Eurotherm 2216L Wiring diagram

-1- HA026202 Issue 2 15/07/99
2216L and 2208L Temperature Controllers
Installing and Operating Instructions
The 2216L and 2208L are precision PID temperature controllers
ideal for plastic extrusion machines, ovens, chillers and other
heating and cooling processes. The 2216L is in a 48 x 48mm panel
size (1/16 DIN) and the 2208L in a 48 x 96 panel size (1/8 DIN).
Both controllers have up to three outputs for heating, cooling and
alarms. In addition the 2208L has two contact closure inputs to
select second setpoint and standby mode (all outputs off, except
alarms).
The controller will have been built and configured according to
the ordering code given on page 5. Check the ordering code on
the controller side labels to determine the configuration of your
particular controller.
This controller meets the European directives on safety
and EMC.
DIMENSIONS AND INSTALLATION
Model 2216L
Model 2208L
ELECTRICAL CONNECTIONS
To install the controller
Please read the safety information on pages 5 & 6 before
proceeding.
Prepare the panel cut-out to the size shown
Insert the controller through the cut-out.
Spring the panel retaining clips into place. Secure the
controller in position by holding it level and pushing both
retaining clips forward.
Unplugging the controller
The controller can be unplugged from its sleeve by easing the
latching ears outwards and pulling it forward out of the sleeve.
When plugging the controller back into its sleeve, ensure that
the latching ears click into place to maintain the IP65 sealing.
Wire Sizes
All electrical connections are made to the
screw terminals at the rear of the
controller. These accept wire sizes from
0.5 to 1.5 mm2 (16 to 22 AWG), and are
protected by a hinged cover to prevent
hands or metal making accidental contact
with live wires. Rear terminal screws
should be tightened to a torque of 0.4 Nm
(3.5 lb in).
.
Setpoint 2
Neutral
Ground
85-264Vac
Heating
Output
Cooling
Output
1B
2A
2B
1A
N
LA
LB
LC
L
AB
AC
VI
V+
V-
AA
Standby
Common
Line
Sensor
input
Alarm
Output
Logic
+
-
or
+
-Pt100
T/C
Logic
+
-
or
Model 2208L
10mm
(0.4in) 38mm
(1.5in)
(Not to
scale
)
Recommended minimum
spacing of controllers for
both sizes
Neutral
Ground
85-264Vac
Heating
Output
Cooling
Output
1B
2A
2B
3A
3B
1A
N
VI
V+
V-
LLine
Sensor
input
Alarm
Output
+
-Pt100
T/C
Logic
+
-
or
Logic
+
-
or
Model 2216L
Output ratings
Relay: 2A, 264Vac resistive
Logic: 18Vdc, 20mA (non-isolated)
Alarm output
The alarm output is non-latching and
de-energised in the alarm state
Grounding
The ground connection is not
required for safety purposes but must
be connected to satisfy EMC
requirements
Panel
cut-out
92 x 45mm
3.62 x 1.77in
96mm
(3.78in)
2208
OP1 OP2
SP2 REM
103mm (4.01in)
48mm (1.89in)
-0
+0.8 -0
+0.6
-0
+0.03 -0
+0.02
DD
DD
DD
DD
Panel retaining clips
RUN
HOLD
2216
MAN
OP1
OP2
SP2
REM
48mm (1.89in)
Panel cut-out
45 x 45mm
-0.0 +0.6
1.77 x 1.77in
-0.00 +0.02
103mm (4.01in)
48mm
(1.89in)
ENG

-2- HA026202 Issue 2 15/07/99
OPERATION
Switch on the controller. Following a 3 second self-test
sequence, you will see the display shown below. It is referred to
as the HOME display.
After 2 secs the lower readout will ‘blink’ indicating that the new
setpoint has been accepted.
OP1 will light when heating is ON
OP2 will light when cooling is ON
The display may flash an alarm message. The tables below list
all of the possible messages and their meaning.
ALARM MESSAGES
Process Alarms
Message Meaning
)
Alarm 1, Full Scale Low alarm: The temperature is
below the low alarm setting
#
Alarm 2, Full Scale High alarm: The temperature
exceeds the high alarm setting
:
Alarm 3, Deviation alarm: The difference between the
setpoint and the temperature exceeds the deviation
alarm setting
D5
Sensor Break:
Input sensor is open circuit or high
resistance. Check the sensor.
Diagnostic alarms
Message Meaning and Action
D5
Electrically Erasable Memory Error:
A parameter value has been corrupted.
Contact Eurotherm Controls.
#<D5
Hardware error:
Return for repair
))))
Low display range exceeded:
Check input signal
####
High display range exceeded:
Check input signal
55
Error 1: ROM self-test fail.
Return for repair
55
Error 2: RAM self-test fail.
Return for repair
55
Error 3: Watchdog fail
.
Return for repair
55
Error 4: Keyboard failure
. Stuck button, or a button
was pressed during power up.
55
Error 5: Input circuit failure.
Return for repair
0=5D
Power failure.
The line voltage is too low.
Check that the supply is within the rated limits
VIEWING THE DISPLAY UNITS
USE OF THE ‘SCROLL’ BUTTON
Pressing the scroll button will display the output power and the
two internal setpoints.
USE OF THE ‘PAGE’ BUTTON
The “PAGE” button accesses parameter LISTS
Parameters are settings in the controller which you can change to
suit the process. Examples are: ‘Alarms’ and ‘Autotune’. They
are found under headings called LISTS and the full set is shown
on the next page.
Keep pressing to
select more list headings
continue around a continuous loop
3rd press
2nd press
Actual Temperature
Output 1 Output 2
Required Temperature
(Setpoint)
OP1 OP2
*
+
Press and hold to
increase temperature
Press and hold to
decrease temperature
0
0
Setpoint 1
Press or to change value
0
D
2nd Press
Output
Actual output power %
3rd Press
4th Press
Upper
readout is
parameter
name.
Lower is
value.
Keep pressing to return to the HOME display
Setpoint 2
Press or to change value
)
)O6 69.
)O6
NOTE
If you get lost, pressing and together will
return you to the HOME display.
If, at any time, no key is pressed within 45 seconds, the display
will always return to the HOME display.
Display Units
/
/
Degrees Centigrade
/
/
Degrees Fahrenheit
Momentarily pressing either
button will flash the display for
0.5 secs
*
*
0.5s
°

-3- HA026202 Issue 2 15/07/99
PARAMETER LISTS
Home List Adjustable Range Default setting Customer setting
Home Measured temperature and Setpoint
0
Output power demand -100.0 to 100.0%
0
Setpoint 1 value As per ordering code
0
Setpoint 2 value As per ordering code
)
)
Alarm List Adjustable Range Default setting Customer setting
)
Full Scale Low alarm setting
to
°
or °
Setpoint minimum
#
Full Scale High alarm setting
to
°
or °
Setpoint maximum
:
Deviation Band alarm setting
to
°
or °
Setpoint maximum
69.
69.
Autotune List (see Tuning) Adjustable Range Default setting Customer setting
69.
Self tune enable
or
/.
0O
0O
PID List (see Tuning) Adjustable Range Default setting Customer setting
0
Proportional band
to
°
or °
6O
Integral time
to
secs
6
Derivative time
to
secs
5
Manual reset (appears when
6O
set to
)
B
to
D D
)
Cutback low
96/
to
°
or °
96/
#
Cutback high
96/
to
°
or °
96/
5)D
Relative cool gain
D
to
D D
/0
/0
Output list Adjustable Range Default setting Customer setting
0D)/
Cooling power limit (Output low limit)
B
to
D
%
B
0D#O
Heating power limit (Output high limit)
D
to
D
%
D
@D#
Heating output cycle time
D
to
D
secs
for logic output
D
for relay
@D
Cooling output cycle time
D
to
D
secs
for logic output
D
for relay
/.6D#
Heating output minimum on time
96/
to
D
secs
96/
(=50mS)
/.6D
Cooling output minimum on time
96/
to
D
secs
96/
(=50mS)
.
.
On/off list (Used for On/Off control) Adjustable Range Default setting Customer setting
$@D#
Heating output hysteresis
to
°
or °
$@D
Cooling output hysteresis
to
°
or °
#D
Heat/Cool dead band
to
°
or °
Access list Used for re-configuring the controller. (Separate instructions required)
Selecting and adjusting a
parameter
1. Press to step through the
list headings
2. Press to step through the
parameters within a particular list
3. The upper display shows the
parameter name and the lower
display its value
4. Press to decrease the
value of a selected parameter
5. Press to increase the value
of a selected parameter.
Notes:
(1) Either the PID list or
the On/Off list will be
present depending
upon the type of control
in use.
(2) The ordering code
specifies which of the
three internal alarms
are attached to the
alarm rela
y
output.
D
D
Home
Display
69.
)O6 0O
)O6
PID(1)
List
)
)O6
Alarm
List(2) Autotune
List
0D )
#
69.
0
6O
6
4
D
)
96/
#
96/
0
0
5)D
D
/0
)O6
Output
List
.
)O6
On Off
List(1)
0D)/
B
0D#O
D
$@D#
$@D
#D
@D#
D
@D
D
/.6D#
96/
/.6D
96/
)O6
Access
List Return to
HOME
Display
:

-4- HA026202 Issue 2 15/07/99
AUTOMATIC TUNING
In PID control, the output from the controller is the sum of three
terms: Proportional, Integral and Derivative. These three terms
deliver just the right amount of power to hold the temperature at
setpoint without oscillation. For stable control, the PID values
must be ‘tuned’ to the characteristics of the process being
controlled. In the 2216L and 2208L this is done automatically
using advanced tuning techniques.
Automatic tuning is performed by switching the output of the
controller On and Off to induce an oscillation in the measured
temperature. From the amplitude and period of the oscillation,
the PID values, shown in the table below, are calculated.
Parameter Display Meaning or Function
Proportional
band
0
The bandwidth in °
or °
over which the output
power is proportioned between minimum and
maximum.
Integral time
6O
Determines the time taken by the controller to
remove steady-state error signals.
Derivative
time
6
Determines how strongly the controller will react
to the rate-of-change of temperature.
Low cutback
)
The number of °
or °
below setpoint at which
the controller will cutback the output power to
prevent overshoot on heat up.
High
Cutback
#
The number of °
or °
above setpoint at which
the controller will increase the output power to
prevent undershoot on cool down.
Relative
cool gain
5)D
Only present if cooling has been configured.
Sets the cooling proportional band by dividing the
Pb value by the
5)D
value.
If the process cannot tolerate 100% heating or cooling during
tuning, the power can be restricted by the heating and cooling
limits in the Output list. However, the measured value must
oscillate to some degree for the tuner to determine values.
Tuning is normally performed only once during the initial
commissioning of the process. However, if the process under
control subsequently becomes unstable (because its
characteristics have changed), you can re-tune again at any time.
It is best to start tuning the process from ambient temperature, to
allow the tuner to calculate more accurately the cutback settings.
Heating and Cooling Output Cycle Times
Before commencing a tuning cycle, set the values of
@D#
(heating output cycle time) and
@D
(cooling output cycle
time) in the
/0
(output) list.
For a logic heating output (switching a solid state relay), set
@D#
to
D
sec.
For a relay output, set
@D#
to
D
sec.
For a logic cooling output used to control a solenoid valve, set
@D
to
D
sec.
Tuning procedure
1. Set the setpoint to the value at which you will normally
operate the process.
2. In the ‘
69.
’ list, select ‘
69.
’ and set it to ‘
/.
’
3. Press the Page and Scroll buttons together to return to the
HOME display. The display will flash ‘
69.
’ to indicate
that tuning is in progress.
4. The controller will induce an oscillation in the temperature by
turning the heating on and then off.
5. After two cycles of oscillation the tuning will be completed
and the tuner will switch itself off.
6. The controller will then calculate the tuning parameters and
resume normal control action.
If you want ‘Proportional only’ or ‘P+D’ or ‘P+I’ control, you
should set the ‘
6O
’ or ‘
6
’ parameters to
before
commencing the tuning cycle. The tuner will leave them off and
will not calculate a value for them.
Typical automatic tuning cycle
Calculation of the cutback values
When low cutback or high cutback is set to ‘
97/
’ their values
will be fixed at three times the proportional band, and will not be
altered during automatic tuning. If set to any other value, they
will be calculated as part of the tuning process.
MANUAL TUNING
If for any reason automatic tuning gives unsatisfactory results,
you can manually tune the controller, as follows:
With the process at its normal running temperature:
1. Set Integral Time ‘
6O
’and Derivative Time ‘
6
’ to
.
2. Set High Cutback and Low Cutback, ‘
#
’ and ‘
)
’, to
‘
96/
’
3. Ignore the fact that the temperature may not settle precisely at
the setpoint
4. Reduce the proportional band ‘
0
’ until the temperature just
starts to oscillate. If the temperature is already oscillating,
increase the proportional band until it just stops oscillating.
Allow enough time between each adjustment for the
temperature to stabilise. Make a note of the proportional band
value ‘B’ and the period of oscillation ‘T’.
5. Set the PID parameter values according to the formula below:
Type of control Proportional
band ‘
0
0
’Integral time
‘
6O
6O
’Derivative time
‘
6
6
’
Proportional only 2xB OFF OFF
P + I 2.2xB 0.8xT OFF
P + I + D 1.7xB 0.5xT 0.12xT
Setting the cutback values
The above procedure sets up the parameters for optimum steady
state control. If unacceptable levels of overshoot or undershoot
occur during start-up or for large step changes in temperature,
then manually set the cutback parameters
)
and
#
.
Proceed as follows:
1. Set the low and high cutback settings to 3 x the proportional
band (that is to say,
)
=
#
= 3 x
0
).
2. Note the level of overshoot or undershoot that occurs for
large temperature changes (see the diagrams below).
In example (a) increase
)
by the overshoot value. In example
(b) reduce
)
by the undershoot value.
Example (a) Example (b)
When the temperature approaches the setpoint from above, you
can set
#
in a similar manner.
Manual reset
When the integral term is set to
the parameter manual reset
(
5
) appears in the
0O )O6D
This parameter sets the
output power when the error signal is zero. This value can be
manually adjusted to remove the steady state error - the function
normally performed by the Integral term.
Time
Temperature
Temperature
Time
Undershoot
Overshoot
Time
Temperature

-5- HA026202 Issue 2 15/07/99
RE-CONFIGURATION INSTRUCTIONS
The 2216L and 2208L are normally supplied pre-configured to a customer’s requirement using the simple ordering code. The type of
heating, cooling and alarm outputs are defined in the ordering code and cannot be changed by the customer because they are part of the fixed
hardware build. You can, however, change the following software features:
1. The setpoint limits.
2. The temperature display units: °C or °F
3. The type of control: On/Off or PID
4. The type of input sensor
5. The alarm output configuration
6. To configure outputs 1 & 2 to heating and cooling
These instructions tell you how to make these changes.
TO CHANGE THE SETPOINT LIMITS
Separate high and low setpoint limits are available for setpoint 1 and setpoint 2. These restrict the range over which the operator can adjust
the temperature thereby preventing damage to the product or the plant. To change the limits, first select ‘FULL’ access level as follows:
Press
Press
Press
Access List Header
Press until you reach the
list header.
Password Entry
Enter the password ‘
’ by pressing the or buttons.
When the correct password has been entered the lower readout will change to
1
indicating that access is now
unlocked.
Go To
9))
9))
Level
Select ‘
9))
’ access level by pressing the or buttons.
Ignore the other possibilities:
05
; Operator level
O
t: Edit level
/.
: Configuration level.
Access List Header
Press to return to the
list header.
You are now in Full Access level.

-6- HA026202 Issue 2 15/07/99
TO CHANGE THE SETPOINT LIMITS … continued from the previous page.
Having selected
8))
level, the
8))
set of parameter lists shown below will be visible. Press to step across the list headers. You
will eventually return to the HOME display. The high and low setpoint limits are in the
0 )O6
. To access them, press until you
reach the
0
)O6
heading. Then press to step down the parameters within the list. Select the required parameter and adjust pressing
the and buttons.
RETURN TO OPERATOR LEVEL
Having adjusted the setpoint limits, return to Operator level as follows.
)
0
0
0
0D)
0D#
0D)
0D#
055
Setpoint select 1 or 2.
Shows currently selected setpoint number
Shows setpoint 1 value
Shows setpoint 2 value
Setpoint 1 low limit. Press and to adjust
Setpoint 1 high limit. Press and to adjust
Setpoint 2 low limit. Press and to adjust
Setpoint 2 high limit. Press and to adjust
Setpoint rate limit. Leave as
D
D
Home
Display
69.
)O6 0O
)O6
PID
List
)
)O6
Alarm
List Autotune
List
0
)O6
Setpoint
List
O0
)O6
Input
List
)O6
Access
List
/0
)O6
Output
List
.
)O6
On Off
List
,
)O6
Comms
List
Goto Operator Level
Press the and to select
05
level.
Access list header
Press as many times as necessary
until you reach the
list header.
Password entry
0
will be displayed. If not, press the
and to enter the password ‘
’.
Press
Press
Access list header
You are now in back in Operator level and can
resume normal operation.
Press to return to the
list header
/
0
)O6
!/6/
05
)O6

-7- HA026202 Issue 2 15/07/99
TO CHANGE:
• THE TEMPERATURE DISPLAY UNITS: °C OR °F
• THE TYPE OF CONTROL: ON/OFF OR PID
• THE INPUT SENSOR TYPE
• OUTPUTS 1 AND 2 TO HEATING OR COOLING
• THE ALARM OUTPUT CONFIGURATION,
First select configuration level, as follows:
Access list header
Press until you reach the
list header.
Password entry
Enter the password ‘
’ by pressing the and buttons.
Once the correct password has been entered the lower readout will change to ‘
0
indicating that access is now unlocked.
Enter Configuration Password entry
Enter the configuration password
by pressing the and buttons. Once the
correct password has been entered, lower readout will change to ‘
0
’.
Configuration level reached
You are now in configuration level.
Goto configuration Level
Select
/.
level by pressing the and buttons
Ignore the other possibilities:
05M
Operator level
O6M
Edit level
9))
: Full access level.
Press
Press
Press
Press
)O6
/
!/6/
/.
/.
O.6
/.

-8- HA026202 Issue 2 15/07/99
CONFIGURATION LEVEL:
Having selected configuration level as shown on the previous page, Pressing the button will step across the configuration parameter list
headings as shown below. The lower readout will show
/.
to indicate that it is a list heading.
TO CHANGE THE TEMPERATURE DISPLAY
UNITS
TO CHANGE THE TYPE OF CONTROL
TO CHANGE THE INPUT SENSOR TYPE
Selecting a new sensor type changes the setpoint limits.
Therefore, after changing the sensor type, reset the setpoint limits
as described earlier in these instructions.
O.6
/.
Instrument
confi
g
uration
)
/. )
/.
Alarm
confi
g
uration
O0
/.
Input
confi
g
uration Calibration
confi
g
uration
)
/. )
/.
/. #
/.
Dig i/p LA
confi
g
uration Dig i/p LB
confi
g
uration
O.6
/.
65)
0O
Press until you reach the
O.6
list header.
Press until the
65)
parameter is displayed
Press to return to the list header
Type of control
Press or to select either:
0OM
PID control
.D M
On/Off control
Alarm o/p AA
confi
g
uration Module HA
confi
g
uration
/.
/.
?O6
./ 0
/.
/.
Module 1A
confi
g
uration
Module 2A
confi
g
uration
Module 3A
confi
g
uration
Password
confi
g
uration
Exit
confi
g
uration
O.6
/.
9.O6
/
Press until you reach the
O.6
list header.
Press
Temperature display units
Press or to select either:
/
M
Celsius
/
M
Fahrenheit
Press to return to the list header
O0
/.
O.16
%6
Press until you reach the
O1
list header.
Press
Press to return to the list header
Input type
Press or to select either:
%D6M
J type thermocouple input
(D6
: K type thermocouple input
)D6M
L type thermocouple input
.D6
: N type thermocouple input
6D6M
T type thermocouple input
56
: 100
*
platinum resistance thermometer

-9- HA026202 Issue 2 15/07/99
TO CHANGE OUTPUTS 1 & 2 TO HEATING OR
COOLING
The controller is supplied with output 1 configured as a heating
output, and output 2 configured as a cooling output. It is possible
to re-configure either output for heating or cooling.
It is also possible to configure both outputs for heating (or
cooling) The advantage of this is that one output can be fitted
with a relay and the other with a logic, which gives the user the
choice of using either a logic output or a relay output for the
same function.
Proceed as follows:
TO RECONFIGURE THE ALARM OUTPUT
The alarm output is operated by up to four internal ‘soft’ alarms
i.e. indication only. These alarms can be individually configured
in the
) /.
list.
Note: If an alarm is disabled it will not appear in the alarm list in
Operator level.
To re-configure the alarm output proceed as follows:
TO RETURN TO OPERATOR LEVEL
?O6
@
Press until you reach the
?O6
list header.
Press or to select
@
:
After a two second delay the controller will return to
operator level and normal operation can be resumed.
)
/.
Press until you reach the
)
list header.
Press
Alarm 1 type
Press or to select either:
M
Alarm disabled
)M
Full Scale Low alarm
#M
Full Scale High alarm
:M
Deviation band alarm
#OM
Deviation High alarm
)/M
Deviation Low alarm
Press
)6$
./
)/
./
Press
Alarm blocking
Press or to select either:
./M
Alarm will be non blocking
@M
Alarm will be blocking. This means that,
after power up, the alarm must first enter a good state
before it becomes active.
)
Alarm latching
Press or to select either:
./M
Non latching alarm
@M
Latching alarm
Repeat the above three steps to configure alarms 2, 3 and 4.
Finally press to return to the list header
/.
Press until you reach the
list header.
9.
#7
Input type
Press or to select
#6D
The choices are:
./.M
The output is inactive
O"
: The output is an alarm
#6
: The output is heating
)
: The output is cooling
Press
/.
Press until you reach the
list header.
9.
#7
Press to return to the list header
Input type
Press or to select
#6D
The choices are:
./.M
The output is inactive
O"
: The output is an alarm
#6
: The output is heating
)
: The output is cooling
Press

-10- HA026202 Issue 2 15/07/99
ORDERING CODE
The controller is built and configured according to the ordering code shown below.
Model
number Control Supply
voltage Heating
Output Cooling
Output Alarm
Output Manual Sensor
input Setpoint
min Setpoint
max Units
2216L
2208L
TECHNICAL SPECIFICATION
Environmental ratings-
Panel sealing: IP65, (EN 60529), or 4X, (NEMA 250).
Operating ambients: 0 to 55oC. Ensure that the enclosure is adequately ventilated. 5 to 95%RH, non condensing
Atmosphere: Not suitable for use above 2000m or in explosive or corrosive atmospheres.
Equipment ratings
Power supply 100 to 240Vac -15%, +10% / 48 to 62Hz, 10Watts maximum consumption
Relay (isolated) Maximum: 264Vac, 2A resistive. Minimum: 12Vdc, 100mA.
Over current protection: Use a minimum of 0.5mm2or 16awg wire for plant connections. External over current protection is required.
Use independent fuses for the controller supply and each relay output. Suitable fuses are EN60127 (type T)
rated at 2A
Logic outputs and inputs Logic outputs: 18V at 20mA, non-isolated. Logic contact closure inputs: Non-isolated from the sensor input.
Electrical safety Meets EN 61010, Installation category II, pollution degree 2.
Voltage transients on any mains power connected to the controller must not exceed 2.5kV.
Isolation: All isolated inputs and outputs have reinforced insulation to protect against electric shock. (See live sensor note)
Cooling Output
X Not fitted
Relay output
A Linear cooling
B Fan cooling
C Water cooling
Logic output
D Linear cooling
E Fan cooling
F Water cooling
Alarm output
X Not fitted
1High & Low
alarms
2 Dev. band
Manual
XXX None
ENG English
FRA French
GER German
NED Dutch
SPA Spanish
SWE Swedish
DEN Danish
ITA Italian
Control
N On/Off control
C PID control
Sensor input Setpoint min & max limits
Thermocouples °C°F
J Type J -210 to 1200 -340 to 2192
K Type K -200 to 1372 -325 to 2500
T Type T -200 to 400 -325 to 750
L Type L -200 to 900 -325 to 1650
N Type N -200 to 1300 -325 to 2370
Z Pt100 -200 to 850 -325 to 1562
Units
C°C
F°F
Heating Output
X Not fitted
1 Logic
2 Relay
Supply voltage
H 85-264Vac

-11- HA026202 Issue 2 15/07/99
SAFETY AND EMC INFORMATION
Safety
This controller complies with the European Low Voltage
Directive 73/23/EEC, amended by 93/68/EEC, by the application
of the safety standard EN 61010.
Electromagnetic compatibility
This controller conforms with the essential protection
requirements of the EMC Directive 89/336/EEC, amended by
93/68/EEC, by the application of a Technical Construction File.
This controller satisfies the general requirements of the industrial
environment defined in EN 50081-2 and EN 50082-2.
GENERAL
The information contained in these instructions is subject to
change without notice. While every effort has been made to
ensure the accuracy of the information, Eurotherm Controls shall
not be held liable for errors contained herein.
Unpacking and storage
The packaging should contain the controller with two panel
retaining clips and this instruction leaflet.
If on receipt, the packaging or the controller are damaged, do not
install it but contact your nearest Eurotherm Controls agent.
If the controller is to be stored before use, protect from humidity
and dust in an ambient temperature range of -30oC to +75oC.
SERVICE AND REPAIR
This controller has no user serviceable parts. Contact your
nearest Eurotherm Controls agent for repair.
C
aution:
Charged capacitors
Before removing a controller from its sleeve, switch off the
supply and wait two minutes to allow capacitors to discharge.
Failure to observe this precaution may damage the controller or
cause some discomfort to the user.
Electrostatic discharge precautions
When the controller is removed from its sleeve, it is vulnerable to
damage by electrostatic discharge from someone handling the
controller. To avoid this, before handling the unplugged
controller discharge yourself to ground.
Cleaning
Do not use water or water based products to clean labels or they
will become illegible. Isopropyl alcohol may be used to clean
labels. A mild soap solution may be used to clean other exterior
surfaces of the product.
Safety Symbols
The following safety symbols are used on the controller:
Caution, (refer to the
accompanying documents) Functional earth
(ground) terminal
!
Personnel
Installation must only be carried out by qualified personnel
Enclosure of live parts
To prevent hands or metal tools touching parts that may be
electrically live, the controller must be installed in an enclosure.
Caution:
Live sensors
The logic outputs and the two contact closure inputs are
electrically connected to the sensor input (e.g. thermocouple). In
some installations the temperature sensor may become live. The
controller is designed to operate under these conditions, but you
must ensure that this will not damage other equipment connected
to these inputs and outputs, and that service personnel do not
touch these connections while they are live. With a live sensor,
all cables, connectors and switches for connecting the sensor and
non-isolated inputs and outputs must be mains rated.
Wiring
Wire the controller in accordance with the wiring data given in
these instructions. Take particular care not to connect AC
supplies to the low voltage sensor input or logic outputs. Only
use copper conductors for connections, (except thermocouple).
Ensure that the installation complies with local wiring
regulations.
Power Isolation
The installation must include a power isolating switch or circuit
breaker that disconnects all current carrying conductors. The
device should be mounted in close proximity to the controller,
within easy reach of the operator and marked as the disconnecting
device for the controller.
Earth leakage current
Due to RFI Filtering, there is an earth leakage current of less than
0.5mA. This may affect the design of an installation of multiple
controllers protected by Residual Current Device (RCD), or
Ground Fault Detector (GFD), type circuit breakers.
Voltage rating
The maximum continuous voltage applied between any
connection and ground must not exceed 264Vac.
For the above reason the controller should not be wired to a three
phase supply with an unearthed star connection. Under fault
conditions such a supply could rise above 264Vac with respect to
ground and the product would not be safe.
Conductive pollution
Electrically conductive pollution must be excluded from the
cabinet in which the controller is mounted. For example, carbon
dust is a form of electrically conductive pollution. Where
condensation is likely, for example at low temperatures, include a
thermostatically controlled heater in the cabinet.
Grounding of the temperature sensor shield
In some installations it is common practice to replace the
temperature sensor while the controller is still powered up. Under
these conditions, as additional protection against electric shock,
we recommend that the shield of the temperature sensor is
grounded. Do not rely on grounding through the framework of
the machine.
Over-temperature protection
When designing any control system it is essential to consider
what will happen if any part of the system should fail. In
temperature control applications the primary danger is that the
heating will remain constantly on. This could damage the
product, the machinery being controlled, or even cause a fire.
Reasons why the heating might remain constantly on include:
• the temperature sensor becoming detached from the process
• thermocouple wiring becoming short circuit;
• the controller failing with its heating output constantly on
• an external valve or contactor sticking in the heating state
Where damage or injury is possible, we recommend fitting a
separate over-temperature protection unit, with an independent
temperature sensor, which will isolate the heating circuit.
Please note that the alarm relays within the controller will not
give protection under all failure conditions.

-12- HA026202 Issue 2 15/07/99
Installation Requirements for EMC
• For general guidance refer to Eurotherm Controls EMC
Installation Guide, HA025464.
• When using relay outputs it may be necessary to fit a filter
suitable for suppressing the conducted emissions. The filter
requirements will depend on the type of load. For typical
applications we recommend Schaffner FN321 or FN612.
Routing of wires
To minimise the pick-up of electrical noise, the sensor input
wiring should be routed away from high-current power cables.
Where it is impractical to do this, use shielded cables with the
shield grounded at both ends.
INTERNATIONAL SALES AND SERVICE
EUROTHERM CONTROLS
LTD
Faraday Close, Durrington,
Worthing, West Sussex BN13
3PL
Telephone Sales:
(01903) 695888
Technical: (01903)
695777
Service: (01903)
695444
Fax (01903) 695666
For countries not listed contact:
Eurotherm Controls Limited,
Export Dept,. Faraday Close,
Durrington,
Worthing, West Sussex, BN13
3PL
Telephone (01903) 268500
Fax (01903) 265982
AUSTRALIA
Eurotherm Pty. Ltd.
Telephone Sydney (+61 2) 9477
7022
Fax (+61 2) 9477 7756
AUSTRIA
Eurotherm GmbH
Telephone Vienna (+43 1) 798
7601
Fax (+43 1) 798 7605
Telex 047 1132000 EIAUT A
BELGIUM
Eurotherm B.V.
Telephone Antwerp (+32 3) 322
3870
Fax (+32 3) 321 7363
DENMARK
Eurotherm A/S
Telephone Copenhagen (+45
31) 871622
Fax (+45 31) 872124
FRANCE
Eurotherm Automation SA
Telephone Lyon (+33 478)
664500
Fax (+33 478) 352490
GERMANY
Eurotherm Regler GmbH
Telephone Limburg (+49 6431)
2980
Fax (+49 6431) 298119
Also regional offices
HONG KONG
Eurotherm Limited
Telephone Hong Kong (+852)
2873 3826
Fax (+852) 2870 0148
Telex 0802 69257 EIFEL HX
INDIA
Eurotherm India Limited
Telephone Chennai (+9144)
4961129
Fax (+9144) 4961831
IRELAND
Eurotherm Ireland Limited
Telephone Naas (+353 45)
879937
Fax (+353 45) 875123
ITALY
Eurotherm SpA
Telephone Como (+39 31)
975111
Fax (+39 31) 977512
Telex 380893 EUROTH I
JAPAN
Eurotherm Japan Limited
Telephone Tokyo (+81 3)
33702951
Fax (+81 3) 33702960
KOREA
Eurotherm Korea Limited
Telephone Seoul (+82 2)
5438507
Fax (+82 2) 545 9758
Telex EIKOR K23105
NETHERLANDS
Eurotherm B.V.
Telephone Alphen a/d Ryn (+31
172) 411752
Fax (+31 172) 417260
NEW ZEALAND
Eurotherm Limited
Telephone Auckland (+64 9)
2635900
Fax: (+64 9) 2635901
NORWAY
Eurotherm A/S
Telephone Oslo (+47 66)
803330
Fax (+47 66) 803331
SPAIN
Eurotherm España SA
Telephone (+34 1) 6616001
Fax (+34 1) 6619093
SWEDEN
Eurotherm AB
Telephone Malmo (+46 40)
384500
Fax (+46 40) 384545
SWITZERLAND
Eurotherm Produkte (Schweiz)
AG
Telephone Zurich (+41 55)
4154400
Fax (+41 55) 4154415
UNITED KINGDOM
Eurotherm Controls Limited
Telephone Worthing (+44 1903)
269888
Fax (+44 1903) 269666
U.S.A
Eurotherm Controls Inc.
Telephone Reston (+1 703) 787
3405
Fax (+1 703) 787 3436
ENG
This manual suits for next models
1
Table of contents
Other Eurotherm Temperature Controllers manuals

Eurotherm
Eurotherm 3116 User manual

Eurotherm
Eurotherm 2116 User manual

Eurotherm
Eurotherm Invensys 3216 User manual

Eurotherm
Eurotherm 2108i Wiring diagram

Eurotherm
Eurotherm Invensys 3216 User manual

Eurotherm
Eurotherm 3116 User manual

Eurotherm
Eurotherm 3116 PID User manual

Eurotherm
Eurotherm 2216e Owner's manual

Eurotherm
Eurotherm 3100 Installation and operation manual

Eurotherm
Eurotherm 2216e Owner's manual