Exhausto EFC 25 Manual

EXHAUSTO A/S
Odensevej 76 · DK-5550 Langeskov
Tlf. +45 65 66 12 34 · Fax +45 65 66 11 10
exhausto@exhausto.dk · www.exhausto.com
EXHAUSTO 3001736-2004-01-21.fm Installation & operating instructions
EFC 25
GB

EXHAUSTO 3001736-2004-01-21.fm 2/12
1. Product information
1.1 EFC 25 Control System for EXHAUSTO Chimney Fans................................... 3
1.2 Description........................................................................................................... 4
2. Installation
2.1 Installation of control panel and external IR-sensor........................................ 5
2.2 Power supply ....................................................................................................... 5
2.3 Standard installation ........................................................................................... 6
2.4 Installation with external start............................................................................ 7
3. Commissioning
3.1 Service mode ....................................................................................................... 8
3.2 Setting of potentiometer ..................................................................................... 9
3.3 Adjustment of pressure differential switch (PDS) ............................................ 9
3.4 Test of commissioning........................................................................................ 9
3.5 Complete the commissioning card .................................................................... 9
4. Daily use
5. Fault finding
6. Technical data
Symbol legend The following terms are used throughout this manual to bring attention to the presence
of potential hazards or important information concerning the product:
DANGER: Indicates an imminently hazardous situation which, if not avoi-
ded, will result in death, serious injury or substantial property damage.
CAUTION: Indicates an imminently hazardous situation which, if not avoi-
ded, may result in personal injury or property damage.
How to use this
manual
The manual concerns EXHAUSTO fireplace control EFC 25 and a remote control.
Safety for personnel and property as well as correct operation of the chimney fan are
obtained by following the directions of this manual.
EXHAUSTO disclaims all responsibility for damages caused by misapplication of this
product in contravention of directions and instructions in this manual.

EXHAUSTO 3001736-2004-01-21.fm 3/12
1. Product information
Applications The EXHAUSTO fireplace control EFC 25 (Fig. 1) has been developed for use with gas
fire control units which have flame detection and automatic ignition, and in connection
with the installation of EXHAUSTO chimney fans.
The control system supervises the fail-safe function. In case of insufficient chimney
draught, the EFC 25 will shut down the fireplace.
The control system is developed to meet BS 5440: Part 1(2000), BS 6644(1991), Gas
Appliance Directive 90/396/EEC, EN 298(1993) and other relevant European standards.
Functions By activating the EFC 25, the chimney fan will immediately start up on full speed. When
the fail-safe supervision confirms sufficient chimney draught, the fireplace will be lit and
the fan speed will adjust to the pre-set value corresponding to the appliance operating
normally, (Fig. 1-J).
The control has a step-up function and a 15-second built-in delay function to avoid
nuisance cut-outs.
By using the remote control (Fig. 2) it is possible to switch between high and low fire.
When EFC 25 is turned off, the chimney fan stops. It is possible to pre-set a run-on time
period of 3 minutes, (Fig. 1-I).
The EFC 25 and RSVG can also be used for venting purposes.
Fail-safe settings. The fail-safe settings can be set by dipswitches (Fig. 1-I) according to local laws and
standards.
• RESET after fail-safe lock-out (manual/automatic).
1.1 EFC 25 Control System for EXHAUSTO Chimney Fans

EXHAUSTO 3001736-2004-01-21.fm 4/12
EFC 25 control
Remote control
1.2 Description
Pos. Description Pos. Description
A Alarm LED J Potentiometer for adjusting the fan
speed
B Operating LED K Socket for external IR-receiver
C ON/OFF button L Product ID
D Fuses T3,15A 230V(spare fuse
included in control box)
M Terminals for Step 2
E PDS pressure differential switch
terminals
N Terminals for start signal to fireplace
control
F Terminals for chimney fan O Terminals for fresh air inlet
G Connection cable P Terminals for external start
H Service mode button Q Terminals for power supply
I Dipswitches R Internal IR-receiver
Fig. 1
Fig. 2
Pos. Description
A Fan speed up.
B ON/OFF button
CStepI/II button
D Fan speed down or Burner start
D
AB
C

EXHAUSTO 3001736-2004-01-21.fm Installation 5/12
2. Installation
All installations must be carried out by competent personnel in
accordance with local laws and regulations.
Isolation switch • An isolation switch must be installed between the controller and
the chimney fan.
• For installation of the isolation switch please consult the
installation instructions for the chimney fan.
• The isolation switch is not supplied by EXHAUSTO.
The control panel is to be installed on a level surface with a minimum distance of 100
mm to any corner.
The front cover is removed from the frame by twisting a screw driver in the two holes on
the sides of the front cover. The front cover can then be tipped carefully and the frame
can be mounted on the wall.
Notice The front cover is mounted with a connection ribbon cable in the right side, which results
in a restricted opening of this side.
The assembling part of the IR-sensor, the black cable, may not be bend.
The control box covers a standard single back box.(Not EXHAUSTO supply)
.
• Installation of the power supply wire must be carried out in
accordance with local laws and regulations.
• The earth wires must always be connected.
• Before the appliance a fused switch must be present that
completely disables power to the appliance. The switch must
always be switched off when the appliance is not in use.
2.1 Installation of control panel and external IR-sensor
Fig. 3
Fig. 4
110
65
Fig. 5
2.2 Power supply

EXHAUSTO 3001736-2004-01-21.fm Installation 6/12
Description The example shows how to connect the EFC25 directly to the fireplace control. This
installation demands a fire with a control unit which has flame detection and automatic
ignition. In case of insufficient flue gas flow (controlled by the PDS in the fan) the
fireplace control will be disconnected, by means of a voltage free contact.
• Connect the earth wires between power supply and chimney fan
• Connect the chimney fan and pressure switch to terminals 1-5
• Connect the start/release signal for the burner control to terminals 12-13 (voltage
free contact)
• Connect Step 2 signal (if any) to terminals 14-15 (voltage free contact)
• Connect the power supply to the terminals marked ”Power”.
Diagram
Application
2.3 Standard installation
Fig. 6
Chimney fan w/PDS
Isolation switch
EFC 25
Gas
Power supply
Fig. 7
Fireplace control
Fused switch

EXHAUSTO 3001736-2004-01-21.fm Installation 7/12
Description The example shows how to connect the EFC25 directly to the fireplace control. This
installation demands a fire with a control unit which has flame detection and automatic
ignition. In case of insufficient flue gas flow (controlled by the PDS in the fan) the
fireplace control will be disconnected, by means of a voltage free contact.
•Connect the earth wires between power supply and chimney fan
• Connect the chimney fan and pressure switch to terminals 1-5
• Connect the external ON/OFF switch to terminals 8-9
• Connect the start/release signal for the burner control to terminals 12-13 (voltage
free contact)
• Connect Step 2 signal (if any) to terminals 14-15 (voltage free contact)
• Connect the power supply to the terminals marked ”Power”.
Diagram
Application
2.4 Installation with external start
Fig. 8
Chimney fan w/PDS
Isolation switch
EFC 25
Gas
Power supply
Fig. 9
External ON/OFF switch
Fireplace control
Fused switch

EXHAUSTO 3001736-2004-01-21.fm Commissioning 8/12
3. Commissioning
Commissioning is carried out with the control panel open. Only touch
the components in the box with electrically insulated tools.
Notice Before commissioning all windows and doors must be closed; if other types of fans are
installed they must be switched on 10 minutes in advance and run at full speed during
commissioning.
Dipswitches Check the factory settings of the dipswitches (Fig. 1-I) before commissioning.
In service mode the safety functions of the flow control (PDS) and the
fresh air inlet are bypassed
• Open control panel
• Press ON/OFF button (Fig. 1-C)
• Wait until constant green light, if the fire has to be lit during commissioning
• Press the service mode button (Fig. 1-H) on reverse of front cover. The alarm
LED (Fig. 1-A will flash RED and operation LED (Fig. 1-B) will flash according to
the position of the PDS switch as follows:
Notice Service mode is turned off next time the ON/OFF button is pressed or after half-an-hour
Dip-
switch Name Factory
setting OFF ON
1 MANUAL
RESET
ON Automatic reset
after power fai-
lure and draught
failure.
Manual reset after
power failure and
draught failure
2AFTER-
VENTILATION
OFF No
after-ventilation.
After-ventilation
period of 3 minutes
3.1 Service mode
RED No flow (C-NC).
GREEN Flow (C-NO).
YELLOW No signal from PDS. Check the wiring.

EXHAUSTO 3001736-2004-01-21.fm Commissioning 9/12
• The potentiometer (Fig. 1-J) is set at maximum by turning clockwise.
• Adjust the speed slowly down by using the potentiometer. Check for spillage by
carrying out a thorough test, all along the edge of the fireplace.
• If spillage is detected, increase the fan speed until spillage cannot be detected.
• If the control unit Step 2 is connected to the gas fire unit, high level can be
activated from the remote control (Fig. 2-C)
The pressure switch is typically placed inside the chimney fan.
• Set the PDS at minimum by turning anti-clockwise. Minimum is 20 Pa, do not
attempt to turn the dial lower than 20 Pa
• Increase slowly the PDS setting until disengagement of the PDS can be
registered (click sound) or the operation LED changes from GREEN to RED.
• Register the PDS value of disengagement.
• Turn back the setting of the PDS until it is connected, the operation LED changes
to GREEN.
• Set the PDS to 10 Pa below the registered value of disengagement.
• Press the ON/OFF button (Fig. 1-C) and the control turns off the service mode.
• Check the start-up function after commissioning by pressing the ON/OFF button
to start the fireplace
• Check the fireplace for spillage with all windows and doors closed; if other types
of fans are installed they must be switched on and running at full speed.
• If spillage is detected, repeat commissioning.
• After 10 minutes without spillage switch off the isolation switch for the chimney
fan and check the fail-safe function. The fireplace must cut-out 15 seconds after
the PDS has disconnected. Remember to turn the isolation switch back on.
• Mount the front cover
• Inform the end-user about the functions of the control and leave the instructions
with the end-user.
• Keep one copy with the appliance
• Post one copy back to EXHAUSTO Ltd. (pre-paid)
3.2 Setting of potentiometer
3.3 Adjustment of pressure differential switch (PDS)
3.4 Test of commissioning
3.5 Complete the commissioning card

EXHAUSTO 3001736-2004-01-21.fm Daily use 10/12
4. Daily use
Operation of EFC
from remote con-
trol
• Press simultaneously the ON/OFF-button (fig. 10-B) and the Burner start for 1
second(fig. 10-D)
• The operating LED (fig 10-E) will flash GREEN until correct air flow has been
confirmed. The operating LED will then turn constant GREEN and the fireplace will
get a signal to fire.
• If available, high and low fire can be changed by using the high/low fire button (fig.
10-C). The operating LED will flash once for low fire and twice for high fire.
• The fan speed can be adjusted during operation by activating the fan speed buttons
(fig. 10-A/10-D) and at the same time the operating LED will flash. The fan speed
cannot be adjusted below the commisioning level.
• To stop the fire and fan press the ON/OFF-button (fig. 10-B).
• For venting purposes press only the ON/OFF-button (fig. 10-B) once.The operating
LED will then turn constant YELLOW
Operation of EFC
control
• Press the ON/OFF-button (fig. 10-F)
• The operating LED (fig 10-E) will flash GREEN until correct air flow has been
confirmed. The operating LED will then turn constant GREEN and the fireplace will
get a signal to fire.
• To stop the fire and fan press the ON/OFF-button (fig. 10-F).
Operation from
external ON/OFF
switch
• The ON/OFF switch can be used for start, stop and reset of the controller
• If the switch is used for start-up it has priority over the control panel and the remote
control.
Notice The switch must be in the off position before trying to restart the controller
Operating LED
Alarm LED Constant RED in the alarm LED only indicates that a power failure has occured. To reset and
start the controller press ON/OFF button once.
If the alarm LED (fig. 10-G) comes on during operation press the ON/OFF-button twice to
stop the fan and restart the control. If the alarm LED is still lit after reset please look at fault
finding for help.
AB
C
E
F
G
D
Fig. 10
Indication of operating LED
(fig. 10-E) Description
Flashing RED Start-up signal from safety-system is missing. Usually due
to restart with the fan still spinning.
Flashing GREEN • Fan has started and control is waiting for confirmation
from safety-system of sufficient draught conditions.
• Remote control is activated.
Flashing YELLOW Sufficient draught conditions confirmed but signal from
fresh air inlet is missing.
Constant GREEN Safety is confirmed and the fireplace can be lit.
Constant YELLOW The fan is operating in venting mode

EXHAUSTO 3001736-2004-01-21.fm Fault finding 11/12
5. Fault finding
Start up
Operating
Observation
Type of fault Solution
Operating
LED Alarm LED
Constant RED Power failure. 1.Press ON/OFF-button or
external ON/OFF switch
for resetting and start.
Flashing RED Failure in failsafe supervision
(PDS-check).
1.Check the wiring.
2.Setting of PDS might be
too low.
3.Adjust the pressure
differential switch.
Flashing
GREEN
Application fault. 1.Check isolation switch
2.Check if chimney fan is
running, if not check
wiring to chimney fan
and PDS.
3.Check the flue, chimney
and chimney fan for any
blocking items.
4.Check flow sensor in
chimney fan.
5.Check settings and redo
commissioning.
Flashing
YELLOW
No signal from air inlet. 1.Re-connect loop on
terminal 10-11.
Flashing RED,
GREEN or
YELLOW
Flashing RED Service mode on. 1.Press ON/OFF-button.
No response No response Battery fault, remote control 1.Change battery
Observation
Type of fault Solution
Operating
LED Alarm LED
Constant
GREEN
Constant RED Insufficient flow , sufficient
flow is re-established.
1.Press ON/OFF-button or
if external ON/OFF
switch is in use turn the
switch off for resetting
2.Press ON/OFF-button or
use external ON/OFF
switch to restart
Flashing
GREEN
Constant RED Flow fault. 1.Check isolation switch.
2.Check if chimney fan is
running, if not check
wiring to chimney fan.
3.Check the flue, chimney
and chimney fan for any
blocking items.
4.Check flow sensor in
chimney.
5.Check settings and redo
commissioning.

EXHAUSTO 3001736-2004-01-21.fm
EXHAUSTO A/S
Odensevej 76
DK-5550 Langeskov
Tel.: +45 6566 1234
Fax: +45 6566 1110
E-mail: [email protected]
www.exhausto.dk
EXHAUSTO GmbH
Am Ockenheimer Graben 40
D-55411 Bingen-Kempten
Tel.: +49 6721 9178-0
Fax: +49 6721 9178-99
E-mail: [email protected]
www.exhausto.de
EXHAUSTO NORGE A/S
Lilleakerveien 4
N-0283 Oslo
Tel.: +47 2412 4200
Fax: +47 2412 4201
E-mail: [email protected]
www.exhausto.no
EXHAUSTO Ltd.
Unit 3 Lancaster Court,
Coronation Road,
Cressex Business Park
GB-High Wycombe HP12 3TD Tel.:
+44 1494 465166
Fax: +44 1494 465163
E-mail: [email protected]
www.exhausto.co.uk
EXHAUSTO AB
Verkstadsgatan 13
S-542 33 Mariestad
Tel.: +46 501 39 33 40
Fax: +46 501 39 33 41
E-mail: [email protected]
www.exhausto.se
EXHAUSTO Inc.
1200 Northmeadow Parkway
Suite 180
Roswell, GA 30076 USA
Tel.: +1 770 587 3238
Fax: +1 770 587 4731
E-mail: [email protected]
www.us.exhausto.com
6. Technical data
EFC control:
Dimensions: 85 mm x 126 mm x 32 mm
Supply voltage: 230 V ± 10% / 50 Hz
Fuses : 3,15 A T
Release out : Max. 3,15 A 250 VAC / 3,15A 30 VDC
Step 2 out : Max. 5 A 250 VAC / 5A 30 VDC
Chimney fan output : Max. 1.8 A/230 V (AC3)
Air inlet : 24 VDC (Closed-circuit supply)
External start : 24 VDC (Closed-circuit supply)
Degree of protection : IP 30
Material : ABS box
Ambient temperature : -10 °C to 40 °C
External IR sensor: Cable: 10 m
IR-remote control:
Battery type : Size AAA 1,5 V (3 pcs.)
Ambient temperature : 0 °C to 40 °C
CE Approval: The EFC control complies with the essential requirements of the
Gas Appliances Directive (90/396/EEC).
The compliance is based on examination to: EN298 (1993), PIN: 0063BN1144
Table of contents
Other Exhausto Control System manuals

Exhausto
Exhausto VEX100 Series User manual

Exhausto
Exhausto EXact2 VEX240 series Installation guide

Exhausto
Exhausto VEX200 series Installation guide

Exhausto
Exhausto VEX320CX User manual

Exhausto
Exhausto EXact2 VEX200 User manual

Exhausto
Exhausto VEX370H User manual

Exhausto
Exhausto EXact2 HMI2-350-TOUCH Installation guide

Exhausto
Exhausto EXact2 HMI2-350-TOUCH Installation guide

Exhausto
Exhausto EXact Installation guide

Exhausto
Exhausto EXact2 VEX240 series User manual