Eurotherm 3100 Installation and operation manual

3100/3200
PID Temperature Controllers
Engineering Manual
e
E
UROTHERM®
invensys®

© 2009 Eurotherm Limited
All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted
in any form by any means, nor may it be stored in a retrieval system other than for the purpose to act as
an aid in operating the equipment to which the document relates, without the prior written permission
of Eurotherm Limited.
Eurotherm Limited pursues a policy of continuous development and product improvement. The speci-
fications in this document may therefore be changed without notice. The information in this document
is given in good faith, but is intended for guidance only. Eurotherm Limited will accept no responsibility
for any losses arising from errors in this document.

3200 Series
Part No HA028651 Issue 7.0 Apr-09 1
3200 Series PID Temperature Controllers
Engineering Handbook Part Number HA028651 Issue 7.0 Apr-09
Includes 3216, 3208, 32h8 and 3204 Controllers.
Contents
1. Installation and Basic Operation .....................................................................................................5
1.1 What Instrument Do I Have? ..............................................................................................................................5
1.2 Unpacking Your Controller.................................................................................................................................5
1.3 Dimensions.........................................................................................................................................................5
1.4 Step 1: Installation ............................................................................................................................................6
1.4.1 Panel Mounting the Controller.........................................................................................................................................................................6
1.4.2 Panel Cut Out Sizes ..............................................................................................................................................................................................6
1.4.3 Recommended minimum spacing of controllers.........................................................................................................................................6
1.4.4 To Remove the Controller from its Sleeve....................................................................................................................................................6
1.5 Order Code ........................................................................................................................................................7
2. Step 2: Wiring ................................................................................................................................8
2.1 Terminal Layout 3216 Controller ........................................................................................................................8
2.2 Terminal Layout 32h8 Controllers.......................................................................................................................9
2.3 Terminal Layout 3208 and 3204 Controllers ........................................................................................................9
2.4 Wire Sizes ..........................................................................................................................................................10
2.5 Precautions ........................................................................................................................................................10
2.6 Sensor Input (Measuring Input) ..........................................................................................................................10
2.6.1 Thermocouple Input............................................................................................................................................................................................10
2.6.2 RTD Input................................................................................................................................................................................................................10
2.6.3 Linear Input (mA or mV) ....................................................................................................................................................................................10
2.6.4 Two-Wire Transmitter Inputs ............................................................................................................................................................................10
2.7 Input/Output 1 & Output 2.................................................................................................................................11
2.7.1 Relay Output (Form A, normally open)..........................................................................................................................................................11
2.7.2 Logic (SSR drive) Output ....................................................................................................................................................................................11
2.7.3 DC Output ..............................................................................................................................................................................................................11
2.7.4 Triac Output...........................................................................................................................................................................................................11
2.7.5 Logic Contact Closure Input (I/O 1 only).......................................................................................................................................................11
2.8 Remote Setpoint Input .......................................................................................................................................11
2.9 Output 3 ............................................................................................................................................................11
2.10 Output 4 (AA Relay) ...........................................................................................................................................11
2.11 General Note About Relays and Inductive Loads ................................................................................................12
2.12 Digital Inputs A & B............................................................................................................................................12
2.13 Current Transformer ..........................................................................................................................................12
2.14 Transmitter Power Supply ..................................................................................................................................12
2.15 Digital Communications .....................................................................................................................................13
2.15.1.1 EIA422 Connections (3216 only) ................................................................................................................................................................13
2.16 Controller Power Supply ....................................................................................................................................14
2.17 Example Heat/Cool Wiring Diagram ...................................................................................................................14
2.17.1 Example CT Wiring Diagram........................................................................................................................................................................14
3. Safety and EMC Information ...........................................................................................................15
3.1 Installation Safety Requirements ........................................................................................................................15
4. Switch On .......................................................................................................................................17
4.1 New Controller...................................................................................................................................................17
4.1.1 Quick Start Code...................................................................................................................................................................................................17
4.2 To Re-Enter Quick Code mode............................................................................................................................18
4.3 Pre-Configured Controller or Subsequent Starts .................................................................................................18
4.4 Front Panel Layout .............................................................................................................................................19
4.4.1 To Set The Target Temperature. ......................................................................................................................................................................19
4.4.2 Alarms......................................................................................................................................................................................................................19
4.4.3 Alarm Indication ...................................................................................................................................................................................................19
4.4.4 Auto, Manual and Off Mode .............................................................................................................................................................................20
4.4.5 To Select Auto, Manual or Off Mode .............................................................................................................................................................20
4.4.6 Level 1 Operator Parameters ............................................................................................................................................................................21
5. Operator Level 2 .............................................................................................................................21
5.1 To Enter Level 2 .................................................................................................................................................21
5.2 To Return to Level 1...........................................................................................................................................21

3200 Series
2 Part No HA028651 Issue 7.0 Apr-09
5.3 Level 2 Parameters .............................................................................................................................................21
5.4 Timer Operation.................................................................................................................................................25
5.5 Dwell Timer .......................................................................................................................................................26
5.6 Delayed Timer....................................................................................................................................................26
5.7 Soft Start Timer .................................................................................................................................................27
5.8 Programmer.......................................................................................................................................................27
5.8.1 Programmer Servo Mode and Power Cycling.............................................................................................................................................. 28
5.8.2 To Operate the Programmer ............................................................................................................................................................................ 28
5.8.3 To Configure the Programmer......................................................................................................................................................................... 29
6. Access to Further Parameters..........................................................................................................30
6.1.1 Level 3..................................................................................................................................................................................................................... 30
6.1.2 Configuration Level ............................................................................................................................................................................................. 30
6.1.3 To Select Access Level 3 or Configuration Level......................................................................................................................................... 31
6.2 Parameter lists ...................................................................................................................................................32
6.2.1 To Choose Parameter List Headers................................................................................................................................................................. 32
6.2.2 To Locate a Parameter ....................................................................................................................................................................................... 32
6.2.3 How Parameters are Displayed ........................................................................................................................................................................ 32
6.2.4 To Change a Parameter Value.......................................................................................................................................................................... 32
6.2.5 To Return to the HOME Display ...................................................................................................................................................................... 32
6.2.6 Time Out ................................................................................................................................................................................................................ 32
6.3 Navigation Diagram ...........................................................................................................................................33
6.4 Access Parameters..............................................................................................................................................34
7. Controller Block Diagram................................................................................................................36
8. Temperature (or Process) Input ......................................................................................................37
8.1 Process Input Parameters ...................................................................................................................................37
8.1.1 Input Types and Ranges ..................................................................................................................................................................................... 38
8.1.2 Operation of Sensor Break................................................................................................................................................................................ 39
8.2 PV Offset............................................................................................................................................................40
8.2.1 Example: To Apply an Offset:- ........................................................................................................................................................................ 40
8.3 PV Input Scaling.................................................................................................................................................40
8.3.1 Example: To Scale a Linear Input ................................................................................................................................................................... 40
9. Input/Output...................................................................................................................................41
9.1 Input/Output Parameters ...................................................................................................................................42
9.1.1 Input/Output 1 List (IO-1)................................................................................................................................................................................ 42
9.1.2 Remote Digital Setpoint Select and Remote Fail........................................................................................................................................ 44
9.1.3 Sense ....................................................................................................................................................................................................................... 44
9.1.4 Source ..................................................................................................................................................................................................................... 44
9.1.5 Power Fail............................................................................................................................................................................................................... 44
9.1.6 Example: To Configure IO-1 Relay to Operate on Alarms 1 and 2:- .................................................................................................... 44
9.1.7 Output List 2 (OP-2) .......................................................................................................................................................................................... 45
9.1.8 Output List 3 (OP-3) .......................................................................................................................................................................................... 46
9.1.9 AA Relay (AA) (Output 4)................................................................................................................................................................................. 47
9.1.10 Digital Input Parameters .............................................................................................................................................................................. 48
9.2 Current Transformer Input Parameters...............................................................................................................49
9.2.1 Analogue Representation of Current Alarms............................................................................................................................................... 49
10. Setpoint Generator .........................................................................................................................50
10.1 Setpoint Parameters...........................................................................................................................................50
10.2 Example: To Set Ramp Rate...............................................................................................................................51
11. Control ...........................................................................................................................................52
11.1 PID Control ........................................................................................................................................................52
11.2 Tuning................................................................................................................................................................52
11.2.1 Automatic Tuning .......................................................................................................................................................................................... 52
11.2.2 How To Tune................................................................................................................................................................................................... 53
11.2.3 Calculation of the cutback values ............................................................................................................................................................. 53
11.2.4 Manual Tuning................................................................................................................................................................................................ 53
11.2.5 Setting the Cutback Values......................................................................................................................................................................... 53
11.3 Integral Action and Manual Reset ......................................................................................................................54
11.4 Relative Cool Gain..............................................................................................................................................54
11.5 Control Action ...................................................................................................................................................54
11.6 On/Off Control...................................................................................................................................................54
11.7 Valve Position Control........................................................................................................................................54
11.8 Loop Break.........................................................................................................................................................54
11.9 Cooling Algorithm..............................................................................................................................................54

3200 Series
Part No HA028651 Issue 7.0 Apr-09 3
11.10 Control Parameters........................................................................................................................................55
11.11 Auto-tune Configures R2G .............................................................................................................................57
11.12 Example: To Configure Heating and Cooling .................................................................................................58
11.12.1 Effect of Control Action, Hysteresis and Deadband .............................................................................................................................59
12. Alarms ............................................................................................................................................60
12.1 Types of Alarm...................................................................................................................................................60
12.1.1 Alarm Relay Output .......................................................................................................................................................................................62
12.1.2 Alarm Indication .............................................................................................................................................................................................62
12.1.3 To Acknowledge An Alarm ..........................................................................................................................................................................62
12.2 Behaviour of Alarms After a Power Cycle ...........................................................................................................63
12.2.1 Example 1 .........................................................................................................................................................................................................63
12.2.2 Example 2 .........................................................................................................................................................................................................63
12.2.3 Example 3 .........................................................................................................................................................................................................63
12.3 Alarm Parameters ..............................................................................................................................................64
12.3.1 Example: To Configure Alarm 1 ................................................................................................................................................................65
12.4 Diagnostic Alarms ..............................................................................................................................................66
12.4.1 Out of Range Indication ...............................................................................................................................................................................66
13. Timer/Programmer .........................................................................................................................67
13.1 Timer Parameters...............................................................................................................................................67
13.2 Programmer .......................................................................................................................................................69
13.2.1 Threshold..........................................................................................................................................................................................................69
13.2.2 Run/End Digital Outputs...............................................................................................................................................................................70
13.2.3 Event Outputs..................................................................................................................................................................................................70
13.2.4 To Configure the Programmer....................................................................................................................................................................71
13.3 Example: To Configure a Dwell Timer as a Simple Two Step Programmer...........................................................72
14. Recipe.............................................................................................................................................75
14.1 To Save Values in a Recipe .................................................................................................................................75
14.2 To Save Values in a Second Recipe.....................................................................................................................75
14.3 To Select a Recipe to Run...................................................................................................................................76
14.3.1 List of Default Recipe Parameters:.............................................................................................................................................................76
15. Digital Communications..................................................................................................................77
15.1 Digital Communications Wiring ..........................................................................................................................77
15.1.1 EIA232................................................................................................................................................................................................................77
15.1.2 EIA485 (2-wire)................................................................................................................................................................................................77
15.1.3 Wiring EIA422 or 4-wire EIA485 .................................................................................................................................................................77
15.2 Digital Communications Parameters...................................................................................................................78
15.2.1 Broadcast Communications .........................................................................................................................................................................79
15.2.2 Broadcast Master Communications...........................................................................................................................................................79
15.2.3 Wiring Connections........................................................................................................................................................................................79
15.3 Example: To Set Up Instrument Address.............................................................................................................80
15.4 DATA ENCODING ...............................................................................................................................................80
15.5 Parameter Modbus Addresses.............................................................................................................................81
16. Calibration...................................................................................................................................... 91
16.1 To Check Input Calibration.................................................................................................................................91
16.1.1 Precautions.......................................................................................................................................................................................................91
16.1.2 To Check mV Input Calibration..................................................................................................................................................................91
16.1.3 To Check Thermocouple Input Calibration.............................................................................................................................................91
16.1.4 To Check RTD Input Calibration.................................................................................................................................................................92
16.2 Offsets ...............................................................................................................................................................92
16.2.1 Two Point Offset.............................................................................................................................................................................................92
16.2.2 To Apply a Two Point Offset .......................................................................................................................................................................93
16.2.3 To Remove the Two Point Offset...............................................................................................................................................................93
16.3 Input Calibration................................................................................................................................................94
16.3.1 To Calibrate mV Input...................................................................................................................................................................................94
16.3.2 To Calibrate Thermocouple Input .............................................................................................................................................................95
16.3.3 To Calibrate RTD Input .................................................................................................................................................................................96
16.3.4 To Calibrate mA Outputs .............................................................................................................................................................................97
16.3.5 To Calibrate Remote Setpoint Input .........................................................................................................................................................98
16.3.6 CT Calibration..................................................................................................................................................................................................99
16.3.7 To Return to Factory Calibration ...............................................................................................................................................................99
16.4 Calibration Parameters.......................................................................................................................................100
17. Configuration Using iTools.............................................................................................................. 101
17.1 Loading an IDM..................................................................................................................................................101

3200 Series
4 Part No HA028651 Issue 7.0 Apr-09
17.2 Connecting a PC to the Controller......................................................................................................................101
17.2.1 Using the H Communications Port............................................................................................................................................................ 101
17.2.2 Configuration Clip ......................................................................................................................................................................................... 101
17.3 Starting iTools....................................................................................................................................................102
17.4 Starting the Wizard ............................................................................................................................................103
17.5 To configure the Input .......................................................................................................................................104
17.5.1 Example 1 - Using the Wizard .................................................................................................................................................................... 104
17.5.2 Example 2 – Using the Browser View....................................................................................................................................................... 104
17.6 To Configure Alarms ..........................................................................................................................................105
17.6.1 Example 1: Using the Wizard..................................................................................................................................................................... 105
17.6.2 Example 2: Using the Browser View ......................................................................................................................................................... 105
17.7 To Customise Messages ......................................................................................................................................106
17.7.1 Example 1: Using the Wizard..................................................................................................................................................................... 106
17.7.2 Example 2: Using the Browser View........................................................................................................................................................ 107
17.7.3 Example 3: Inverted Status Word............................................................................................................................................................. 108
17.7.4 Example 4: Display the message ‘OUT OF CONTROL’ if both Alarm 1 and Alarm 2 are active. ............................................ 109
17.8 To Promote Parameters......................................................................................................................................110
17.8.1 Example 1: Using the Wizard..................................................................................................................................................................... 110
17.8.2 Example 2: Using the Browser view......................................................................................................................................................... 111
17.9 To Load A Special Linearisation Table ................................................................................................................112
17.9.1 Example: Using the Browser view ............................................................................................................................................................ 112
17.10 To Set up Recipes ..........................................................................................................................................113
17.10.1 Example 1: Using the Browser view......................................................................................................................................................... 113
17.10.2 Example 2: Using the Wizard..................................................................................................................................................................... 114
17.10.2.1 Recipe Definition ..................................................................................................................................................................................... 114
17.10.2.2 Editing Recipe Values ............................................................................................................................................................................. 115
17.10.2.3 Recipe Names ........................................................................................................................................................................................... 115
17.11 Summary .......................................................................................................................................................116
17.11.1 Example 1: Using the Wizard..................................................................................................................................................................... 116
17.11.2 Example 2: Using the browser view......................................................................................................................................................... 116
17.12 Cloning..........................................................................................................................................................117
17.12.1 Save to File ...................................................................................................................................................................................................... 117
17.12.2 To Clone a New Controller ......................................................................................................................................................................... 117
18. Appendix A TECHNICAL SPECIFICATION ........................................................................................118
19. Parameter Index .............................................................................................................................120
20. Index...............................................................................................................................................123
Issue Status of this Manual
Issue 5 of this Handbook applies to software versions 2.09 and above for PID controller and 2.29 and above for Valve
Position controllers and includes:-
•Remote Setpoint Input Option RCL
•Programmer Cycles
•Triac output
•EIA422 4-wire Digital Communications, Option 6XX available in 3216 only
It also applies to firmware versions 2.11 and includes new parameters:-
Inverted status word, section 17.7.3.
Rate of change alarms, section 12.3.
Setpoint retransmission limits, section 10.1.
Input filter, section 8.1.
Note:-
The 3116 controller is no longer available. Details may be found in issue 4 of this manual.
Issue 6 includes parameter ‘AT.R2G’, section 11.11.
Issue 7 corrects range limits in section 8.1.1. Change to definition of LOC.T. in section 10.1. Correct description of
enumerations for parameter IM section 15.5.

3200 Series
Part No HA028651 Issue 7.0 Apr-09 5
1. Installation and Basic Operation
1.1 What Instrument Do I Have?
Thank you for choosing this 3200 series Temperature
Controller/Programmer.
The 3200 series provide precise temperature control of
industrial processes and is available in three standard
DIN sizes:-
•1/16 DIN Model Number 3216
•1/8 DIN Model Number 3208
•1/8 DIN Horizontal Model Number 32h8
•1/4 DIN Model Number 3204
A universal input accepts various thermocouples, RTDs or
process inputs. Up to three (3216) or four (3208, 32h8
and 3204) outputs can be configured for control, alarm
or re-transmission purposes. Digital communications and
a current transformer input are available as options.
The controller may have been ordered to a hardware
code only or pre-configured using an optional ‘Quick
Start’ code.
The label fitted to the side of the sleeve shows the
ordering code that the controller was supplied to.
The last two sets of five digits show the Quick Start Code.
If the Quick Start Code shows *****/***** the controller
was supplied with default parameters and will need to be
configured when it is first switched on.
This Manual takes you through all aspects of installation,
wiring, configuration and use of the controller.
1.2 Unpacking Your Controller
The controller is supplied with:-
•Sleeve (with the controller fitted in the sleeve)
•Two panel retaining clips and IP65 sealing gasket
mounted on the sleeve
•Component packet containing a snubber for each
relay output (see section 2.11) and a 2.49Ωresistor
for current inputs (see section 2.6)
•Installation sheet Part Number HA029714
1.3 Dimensions
General views of the controllers are shown below
together with overall dimensions.
3216
3208, 32h8 and 3204
Panel retaining clip
90mm (3.54in)
Top View
Label showing
Order Code
Serial Number
including date of
manufacture
90mm (3.54in)
IP65 Sealing Gasket
Latching
ears
Side View
Latching
ears
96mm
(3.78in)
48mm
(1.89in)
96mm (3.78in)
Front Views 48mm
(1.89in)
3208 3204
32h8
Front View
48mm
(1.89in)
48mm
(1.89in)
Side View
Panel retaining clips
IP65 Sealing Gasket
1.25mm
(0.5in)
Latching
ears

3200 Series
6 Part No HA028651 Issue 7.0 Apr-09
1.4 Step 1: Installation
This instrument is intended for permanent installation,
for indoor use only, and enclosed in an electrical panel
Select a location which is subject to minimum vibrations
the ambient temperature is within 0 and 55oC (32 -
131oF) and humidity 5 to 95% RH non condensing.
The instrument can be mounted on a panel up to 15mm
thick.
To ensure IP65 and NEMA 4 front protection, mount on
a non-textured surface.
Please read the safety information in section 3 before
proceeding. The EMC Booklet part number HA025464
gives further installation information.
1.4.1 Panel Mounting the Controller
1. Prepare a cut-out in the mounting panel to the size
shown. If a number of controllers are to be mounted
in the same panel observe the minimum spacing
shown.
2. Fit the IP65 sealing gasket behind the front bezel of
the controller
3. Insert the controller through the cut-out
4. Spring the panel retaining clips into place. Secure
the controller in position by holding it level and
pushing both retaining clips forward.
5. Peel off the protective cover from the display.
1.4.2 Panel Cut Out Sizes
1.4.3 Recommended minimum spacing of
controllers
Applies to all models.
1.4.4 To Remove the Controller from its
Sleeve
The controller can be unplugged from its sleeve by
easing the latching ears outwards and pulling it forward
out of the sleeve. When plugging it back into its sleeve,
ensure that the latching ears click back into place to
maintain the IP65 sealing
10mm (0.4 in)
38mm (1.5 in)
(Not to scale)
45 mm
- 0.0 + 0.6
1.77 in
-0.00, +0.02
45 mm - 0.0 + 0.6
1.77 in -0.00, +0.02
92 mm
- 0.0 + 0.8
3.62 in
-0.00, +0.03
92 mm - 0.0 + 0.8
3.62 in -0.00, +0.03
Model 3216
Model 3208 Model 3204
Model 32h8

3200 Series
Part No HA028651 Issue 7.0 Apr-09 7
1.5 Order Code
1 2 3 4 5 6 7 8 9 10 11 12 13 14
3216
3208
32h8
3204
3. Power Supply
24Vac/dc VL
100–240Vac VH
7. Fascia colour/type
Green G
Silver S
Wash down fascia
(not 32h8/04)
W
6. Options
Not fitted XXX
EIA485 & Digital input A 4XL*
EIA232 & Digital input A 2XL*
EIA485, CT & Dig in A 4CL
EIA232, CT & Dig in A 2CL
Digital input A XXL*
CT & Digital input A XCL
Remote SP and Logic IP RCL
4-wire EIA485 (EIA422)
Comms (3216 only)
6XX
* 3216 only
10. Extended Warranty
Standard XXXXX
Extended WL005
11. Certificates
XXXXX None
Cert of conformity CERT1
Factory calibration CERT2
12. Custom Label
None XXXXX
13. Specials Number
None XXXXXX
250Ω; 0-5Vdc OP RES250
500Ω; 0-10Vdc OP RES500
2. Function
Controller CC
Programmer CP
valve controller VC
Valve programmer VP
5. AA Relay (OP4)
Disabled X
Relay (Form C) R
1. Model No.
1/16 DIN size 3216
1/8 DIN size
vertical
3208
1/8 DIN horizontal 32h8
1/4 DIN size 3204
8/9 Product/Manual Language
English ENG
French FRA
German GER
Italian ITA
Spanish SPA
4. Outputs 1, 2 and 3 3208/H8/04
OP1 OP2 OP3
L R R X
R R R X
L L R X
L R D X
R R D X
D D D X
L L D X
L D D X
D R D X
L T R X
T T R X
L T D X
T T D X
4. Output 1 & 2 3216
OP1 OP2
L X X X
L R X X
R R X X
L L X X
L D X X
D D X X
D R X X
R C X X
L C X X
D C X X
L T X X
T T X X
Triac not available with low voltage supply option.
L = Logic; R = Relay; D = DC; T = Triac:
C = Isolated 0-20mA

3200 Series
8 Part No HA028651 Issue 7.0 Apr-09
2. Step 2: Wiring
2.1 Terminal Layout 3216 Controller
(1) Option 6XX - EIA232 digital communications uses terminals C to HF.
When this option is fitted, CT/LA inputs are not available see section 2.15.1.1
Key to symbols used in wiring diagrams
Logic (SSR drive)
output
Relay output Contact input
mA analogue
output
Triac output Current transformer
input
!Ensure that you have the correct
supply for your indicator
Check order code of the controller supplied
Digital Communications
EIA232, EIA485, or EIA422 (1) Or
Remote Setpoint IP
See section 2.8
Output 4 (AA Relay)
AA
AB
AC
VI
V+
V-
CT
C
LA
HD
HE
HF
COM
A(+)
B(-)
-
+
T/C
mV
-
Sensor
Input
Pt100
2.49
Ω
mA
-
++
Line Supply 100 to 240Vac 48 to
62Hz
OR
Low Voltage Supply 20 -29Vac/dc
Input/Output 1
Output 2
10V
Potential divider
module
Part No SUB21/IV10
-
+
10V
Input
+ +
- -
+ +
- -
1A
1B
2A
2B
L
N

3200 Series
Part No HA028651 Issue 7.0 Apr-09 9
2.2 Terminal Layout 32h8 Controllers
2.3 Terminal Layout 3208 and 3204 Controllers
Key to symbols used in wiring diagrams
Logic (SSR drive) output Relay output Contact input
mA analogue output Triac output Current transformer input
Digital Communications
EIA232 or EIA485
Or
Remote Setpoint IP See section 2.8
Output 4 (AA Relay)
Line Supply 100 to 240Vac 48 to 62 Hz
OR
Low Voltage Supply 20 - 29Vac/dc
Input/Output 1
CT input
Digital input A
AA
AB
AC
HD
HE
HF
CT
C
LA
VI
V+
V-
1A
1B
2A
2B
LB
LC
3A
3B
3C
3D
L
N
COM
A(+)
B(-)
-
+
T/C
+
mV
-
PV Input
Pt100
2.49Ω
mA
-
+
+
- +
24V
-
Output 2
Digital Input B
Output 3
24V Transducer Supply
10V
Potential divider
module
Part No
SUB21/IV10
-
+
10V
Input
+ +
- -
+ +
- -
- + - +
- + - +
- + C NO C NO
Line Supply 100 to 240Vac 48 to
62 Hz
OR
Low Voltage Supply 24Vac/dc
10V Potential divider
module
Part No SUB21/IV10
- +
10V Input
Output
3
24V Transmitter Supply
AA Relay (OP4)
B(-) A(+) COM
Digital Comms
Or
Remote
Setpoint IP
See section 2.8
- +
T/C
Sensor
Input
Pt100
V- V+ VI LA C CT HF HE HD AC AB AA
N L 3D 3C 3B 3A LC LB 2B 2A 1B 1A
2.49Ω
mA/mV
+
-
-
+
32h8 Controller
Dig in A
CT input
Output
2
Input/
Output 1
Dig
in B
C NO
!Ensure that you have the correct
supply for your indicator
Check order code of the controller supplied
!Ensure that you have the correct
supply for your indicator
Check order code of the controller supplied

3200 Series
10 Part No HA028651 Issue 7.0 Apr-09
2.4 Wire Sizes
The screw terminals accept wire sizes from 0.5 to 1.5 mm
(16 to 22AWG). Hinged covers prevent hands or metal
making accidental contact with live wires. The rear
terminal screws should be tightened to 0.4Nm (3.5lb in).
2.5 Precautions
•Do not run input wires together with power cables
•When shielded cable is used, it should be grounded
at one point only
•Any external components (such as zener barriers,
etc) connected between sensor and input terminals
may cause errors in measurement due to excessive
and/or un-balanced line resistance or possible
leakage currents
•Not isolated from the logic outputs & digital inputs
•Pay attention to line resistance; a high line resistance
may cause measurement errors
2.6 Sensor Input (Measuring Input)
2.6.1 Thermocouple Input
Positive
Negative
•Use the correct compensating cable preferably
shielded
2.6.2 RTD Input
PRT
PRT
Leadcompensation
•The resistance of the three wires must be the same.
The line resistance may cause errors if it is greater
than 22Ω
2.6.3 Linear Input (mA or mV)
•If shielded cable is used it should be grounded in
one place only as shown
•For a mA input connect the 2.49Ωburden resistor
supplied between the V+ and V- terminals as shown
•For a 0-10Vdc input an external input adapter is
required (not supplied). Part number: SUB21/IV10
Sensor break alarm does not operate with this adaptor
fitted.
2.6.4 Two-Wire Transmitter Inputs
100KΩ
806Ω
+
0-10V
Input
-
+
-
-
+
V+
V-
VI
V+
V-
-
2.49Ω
+
V+
V-
Shield
+
mA / mV input
-
Using internal 24V power supply (3208, 32h8 and 3204 only)
-
+
V+
V-
-
+
2-Wire
Transmitter
-
+
2.49Ω
3C
3D
Using external power
su
pp
l
y
+
-
External power
supply
-
+
2-Wire
Transmitter
-
+
2.49Ω
V+
V-

3200 Series
Part No HA028651 Issue 7.0 Apr-09 11
2.7 Input/Output 1 & Output 2
These outputs can be logic (SSR drive), or relay, or mA
dc. In addition the logic output 1 can be used as a
contact closure input.
For input/output functions, see Quick Start Code in
section 4.1.1.
2.7.1 Relay Output (Form A, normally open)
•Isolated output 240Vac CAT II
•Contact rating: 2A 264Vac
resistive
2.7.2 Logic (SSR drive) Output
•Not isolated from the sensor
input
•Output ON state: 12Vdc at
40mA max
•Output OFF state: <300mV, <100μA
•The output switching rate must be set to prevent
damage to the output device in use. See
parameter 1.PLS or 2.PLS in section 5.3.
2.7.3 DC Output
•Order code C (OP2) only isolated 240Vac
•Order code D not isolated from the sensor input
•Software configurable: 0-20mA or 4-20mA.
•Max load resistance: 500Ω
•Calibration accuracy: +(<1% of reading + <100μA)
2.7.4 Triac Output
•Isolated output 240Vac CATII
•Rating: 0.75A rms, 30 to 264Vac resistive
2.7.5 Logic Contact Closure Input (I/O 1
only)
•Not isolated from the sensor input
•Switching: 12Vdc at 40mA max
•Contact open > 500Ω. Contact closed <
150Ω
2.8 Remote Setpoint Input
•There are two inputs; 4-
20mA and 0-10 Volts which
can be fitted in place of
digital communications
•It is not necessary to fit an
external burden resistor to the 4-20mA input
•If the 4-20mA remote setpoint input is connected and
valid (>3.5mA; < 22mA) it will be used as the main
setpoint. If it is not valid or not connected the
controller will try to use the Volts input. Volts sensor
break occurs at <-1; >+11V. The two inputs are not
isolated from each other
•If neither remote input is valid the controller will fall
back to the internal setpoint, SP1 or SP2 and flash the
alarm beacon. The alarm can also be configured to
activate a relay (see section 12.1.1) or read over digital
communications.
•To calibrate the remote setpoint, if required, see
section 16.3.5
•A local SP trim value is available in access level 3 (see
section 10.1).
2.9 Output 3
Output 3 is available only in the models 3208, 32h8 and
3204. It will be either a relay or a mA output.
For output functions, see Quick Start Code in section
4.1.1.
Relay Output (Form A, normally open)
Isolated output 240Vac CAT II
•Contact rating: 2A 264Vac resistive
DC Output
•Isolated output 240Vac CAT II
•Software configurable: 0-20mA or 4-
20mA
•Max load resistance: 500Ω
•Calibration accuracy: 0.5%, +100μA
2.10 Output 4 (AA Relay)
Output 4 is a relay and optionally available in all models.
For output functions, see Quick Start Code in section
4.1.1.
Relay Output (Form C)
•Isolated output 240Vac CAT II
•Contact rating: 2A 264Vac resistive
1(2) A
1(2)B
OP1 OP2
1A
1B
2A
2B
+
-
OP2
2A
2B
+
-
OP1
1A
1B
OP1
1A
1B
OP3
3A
3B
0-10 Volts
4-20 mA
Common
HD
HE
HF
+
-
OP3
3A
3B
OP4
AA
AB
AC
+
-
OP1
1A
1B
+
-
OP2
2A
2B

3200 Series
12 Part No HA028651 Issue 7.0 Apr-09
2.11 General Note About Relays and
Inductive Loads
High voltage transients may occur when switching
inductive loads such as some contactors or solenoid
valves. Through the internal contacts, these transients
may introduce disturbances which could affect the
performance of the instrument.
For this type of load it is recommended that a ‘snubber’
is connected across the normally open contact of the
relay switching the load. The snubber recommended
consists of a series connected resistor/capacitor (typically
15nF/100Ω). A snubber will also prolong the life of the
relay contacts.
A snubber should also be connected across the output
terminal of a triac output to prevent false triggering
under line transient conditions.
WARNING
When the relay contact is open or it is connected to
a high impedance load, the snubber passes a current
(typically 0.6mA at 110Vac and 1.2mA at 240Vac).
You must ensure that this current will not hold on
low power electrical loads. If the load is of this type
the snubber should not be connected.
2.12 Digital Inputs A & B
Digital input A is an optional input in all 3200 series
controllers.Digital input B is always fitted in models
3208, 32h8 and 3204, but is not available in 3216.
•Not isolated from the current transformer input or
the sensor input
•Switching: 12Vdc at 40mA max
•Contact open > 500Ω. Contact closed < 200Ω
•Input functions: Please refer to the list in the quick
codes.
☺If EIA232 digital communications is fitted (3216
only), Digital Input A is not available.
2.13 Current Transformer
The current transformer input is an optional input in all
3200 series controllers.
☺If EIA232 digital communications is fitted (3216
only), Current Transformer Input is not available.
It can be connected to monitor the rms current in an
electrical load and to provide load diagnostics. The
following fault conditions can be detected: SSR (solid
state relay) short circuit, heater open circuit and partial
load failure. These faults are displayed as alarm
messages on the controller front panel.
Note: C terminal is common to both the CT input and
Digital input A. They are, therefore, not isolated from
each other or the PV input.
•CT input current: 0-50mA rms (sine wave, calibrated)
50/60Hz
•A burden resistor, value 10Ω, is fitted inside the
controller.
•It is recommended that the current
transformer is fitted with a voltage
limiting device to prevent high voltage
transients if the controller is unplugged.
For example, two back to back zener diodes. The
zener voltage should be between 3 and 10V, rated
at 50mA.
•CT input resolution: 0.1A for scale up to 10A, 1A for
scale 11 to 100A
•CT input accuracy: +4% of reading.
2.14 Transmitter Power Supply
The Transmitter Supply is not available in the Model
3216. It is fitted as standard in the Models 3208, 32h8
and 3204.
•Isolated output 240Vac CAT II
•Output: 24Vdc, +/- 10%. 28mA max.
•inside the controller
Dig in A
C
LA
Dig in B
LB
LC
CT Input
CT
C
24Vdc
Transmitter Supply
3C
3D

3200 Series
Part No HA028651 Issue 7.0 Apr-09 13
2.15 Digital Communications
Optional.
Digital communications uses the Modbus protocol. The
interface may be ordered as EIA232 or EIA485 (2-wire).
In 3216 controllers only, EIA422 (4-wire) is available as
option 6XX.
☺Digital communications is not available if Remote
Setpoint is fitted
☺Cable screen should be grounded at one point only
to prevent earth loops.
•Isolated 240Vac CAT II.
EIA232 Connections
EIA485 Connections
2.15.1.1 EIA422 Connections (3216 only)
☺If EIA422 serial communications is fitted, the CT and
LA digital input option is not possible since EIA422 shares
the same terminals as the CT and LA.
☺The KD485 communications converter is
recommended for:
•Interfacing 4-wire to 2-wire connections.
•To buffer an EIA422/485 network when more than
32 instruments on the same bus are required
•To bridge 2-wire EIA485 to 4-wire EIA422.
Common
Rx A(+)
Tx B(-)
Screen
Local ground
Com
Rx
Tx
HD
HE
HF
220Ωtermination
resistor
* EIA232/EIA485 2-wire
communications converter
eg Type KD485
Daisy Chain to
further
controllers
Com
220Ωtermination
resistor on last
controller in the line
Twisted pair
Tx Rx Com
Rx Tx Com
Screen
RxB/
TxB
RxA/
TxA
*
Common
Rx A(+)
Tx B(-)
HD
HE
HF
Com
Tx
Com Rx Tx
Screen
no connection
Rx+
Rx-
Common
Tx+
Tx-
Daisy Chain
to further
controllers
Twised
pairs
220Ωtermination
resistor 220Ωtermination
resistor on last
controller in the
line
EIA232 to EIA422/EIA485 4-
wire communications
converter
Eg Type KD485
RxB Com TxA
RxA TxB
Com Tx Rx
CT
C
LA
HD
HE
HF
Screen

3200 Series
14 Part No HA028651 Issue 7.0 Apr-09
2.16 Controller Power Supply
1. Before connecting the instrument to the power line,
make sure that the line voltage corresponds to the
description on the identification label.
2. Use copper conductors only.
3. For 24V the polarity is not important
4. The power supply input is not fuse protected. This
should be provided externally
•High voltage supply: 100 to 240Vac, -15%, +10%, 48
to 62 Hz
•Low voltage supply: 24Vac/dc, -15%, +10%
•Recommended external fuse ratings are as follows:-
For 24 V ac/dc, fuse type: T rated 2A 250V
For 100-240Vac, fuse type: T rated 2A 250V.
2.17 Example Heat/Cool Wiring Diagram
This example shows a heat/cool temperature controller
where the heater control uses a SSR and the cooling
control uses a relay.
Safety requirements for permanently connected
equipment state:
•A switch or circuit breaker shall be included in the
building installation
•It shall be in close proximity to the equipment and
within easy reach of the operator
•It shall be marked as the disconnecting device for
the equipment
☺A single switch or circuit breaker can drive more
than one instrument
2.17.1 Example CT Wiring Diagram
This diagram shows an example of wiring for a CT input.
Line
Neutral
Power Supply
L
N
N
Heater fuse
Controller fuse
Heater
T/C
Solid State
Relay
(e.g. TE10)
L
+
-
J
JF
B
3216
1A
1B
2A
2B
L
N
CT
C
LA
HD
HE
HF
AA
AB
AC
VI
V+
V-
L
N
Note: the burden resistor value 10Ωis mounted inside
the controller. It is recommended that the current
transformer is fitted with a voltage limiting device such
as two back to back zener diodes between 3 and 10V
and rated for 50mA.
Current Transformer
CT
N
Heater
fuse
Relay
output
fuse
Controller fuse
Heater
T/C
Solid State
Relay
(e.g. TE10)
Snubber*
L
+
-
Cooling or
alarm relay
J
J
F
B
CT
C
LA
HD
HE
HF
AA
AB
AC
VI
V+
V-
1A
1B
2A
2B
L
N
24V
24V
Power Supply
24
24

3200 Series
Part No HA028651 Issue 7.0 Apr-09 15
3. Safety and EMC Information
This controller is intended for industrial temperature and
process control applications when it will meet the
requirements of the European Directives on Safety and
EMC. Use in other applications, or failure to observe the
installation instructions of this handbook may impair
safety or EMC. The installer must ensure the safety and
EMC of any particular installation.
Safety
This controller complies with the European Low Voltage
Directive 73/23/EEC, by the application of the safety
standard EN 61010.
Electromagnetic compatibility
This controller conforms with the essential protection
requirements of the EMC Directive 89/336/EEC, by the
application of a Technical Construction File. This
instrument satisfies the general requirements of the
industrial environment defined in EN 61326. For more
information on product compliance refer to the
Technical Construction File.
GENERAL
The information contained in this manual is subject to
change without notice. While every effort has been
made to ensure the accuracy of the information, your
supplier shall not be held liable for errors contained
herein.
Unpacking and storage
The packaging should contain an instrument mounted in
its sleeve, two mounting brackets for panel installation
and an Installation & Operating guide. Certain ranges are
supplied with an input adapter.
If on receipt, the packaging or the instrument are
damaged, do not install the product but contact your
supplier. If the instrument is to be stored before use,
protect from humidity and dust in an ambient
temperature range of -30oC to +75oC.
SERVICE AND REPAIR
This controller has no user serviceable parts. Contact
your supplier for repair.
Caution: Charged capacitors
Before removing an instrument from its sleeve,
disconnect the supply and wait at least two minutes to
allow capacitors to discharge. It may be convenient to
partially withdraw the instrument from the sleeve, then
pause before completing the removal. In any case, avoid
touching the exposed electronics of an instrument when
withdrawing it from the sleeve.
Failure to observe these precautions may cause damage
to components of the instrument or some discomfort to
the user.
Electrostatic discharge precautions
When the controller is removed from its sleeve, some of
the exposed electronic components are vulnerable to
damage by electrostatic discharge from someone
handling the controller. To avoid this, before handling
the unplugged controller discharge yourself to ground.
Cleaning
Do not use water or water based products to clean labels
or they will become illegible. Isopropyl alcohol may be
used to clean labels. A mild soap solution may be used
to clean other exterior surfaces of the product.
3.1 Installation Safety Requirements
Safety Symbols
Various symbols may be used on the controller. They
have the following meaning:
☺Helpful hints
Personnel
Installation must only be carried out by suitably qualified
personnel in accordance with the instructions in this
handbook.
Enclosure of Live Parts
To prevent hands or metal tools touching parts that may
be electrically live, the controller must be enclosed in an
enclosure.
Caution: Live sensors
The controller is designed to operate if the temperature
sensor is connected directly to an electrical heating
element. However you must ensure that service
personnel do not touch connections to these inputs
while they are live. With a live sensor, all cables,
connectors and switches for connecting the sensor must
be mains rated.
Wiring
It is important to connect the controller in accordance
with the wiring data given in this guide. Take particular
care not to connect AC supplies to the low voltage
sensor input or other low level inputs and outputs. Only
use copper conductors for connections (except
thermocouple inputs) and ensure that the wiring of
installations comply with all local wiring regulations. For
example in the UK use the latest version of the IEE wiring
regulations, (BS7671). In the USA use NEC Class 1 wiring
methods.
Power Isolation
The installation must include a power isolating switch or
circuit breaker. This device should be in close proximity to
the controller, within easy reach of the operator and marked
as the disconnecting device for the instrument.
Overcurrent protection
The power supply to the system should be fused
appropriately to protect the cabling to the units.
!Caution, (refer to
accompanying documents)
Equipment protected
throughout by DOUBLE
INSULATION

3200 Series
16 Part No HA028651 Issue 7.0 Apr-09
Voltage rating
The maximum continuous voltage applied between any
of the following terminals must not exceed 264Vac:
•relay output to logic, dc or sensor connections;
•any connection to ground.
The controller must not be wired to a three phase supply
with an unearthed star connection. Under fault
conditions such a supply could rise above 264Vac with
respect to ground and the product would not be safe.
Conductive pollution
Electrically conductive pollution must be excluded from
the cabinet in which the controller is mounted. For
example, carbon dust is a form of electrically conductive
pollution. To secure a suitable atmosphere in conditions
of conductive pollution, fit an air filter to the air intake
of the cabinet. Where condensation is likely, for
example at low temperatures, include a thermostatically
controlled heater in the cabinet.
This product has been designed to conform to BSEN61010
installation category II, pollution degree 2. These are
defined as follows:-
Installation Category II (CAT II)
The rated impulse voltage for equipment on nominal 230V
supply is 2500V.
Pollution Degree 2
Normally only non conductive pollution occurs.
Occasionally, however, a temporary conductivity caused by
condensation shall be expected.
Grounding of the temperature sensor shield
In some installations it is common practice to replace the
temperature sensor while the controller is still powered
up. Under these conditions, as additional protection
against electric shock, we recommend that the shield of
the temperature sensor is grounded. Do not rely on
grounding through the framework of the machine.
Over-temperature protection
When designing any control system it is essential to
consider what will happen if any part of the system
should fail. In temperature control applications the
primary danger is that the heating will remain constantly
on. Apart from spoiling the product, this could damage
any process machinery being controlled, or even cause a
fire.
Reasons why the heating might remain constantly on
include:
•the temperature sensor becoming detached from the
process
•thermocouple wiring becoming short circuit;
•the controller failing with its heating output
constantly on
•an external valve or contactor sticking in the heating
condition
•the controller setpoint set too high.
Where damage or injury is possible, we recommend
fitting a separate over-temperature protection unit, with
an independent temperature sensor, which will isolate
the heating circuit.
Please note that the alarm relays within the controller
will not give protection under all failure conditions.
Installation requirements for EMC
To ensure compliance with the European EMC directive
certain installation precautions are necessary as follows:
•For general guidance refer to Eurotherm Controls
EMC Installation Guide, HA025464.
•When using relay outputs it may be necessary to fit
a filter suitable for suppressing the emissions. The
filter requirements will depend on the type of load.
For typical applications we recommend Schaffner
FN321 or FN612.
•If the unit is used in table top equipment which is
plugged into a standard power socket, then it is likely
that compliance to the commercial and light
industrial emissions standard is required. In this case
to meet the conducted emissions requirement, a
suitable mains filter should be installed. We
recommend Schaffner types FN321 and FN612.
Routing of wires
To minimise the pick-up of electrical noise, the low
voltage DC connections and the sensor input wiring
should be routed away from high-current power cables.
Where it is impractical to do this, use shielded cables
with the shield grounded at both ends. In general keep
cable lengths to a minimum.

3200 Series
Part No HA028651 Issue 7.0 Apr-09 17
4. Switch On
The way in which the controller starts up depends on
factors described below in sections 4.1, 4.2 and 4.3.
4.1 New Controller
If the controller is new AND has not previously been
configured it will start up showing the ‘Quick
Configuration’ codes. This is a built in tool which enables
you to configure the input type and range, the output
functions and the display format.
!Incorrect configuration can result in damage
to the process and/or personal injury and must be
carried out by a competent person authorised to do
so. It is the responsibility of the person
commissioning the controller to ensure the
configuration is correct
4.1.1 Quick Start Code
The quick start code consists of two ‘SETS’
of five characters. The upper section of the
display shows the set selected, the lower
section shows the five digits which make up the set.
Adjust these as follows:-.
1. Press any button.The characters will change to ‘-‘,
the first one flashing.
2. Press Vor Wto change the flashing character to
the required code shown in the quick code tables –
see below. Note: An xindicates that the option is
not fitted.
3. Press °to scroll to the next character.
☺You cannot scroll to the next character until the
current character is configured.
☺To return to the first character press
4. When all five characters have been configured the
display will go to Set 2.
5. When the last digit has been entered press °
again, the display will show
Press Vor Wto .
The controller will then automatically go to the operator
level, section 4.3.
SET 1
Input type Range Input/Output 1 Output 2 Output 4
Thermocouple Full range X Unconfigured
B Type B C oC H PID Heating [logic, relay (1) or 4-20mA] or motor valve open [VC and VP only]
JType J F oF C PID Cooling [logic, relay (1) or 4-20mA] or motor valve close [VC and VP only]
KType K Centigrade J ON/OFF Heating [logic or relay (1)], or PID 0-20mA heating
LType L 0 0-100 K ON/OFF Cooling [logic or relay (1)], or PID 0-20mA cooling
Note (1) O/P4 is
relay only.
NType N 1 0-200 Alarm (2): energised in alarm Alarm (2): de-energised in alarm
R Type R 2 0-400 0 High alarm 5 High alarm
S Type S 3 0-600 1 Low alarm 6 Low alarm
T Type T 4 0-800 2 Deviation high 7 Deviation high
C Custom 5 0-1000 3 Deviation low 8 Deviation low
RTD 6 0-1200 4 Deviation band 9 Deviation band
Note (2)
OP1 = alarm 1
OP2 = alarm 2
OP3 = alarm 3
OP4 = alarm 4
P Pt100 7 0-1400
DC Retransmission (not O/P4)
Linear 8 0-1600 D 4-20mA Setpoint N 0-20mA Setpoint
M 0-80mV 9 0-1800 E 4-20mA Temperature Y 0-20mA Temperature
2 0-20mA Fahrenheit F 4-20mA output Z 0-20mA output
4 4-20mA G 32-212 Logic input functions (Input/Output 1 only)
H 32-392 W Alarm acknowledge V Recipe 2/1 select
J 32-752 M Manual select A Remote UP button
K 32-1112 R Timer/program run B Remote DOWN button
L 32-1472 L Keylock G Timer/Prog Run/Reset
M 32-1832 P Setpoint 2 select I Timer/Program Hold
N 32-2192 T Timer/program Reset Q Standby select
P 32-2552 U Remote SP enable
R 32-2912
T 32-3272
KCHC0

3200 Series
18 Part No HA028651 Issue 7.0 Apr-09
SET 2
Input CT Scaling Digital Input A Digital Input B (2) Output 3 (2) Lower Display
X Unconfigured X
Unconfigured X Unconfigured T Setpoint (std)
1 10 Amps W Alarm acknowledge H PID heating or motor valve open (3) P Output
2 25 Amps M Manual select C PID cooling or motor valve close (3) R Time remaining
5 50 Amps R Timer/Program Run J ON/OFF heating (not shown if VC or VP) E Elapsed time
6 100 Amps L Keylock K ON/OFF cooling (not shown if VC or VP) 1 Alarm setpoint
P Setpoint 2 select Alarm Outputs (1) A Load Amps
T Timer/Program reset Energised in alarm De-energised in alarm D Dwell/Ramp
U Remote SP enable
0 High alarm 5 High alarm Time/Target
V Recipe 2/1 select 1 Low alarm 6 Low alarm N None
A Remote UP button
2 Dev High 7 Dev High C Setpoint with
Note (1)
OP1 = alarm 1 (I/O1)
OP2 = alarm 2
OP3 = alarm 3
OP4 = alarm 4 (AA) B Remote DOWN button 3 Dev Low 8 Dev Low Output meter (2)
G Timer/Prog Run/Reset 4 Dev Band 9 Dev Band M Setpoint with
Note (2)
3208 & 3204 only I Timer/Program Hold DC outputs Ammeter (2)
Q Standby select H 4-20mA heating
Note (3)
VP, VC only C 4-20mA cooling
J 0-20mA heating
K 0-20mA cooling
Retransmission output
D 4-20 Setpoint
E 4-20 Measured Temperature
F 4-20mA output
N 0-20 Setpoint
Y 0-20 Measured Temperature
Z 0-20mA output
4.2 To Re-Enter Quick Code mode
If you need to re-enter the ‘Quick Configuration’ mode
this can always be done as follows:-
1. Power down the controller
2. Hold down the button, and power up the
controller again.
3. Keep the button pressed until code is displayed.
4. Enter the configuration code (this is defaulted to 4
in a new controller)
5. The quick start codes may then be set as described
previously
☺Parameters may also be configured using a deeper
level of access. This is described in later chapters of this
handbook.
☺If the controller is started with the button held
down, as described above, and the quick start codes are
shown with dots (e.g. J.C.X.X.X), this indicates that the
controller has been re-configured in a deeper level of
access and, therefore, the quick start codes may not be
valid. If the quick start codes are accepted by scrolling
to then the quick start codes are reinstated.
4.3 Pre-Configured Controller or
Subsequent Starts
A brief start up sequence consists of a self test during
which the software version number is shown followed
briefly by the quick start codes.
It will then proceed to Operator Level 1..
You will see the display shown below. It is called the
HOME display.
☺If the quick start codes do not appear during this
start up, it means that the controller has been configured
in a deeper level of access, see the note in section 4.2.
The quick start codes may then not be valid and are
therefore not shown.
1WRDT
Measured Temperature
(or Process Value ‘PV’)
Target Temperature
(Setpoint ‘SP’)
The ALM beacon
will show red if an
alarm is present.
The OP4 beacon
will be on if output
4 is active
This manual suits for next models
1
Table of contents
Other Eurotherm Temperature Controllers manuals

Eurotherm
Eurotherm 2208L User manual

Eurotherm
Eurotherm Invensys 3216 User manual

Eurotherm
Eurotherm 2216e Owner's manual

Eurotherm
Eurotherm 3116 User manual

Eurotherm
Eurotherm 2216e Owner's manual

Eurotherm
Eurotherm 216 User manual

Eurotherm
Eurotherm 3116 PID User manual

Eurotherm
Eurotherm 2408i User manual

Eurotherm
Eurotherm 2208e Owner's manual

Eurotherm
Eurotherm 2116 User manual