
17
NORDIC S4
7. Installing and adjusting the
kitchen fan
7.1. INSTALLATION
If an external kitchen fan is going to be used,
documentation regarding installation and adjustment
ofair ow rates is supplied with the fans.
7.1.1.Kitchen fan without motor
(connected to unit with duct connection)
The air handling unit has a separate connection point
for kitchen fans without a motor. An electric cable (low-
voltage) must be connected between the unit and the
fan in order to force the air ow in the hood via the
switch on the hood.
7.1.2.Kitchen fan with motor
(not connected to unit)
The kitchen fan with motor is not connected to the
unit. It has a completely separate duct system for air
evacuation.
With the kitchen fan it is possible to compensate
fortheamount of air drawn out of the house. See
chap.7.2. Adjusting for more information.
7.2. ADJUSTING
If the kitchen fan is not supplied by Flexit, the fan
supplier must plan air ow rates for extract air in the
hood, and arrange for supply air to the hood.
To reduce the risk of negative pressure in the home,
when using a kitchen fan with an air volume above
approx. 200m3/h is compensated for this with, for
example, an outdoor air valve in the wall.
7.2.1.Kitchen fan without motor
(connected tounit)
To reduce the risk of forced ventilation through the
cooker hood causing imbalance between extract air
and supply air, the ow should also be adjusted on the
“Cooker hood” setting on the fans. The ow between the
attachment and the cooker hood can be measured with
an air-ow meter.
The method for adjusting the fan force will vary,
depending on which control unit is used (NordicPanel or
the Flexit GO app). In this description the Flexit GO app
is used.
Procedure:
1. Choose the cooker hood setting with the damper
open and the “cooker hood” signal activated. Adjust
the extract force in the “cooker hood” position until
the ow over the cooker hood is 150-180m3/h, to
obtain odour capture of approx. 75%.
2. Then measure the ow from all air extractors and
add this ow to the ow over the cooker hood.
3. Measure and add up the ows on all supply air units.
Adjust the fan force in the “cooker hood” setting for
the supply air fan to the point where the ow is the
same for both fans.
7.2.2. Kitchen fan with motor
(not connected via duct to unit)
If a kitchen fan with a motor is used, the volume of air
extracted from the building increases. The air handling
unit can be adjusted to provide more supply air than
extract air to compensate for this.
A signal to the unit is required when the kitchen fan
isused:
Connect an external switch with potential-free ON/OFF
signal to the 3-core cable on the unit (DI2, see wiring
diagram).
Install the pressure relay (accessory).
The cooker hood function works as follows:
The supply air fan will speed up, while the extract air fan
will continue at a low level to partly compensate for the
air ow that the cooker hood extracts from the house.
Check the kitchen fan’s maximum capacity (based on the
capacity diagram on the kitchen fan).
Ensure that the kitchen fan receives sucient air via one
or more fresh air valves, for example.