmp
rmprmp
rmp
The status may be any one of the following:
rmp Ramping from SP1 to SP2
dwel Dwelling at SP2
End The program is complete.
If End.t = rSEt, End will flash briefly
before changing to OFF
OFF The program is in the reset state
This manual suits for next models
1
Table of contents
Other Eurotherm Temperature Controllers manuals

Eurotherm
Eurotherm 2408i User manual

Eurotherm
Eurotherm 3116 User manual

Eurotherm
Eurotherm Invensys 3216 User manual

Eurotherm
Eurotherm 3200 User manual

Eurotherm
Eurotherm 2116 User manual

Eurotherm
Eurotherm 3116 User manual

Eurotherm
Eurotherm 3100 Installation and operation manual

Eurotherm
Eurotherm 2208L User manual

Eurotherm
Eurotherm 2216L Wiring diagram

Eurotherm
Eurotherm 2216e Owner's manual