GE PACSystems RX3i CPE400 User manual

GE
Automation & Controls
Programmable Control Products
PACSystems* IC695CPE400
RX3i 1.2GHz 64MB
Rackless CPU w/Field Agent
Quick Start Guide
GFK-3002A
October 2017
g


i IC695CPE400 Rackless CPU w/Field Agent Quick Start Guide GFK-3002A
Contents
User Features .................................................................................................................1
Switches........................................................................................................... 4
Displays and Indicators (LEDs)......................................................................... 4
Front-Panel Ethernet Ports ............................................................................... 7
Serial COM Port................................................................................................ 8
Video Display Port ............................................................................................ 8
Field Agent Port................................................................................................ 8
Energy Pack Connector.................................................................................... 9
Input Power Connector ..................................................................................... 9
Removable Data Storage Device (RDSD)......................................................... 9
Hardware Installation.................................................................................................10
Initial Checks ...................................................................................................10
Installation .......................................................................................................10
Installation in Hazardous Areas........................................................................12
Connect to Power Supply.................................................................................13
Grounding........................................................................................................14
Module Start-up...........................................................................................................15
You Will Need:.................................................................................................15
Basic Start-up Steps:.......................................................................................16
Configuration ...............................................................................................................17
Backwards Compatibility..................................................................................17
PROFINET Controller Configuration ................................................................17
Field Agent Configuration.................................................................................18
4.3.1. Start the Embedded Field Agent (EFA)............................................................18
4.3.2. Log into the Web Console................................................................................18
4.3.3. Configure the Network .....................................................................................20
Redundancy Configuration...............................................................................24
Additional Information ...............................................................................................25


1 IC695CPE400 Rackless CPU w/Field Agent Quick Start Guide GFK-3002A
User Features
Figure 1: CPE400 Features at a Glance
The PACSystems* RX3i CPE400, part of GE’s Industrial Internet Control System, is the
industry’s first outcome optimizing controller. It augments real-time deterministic
control with Field Agent technology, delivering near real time advice through market
analysis, fleet and enterprise data, or asset/process knowledge to optimize the
outcomes that today’s businesses require. The Predix™ enabled CPE400 provides
reliable, secure communication and analytics using either cloud-based or edge-
based outcome optimizing apps. Controls can now be programmed to dynamically
influence business outcomes, generate new forms of revenue, and improve
profitability.

GFK-3002A October 2017 2
•The stand-alone CPE400 uses a 1.2GHz quad-core microprocessor and real-time
hypervisor technology to run real time deterministic control applications
concurrently with Field Agent technology without any adverse impact of one
over the other.
•A built-in RX3i PLC:
oUser may program in Ladder Diagram, Structured Text, Function Block
Diagram, or C.
oContains 64Mbytes of configurable data and program memory.
oSupports auto-located Symbolic Variables that can use any amount of user
memory.
oReference table sizes include 32k bits for discrete %I and %Q and up to 32k
words each for analog %AI and %AQ. Bulk memory (%W) also supported for
data exchanges.
oSupports up to 512 program blocks. Maximum size for a block is 128KB.
•Field Agent technology is a platform for securely applying Predix applications
and secure connectivity to the Predix Cloud as well as running edge apps.
Running the Field Agent concurrently with the real-time control applications
allows the CPE400 to rapidly leverage external data. External monitoring may be
used to analyze and optimize entire business operations. The analysis can then
be used to dynamically adjust real-time industrial controls to align with changing
business objectives in today’s Industrial Internet age.
•Supports four independent 10/100/1000 Ethernet LANs. Three are located on the
front panel, as shown in Figure 1. LAN1 attaches via the upper, dedicated RJ 45
connector. LAN2 and LAN3 each attach via a pair of internally-switched RJ 45
connectors. The fourth LAN, labeled EFA (Embedded Field Agent), is located on
the underside (Figure 2), and is specifically used for Field Agent connectivity (see
Field Agent bullet just above).
•The embedded communications interface has dedicated processing capability,
which permits the CPU to independently support LAN1 and LAN2 with:
oup to 48 simultaneous SRTP Server connections;
oup to 16 simultaneous Modbus/TCP Server connections;
o32 Clients are permitted; each may be SRTP or Modbus/TCP.
oOPC UA Server with support for up to 5 concurrent sessions with up to
10 concurrent variable subscriptions and up to 12,500 variables;
oup to 255 simultaneous Class 1 Ethernet Global Data (EGD) exchanges.

3 IC695CPE400 Rackless CPU w/Field Agent Quick Start Guide GFK-3002A
•The embedded PLC may use one or both of the Ethernet LAN2 ports to support
the embedded Simplex PROFINET I/O Controller. PROFINET supports up to 32 I/O
devices with update rates of 1 –512ms. I/O device update rates of 8ms and
faster are possible with 16 or fewer devices. Update rates of 16ms and higher
result whenever more than 16 devices are configured.
•Media Redundancy Protocol (MRP) allows the CPE400 to participate in a
PROFINET I/O network with MRP ring technology. This eliminates the I/O network
as a single point of failure. The CPE400 may be used as either a Media
Redundancy Manager or Media Redundancy Client.
•Effective with firmware release 9.30, the CPE400 supports Hot Standby
Redundancy with PROFINET IO. In this configuration, LAN3 is used as a high-
speed data synchronization link between the two redundant CPUs. Only the
Primary and Secondary CPUs may be attached to LAN3. Two OLED menu items
support Redundancy operation: RDN Info and RDN Command. The RACT and
RBOK LEDs reflect the status of the Redundant CPUs.
•Effective with firmware release 9.30, the CPE400 supports two independent
Redundant IP addresses, one for LAN1 and one for LAN2. LAN2 Redundant IP is
supported when configured for Ethernet mode only. Redundant IP is supported
by the SRTP Server, Modbus TCP Server, and EGD protocols. It is not possible to
use Redundant IP with the OPC UA Server or with the Ethernet firmware update
web page.
•The CPE400 is secure by design, incorporating technologies such as Trusted
Platform Modules, secure boot, and encrypted firmware updates.
•Optional Energy Pack, IC695ACC403, allows CPE400 to instantly save user
memory to non-volatile storage in the event of loss of power.
•OPC UA Sweep Mode & Sweep Time: The CPE400’s sweep mode and sweep time
are available through the OPC UA server. The Sweep Mode variable reports the
controller’s current mode: Stop Disabled, Run Enabled, Stop Enabled,
Run Disabled, Stop Faulted, and Stop Halted. The Sweep Time variable reports
the sweep time in seconds. These variables are located under
GE Device Information -> PACSystems RX3i -> Controller.
•An OLED display that provides access to basic CPE400 status and control
information including each LAN’s configured IP Address.
•Operating temperature range -40C to 70C (-40F to 158F).
•Alternate panel-mount adaptor plate included.

GFK-3002A October 2017 4
Switches
All user-accessible switches are provided as pushbuttons on the front panel (Figure 1)
as described below.
Pushbutton
Function
DISP
Permits user to navigate menus in the OLED display.
SEL
Permits user to select the menu item on the OLED display.
RUN
Activates OLED Menu to select RUN/Enabled or RUN/Disabled
Mode for the embedded PLC.
STOP
Activates OLED Menu to select STOP/Enabled or STOP/Disabled
Mode for the embedded PLC.
PHY PRES
Not functional.
PWR
Hold down for brief period to induce CPU Reset.
Note that this does not turn unit power off, but only holds unit in Reset
Displays and Indicators (LEDs)
OLED Display
The monochrome organic light-emitting diode (OLED) display (Figure 1) is used to
display CPE400 system menus. It interacts with the DISP pushbutton, which jogs the
cursor from one menu item to the next, and with the SEL pushbutton, which activates
the currently indicated menu item for further action.
The OLED display permits the user to:
•Display Ethernet LAN Settings: IPv4 address.
•Display the PLC firmware revision.
•Set/view PLC mode and view sweep time.
•Set the PLC mode to RUN/STOP with I/O Enabled/Disabled via the display.
Note: the RUN and STOP pushbuttons activate the PLC Mode menu items per
Section 1.1.
•View whether all, some, or none of the PROFINET I/O devices are connected.
•Display EFA Settings: IPv4 address, subnet mask, gateway, MAC address,
IPv6 address.
•Issue Field Agent Commands: Enter/Exit Configuration mode, Clear
Configuration, Perform factory reset.
•View Field Agent Status: Off, Starting, Connecting, Connected, Connected-ACT.
•View HSB Redundancy Mode and State (Release 9.30 and later)
•Command an HSB Redundancy Role Switch (Release 9.30 and later)

5 IC695CPE400 Rackless CPU w/Field Agent Quick Start Guide GFK-3002A
Status Indicators (LEDs)
LED
LED State
Operating State
PLC
MODE1
On Green
PLC is in RUN mode.
Off
PLC is in STOP mode.
RUN
Blinking in
unison
CPU is updating an internal programmable hardware
device.
OE
PHY
PRES
On Green
TPM Physical Presence (not functional).
Off
SSD
On Green
Activity detected on Solid State Disk.
Off
No activity detected on Solid State Disk.
TEMP
On Red
CPU Overtemperature condition detected.
Off
Overtemperature condition not detected.
OK
On Green
CPU has passed its power-up diagnostics and is
functioning properly. (Following initialization sequence.)
Off
Power is not applied or CPU has a problem.
Blinking;
All other
LEDs off
PLC in STOP/Halt state; possible watchdog timer fault.
If the programmer cannot connect, cycle power with
charged Energy Pack attached and refer to fault tables.
OK
Blinking
alternately
CPU encountered a Secure Boot Error.
OE
OE
On Green
Output scan is enabled.
Off
Output scan is disabled.
FRC
On Yellow
One or more Overrides active in I/O Reference Table(s).
Off
No Overrides active in any I/O Reference Table.
FLT
On Red
PLC is in STOP/Faulted mode: a fatal fault has occurred.
Off
No fatal faults detected.
IO
On Green
PROFINET Connection Status = OK.
Off
PROFINET Connection Status not OK.
RACT
On Green
Local Redundant CPU is Ready & Active.
Off
Local Redundant CPU is not Ready.
1
This LED is located between the RUN and STOP pushbuttons. It indicates the PLC Mode.

GFK-3002A October 2017 6
LED
LED State
Operating State
RBOK
On Green
Remote Redundant CPU is Ready.
Off
Remote Redundant CPU is not Ready.
FAOK
On Green
Field Agent Running and Connected to Cloud.
Blinking
Green
Blink at 0.5 Hz: Field Agent Starting.
Blink at 1 Hz: Field Agent Running.
Off
Field Agent Off.
PWR
On Green
CPU running.
Blinking
Green
Booting up –diagnostics in progress.
On Red
Off
Off
Reset / Power not detected.
Front Ethernet Indicators (LAN1, LAN2, LAN3 RJ45 Built-in LEDs)
LED
LED State
Operating State
Link
Status
(upper)
On Green
The corresponding link has been established.
Blinking
Green
Traffic is detected at the corresponding port.
Off
No connection established at corresponding port.
Link
Speed
(lower)
On Green
Corresponding data speed is 1 Gbps or 100 Mbps.
Off
Corresponding network data speed is 10 Mbps
Bottom Ethernet Indicators (EFA RJ45 Built-in LED)
LED
LED State
Operating State
Link
Status
(upper)
On Green
The corresponding link has been established.
Blinking
Green
Traffic is detected at the corresponding port.
Off
No connection established at corresponding port.
Link
Speed
(lower)
On Green
Corresponding network data speed is 1 Gbps.
On Yellow
EFA port only: network data speed is 100 Mbps
Off
Corresponding network data speed is 10 Mbps

7 IC695CPE400 Rackless CPU w/Field Agent Quick Start Guide GFK-3002A
Front-Panel Ethernet Ports
LAN1 connects to the uppermost RJ45 connector (Figure 1). It is not switched.
LAN2 connects to the middle two RJ45 connectors (Figure 1). These two ports are
switched internally.
LAN3 connects to the two lower RJ45 connectors (Figure 1). These two ports are
switched internally. LAN3 may only be used to supply a high-speed synchronization
link between the Primary and Secondary CPUs in Hot Standby Redundancy. Both
ports are typically used, as described in the PACSystems Hot Standby CPU
Redundancy User Manual, GFK-2308 (revision L or later).
Each of the embedded Ethernet interfaces automatically senses the data rate
(10 Mbps or 100 Mbps or 1 Gbps), communications mode (half-duplex or full-duplex),
and cabling arrangement (straight-through or crossover) of the attached link. LEDs
embedded in each RJ45 connector provide indications per the table above.
LAN1 or LAN2 may be used to communicate with the PME programming software
using the Service Request Transport Protocol (SRTP, a proprietary GE protocol, used
primarily for communication with the programmer).
To establish Ethernet communications between the PME programming and
configuration software and the CPU, you first need to know the target IP address. Use
the OLED menu function to check the IP Address. The factory-shipped default settings
are:
CPE400 LAN1
CPE400 LAN2
CPE400 LAN3
IP Address:
192.168.0.100
10.10.0.100
N/A
Subnet Mask:
255.255.255.0
255.255.255.0
N/A
Gateway:
0.0.0.0
0.0.0.0
N/A

GFK-3002A October 2017 8
Serial COM Port
The RJ45 port marked COM is located on
the underside of the CPE400, as shown
in Figure 2. This port is not currently
supported.
Video Display Port
The Display Port is located on the
underside of the CPE400, as shown in
Figure 2. It provides signals for
connecting either a suitable monitor or
video adapter to the unit. This port is
not currently supported.
Figure 2: Underside Ports & Connectors2
Field Agent Port
The RJ45 port marked EFA is located on the underside of the CPE400, as shown in
Figure 2. This is an Ethernet port pre-configured to connect securely to the Predix
cloud environment. For additional information concerning use of this port, refer to the
PACSystems RX7i, RX3i and RSTi-EP CPU Reference Manual, GFK-2222Y or later. For
more detailed information regarding Field Agent, refer to the Field Agent User’s Guide,
GFK-2993.
The FAOK LED, located on the front panel, indicates the status (page 6) of the Field
Agent interface.
2
Only the 24Vdc In Connector is shipped with the CPE400.

9 IC695CPE400 Rackless CPU w/Field Agent Quick Start Guide GFK-3002A
Energy Pack Connector
The CPE400 compatible Energy Pack, IC695ACC403, is supplied with a purpose-built
cable, IC695CBL003, which installs in the 24Vdc In and Energy Pack Control & Status
connectors shown in Figure 2. Use of the Energy Pack is optional. When used, it
allows the CPE400 to save its current state upon loss of power. Refer to the
PACSystems RX3i Rackless Energy Pack IC695ACC403 Quick Start Guide, GFK-3000, for
complete wiring and grounding instructions.
Input Power Connector
If no Energy Pack is to be connected, refer to Section 2.4. Otherwise, refer to the
PACSystems RX3i Rackless Energy Pack IC695ACC403 Quick Start Guide, GFK-3000.
Removable Data Storage Device (RDSD)
The CPE400 is equipped with a micro-SD card slot and two USB ports (Figure 1). These
are not currently supported.

GFK-3002A October 2017 10
Hardware Installation
Initial Checks
Upon receiving your equipment, carefully inspect all shipping containers for damage.
If any part of the system is damaged, notify the carrier immediately. The damaged
shipping container should be saved as evidence for inspection by the carrier.
As the consignee, it is your responsibility to register a claim with the carrier for
damage incurred during shipment. GE will fully cooperate with you, however, should
such action be necessary.
After unpacking the equipment, record all serial numbers. Serial numbers are
required if you should need to contact Customer Care during the warranty period. All
shipping containers and all packing material should be saved should it be necessary
to transport or ship any part of the system.
Verify that all components of the system have been received and that they agree
with your order. If the system received does not agree with your order, contact
Customer Care.
Installation
As shipped, the CPE400 is intended for mounting on a DIN rail. A panel-mount
adaptor is also available. If panel-mounting is required, replace the DIN-rail adaptor
with the panel-mount adaptor using the screws supplied with that adaptor. Both
adaptors attach to the rear of the CPE400 chassis using four Torx M3 screws. Torque
newly-installed screws to 5.3 in-Ibs (0.6 Nm) if installing a new adaptor plate.
For installation to standards, refer to the Installation and Maintenance Requirements
document, GFK-3004.
Note the thermal requirements for mounting the equipment (Figure 3).
Mount on the DIN rail per Figure 4. (1) Incline the unit so that the upper hooks of the
DIN rail adaptor engage with the upper edge of the DIN rail. (2) Press on the lower
part of the unit until you hear a click. The click indicates that the lower hooks of the
DIN rail adaptor have engaged with the lower edge of the DIN rail.
Dismount from the DIN rail per Figure 5. (1) Grasp the unit securely. (2) Press down on
the release bar as indicated. (3) Swivel the unit away from the DIN rail, then remove.

11 IC695CPE400 Rackless CPU w/Field Agent Quick Start Guide GFK-3002A
50mm 50mm
100mm 100mm
Air flow
adjacent device right
adjacent device left
adjacent device below
adjacent device above
25mm
Air flow
max. 70°C
Figure 3: Thermal Requirements
Figure 4: Mounting on DIN Rail
Figure 5: Dismounting from DIN Rail

GFK-3002A October 2017 12
If using the panel-mount adaptor, two options are available: mount using two screws
(Figure 6) or, for more secure mounting, mount using four screws (Figure 7).
Figure 6: 2-screw panel mount
Figure 7: 4-screw panel mount
Installation in Hazardous Areas
Refer to the Installation and Maintenance Requirements document, GFK-3004.

13 IC695CPE400 Rackless CPU w/Field Agent Quick Start Guide GFK-3002A
Connect to Power Supply
The 24Vdc power input connector is located on
the underside of the CPE400, as shown in Figure 8.
The signal pinouts are also indicated.
The mating connector for the CPE400 24Vdc
power input is the 3-pin Phoenix 1827716 shown
in Figure 9. The power supply cable prepared by
the user must use the specified mating connector.
The positive “+” and negative “-“ signals are
required. FGND is optional, but recommended.
For the mating connector, the compatible
conductor size is from 24AWG to 16AWG. Strip the
wires back 7mm before inserting into the
connector. Tightening torque for the three signal
screws is 2.2 in-Ibs (0.248Nm). Secure the mating
connector to the power input connector via the
two captive screws provided.
The user-supplied SELV3power supply must
supply voltage in the range of 18Vdc to 30Vdc.
Once the power supply cable (or compatible
Energy Pack ACC403) has been attached to the
CPE400 and the power supply has been turned on,
the unit will start booting. There is no need to push
any button.
The unit is equipped with built-in reverse polarity
protection. If + and - are swapped the unit will not
power-up. If + is connected to FGND, this will
cause a short. The power supply needs to protect
itself against this condition.
Figure 8: 24Vdc Power Input
Connector
Figure 9: 24Vdc Power Input
Mating Connector
Inrush Current
The CPE400 may experience an inrush current of up to 49A for 15µs.
3
SELV = Safety Extra Low Voltage

GFK-3002A October 2017 14
Overvoltage protection
In the CPE400, the voltage to the inner loads is clamped to 33Vdc. At 33Vdc, the
internal clamping diode starts conducting at 1mA. Any further increase in the voltage
will cause the internal current fuse to blow and/or the clamping diode to break.
•CAUTION –EQUIPMENT REPAIR REQUIRED –Internal components must be
repaired at the factory; they are not field replaceable. Contact the GE
support team at https://ge-ip.force.com/communities/CC_Contact
Overcurrent protection
The function protects the internal circuitry from overcurrent conditions before serious
damage can occur, such as overheating of the equipment. The fuse is rated for 4A
continuous current. Once the sensed current reaches 40A, the fuse will blow after a
period of 10ms to 100ms.
•CAUTION –EQUIPMENT REPAIR REQUIRED –Internal components must be
repaired at the factory; they are not field replaceable. Contact the GE
support team at https://ge-ip.force.com/communities/CC_Contact
Grounding
Grounding via the FGND connection on the 3-pin 24Vdc In power header is
recommended (see section 2.4), but is not required if the CPE400 is mounted to a
grounded metal panel. Furthermore, if an Energy Pack is connected, be sure to
comply with grounding procedures as described in PACSystems RX3i Rackless Energy
Pack IC695ACC403 Quick Start Guide, GFK-3000.

15 IC695CPE400 Rackless CPU w/Field Agent Quick Start Guide GFK-3002A
Module Start-up
You Will Need:
•This PACSystems Rackless RX3i CPU.
•A compatible SELV 24Vdc, 48W power supply (72W if Energy Pack attached).
•(Optionally) A compatible Energy Pack, IC695ACC403, and corresponding cable.
•If no Energy Pack is to be attached, use the power supply cable described in
Section 2.4.
•A DIN rail, typically mounted in an enclosure, as discussed above. Alternately,
mount the unit using the compatible panel-mount adaptor.
•A computer running Proficy Machine Edition (PME) configuration and
programming software. PME Version 9.00 SIM 8 or later supports the CPE400.
Version 9.50 SIM 5 is required for Hot Standby Redundancy.
•Ethernet cable for connecting the PME programmer computer to the CPE400.
•Additional cables, as needed, to connect each port employed in the application.
•A very small slotted screwdriver to secure the 24Vdc mating connector.
•A T8 Torx screwdriver, if the micro-SD slot cover is to be removed. Note that the
cover must be replaced to achieve immunity from electrical noise.
•A T10 Torx screwdriver, if exchanging the mounting adaptors.

GFK-3002A October 2017 16
Basic Start-up Steps:
For startup and configuration of the CPE400, complete the following steps. For full
details on CPE400 operation, refer to the PACSystems RX3i and RX7i CPU Reference
Manual, GFK-2222Y or later.
1. Mount the CPE400, as described in Section 2.2 and per the Installation and
Maintenance Requirements document, GFK-3004.
2. Attach the user-supplied power supply cable as described in Section 2.4 if no
Energy Pack is being used.
3. (optionally) Mount and attach the compatible Energy Pack, IC695ACC403, as
described in the PACSystems RX3i Rackless Energy Pack IC695ACC403 Quick Start
Guide, GFK-3000.
4. Turn on the power supply unit: the unit should then run without the need to press
any buttons.
5. If not previously configured, configure the RX3i PLC using PME 9.00 SIM 8 or later,
as described in the Configuration section below.
Note: When the ACC403 Energy Pack is powered up, a finite period is required to
charge it up to its operating level. During this time, the Energy Pack will
indicate this condition via its LEDs (refer to the PACSystems RX3i Rackless
Energy Pack IC695ACC403 Quick Start Guide, GFK-3000).
The CPE400 will begin its boot cycle immediately upon power application.
However, the embedded controller will not start its control until the ACC403 is
charged. This typically takes 45 seconds or less. In the event the ACC403 is
faulty or is not communicating, CPE400 commences operation without the
Energy Pack.
Note: In the event of loss of power, with the ACC403 Energy Pack connected and
charged up, the CPE400 remains on for 4 seconds to backup user memory
into its non-volatile memory.
Table of contents
Other GE Control System manuals

GE
GE Mark VIe Manual

GE
GE MX350 User manual

GE
GE Multilin G650 User manual

GE
GE TRANSFORMER MANAGEMENT RELAY 745 User manual

GE
GE WH12X10457 Configuration guide

GE
GE PACSystems RX7i User manual

GE
GE SPEEDTRONIC Mark V User manual

GE
GE Multilin DGT Series User manual

GE
GE Multilin MM300 User manual

GE
GE Mark VIe Parts list manual
Popular Control System manuals by other brands

Alpha Communications
Alpha Communications TekTone CM800 Installation & operating instructions

Draper
Draper EZ-Pad 3.0 instructions

Thermo King
Thermo King SR-2 SmartReefer2 Diagnostic manual

Pentair
Pentair EASYTOUCH PL4 installation guide

MKS
MKS 49 Series User manual & installation guide

Tecnoalarm
Tecnoalarm TP8-64 BUS Installer manual