
NOTES
•Horizontal mounting of the power converter is recommended although it can be mounted in any position
that provides unobstructed ventilation to the fan and vent holes.
•The OEM should test the power converter under full load conditions in its intended mounting location. This
will ensure there is sufficient ventilation to the converter allowing it to operate at its maximum rated output.
Failure to provide adequate ventilation to the converter will cause the converter output to be reduced as it
responds to ambient conditions.
•The INTELI-POWER converters are not designed for zero clearance compartments.
•Use a 5/32” hex driver to tighten the output screws. Do not exceed 50 in-lb torque on the output terminals.
•The INTELI-POWER converters are not weather-tight or designed for wet mounting locations. They must be
protected from direct contact with water.
•Avoid the introduction of foreign materials into the case as this could damage or cause a malfunction of the
converter.
INSTALLATION
1. Secure the converter firmly to the mounting surface.
2. Connect chassis ground lug (found on unit base) to chassis. Ground wire to be 10 AWG copper wire
minimum (follow all applicable codes when sizing conductor).
3. Disconnect the battery from both positive (+) and ground (-) cables.
4. Connect battery ground (-) to converter NEG (-) lug. Conductor to be minimum 8AWG copper with minimum
75 ⁰C jacket rating (follow all applicable codes when sizing conductor).
5. Disconnect any optional accessories or modules.
6. Plug the converter into the appropriate outlet.
7. Using a DC voltmeter, verify the converter output. If no output is measured, refer to the troubleshooting
guide in this manual or on the Expion360 website.
8. Disconnect power to the converter.
9. Connect battery POS (+) to converter POS (+) lug. Conductor to be minimum 8AWG copper with a minimum
75 ⁰C jacket rating (follow all applicable codes when sizing conductor). Note: When connecting the battery to
converter POS (+), a spark may occur. This is normal.
10. Reconnect cables.
11. Reconnect any optional accessories or modules.
12. Reconnect power to the converter.
DC Lugs: 30 to 50 in-lb
Chassis Ground Lug:
25 to 35 in-lb
DO NOT REMOVE TERMINAL BLOCK SCREWS
The chassis bonding wire must be a separate wire connected
directly from the grounding lug provided on the converter.
DO NOT
connect output negative to chassis using the same wire.