Extraflame LUCREZIA IDRO LCD User manual

LUCREZIA IDRO LCD USER MANUAL
ENGLISH/INGLESE


index
3
We thank you for having chosen our company; our product is a great heating solution developed from the
most advanced technology with top quality machining and modern design, aimed at making you enjoy
the fantastic sensation that the heat of a ame gives, in complete safety.
Extraame S. p. A.
Warnings..................................................................................................................................................................................5
safety........................................................................................................................................................................................5
HydraULiC systeM.................................................................................................................................................................. 6
InstallatIon and safety devIces................................................................................................................................................................................. 6
safety devIces for closed vessel system ............................................................................................................................................................. 6
dIstances of safety devIces accordIng to the standard ........................................................................................................................ 6
type of systeM........................................................................................................................................................................ 7
closed vessel system .......................................................................................................................................................................................................... 7
safety valves............................................................................................................................................................................................................................. 7
closed expansIon vessel................................................................................................................................................................................................... 8
commIssIonIng checks....................................................................................................................................................................................................... 8
automatIc thermostatIc mIxer valve (mandatory) ....................................................................................................................................... 8
HydraULiC systeM basiC LayoUt ....................................................................................................................................... 9
instant doMestiC Hot Water prodUCtion kit ...........................................................................................................10
stove posItIonIng ................................................................................................................................................................................................................10
rearM.......................................................................................................................................................................................10
tHerMo-prodUCts featUres ............................................................................................................................................10
safety deviCes......................................................................................................................................................................11
instaLLation..........................................................................................................................................................................11
InstallatIons allowed ....................................................................................................................................................................................................12
InstallatIons not allowed ..........................................................................................................................................................................................12
connectIon to the smoke evacuatIon system.................................................................................................................................................12
smoke channel or fIttIngs...........................................................................................................................................................................................12
chImney or IndIvIdual flue...........................................................................................................................................................................................13
chImney cap .............................................................................................................................................................................................................................14
connectIon to external aIr Inlets .........................................................................................................................................................................15
InsulatIon, fInIshIngs, coverIng and safety recommendatIons ......................................................................................................15
peLLets and feeding ...........................................................................................................................................................15
ControL board.....................................................................................................................................................................16
dIsplay Icons key..................................................................................................................................................................................................................16
generaL MenU .......................................................................................................................................................................17
BasIc InstructIons .............................................................................................................................................................................................................17
tHe reMote ControL...........................................................................................................................................................18
enaBle delayed swItch-off...........................................................................................................................................................................................18
type and replacement of BatterIes........................................................................................................................................................................18
CoMMissioning settings...................................................................................................................................................19
adjustIng the tIme, day, month and year............................................................................................................................................................19
adjustIng the language.................................................................................................................................................................................................19
operation and LogiC ..........................................................................................................................................................20
additionaL tHerMostat....................................................................................................................................................21
addItIonal thermostat functIonIng wIth stBy actIve.............................................................................................................................21
addItIonal thermostat functIonIng wIth stBy deactIvated...............................................................................................................21
addItIonal thermostat InstallatIon....................................................................................................................................................................21

index
4
MenU strUCtUre...................................................................................................................................................................22
set power .................................................................................................................................................................................................................................23
set temperature....................................................................................................................................................................................................................23
set adjustments ..................................................................................................................................................................................................................23
enaBle chrono.......................................................................................................................................................................................................................23
pellet regulatIon................................................................................................................................................................................................................23
user menu..................................................................................................................................................................................................................................24
chrono........................................................................................................................................................................................................................................24
programmIng example.....................................................................................................................................................................................................25
adjustIng language..........................................................................................................................................................................................................26
dIsplay .........................................................................................................................................................................................................................................26
reset ..............................................................................................................................................................................................................................................26
otHer fUnCtions..................................................................................................................................................................26
aIr dIscharge ..........................................................................................................................................................................................................................26
CLeaning Under User's responsibiLity.........................................................................................................................27
roUtine MaintenanCe .......................................................................................................................................................28
dispLays ..................................................................................................................................................................................30
aLarMs ....................................................................................................................................................................................31
Warranty Conditions .......................................................................................................................................................32

5
WARNINGS
The instruction manual is an integral part of the product: make sure that it always accompanies the appliance, even if transferred
to another owner or user or if transferred to another place. If it is damaged or lost,request another copy from the area technician.
This product must be intended for the use it has been specically made for. The manufacturer is exempt from any liability,
contractual and extracontractual, for injury/damage caused to persons/animals and objects, due to installation, adjustment
and maintenance errors and improper use. Installation must be performed by qualied sta, which assumes complete
responsibility for the denitive installation and consequent good functioning of the product installed. It is necessary to
bear in mind all laws and national, regional, provincial and town council Standards present in the country the appliance
has been installed.
Extraame S.p.A. cannot be held responsible for the failure to comply with such precautions.
After removing the packaging, ensure that the content is intact and complete. Otherwise, contact the dealer where the appliance
was purchased from.
All electric components that make up the product must be replaced with original spare parts exclusively by an authorised after-
sales centre, thus guaranteeing correct functioning.
SAFETY
The stove must not be used by persons (including children) with reduced physical, sensorial and mental capacities or who
are unskilled, unless they are supervised and trained regarding use of the appliance by a person responsible for their safety.
Children must be monitored to ensure they do not play with the appliance.
Do not touch the stove when you are barefoot or when parts of the body are wet or humid.
The safety and adjustment devices must not be modied without the authorisation or indications of the manufacturer.
Do not pull, disconnect, twist electric cables leaving the stove, even if disconnected from the electric power supply mains.
It is recommended to position the power supply cable in a way that it does not come into contact with hot parts of the
appliance.
The power supply plug must be accessible after installation.
Do not close or reduce the dimensions of the airing vents in the place of installation. The airing vents are indispensable
for correct combustion.
Do not leave the packaging elements within reach of children or unassisted disabled persons.
The hearth door must always be closed during normal functioning of the product.
When the appliance is functioning and hot to the touch, especially all external surfaces, attention must be paid
Check for the presence of any obstructions before switching the appliance on following a prolonged standstill period.
The stove has been designed to function in any climatic condition (also critical). In particularly adverse conditions (strong
wind, freezing) safety systems may intervene that switch the stove o. If this occurs, contact the technical after-sales service
and always disable the safety system.
If the ue should catch re, be equipped with suitable systems for suocating the ames or request help from the re
service.
This appliance must not be used to burn waste
Do not use any inammable liquids for ignition
During the lling phase do not allow the bag of pellets to come into contact with the product
The majolicas are top quality artisan products and as such can have micro-dots, crackles and chromatic imperfections.
These features highlight their valuable nature. Due to their dierent dilation coecient, enamel and majolica produce
crackling, which demonstrate their eective authenticity. To clean the majolicas, it is recommended to use a soft, dry cloth. If
a detergent or liquid is used, the latter could penetrate the crackles, thereby making them show more.
ROUTINE MAINTENANCE
Based on the Decree 22 January 2008 n°37 art.2, routine maintenance means interventions aimed at reducing degradation from
normal use, as well as dealing with accidental events entailing the need of rst interventions, which however do not modify the
structure of the system upon which one is intervening or its intended use according to the prescriptions foreseen by technical
standards in force and by the manufacturer's use and maintenance booklet.
| ENGLISH

6
HYDRAULIC SYSTEM
Certain concepts referring to the Italian UNI 10412-2 (2009) Standard are described in this chapter.
As previously described, when installing, all national, regional, provincial and town council Standards in force provided by the
country in which the appliance has been installed must be complied with.
During installation of the stove it is MANDATORY to adjust the system with a manometer in order to display the water pressure.
INSTALLATION AND SAFETY DEVICES
The installation, relative system connections, commissioning and inspection of correct functioning must be carried out perfectly,
in full compliance with Standards in force, national, regional and municipal, as well as these instructions.
For Italy, installation must be carried out by professionally authorised sta (Ministerial Decree dated 22.01.08 n°37).
Extraame S.p.A. declines all responsibility for damage to objects and/or persons caused by the system.
SAFETY DEVICES FOR CLOSED VESSEL SYSTEM
According to the UNI 10412-2 (2009) Standard in force in Italy, the closed systems must have: safety valve, pump control
thermostat, acoustic alarm activation thermostat, temperature indicator, pressure indicator, acoustic alarm, regulation automatic
circuit breaker switch, automatic circuit breaker block switch (block thermostat), circulation system, expansion system, safety
dissipation system incorporated with the generator with thermal safety valve (self-activated), whenever the appliance does not
have a temperature self-adjustment system.
DISTANCES OF SAFETY DEVICES ACCORDING TO THE STANDARD
The temperature safety sensors must be in place on the machine at a distance no greater than 30 cm from the ow connection.
Whenever the generators lack a device, those missing can be installed on the generator ow pipe, within a distance no greater
than 1m from the machine.
| ENGLISH
TABLE OF SAFETY DEVICES FOR CLOSED VESSEL SYSTEM
AND NOT PRESENT IN THE PRODUCT
Safety valve R
Pump control thermostat (it is managed by the water
probe and the board program) R
Acoustic alarm activation thermostat
Water temperature indicator (display) R
Pressure indicator
Acoustic alarm
Regulation automatic circuit breaker switch (managed
by board program) R
Minimum and maximum pressure pressure switch R
Water overheating automatic circuit breaker switch (block
thermostat) R
Circulation system (pump) R
Expansion system R
SAFETY DEVICES
CIRCUIT BOARD:
Intervenes directly by sending the product into alarm conditions until
complete cooling, in the case of: breakage of ue gas motor, pellet
feed motor breakage, black out (if more than 10 seconds), no ignition
FLOW SENSOR:
In the event of inadequate ow, it takes the machine to alarm conditions
F2.5 A 250V FUSE STOVES:
Protect the machine from violent current drops
85 CALIBRATED MECHANICAL BULB WITH MANUAL REARM:
Intervenes by blocking fuel feed whenever the pellet tank t° reaches
the limit of 85°C. Rearm must be performed by qualied sta and/
or the manufacturer's technical after-sales assistance.
100°C CALIBRATED MECHANICAL BULB WITH MANUAL REARM:
Intervenes by blocking the fuel feed whenever the t° of the water
inside the product is near to 100°. Rearm must be performed by
qualied sta and/or the manufacturer's technical after-sales
assistance.
MINIMUM AND MAXIMUM PRESSURE SWITCH:
Intervenes in the event of inadequate water pressure. Rearm must
be performed by qualied sta and/or the manufacturer's
technical after-sales assistance.
MECHANICAL AIR PRESSURE SWITCH:
Blocks the pellet in the event of insucient depression

7
COMPONENT DISTANCE
Temperature safety sensors On the machine or not exceeding 30 cm
Missing devices because not as per standard Not exceeding one metre, on the ow pipe
The domestic heating appliances with automatic feeding must: be supplied with a fuel block thermostat or be supplied with a
cooling circuit set-up by the appliance manufacturer.
The cooling circuit must be activated by a heat safety valve such to guarantee that the limit temperature set by the Standard is
not exceeded.
Connection between the power supply unit and the valve must be free from interceptions.
The pressure upstream from the cooling circuit must be at least 1.5 bar.
TYPE OF SYSTEM
There are two dierent types of system:
Open vessel system and closed vessel system.
The product has been designed and realised to work with closed vessel systems.
CLOSED VESSEL SYSTEM
System in which the water it contains is not in direct or indirect communication with the atmosphere. Generally, the closed
vessel system has one of the following expansion vessels:
Pre-loaded closed expansion vessel with membrane impermeable to the passage of gases.
Automatic closed expansion system with compressor and membrane impermeable to the passage of gases.
Automatic closed expansion system with transfer pump and membrane impermeable to the passage of gases.
Expansion system without diaphragm.
GENERALITY
The closed systems must have:
Safety valve
Pump control thermostat
Acoustic alarm activation thermostat
Temperature indicator
Pressure indicator
Acoustic alarm
Adjustment automatic circuit breaker switch
Automatic circuit breaker switch (block thermostat)
Circulation system
Expansion system
Safety dissipation system incorporated with the generator with thermal safety valve (self-activated), whenever the
appliance does not have a temperature self-adjustment system
SAFETY VALVES
The load capacity of the safety valve must allow the discharge of a quantity of vapour, not lower than: Q / 0.58 [kg/h] where: Q
is the useful outlet power to the generator water expressed in kilowatt. The diameter of the minimum net transversal section
of the valve inlet must not be lower than 15 mm. The valve load pressure, equal to the calibration pressure, increased by the
overpressure, cannot exceed the maximum exercise pressure of the heat generator. The designer must check that the maximum
pressure existing in every point of the system, does not exceed the maximum exercise pressure of its every component . The
safety valve must be connected to the highest part of the heat generator or outlet pipes, immediately near the generator. The
length of the pipes route included between the attachment to the generator and the safety valve must not be more than 1 m.
The connection piping of the safety valve to the heat generator must not be traceable and must not present, in any point, a
| ENGLISH

1
2
3
8
smaller section than the inlet of the safety valve or the sum of the inlet sections in case of more valves heading a single pipe.
The discharge piping of the safety valve must be realised in order not to prevent the regular functioning of the valves and
not to cause damages to persons; the discharge must ow immediately near the safety valve and be accessible and visible.
The diameter of the discharge piping must not however be lower than that of the outlet connection of the safety valve. For
diameter of outlet connection it is intended the minimum internal diameter on the valve outlet upstream of the eventual
internal threading.
CLOSED EXPANSION VESSEL
Warnings: check that the preload of the expansion vessel is set to 1.5 bar.
The vessel maximum exercise pressure must not be lower than the calibration pressure of the safety valve, increased by
overpressures, characteristic of the same valve, bearing in mind the eventual level dierence between vessel and valve and
the pressure generated by the functioning of the pump. The capacity of the expansion vessel/s is evaluated depending on the
total system capacity as results from the project. The closed expansion vessels must comply with the dispositions regarding the
planning, manufacturing, evaluation of conformity and use for pressure appliances. Intercepting objects or section decreases
must be inserted/practiced on the connection piping, which can be constituted by system portions. The insertion of a three-
way intercepting valve which allows connection between the vessel and the atmosphere for maintenance operations, is
allowed. Such device must be protected against accidental manoeuvres. The connection pipe must be realised in order not to
present scales or deposits storage points. In case of more heat generators which feed the same system or the same secondary
circuit, each heat generator must be connected directly to the expansion vessel or system expansion vessels unit, altogether
dimensioned for the total volume of water contained in the same system or the same independent circuit.Where it is necessary
to separate the individual heat generator from the expansion vessel or expansion vessels unit, a three-way tap must be applied
on the connection piping between the generator and the vessel, in order to ensure, in every position, the connection of the
generator with the expansion vessel or with the atmosphere. The expansion vessels, the connecting pipes, the bleed pipes and
drain pipes must be protected from freezing, where this phenomenon occurs. The solution used for this purpose is described
in the design.
COMMISSIONING CHECKS
Before connecting the boiler:
a) wash all system piping in order to remove any residues which might compromise the correct functioning of certain system
components (pumps, valves, etc.).
b) check to verify that the ue has adequate draft, is not narrowed and that other appliances do not discharge into the ue.
This is to prevent unexpected power increases. Only after this control can the ue tting be mounted between the boiler and
the ue. A check of the connections with pre-existing ues is recommended.
AUTOMATIC THERMOSTATIC MIXER VALVE MANDATORY
Theautomaticthermostatic mixing valve nds applications insolidfuel boilers as itpreventscoldwaterreturnintotheexchanger.
Routes 1 and 3 are always open and, together with the pump
installed on the return, they guarantee water circulation
inside the biomass boiler exchanger.
An elevated return temperature, allows eciency
improvement, reduces formation of combustion product
condensation and prolongs the boiler life span.
Valves on the market have dierent calibrations. Extraame
advises use of 55°C model with 1" hydraulic connections.
Once the valve calibration temperature is reached,
route 2 is opened and the boiler water goes to the system via
the ow.
Valve sold as an accessory (optional)
| ENGLISH

T2
T1
T3
A
B
AUX
STBY
1 2
3
SI
TM
S
G
VB
VMTA
9
HYDRAULIC SYSTEM BASIC LAYOUT
NOTA BENE:
the drawing in the gure is an example.
| ENGLISH
KEY
APrimary air inlet Ø 60mm
B Smoke exhaust outlet Ø 120mm
CPump (in the models envisioned) 1/2 "
T1 3 bar safety drain 1/2 "
T2 Boiler ow/output 1"
T3 Boiler return/inlet 1"
M Manometer
T Thermometer
G Filling system
SSafety valve discharge
VB Balance valve
YES System exhaust
VMTA Thermostatic mixer valve 55°C
IT IS RECOMMENDED TO CONSULT THE TEMPLATES MANUAL AT FOR FURTHER INFORMATION RELATIVE
TO THE HYDRAULIC CONNECTIONS, AIR INTAKE/FLUE EXHAUST AND DIMENSION SPECIFICATIONS OF THE
PRODUCT IN QUESTION.

0,0 0,5 1,0 1,5 2,0
2,5
0
1
2
3
4
5
6
85°C
100°C
10
| ENGLISH
INSTANT DOMESTIC HOT WATER PRODUCTION KIT
WARNINGS: if the instant hot water production kit is to be used, contact the company technical after-sales service.
STOVE POSITIONING
For correct product functioning, it is recommended to position it in a way that it is perfectly level, with the aid of a spirit level.
*Content of water in the system in addition to that of the
thermo product that can be managed with the integrated
expansion vessel. An additional expansion vessel must be
installed for a higher content of water.
The diagram at the side illustrates the behaviour of the pump
used on our thermo-products at the speeds that can be set.
Flow rate (m3/h)
Head (m)
REARM
The gures below show the rearm positions
of the tank (85°C) and H2O (100°C). It is recommended to
contact the qualied technician if one of the rearms should
be triggered, so as to verify the cause.
THERMOPRODUCTS FEATURES
LUCREZIA IDRO
Water content of the thermo product heat exchanger (l) 32
Volume of expansion vessel integrated into thermo-product (l) 6
Maximum content of water in the system for integrated expansion vessel (l)* 4
3 bar safety valve integrated into the thermo-product YES
Minimum and maximum pressure switch integrated into the thermo-product YES
Pump integrated into the thermo-product YES
Pump max. head (m) 5

11
SAFETY DEVICES
SAFETY DEVICES
KEY: * = PRESENT, = NOT PRESENT
STOVES
Circuit board: intervenes directly by sending the product
into alarm conditions until complete cooling, in the case
of: breakage of ue gas motor, pellet feed motor breakage,
black out (if more than 10 seconds), no ignition
*
Door micro switch: With the door open, burn pot system
operation is blocked
Electronic pressure switch: in the event of inadequate
depression, it takes the machine to alarm conditions *
F 2.5 A 250 V fuse (stoves): protects the machine from
violent current drops *
85°C calibrated mechanical bulb with manual rearm:
intervenes by blocking fuel feed whenever the pellet tank
t° reaches the limit of 85°C. Rearm must be performed
by qualied sta and/or the manufacturer's technical
after-sales assistance.
*
Pellet feed-box temperature control probe: if the tank
over-heats, the machine automatically modulates to return
to normal temperature values (*in the models envisioned)
*
Mechanical air pressure switch: blocks the pellet in the
event of insucient depression (in the models envisioned) *
INSTALLATION
The installation must be in compliance with:
UNI 10683 (2005) heat generators fed with wood and
other solid fuels: installation.
The chimneys must be in compliance with:
EN 13384 Thermal and uid dynamic calculation
methods.
UNI 1443 (2005) chimneys: general requirements.
UNI 1457 (2012) chimneys: clay/ceramic ue liners.
UNI/TS 11278 (2008) Chimneys/smoke channels/pipes/
ues/metal pipes.
UNI 7129 point 4.3.3 Fire Department dispositions, local
rules and prescriptions.
NATIONAL, REGIONAL, PROVINCIAL AND TOWN
COUNCIL REGULATIONS
It is necessary to bear in mind all laws and national, regional,
provincial and town council Standards present in the country
the appliance has been installed.
GLOSSARY
CLOSED HEARTH APPLIANCE
Heat generator which opening is only allowed through the
loading of the fuel during use.
BIOMASS
Biological material, excluding the material incorporated in
geological formations and transformed into fossils.
BIOFUEL
Fuel produced directly or indirectly by biomass.
CHIMNEY
Vertical pipe with the aim of collecting and expelling the fuel
products coming from only one appliance, at a convenient
height from the ground.
SMOKE CHANNEL OR FITTING
Pipe or connecting element between heat generator appliance
and chimney to evacuate combustion products.
INSULATION
Group of set-ups and materials used to prevent the
transmission of heat through a wall that separates rooms with
dierent temperatures.
CHIMNEY CAP
Device positioned at chimney peak to ease the dispersion of
combustion products into the atmosphere.
CONDENSATE
Liquid products that form when the combustion gas
temperature is lower or equal to the water dew point.
HEAT GENERATORS
Appliance which allows to produce thermal energy (heat)
through the rapid transformation, via combustion, of the
chemical energy of the same fuel.
GATE VALVE
Mechanism for modifying the combustion gas dynamic
resistance.
COMBUSTION PRODUCT EVACUATION SYSTEMS
Flue gas exhaust system independent from the appliance
constituted by a tting or smoke channel, chimney or
individual ue and chimney cap.
FORCED DRAUGHT
Air circulation by means of the fan activated by electric motor.
NATURAL DRAUGHT
Draught which is determined in a chimney/ue for eect of
the volume mass dierence existing between smoke (hot) and
surrounding atmosphere air, without any mechanical intake
aid installed inside it or at its peak.
| ENGLISH

12
| ENGLISH
RADIATION AREA
Area immediately near the hearth in which the heat caused by
combustion is diused, where no combustion materials must
be present.
REFLUX AREA
Area where leaking of the combustion products is veried,
from the appliance towards the installation room.
The installation must be preceded by checking the chimneys,
ues or unload terminals positioning of appliances similarly
to:
Installation prohibitions
Legal distances
Limitations disposed by local administrative regulations
or particular authority prescriptions.
Conventional limitations deriving from condominium
regulations, constraints or contracts.
INSTALLATIONS ALLOWED
Only appliances working in a sealed manner respect to the
room or which do not place the room in depression respect to
the external environment, can exist or be installed in the room
where the heat generator will be installed.
Appliances for cooking food and relative hoods without
extractor are only allowed in kitchens.
INSTALLATIONS NOT ALLOWED
In the room where the heat generator will be installed the
following must not pre-exist or be installed:
hoods with extractor
collective type ventilation pipes.
Should these appliances be in rooms adjacent, communicating
with the installation room, the simultaneous use of the heat
generator is forbidden, where a risk exists of one of the two
rooms being placed in depression respect to the other.
CONNECTION TO THE SMOKE EVACUATION SYSTEM
UNI 10683 (2005) Standard
SMOKE CHANNEL OR FITTINGS
To mount the smoke channels, non-ammable elements will
have to be used, ideal for resisting combustion products and
their eventual condensing.
The use of exible metal and asbestos cement pipes to
connect the appliances to the ue is forbidden, even for pre-
existing smoke channels.
There must be continuity between the smoke channel and the
ue so that the ue does not lean on the generator.The smoke
channels must not cross rooms where the installation of the
combustion appliances is not allowed.
The mounting of the smoke channels must be carried out in
order to guarantee smoke seal for the appliance functioning
conditions, limit the forming of condensate and avoid it being
transported towards the appliance.
The mounting of horizontal routes must be avoided.
For appliances where ceiling or wall non-coaxial discharges
with respect to the appliance combustion product outlet
have to be reached, the direction changes will have to realised
using open bends not greater than 45° (see gures below).
For the heat generator appliances equipped with electric fan
for expelling combustion products, the instructions below
must be followed:
45°
<
45°
<
The horizontal routes will have to have a minimum
upward slope of 3%
The length of the horizontal route must be minimal and,
however, not longer than 3 metres
The number of direction changes including the one for
eect of using the "T" element must not be more than 4.
In any case, the smoke channels must seal the combustion and
condensate products and be insulated if they pass outside the
installation room.
The use of counterslope elements is forbidden.
The smoke channel must allow the recovery of soot or be
brushable.
The smoke channel must have constant section. Any section
changes are only allowed at the ue coupling.
It is forbidden to have other air supply channels and pipes for
system engineering, especially if over-sized, transit inside the
smoke channels.The mounting of manual draught adjustment
devices on forced draught appliances is forbidden.
Insulating
product
Flue
pipe
Inspection

BC
A
S
< 3 m
3 - 5 %
13
CHIMNEY OR INDIVIDUAL FLUE
The chimney or individual ue must respond to the following requisites:
seal the combustion products, be waterproof and adequately insulated in line with the use conditions;
be realised with materials which resist the normal mechanical stress, heat, action of the combustion products and any
condensate;
have mainly vertical progress with deviations from the axis not higher than 45°;
be adequately distanced from fuel or ammable materials through air space or opportune insulation;
have preferably circular internal section: the square or rectangular sections must have round corners with a radius not
lower than 20 mm;
have constant internal section, free and independent;
have rectangular section with max. ratio between the sides of 1.5.
It is recommended that the smoke pipe be equipped with a collection chamber for solid materials and any condensate situated
under the smoke channel inlet, so that it can be easily opened and inspected from airtight door.
REFERENCES INFLAMMABLE OBJECTS NONINFLAMMABLE OBJECTS
A 200 mm 100 mm
B 1,500 mm 750 mm
C 200 mm 100 mm
Minimum 80 cm2
S= oor protection
Air inlets
Chimney cap
windproof
Flue
Inspection
Inspection
Flue
Inspection
| ENGLISH

< 3 m
45°
45°
50 cm
< 5 m > 5 m < 5 m
50 cm
H min
β
>A
<A
>50 cm
Z
14
External pipe
that is isolated
Inspection
Inspection
Appliance connection to the ue and combustion products evacuation
The ue must receive the discharge from only one heat generator.
Direct discharge towards closed spaces is forbidden, even with clear sky.
The direct discharge of the combustion products must be at roof and the smoke pipe must have the features provided in the
"Chimney or individual ue" section.
CHIMNEY CAP
The chimney cap must comply with the following requisites:
have an internal section equivalent to that of the chimney;
have useful outlet section not lower than double the chimney internal section;
be built in order to avoid rain, snow, foreign bodies penetrating the chimney and so that, in the event of winds in any
direction and inclination, the discharge of the combustion products is assured.
be positioned in a way to guarantee an adequate dispersion and dilution of the combustion products and, however, outside
the reux area in which the formation of counterpressures occurs. Such area has dierent dimensions and conguration
depending on the covering inclination angle. It is therefore necessary to adopt the minimum heights indicated in the gure
layouts below.
The chimney cap must not have mechanical intake means.
FLAT ROOF SLOPING ROOF
Z=REFLUX AREA
| ENGLISH

15
CONNECTION TO EXTERNAL AIR INLETS
The appliance must be able to use the necessary air to guarantee regular functioning through external air inlet. The air inlets
must comply with the following requisites:
have a total free section of at least 80 cm².
must be protected by grates, metal net or suitable protections as long as they do not reduce the minimum section stated
in the previous point and positioned in order to avoid them being obstructed.
If the combustion agent air is withdrawn directly from outside through a pipe, a downward bend must be mounted outside
or a protection against the wind and no grates or similar must be positioned, (it is recommended that the air vent always
communicates directly with the installation room even if the air is withdrawn from outside through a pipe). The air ow can also
be obtained from an adjacent room, as long as the ow takes place freely through permanent openings communicating with
the outside.
The adjacent room, with respect to the installation room, must not be put in depression with respect to the external environment
by means of reverse draught caused by the presence of another used appliance or intake device in such room. The permanent
openings in the adjacent room must comply with the above-described requisites.The adjacent room cannot be set up as garage,
storage for combustion material or activity with danger of re.
INSULATION, FINISHINGS, COVERING AND SAFETY RECOMMENDATIONS
The coverings, independently from the materials from which they are made, must constitute a self-supporting construction
with respect to the heating block and not be in contact with it.
The cross members and nishings in wood or combustion materials must be positioned outside the hearth radiation area or
adequately insulated.
If coverings in combustion material or sensitive to heat exist in the space above the generator, an insulating and non combustible
protection diaphragm must be inserted.
Elements in combustible or inammable material like wooden furniture, curtains, etc. directly exposed to the hearth radiation,
must be positioned at a safe distance. The appliance installation must guarantee easy access for cleaning the appliance itself,
discharge gas pipe and ue.
CHIMNEY CAPS, DISTANCES AND POSITIONING
Roof inclination Distance between the ridge and the chimney Minimum chimney height (measured from outlet)
β A (m) H (m)
15° < 1,85 0.50 m over the ridge
> 1,85 1.00 m from roof
30° < 1,50 0.50 m over the ridge
> 1,50 1.30 m from roof
45° < 1,30 0.50 m over the ridge
> 1,30 2.00 m from roof
60° < 1,20 0.50 m over the ridge
> 1,20 2.60 m from roof
| ENGLISH
Open the tank lid and load the pellets using a scoop.
PELLETS AND FEEDING
The pellets used must comply with the features described by
the Standard:
Ö-norm M 7135
DIN plus 51731
UNI CEN/TS 14961
Extraame recommends the use of pellets with
use pellet having a 6 mm diameter.
THE USE OF BAD QUALITY PELLETS OR ANY OTHER MATERIAL CAN DAMAGE YOUR STOVE AND WILL MAKE THE
WARRANTY NULL AND VOID, RELEASING THE MANUFACTURER FROM ANY LIABILITY.

OFF
16
CONTROL BOARD
ON/OFF
BUTTON
DISPLAY OF VARIOUS
TEXT MESSAGES
TO ACCESS
THE MENU
TEMPERATURE
SETTING
OPERATION POWER
ADJUSTMENT
| ENGLISH
DISPLAY ICONS KEY
Indicates the receipt of the radio signal
On = during radio communication
O = no radio communication
Flashing = excluded serial port
Indicates the stove modulation
On = the stove is working at the set power
Flashing = the power at which the stove is working is dierent to
the power set, the stove is modulating (for various reasons)
Indicates the presence of an alarm.
On: indicates the presence of an alarm
O: indicates the absence of alarms
Flashing: indicates the deactivation of the depression sensor.
It indicates weekly programming functioning
Indicator on = Weekly programming active
Indicator o = Weekly programming not active
Indicates the water temperature status
O = the T° read by the probe is over the set temperature set
On = the T° read by the probe is below the set temperature set
Indicates the contact of the external additional thermostat
Contact closed: the contact of the external additional thermostat
is closed.
Contact open: the contact of the external additional thermostat is
open.
Flashing with closed contact: the contact of the external additional
thermostat is closed and the STBY function is activated
Flashing with open contact: the contact of the external additional
thermostat is open and the STBY function is activated
It indicates functioning of the fumes motor.
O = ue gas motor deactivated
On = ue gas motor active
Flashing = breakdown (contact technical after-sales service)
It indicates the summer / winter function (with an additional board)
O: Activates the winter function
On: Activates the summer function
Not used
It indicates the boiler request (with an additional board)
O: DHW satised, pump o
Flashing: the DHW request exists but the work conditions are not
satised, pump o
On: the DHW is in request mode and the work conditions are
satised, pump on
It indicates functioning of the pellet feed motor.
O = pellet feed motor deactivated
On = pellet feed motor active.
It indicates the heating request (with an additional board)
O: heating satised, pump o
Flashing: the heating request exists but the work conditions are not
satised, pump o
On: the heating is in request mode and the work conditions are
satised, pump on
It indicates pump functioning
O = pump deactivated
On = pump active
Flashing = the safety device is active (H2O temperature > 85°C)
It indicates the puer request (with an additional board)
O: puer satised, pump o
Flashing: the puer request exists but the work conditions are not
satised, pump o
On: the puer is in request mode and the work conditions are satis-
ed, pump on

1
23
45
6
OFF
1 4
3
2
5
6
6
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
6
6
6
2
2
2
2
2
6
17
GENERAL MENU
TECHNIC SET
RESERVED TO THE QUALIFIED
TECHNICIAN
GO BACK EXIT
BROWSE PARAMETERS: NEXT 2; PREVIOUS 3
MODIFY SETTING DATA: INCREASE 4; DECREASE 5
CONFIRM ACCESS MENU
BASIC INSTRUCTIONS
The following recommendations must be followed the rst
times the stove is ignited:
It is possible that slight odours are produced due to the
drying of the paints and silicones used. Do not remain in the
environment for long periods.
Do not touch the surfaces as they could still be
unstable.
Air the room well several times.
The hardening of the surfaces is terminated after several
heating processes.
This appliance must not be used to burn waste.
Before lighting the stove, the following points must be
veried:
The hydraulic system must be completed in compliance
with the guidelines of the regulations and the manual.
The tank must be full of pellets
The combustion chamber must be clean
The burn pot must be completely free and clean
Check the hermetic closure of the re door and the ash
drawer
Check that the power supply cable is connected correctly
The bipolar switch in the rear right part must be positioned
on 1.
| ENGLISH
SET TEMPERATURE
SET ADJUSTMENTS
STATUS
SET POWER
STOVE STATUS
BOILER STATUS
PUFFER STATUS
HEAT. STATUS
ENABLE CHRONO
BIOMASS
BIOMASS/AUX
AUX
SUMMER/WINTER
ENABLE/DISABLE
BOILER CHRONO
PELLETS
SET H2O
SET PUFFER MAX
SET BOILER MAX
SET PUFFER MIN
SET BOILER MIN
USER MENU SET CLOCK
DISPLAY
LANGUAGE
SET CHRONO
RESET
All windows highlighted in LIGHT are managed by the additional board. The highlighted windows represent menus that will be displayed only if
the component (domestic hot water storage tank, puer or instant heat exchanger) has been activated in board by the after-sales sta.
DO NOT USE ANY INFLAMMABLE LIQUIDS FOR IGNITION!
DO NOT ALLOW THE BAG OF PELLETS TO COME INTO CONTACT WITH THE BOILING HOT STOVE DURING THE FILLING PHASE!
IN THE EVENT OF CONTINUOUS NO IGNITION, CONTACT AN AUTHORISED TECHNICIAN.
BOILER CHRONO

18
THE REMOTE CONTROL
All that can normally be implemented through the LCD can be adjusted can be adjusted using the remote control.
The table below provides a detailed description of the various functions:
INFO
1
2
3
4
5
6
7
8
9
10
11 12 13
14 15 16
1ON / OFF Pressing the key for three seconds, the stove will switch-on or o
2POWER INCREASE Pressing the key will increase the operating power
3POWER DECREASE Pressing the key will decrease the operating power
4T° INCREASE The set temperature can be increased by pressing this key
5T° DECREASE The set temperature can be decreased by pressing this key
6ENABLE/DISABLE
CHRONO Pressing the key once will enable or disable the chrono
7ENABLE DELAYED
SWITCHOFF
The delayed switch-o can be set by pressing this key.
For example, if the stove is set to switch-o in an hour, it shall switch-o
automatically once the set time elapses, displaying the countdown every
minute.
8MENU This key provides access to the user and technical menu (the technical
menu is reserved for assistance)
9INCREASE The set temperature can be increased by pressing this key
10 ESC KEY The key allows the user to exit any programme or display and returns to
the main menu without saving the data
11 REVERSE The key returns to the display of the various menus
12 CONFIRMATION KEY This key conrms the adjustments made during the user menu
programming phase
13 FORWARD The key moves forward in the various menus
14 ENABLE F1 FUNCTION Pre-set key for future applications
15 DECREASE The key decreases the value to be set
16 STOVE STATUS Pressing this key will display the general status of the stove
Note: the numbers shown on the remote control are purely indicative and are not present on the remote control supplied with the product.
TYPE AND REPLACEMENT OF BATTERIES
The batteries are housed in the lower part of the remote
control.
To replace them, remove the battery holder (as indicated in the
gure at the back of the remote control), remove or
insert the battery according to the symbol on the
remote control and on the battery itself.
For operation, 1 CR2025, 3V lithium buer battery is
required.
If the remote control is o because it has no
batteries, stove can be controlled from the
control panel on top of it.
While replacing the battery, pay attention to the
polarity by observing the symbol on the inside
compartment of the remote control.
The batteries used contain metals harmful
for the environment. They must therefore
be disposed of separately in appropriate
containers.
| ENGLISH

19
| ENGLISH
COMMISSIONING SETTINGS
Once the power cable at the back of the stove has been connected, move the switch, also located on the back, to (I).
The switch at the back of the stove powers the stove board.
The stove remains o and a rst screen appears on the panel
reading OFF.
ADJUSTING THE TIME, DAY, MONTH AND YEAR
Set clock allows to adjust the time and date
CONTROLS PROCEDURE
Press P6 and SET POWER will appear
Press key 2 several times until USER MENU is displayed
Confirm using key 6
SET CLOCK will appear
Confirm using key 6
Use key 4 or 5 to assign the day
Proceed by pressing key 2
Use the same procedure: 4 or 5 to set and key 2 to move forward; to
adjust the hours, minutes, day, month and year
Press key 1 several times to conrm and exit the Menu
SET CLOCK
DAY MON,TUE,WED,…SUN
HOUR 0...23
MINUTES 00...59
DATE 1...31
MONTH 1...12
YEAR 00...99
ADJUSTING THE LANGUAGE
It is possible to select the preferred language to display the various messages.
CONTROLS PROCEDURE
Press P6 and SET POWER will appear
Press key 2 several times until USER MENU is displayed
Confirm using key 6
SET CLOCK will appear
Press key 2 until SET LANGUAGE
Confirm using key 6
Select the language using key 4 or 5.
Press key 1 several times to conrm and exit the Menu
SET LANGUAGE
LANGUAGE
ITALIAN
ENGLISH
GERMAN
FRENCH
SPANISH
J
NO FLOW ALARM CLEAN CHECK UP ALARM
SHOULD THE "ALL NO FLOW ALL CLEAN CHECK UP" ALARM BE
TRIGGERED, MAKE SURE THAT THE BOTTOM OF THE BURN POT IS
FREE OF RESIDUE OR SCALES. THE HOLES AT THE BOTTOM MUST BE
COMPLETELY FREE TO GUARANTEE CORRECT COMBUSTION. THE "PELLET
FEED REGULATION" FUNCTION CAN BE USED
TO ADJUST COMBUSTION BASED ON THE DESCRIBED REQUIREMENTS. IF
THE ALARM PERSISTS AND THE ABOVE LISTED CONDITIONS HAVE BEEN
CHECKED, CONTACT THE QUALIFIED AFTERSALES ASSISTANCE CENTRE.
BURN POT BOTTOM
IT IS FORBIDDEN TO USE THE APPLIANCE WITHOUT THE DIVIDER AND/
OR GLASS PROTECTION SEE THE FIGURE AT THE SIDE. ITS REMOVAL
JEOPARDISES THE SAFETY OF THE PRODUCT AND IMMEDIATELY RENDERS
THE WARRANTY PERIOD NULL AND VOID. IN THE CASE OF WEAR OR
DETERIORATION REQUEST AFTERSALES ASSISTANCE FOR REPLACEMENT
OF THE PART REPLACEMENT THAT IS NOT UNDER GUARANTEE AS THE
COMPONENT IS SUBJECT TO WEAR.
UPPER DIVIDER BURN POT - KEEP THE CORRECT POSITION AS
INDICATED IN THE FIGURE
GLASS PROTECTION

OFF
20
OPERATION AND LOGIC
IGNITION
Once the points listed previously have been checked, press key 1 for three seconds to ignite the stove.
15 minutes are available for the ignition phase. After ignition and having reached the control temperature, the stove interrupts
the ignition phase and passes to STARTING.
STARTING
During the starting phase, the stove stabilises combustion, increasing it progressively, to then start ventilation and pass on to
WORK.
WORK
During the work phase, the stove reaches the set power; see following item.
ADJUSTING THE POWER SETTING
Set the functioning power from 1 to 5 (settable using keys 2 - 3).
Power 1 = minimum level - Power 5 = maximum level.
H2O TEMPERATURE SET ADJUSTMENT
Set the boiler temperature from 65 - 80°C (settable using keys 4 - 5).
PUMP OPERATION
The pump activates water circulation when the temperature of the water inside the stove reaches approx. 60°C. As the pump
always functions above 60°, an always-open heating area is recommended to make product functioning homogenous, avoiding
overheating blocks. Normally this area is dened“Safety zone”.
ENVIRONMENTAL TEMPERATURE in the models envisioned)
The front ventilation can be activated/deactivated and the room temperature controlled by means of the room probe (as per
standard). (See the "enable fan" chapter on the following pages.)
BURN POT CLEANING
While working, the stove has an internal counter which cleans the burn pot after a set amount of time.
This phase will be shown on the display, it will bring the stove to a lower power level and will increase the ue gas motor for a
programmed amount of time. When the cleaning phase is nished, the stove will continue work going back to the selected power
level.
MODULATION and H-OFF
As the water temperature approaches the set point, the boiler starts to modulate automatically bringing itself to the minimum
power.
If the temperature increases beyond the set point, it will automatically switch o indicating HOFF and will automatically go
back on when the temperature drops below the set point.
SWITCHOFF
Press key 1 for three seconds.
When the operation has been performed, the appliance automatically enters the switch- o phase, blocking the supply of pellets.
The ue exhaust motor and the hot air ventilation motor will remain on until the temperature of the stove has dropped
below the factory parameters.
REIGNITION
The stove can only be re-ignited automatically or manually when the cooling cycle conditions and the preset timer have been
satised.
| ENGLISH
J
NO IGNITION
FIRST IGNITION COULD EVEN FAIL AS THE AUGER IS EMPTY AND IS NOT ALWAYS ABLE TO LOAD THE BURN POT
WITH THE REQUIRED AMOUNT OF PELLETS ON TIME TO REGULARLY START THE FLAME.
IF THE PROBLEM OCCURS AFTER ONLY A FEW MONTHS WORKING, CHECK THAT ROUTINE CLEANING STATED IN THE
STOVE BOOKLET, HAS BEEN CARRIED OUT CORRECTLY.
Other manuals for LUCREZIA IDRO LCD
3
Table of contents
Popular Heating System manuals by other brands

Salda
Salda RIS 400PE EKO 3.0 Technical manual

Viessmann
Viessmann VITOTRONIC 100 operating instructions

Toyotomi
Toyotomi Oil Miser OM-22 Installation and operation instructions

OSTBERG
OSTBERG HERU S Operation & maintenance manual

Anda
Anda 443423 Installation, maintenance & user instructions

Dimplex
Dimplex DF3033ST troubleshooting guide

Nibe
Nibe ECS 40 Installer manual

Immergas
Immergas BASIC MAGIS PRO Instructions and warnings

Toyotomi
Toyotomi OM-22 Type A Installation and operation instructions

Carrier
Carrier 48ZG User's information manual

Cetetherm
Cetetherm Mini UK Installation, service and operating instruction

Spirax Sarco
Spirax Sarco SpiraHeat Installation and maintenance instructions