FATEK P5043S User manual

R
Thank you for purchasing FATEK HMI. Before installing or operating the unit, please
read this installation guide carefully to ensure correct use.
1. Safety Precautions
(Read these precautions before use.)
1.1 General
Unpack and check the delivery for transportation damage. If any damage o
r
deformation is found, please notify the supplier.
The supplier is not responsible for the disassembled, altered or modified
device.
Never allow fluid or any conductive particles to enter into the HMI.
Otherwise, it may damage the HMI, cause fire or malfunction.
Only qualified personnel may install the HMI, perform maintenance and
inspection.
The liquid crystal inside the LCD panel is a hazardous substance. If the
panel is damaged, avoid contact with the leaked liquid crystal. If the liquid
crystal spills on clothing or skin, use soap and wash off thoroughly. In case
of eye contact the liquid, hold the eye open, flush with plenty water and get
medical attention as soon as possible.
Do not touch any terminals while the power is on. Otherwise, it may cause
injury due to electrical shock.
Disconnect the power supply before installing the HMI, do wiring operation,
perform maintenance or inspection. Otherwise, it may cause damage o
r
electrical shock.
1.2 Installation
The installation may be carried out by qualified personnel only.
Install the HMI according to the installation procedures.
Check the power source voltage is within the specified range and the
polarity is correct before connecting the HMI.
Keep signal and power supply cables away from high-voltage, large-current
carrying cables.
P5043S/N
HMI
Installation
Guide
1

Caution
Make sure the HMI is properly grounded to prevent electrical
shock, fire or malfunction.
HMI unit and other equipment should have the same
electrical
grounding
(reference voltage level),
otherwise
communication errors may occur.
1.3 Operation
Do not use sharp objects or excessive force to press the touch screen. This
may damage the touch screen. HMSP043 screen protector can be applied
to the HMI screen to protect it from damage, for ordering information, please
contact our sales department.
Do not use the output signal of the device as any safety function or system
emergency stop. It may result in personal injury or equipment damage if a
malfunction of the touch occurs.
1.4 Maintenance and Service
The agreed guarantee applies.
Only qualified personnel should make repairs and perform maintenance.
Disconnect the device from the power supply before carrying out cleaning or
maintenance.
Clean the front panel with a soft cloth and mild detergent.
Please use original replacement spare parts or accessories.
Recommended Prohibited
No Connected
DC24V
+
-
FG
DC24V
+
-
FG
HMI
unit Other
equipment
HMI
unit
Other
equipment
GOOD BAD
2

3
3
1
2
W
H
D
4
5678
2. Part Names and Dimensions
① Power Indicator Light
② Mounting Hole
③ Power Connector
④ COM2/COM3
Termination Switch
⑤ COM1/COM2/COM3:
DB-9 Male Connector
⑥ USB Connector
⑦ Mini USB Connector
⑧ Ethernet RJ45
Connector
(for N model)
W 128.0 mm
H 102.0 mm
D 38.1 mm

4
3. Specifications
Model P5043S P5043N
UL 61010-1
Technical
Consideraon
Type of item tested Control
Product Descripon Operator Panel
Connecons to mains
supply Permanent
Overvoltage category II
Polluon degree 2
Means of Protecon Class III
Environmental condions Operang Temp. 0~50°C
Storage Temp. -20 ~ 60°C
For use in wet locaons No
Equipment mobility Built in
Operang condions Connuous
Overall size 128.0 x 102.0 x 38.1 (mm)
Weight 215 (g) 235 (g)
Marked degree of
protecon
Front panel: IP65 / Rear Case: IP20 to IEC 60529
Type 1 to UL 50E
Equipment classificaon Industrial, Professional, Commercial
Equipment class Class III
Equipment type Permanently connected, Fixed
I/O Port
Serial 1
Connector: D-Sub 9-Pin
COM1: RS-232 (TXD, RXD)
COM2: RS-422/485
COM3: RS-485
Serial 2 ---
LAN --- 10M/100M
USB USB2.0 Type-A (Host)x1
USB2.0 Type mini-B (Device)x1
Micro SD ---
Audio ---
PLC Extension ---
Terminaon
Switch Yes (For RS-422/485)
Power
Power Input 24VDC±20%
Consumpon 350mA@24VDC
Insulaon 50MΩat 500VDC
Environment
Relave Humidity 10%~90%@ 40°C (non-condensing)
Withstand Voltage AC500V/20mA/1 Min. (between charger & FG terminals)
Vibraon
5 to 9Hz Half-amplitude: 3.5mm
9 to 150 Hz Constant acceleraon: 19.6m/s2 (2G)
3 direcons of X, Y, Z: 10mes (IEC61131-2 complaints)
Noise Suppression 1000Vp-p, width 1us, rising me 1ns
Grounding Resistance Below 100Ω
Dimension Cut-out 118.5 x 92.5 (mm)

4.
Unpacking
the Unit
FATEK HMI x1
Hook and Screw x4
A4 Double-sided Installation Guide x1
5.
Installation Procedures
Push the HMI
into the cutout
until the
waterproof ring
contacts the
plate.
Insert a hook into each mounting hole
on the HMI, and then tighten the
screws evenly with a moderate torque.
Failure to tighten the screws may
cause the HMI to fall, malfunction
or
short-circuit. Excessive tightening may
cause deformation.
The necessary
torque
is
about 0.16N·m.
5
Power Connector x1

6. Power Connection
Be sure to connect the ground FG
terminal to a class-3 ground (Ground
resistance should not exceed 100Ω).
Try to make the ground wire as short
as possible.
Use 28–12 AWG (0.5–1.5 mm
2
) wire
for the power connections.
7. Termination Switch
P5043S/N HMI has a built-in termination resistor switch.
To enable or disable the termination resistor please follow the configuration
shown in the table below. The termination switch is for COM2 [RS-422 /
RS-485] and COM3 [RS-485].
Configuration of Termination Resistor Switch.
Termination Resistor
No. COM2 [RS-422] COM2 [RS-485] COM3 [RS-485]
Enable Disable Enable Disable Enable Disable
1 ON OFF OFF OFF OFF OFF
2 ON OFF OFF OFF OFF OFF
3 ON OFF ON OFF OFF OFF
4 ON OFF ON OFF OFF OFF
5 OFF OFF OFF OFF ON OFF
6 OFF OFF OFF OFF ON OFF
6
DC24V
+
-
FG

8. Pin-out of COM Ports
7
DB-9 Male Connector
PIN# COM1
[RS-232] COM2
[RS-422] COM2
[RS-485] COM3
[RS-485]
1 NC*1 TX+ DATA+ NC
2 RX NC NC NC
3 TX NC NC NC
4 NC RX+ NC NC
5 GND GND GND GND
6 NC TX- DATA- NC
7 NC NC NC DATA+
8 NC NC NC DATA-
9 NC RX- NC NC
*1 NC: No Connection