manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. FANOX
  6. •
  7. Timer
  8. •
  9. FANOX MTR 10 User manual

FANOX MTR 10 User manual

A1 A3 15 25
S M
16 18 26 28 R A2
8R
PROG
I II
OK
MTR 10
1 5 3
9
6 4 2
•ATTENTION: To prevent electrical shock, disconnect from power source before installing or servicing.
• Check that the auxiliary voltage supply is correct.
MULTIFUNCTION DIGITAL TIMER MTR 10
12
34
56
7
8
9
Auxiliary supply
Output contact
Command contact
Display
Red LED: energized output relay
Programmation push-button
A1 - A2: 230Vac (+15-10%)
A2 - A3: 24Vac, cc (+15-10%)
OUTPUT RELAY
OFF
15 25
16 18 26 28
ON
15 25
16 18 26 28
Technical data
Auxiliary supply 230V 50/60 Hz / 8VA
+15-10% / Consumption 24V Vdc.ac / 1W
Accuracy 1% ±10 ms
Repeat accuracy 0,5%
Output contacts: C300 - 125/250V
I
th= 5 A
1 relay with 2 timed AC15 - 250V - 2A
change over contacts DC13 - 30V - 2A
NO-NC DC13 - 115V - 2A
Terminals: max section / 2,5mm2, No.22 - 12AWG/
screw torque 20 Ncm, 1,8 LB - IN
Mechanical / >20 x 106OP /
electrical life 105OP
Protection degree / IP40 front /
weight
0,15 kg
Storage / -30ºC +70ºC /
operation temperature -20°C +55°C
1º Initial state of output relays:
energized (1H) or de-energized (1L).
2º Working mode: cycle (C1) or non-cycle (CO).
3º Number of different times per program: up to 8 in cycle mode
and up to 9 in non-cycle.
4º Time setting range: from 0,1 seconds to 99 hours.
5º Command contact.
With built-in battery which allows timer to be programmed
without connecting to auxiliary voltage.
Can be switched in two ways:
• By closing an external voltage free contact between M and S.
• By connecting 5-35 Vac,dc between M(+) and R(-)
Each diagram represents the effet of the command contact for
the two initial states of the output relay: de-energized (1L) and
energized (1H).
U: power supply
Switched off contact. Its
function is blocked.
Su función está inhibida
Reset contact
When connected the output
relay is de-energized upon
disconnecting,the programmed
timing starts.
Lock contact
Apartial shutdown of the timing
takes place during its operation.
U: power supply
R: output relay
Output relay at start: 1L de-energized; 1H energized.
Work mode: CO non-cycle; C1 cycle.
Command contact: cu, cr, cl, ci, co.
Delay ON
1L- CO - cu
Timing ON
1H - CO - cu
Delay OFF with
command contact
1H - CO - co
Double timing
1L- CO - cu
Double timing cycle
work mode
1H - C1 - cu
Four timings cycle
work mode
1H - C1 - cu
Timing with
partial shutdown
by command contact
1L- CO - cl
U
RT
U
1L
cl
1H Tl
T+Tl
U
1L
cr
1H T T
Tl
T1+Tl T2
U
R
cl
T1 T2
U
R
U
RT
co
U
RT
U
RT1 T2
C1 C2 C3
T1 T2 T3 T4
C1 C2 C3
U
R
Command contact
Function examples diagrams
cu
cr
cl
U
1L
ci
1H T T
U
1L
co
1H T T
Delay on contact
When disconnected the output
relay is de-energized; when
connected the programmed
timings starts.
Delay off contact
When disconnected the output
relay is de-energized. When
connected, the relay is
energized. When disconnected
again, the programmed timings
starts.
ci
co
1 ÷99 s
[s]
1 ÷99 m
[m]
1 ÷99 h
[h]
0.1 ÷9.9 s
[s]
0.1 ÷9.9 m
[m]
0.1 ÷9.9 h
[h]
TIMES RANGES: THREE (seconds, minutes and hours)
35
9045
53
58
Dimensions
PROGRAMMABLES PARAMETERS
7
6End of timing
5Time settings
4Number of timings
3
Working mode
The built-in battery allows timer to be programmed without connecting
to auxiliary voltage.
Hold down OK , and in less than 4 seconds, first push Iand then push II .
Release OK
1Start
Display
Flashing Display
Permanent
1L: de-energized "0"
CO: non cycle
C1: cycle
Non cycle mode (CO)
1, 2, 3, 4, 5, 6, 7, 8 or 9
Cycle mode (C1)
2, 4, 6 or 8
Digits
5.1
Left digit
Right digit
OK
II <4s
OK
OK OK
II
II
OK OK
II
II II II II
II II
OK
OK
I
I
OK
I
II
II
II
OK
II
OK OK
II
II
II
OK
NO
<4s
OFF
F1: without decimal point (x1)
F.1: with decimal point (x0,1)
Conversion factor
5.2
Unit
5.3
: seconds
: minutes
: hours
¿Last timing?
• NO: go to
• YES: display shows for 4s and then:
– Programmation with battery:
Its turns off.
– Programmation with auxiliary voltage:
The program starts.
2
Initial state of output relay
1H: energized "1"
16/26
18/28
15/25
5.1
I
5.1
II
I
I
II
5
Programmation
Programmation
7Command contact
With timer working. Timing does not stop.
I
3s3s
3s
II
- Programmed value per timing.
• Select the timing number.
II
II
II
OK
3,5s
3,5s
Nearly each 10s information about the number of timings in curse and the display time
unit appears for 2s.
• First digit:
seconds
minutes
hours
•Second digit: timing number.
1ª, 2ª, 3ª, ...
• Programmed time value.
• Time unit:
Seconds:
Minutes:
Hours:
Present timing time is showed.
2s
e.g.
[m] 2nd
At the end of programmation, select command contact mode.
Hold down OF for 10s.
The programmed mode is shows in 5s. The timer is supplied with cu (function
blocked).
OK
10s
5s
II
II
II
II
OK
The display shows during 4s and then:
– Programmation with battery:
Its turns off.
– Programmation with auxiliary voltage:
The program starts.
4s
10s
II
OFF
Review of the programmed settings
- The initial state of output relay is showed for 3s: 1Lor 1H
- The working cycle is showed for 3s: CO or C1
- The number of timings is showed for 3s.
• Non cycle mode CO.
1, 2, 3, 4, 5, 6, 7, 8 or 9
- Present timing time is showed.
• Cycle mode C1
2, 4, 6 or 8
Timing monitoring
16/26
18/28
15/25

Popular Timer manuals by other brands

Clas Ohlson EMT445 quick start guide

Clas Ohlson

Clas Ohlson EMT445 quick start guide

hager EGN200AU manual

hager

hager EGN200AU manual

WorkChoice WC1009 quick start guide

WorkChoice

WorkChoice WC1009 quick start guide

TFA 38.1039 instruction manual

TFA

TFA 38.1039 instruction manual

RainPoint TTV103WRF instruction manual

RainPoint

RainPoint TTV103WRF instruction manual

Toa TT-104B operating instructions

Toa

Toa TT-104B operating instructions

Orbit 57594-50 rB quick start guide

Orbit

Orbit 57594-50 rB quick start guide

Webasto 1531 operating instructions

Webasto

Webasto 1531 operating instructions

Vincent Associates UNIBLITZ VMM-T1 user manual

Vincent Associates

Vincent Associates UNIBLITZ VMM-T1 user manual

KingShield T106-C Installation/operating

KingShield

KingShield T106-C Installation/operating

Intermatic EI215 supplementary guide

Intermatic

Intermatic EI215 supplementary guide

Orbit 57096 user manual

Orbit

Orbit 57096 user manual

Sygonix 2589190 operating instructions

Sygonix

Sygonix 2589190 operating instructions

ADC ML-25V installation manual

ADC

ADC ML-25V installation manual

MULTISPAN MDT-4310 operating manual

MULTISPAN

MULTISPAN MDT-4310 operating manual

UPM DT420 owner's manual

UPM

UPM DT420 owner's manual

Omron H3RN manual

Omron

Omron H3RN manual

Emos 15FD/3A quick guide

Emos

Emos 15FD/3A quick guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.