FineTek EB5 Series User manual

08-EB5XXX-B1-EM, 03/10/2014
RF Admittance Level Transmitter
Operation Manual
Thank for buying FineTek's products. Please
read the user manual first before using it. It
is important to be familiar with product's
performance and function. Please keep the
user manual for operation reference.
EB5 Series
WORKING PRINCIPLE
OSC CPU Voltage
regulator
Signal
output
RF Admittance
Level Transmitter
Tank
Sensing probe
24VdcA10%
DESCRIPTION OF PANEL
PF & ACCURACY CHART
SPECIFICATION
18~30Vdc
4~20mA ( )2 wire
20mA
4mA
Option
A1%F.S. or 0.5pFA
-40BC~85BC
0~85% RH, non-condensing
<A0.2% F.S. per BC or 0.1pF per BC
-1999~9999
IP 65
20~2000pF
<(Vs-22)H50W Vs: Power Voltage (volt)
According to the specification of probe
Power supply
Measuring range
Output current
Upper limit
Lower limit
HART
Linearity
Load resistance
Environment
temperature
Operation
temperature
Environment
humidity
Temperature
coefficient
LCD Display
range
Protection degree
DESCRIPTION OF PANEL
DESCRIPTION OF PARAMETERS PROGRAM SETTING FLOW CHART
DESCRIPTION OF ALARM MODES
LCD display
"UP" button
"Shift" button
"Enter" button
Power supply
L
E
V
E
L
E
C
T
R
N
A
A
T
N
T
S
I
M
M
I
D
T
T
A
E
F
R
R
Display value
2sec
Error Message Correction
No Display
Display "-1"
Display "1"
Display "Over"
"SPAN" ,"WARN"Glisten
Display "NULL"
The output change rapidly
when level disturbance
The output change rapidly
when level is stable(<3%)
The output change rapidly
when level is stable(>3%)
The output is not porpotional
to the level
The LCD Display low point but the
display on the Panel at control
is not equal low point
The LCD Display but the
display on the Panel at control
is not equal high point
high point
Make sure the power supply 24V±10%
Recalibrate LOPT
Recalibrate HIPT
The capacitance is too much , please select plastic coating version,
or caused to short between probe and wall.
The output is latched , enter CTRL LACH to turn off this function
The output range is smaller than 20Pf, Adjust range to low level and recalibrate it
There is shortcut between probe and tank wall, please recheck the installation
Increase "DAMP"value
Set "FILT" to HI ,increase the frequence of filter
1. Enter manu"CAP" to check if the value change
2.When level remains , but the value change <1pF , please recalibrate HIPT &LOPT
3.When level remains, but the value change >1pF , please recheck the wiring.
Enter the manu to E_4, If the display at the control room > , decrease
E_4 value ;if the display at the control room< low point , increase E_4 value
low point
Enter the manu to E_20, If the display at the control room > , decrease
E_20 value ;if the display at the control room<high point, increase E_20 value
high point
Remark 1: Please refer to calibration procedure for HIPT & LOPT setting.
Remark 2:
Remark 3:
Remark 4:
The output is latched when display is up to 110% or -10%
Re-calibration is essential when the measuring range is revised.
When calibrating 4 .20mA, 0.24uA per step will be changed
when press up bottom once.
0~3
-1999~9999
-1999~9999
DOT1
100.0
0
100.0
0.0
ON, OFF
1~60sec
OFF
1
SAVE,RSET
BACK
SAVE,RSET
BACK
Lo,MID,HI
SAVE
SAVE
LO
-1999~9999
-1999~9999
0~9999
0~9999 400
0~9999 200
-1999~9999 0
-1999~9999 0
LO,MID,HI HI Measuring range remark 3.
Decimal point setting
20mA corresponding
display value
4mA corresponding
display value
Corresponding calibration value for
high point (Hipt). See remark 1
Corresponding Calibration Value for
low point (Lopt). See remark 1
Memory for max & mini value
during operation.SAVE:Save value
into Eeprom
REST:Clear present value and
memoryBACK:Go back to sub-menu
Output latch enable or disable.
See remark 2.
Software Filter
Display current capacitance value
High point Capacity Value
4mA micro setting value
20mA micro setting value
Default
Output updated time
Main
Menu
Sub-
Menu Range Default Description
1. Button Protection, requiring to press ENT+UP
buttons for 2 seconds in order to get into main menu.
2. Three input buttons; user-friendly.
3. Any two points for calibration
4. Retention for maximum and minimum values.
Low point Capacity Value
When the probe is surrounding by the air , little capacitance
(C ) is measured by the equivalent capacitor , the
A
capacitance increase gradually as computing media, the
max. capacitance (C ) will be measured while the tank is
B
full, the difference (dC)between C andC is proportional to
A B
the level.
=25 ~2000 pF)(Recommend range dC
"LACH" "1234"
Y:
Z:
Y:
Z:
G:
L:
H: J: K:
I:
G:
L:
H: J: K:
I:
B: C:
E:
A: F:
D:
B: C:
E:
A: F:
D:
Q:
R:
M: O: P:
N:
Q:
R:
M: O: P:
N:
V: W:
T: U:
S:
X:
V: W:
T: U:
S:
X:
Output
Try to calibrate at 0% & 100% , the accuracy is higher when the setting is closer to 0%&100%
CODE
(PF)
Accuracy(%)
500 1000 1500 2000 2500
0.0%0100
0.1%
0.2%
0.3%
0.4%
0.5%
0.6%
0.7%
0.8%
0.9%
1.0%
5.0%
LCD monitor: -20BC~85BC

+24V
EXC 24V
A Input
Signal GND
1
2
3
4
5
6
7
8
+24V
EXC 24V
A Input
Signal GND
1
2
3
4
5
6
7
8
[ Description of wiring ]
The Signal GND of panel meter should not be connected
with tank wall or the cover of the EB Transmitter, otherwise
the measurement will be incorrect.
(Diagram 1) Power supply
Panel meter Panel meter
Warning
CALIBRATION PROCEDURESSETTING FLOWCHART FOR EACH FUNCTION
Standard procedures:
1.SCH : Set the max display value corresponding to 20mA at SCH.
2.SCL : Set the min display value corresponding to 4mA at SCL.
3.HIPT : Input and save the corresponding value at HIPT, while the
medium is in high level.
4.LOPT: Input and save the corresponding value at LOPT, while the
medium in is in low level.
Completed Calibration
Example 1:
The lowest value sets at 0 and the output sets at 4mA.
The highest value sets at 100.0 and the output sets at 20mA
Calibration is done in empty and full tank.
Example 2:
The lowest value sets at 100.0 and the output sets at 4mA.
The highest value sets at 200.0 and the output sets at 20mA
It is calibrated at 10% of tank high and 90% of tank high. The 0%
of the total height of the tank is corresponded to 4mA, while the
100% of the total height of the tank is corresponded to 20mA.
Procedures of calibration for example 2
1. Input:
Dot=1, SCL=100.0,
SCH=200.0
(It can be adjusted anytime; Nothing is related with the status
of tank.)
2. To fill the medium till reaching to
the 10% height of the tank, go to
the LOPT setting and input the
value of 10.0 and then press
"ENT" "SAVE'' (Remark 2).
3. To fill the medium till reaching
to the 90% height of the tank,
go to HIPT setting and input
the value of 90.0 and then
press "ENT" "SAVE''
(Remark 3).
3. When the tank is full, go to
HIPT setting and input 100.0,
then press "ENT" "SAVE"
(remark 1).
Procedures of calibration for example 1
1.Input:
Dot=1, SCL=0.0
SCH=100.0,
(It can be adjusted anytime; Nothing is related with the status
of tank.)
2. When the tank is empty, go to
the LOPT setting and input 0.0,
then press "ENT" "SAVE"
(remark 1).
Lowest point
Highest
point
10%
90%
Remark 1: Under the setting for Hipt & Lopt, press "ENT" to show
(screen flashing)
Press "ENT" button to save the value and then press "UP" button
to escape the setting.
Remark 2: When Hipt or Lopt setting is over range, the LCD show
"Err", Please reset the value.
Compact Capacitance Level Transmitter is to press the three
( )
buttons UP, SHIFT, ENTER on display panel. Firstly, selecting
the setting menu then input value by using three buttons
showing below:
Selection
Escape button
Enter button
Swap button
Setting
Increment button
Position shift button
Confirmation button
Up button
SHIFT button
ENTER button
●Swap Button is for swapping
to different menus, such as
from main menu to main
menu or from sub menu to
sub menu.
Enter Button
●Confirmation button. After revising
the SCH value, press enter button
to save the revised value.
Flashing alternately
:Revise Parameters
:Save Parameters
1 342
1234
SHIFT Button
●Shift Button is for entering a
sub menu from main menu
or doing a position shifting
after entering sub menu.
●Position Shift Button. After entering
revision mode, press this button to
shift into revisable position.
Flashing alternately
(Digit flashing means
the value is revisable.)
1234
12 43
Flashing alternately
1234
1230
●Increment button. After entering
revise mode, press this button to
increase the revisable value.
For example, changing SCH
value from "1230" to "1234" is to
press this button fourth.
UP Button
●Up button is enable to escape
from revision mode or to
escape from sub menu to
main menu.
Display value
Setting
value
Setting
value
Setting
value
Setting
value
Setting
value
WIRING AND CAUTION
1. Please install a concentric circles
2. The rod or wire probe should be parallel to the tank wall. To
prevent material from sticking between the probe and tank
wall , the probe shouldn't be too close to the tank wall.
3. If the container is irregular-shaped, such as a cylindrical ,
and the medium is liquid with low viscosity, the rod should
be placed inside a concentric circles metal with
vent hole at the top.(Fig. 1)
4. Coating Probe type is necessary for conductive media (eg.
Water...) , as the bare electrode can't operation normally in
conductive media.
5. During the installation, the process connection should be
grounded. An installation without proper grounding will not
guarantee normal operation of the device later on.
6. For non-conductive medium of powder or granules in big
tank , the wire probe should be fixed to the bottom of tank
7. When all electrical connections inside of Admittance Level
Transmitter housing are finished, the housing cover and the
conduit opening should be sealed and tightened to prevent
moisture from soaking in.
8. If an agitator is in place (see fig. 3), a pipe shield outside the
probe is recommended.
metal pipe shield with vent
hole at the top outside the probe (Fig. 1)
pipe shield
INSTALLATION
(Fig. 1)
(Fig. 2)(Fig. 3)
100%100%
0%0%
Empty TankEmpty Tank Full TankFull Tank
4mA
20mA
1.Read installation notice before calibration.
2.It is recommended to have the media touched probe
bottom when users calibrate lowest value for empty tank.
3.Doring calibration, pribe should be put into the tank.
Don't calibrate the product outside the tank.
4.Please keep at least 50% distance between HIPT and LOPT
to ensure accuracy. It is recommended to calibrate with
empty and highest level in the tank.
2
2
2
2
2 Connect isolation cable with GND of power.
2 Connect tank with heater or cover of electric device to decrease
EMI.
After installation of the Compact Capacitance LevelTransmitter on
the top of tank, please make sure the cover of the transmitter is
contacted with tank perfectly. Please avoid the grounding of panel
meter to touch the tank wall.
While the panel meter is not supplied with a power supply, please
prepare a 24V power supply for use. The wiring for panel meter is
showing in diagram 1.
The max cable length is depends on the max resistance.
Maximum resistance is not to exceed (Vs-15)H50W to
ensure the accuracy of measurement.
Make sure to separate the signal cable with other big power
cables (such as pump, conveyer and solenoid valve)while wiring.
Before turning on power, make sure all wirings are correct.
Material Dielectric
Constant.
DIELECTRIC CONSTANTS CHART
Air 1
Rice
Cement
Grain
Corn
Heavy Oil
Diesel
Edible Oil
3~8
4~6
2.5~4.5
2.3~2.6
2.6~3.0
2.1
2~4
Water
Sulfuric Acid
Ethanol
Acetone
Carbide
Powder
Ammonia
Butanol
81
84
16~31
20~30
5.8~7.0
21
11
Gasoline 1.9
Material Dielectric
Constant.
Rod probe
Cable probe
Rod probe
Agitator
Vent hole
Isolate
supporter
Ceramic
isolator
wire probe
Tube
Tel 886-2-22696789
Email: [email protected] http://www.fine-tek.com
: Fax: 886-2-22686682
No.16, Tzuchiang St., Tucheng Industrial Park, New Taipei City 23678, Taiwan.
FineTek Co. , Ltd.
Other FineTek Transmitter manuals
Popular Transmitter manuals by other brands

Intercoax
Intercoax Ipify ECP-2704R-4T-PKG Quick install guide

Intelix
Intelix AvoCat AVO-V2A2-WP-F installation manual

RCA
RCA MI-8167-H instructions

Burkert
Burkert 8138 operating instructions

Greystone Energy Systems
Greystone Energy Systems HATDFL Series installation instructions

Evikon
Evikon PluraSens E2670-NO2 user manual