FLORABEST F Series User manual

F133-P
DELIVERY / DISPENSE CONTROLLER
with pump start and valve control
Signal input flowmeter: pulse, Namur and coil.
Status inputs: start and stop.
Control outputs: two pump / valve control outputs.
Options: Intrinsically Safe, Modbus communication and backlight.
F-Series - Field mounted indicators for safe and hazardous areas.
More info: www.fluidwell.com/fseries

FW_F133-P_M_v0601_01_EN
Page 2

FW_F133-P_M_v0601_01_EN
Page 3
SAFETY INSTRUCTIONS
Any responsibility is lapsed if the instructions and procedures as described in this
manual are not followed.
LIFE SUPPORT APPLICATIONS: The F133-P is not designed for use in life support
appliances, devices, or systems where malfunction of the product can reasonably be
expected to result in a personal injury. Customers using or selling these products for
use in such applications do so at their own risk and agree to fully indemnify the
manufacturer and supplier for any damages resulting from such improper use or sale.
Electro static discharge does inflict irreparable damage to electronics! Before installing
or opening the unit, the installer has to discharge himself by touching a well-grounded
object.
This unit must be installed in accordance with the EMC guidelines (Electro Magnetic
Compatibility).
Do connect a proper grounding to the aluminum casing as indicated if the F133-P has
been supplied with the 115-230V AC power-supply type PM. The protective earth (PE)
wire between the back-casing and removable terminal-block shall never be removed.
Intrinsically Safe applications: follow the instructions as mentioned in Chapter 5 and
consult “Fluidwell F1..-..-XI - Documentation for Intrinsic Safety”.
DISPOSAL
At the end of its life this product should be disposed of according to local regulations regarding
waste electronic equipment. If a battery is present in this product it should be disposed of
separately. The separate collection and recycling of your waste equipment will help to conserve
natural resources and ensure that it is recycled in a manner that protects the environment.
SAFETY RULES AND PRECAUTIONARY MEASURES
The manufacturer accepts no responsibility whatsoever if the following safety rules and
precautions instructions and the procedures as described in this manual are not followed.
Modifications of the F133-P implemented without preceding written consent from the
manufacturer, will result in the immediate termination of product liability and warranty period.
Installation, use, maintenance and servicing of this equipment must be carried out by authorized
technicians.
Check the mains voltage and information on the manufacturer's plate before installing the unit.
Check all connections, settings and technical specifications of the various peripheral devices
with the F133-P supplied.
Open the casing only if all leads are free of potential.
Never touch the electronic components (ESD sensitivity).
Never expose the system to heavier conditions than allowed according to the casing
classification (see manufacture's plate and chapter 4.2.).
If the operator detects errors or dangers, or disagrees with the safety precautions taken, then
inform the owner or principal responsible.
The local labor and safety laws and regulations must be adhered to.

FW_F133-P_M_v0601_01_EN
Page 4
ABOUT THE OPERATION MANUAL
This operation manual is divided into two main sections:
The daily use of the unit is described in chapter 2 "Operation". These instructions are meant for
users.
The following chapters and appendices are exclusively meant for electricians/technicians. These
provide a detailed description of all software settings and hardware installation guidance.
This operation manual describes the standard unit as well as most of the options available. For
additional information, please contact your supplier.
A hazardous situation may occur if the F133-P is not used for the purpose it was designed for
or is used incorrectly. Please carefully note the information in this operating manual
indicated by the pictograms:
A "warning" indicates actions or procedures which, if not performed correctly, may lead to
personal injury, a safety hazard or damage of the F133-P or connected instruments.
A "caution" indicates actions or procedures which, if not performed correctly, may lead to
personal injury or incorrect functioning of the F133-P or connected instruments.
A "note" indicates actions or procedures which, if not performed correctly, may indirectly
affect operation or may lead to an instrument response which is not planned.
Hardware Version: 1b03.01.03
Software Version: 03.03.01
Manual : FW_F133-P_M_v0601_01_EN
© Copyright 2016 Fluidwell B.V. - The Netherlands.
Information in this manual is subject to change without prior notice. The
manufacturer is not responsible for mistakes in this material or for incidental
damage caused as a direct or indirect result of the delivery, performance or
use of this material.
© All rights reserved. No parts of this publication may be reproduced or used
in any form or by any means without written permission of your supplier.

FW_F133-P_M_v0601_01_EN
Page 5
CONTENTS MANUAL
Safety instructions.................................................................................................................................3
Disposal 3
Safety rules and precautionary measures.............................................................................................3
About the operation manual..................................................................................................................4
Contents manual...................................................................................................................................5
1. Introduction.......................................................................................................................6
2. Operational .......................................................................................................................7
3. Configuration...................................................................................................................11
4. Installation.......................................................................................................................19
5. Intrinsically safe applications ..........................................................................................31
6. Maintenance ...................................................................................................................37
Appendix A: Technical specification....................................................................................................38
Appendix B: Problem solving ..............................................................................................................41
Appendix C: Communication variables ...............................................................................................42
APPENDIX D: Declaration of Conformity............................................................................................46
Index of this manual............................................................................................................................47

FW_F133-P_M_v0601_01_EN
Page 6
1. INTRODUCTION
1.1. SYSTEM DESCRIPTION OF THE F133-P
Functions and features
The delivery controller / dispenser model F133-P is a microprocessor driven instrument designed for
the delivery of unknown quantities as well as displaying the flowrate, delivered total and delivered
accumulated total.
This product has been designed with a focus on:
ultra-low power consumption to allow long-life battery powered applications (type PB / PC),
intrinsic safety for use in hazardous applications (type XI),
several mounting possibilities with aluminum or GRP enclosures for harsh industrial
surroundings,
ability to process all types of flowmeter signals,
transmitting possibilities with communication (option) outputs.
Flowmeter input
This manual describes the unit with a pulse type input from the flowmeter "-P version". Other
versions are available to process (0)4-20mA or 0-10V flowmeter signals.
One flowmeter with a passive or active pulse, Namur or sine wave (coil) signal output can be
connected to the F133-P. To power the sensor, several options are available.
Standard outputs
Two transistor or relay (option) outputs: to control a pump and a valve. All kind of switch
conditions can be set to optimize the process control.
Fig. 1: Typical application for the F133-P.
Overview typical application F133
external START or
CONTINOUS signal
RS232 / RS485 / TTL
Modbus communication (option)
external PAUSE / STOP

FW_F133-P_M_v0601_01_EN
Page 7
Configuration of the unit
The F133-P was designed to be implemented in many types of applications. For that reason, a
SETUP-level is available to configure your F133-P according to your specific requirements.
SETUP includes several important features, such as K-factors, measurement units, signal selection
etc. All settings are stored in EEPROM memory and will not be lost in the event of power failure or a
drained battery.
To extend the battery-life time (option), please make use of the power-management functions as
described in chapter 3.2.3.
Display information
The unit has a large LCD to show the process data, the alarms and the setup menu.
A backup of the total and accumulated total in EEPROM memory is made every minute.
Options
The following options are available: Modbus communication RS232/485 (also battery powered),
intrinsic safety, mechanical relay or active outputs, power- and sensor-supply options, panel-mount,
wall-mount and weather-proof enclosures, flame proof enclosure and LED backlight.
2. OPERATIONAL
2.1. GENERAL
The F133-P may only be operated by personnel who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Take careful notice of the " Safety rules, instructions and precautionary measures " at
the beginning of this manual.
This chapter describes the daily use of the F133-P. This instruction is meant for users / operators.
2.2. CONTROL PANEL
The following keys are available:
Fig. 2: Control Panel.
Functions of the keys
This key is used to program and save new values or settings.
It is also used to gain access to SETUP-level; please read chapter 3.
This key is used to START the dispense process.
The arrow-key is used to increase a value after PROG has been pressed or
to configure the F133-P; please read chapter 3.
Press STOP to interrupt or cancel the delivery (function depends on
configuration of the unit).
STOP is also used to select batch total, batch counter, total and accumulated
total.
The arrow-key is used to select a digit after PROG has been pressed or to
configure the F133-P; please read chapter 3.

FW_F133-P_M_v0601_01_EN
Page 8
2.3. OPERATOR INFORMATION AND FUNCTIONS
In general, the F133-P will always function at Operator level. The information displayed is dependent
upon the SETUP-settings. All pulses generated by the connected flowmeter are measured by the
F133-P in the background, whichever screen refresh rate setting is chosen. After pressing a key, the
display will be updated very quickly during a 30 second period, after which it will slow-down again.
Start-up the delivery
You only can start-up when the "READY" indicator is shown on the display. When "READY" is
shown, the data of the last delivery is shown. When you press the "START" key, the F133-P initiates
a new delivery, the "RUN" indicator comes on and temporarily the total shows "8888888" and the
flow rate "88888". Depending on the setup of the F133-P, relays are switched to start the pump(s)
and to open the valve(s). In the software, a timer is started to monitor the flow rate.
When a flow is detected, the delivery will start and the total and the flow rate show the actual status.
When the flow rate is not sufficient, the delivery will not start and the Alarm indicator comes on, the
total shows "0000000" and the flow rate shows "not started". The startup sequence is stopped.
Fig. 3: Display information during start-up.
Fig. 4: Display information during delivery.
Interrupt the delivery
After the startup sequence is completed, the dispense sequence becomes active. During the
dispense sequence you can interrupt the delivery temporarily with the STOP command. The
"PAUSE" indicator comes on and an internal restart timer is started. Note that the pump stays on
and the valve is closed. The delivery is continued when the restart timer still active and the START
command is given. When the restart timer is lapsed, the delivery is stopped automatically.
Fig. 5: Display information during pause.
Selecting total, accumulated total and batch-counter
When "READY" is displayed, following functions are available:
Batch-total
To display the batch-total, use the STOP button. This quantity equals the accumulated
delivered quantity (from the START moment till the READY moment) and cannot be initialized
by the operator. It will count up to 9999999.
Press STOP a few times to return to the main display information.
Batch-counter
To display the batch-counter, press STOP again. This counter displays the number of
deliveries that have been made successfully and cannot be initialized by the operator.
It will count up to 9999999.
Press STOP a few times to return to the main display information.
RUN
PAUSE
RUN

FW_F133-P_M_v0601_01_EN
Page 9
Display Total and accumulated Total
Press STOP to display the Total and Accumulated Total. These totalizers do count the
flowmeters signal continuously, even when no process is running.
The value for Total can be initialized. To do so, be sure Total is displayed.
First press PROG followed by STOP. After pressing PROG, the text "PUSH STOP" is
displayed. To avoid initialization in that stage, press a different key or wait for 20 seconds.
Initialization of Total DOES NOT influence accumulated Total.
Accumulated Total can never be initialized. This value will count up to 99999999999.
Press STOP a few times to return to the main display information.
Alarms
The following alarms can occur:
Flowrate alarm:
When the actual flowrate is outside the allowed range (as set in the setup menu), the delivery
will be paused automatically and an alarm message will be displayed indicating the type of
flow rate alarm: "LO RATE" or "HI RATE". If pause is enabled, the delivery can be restarted.
Maximum batch:
When the total quantity delivered exceeds a certain quantity, the F133-P will switch-off all
relays and generate an "MAX BATCH" alarm.
If pause is enabled, the delivery can be restarted.
Low-battery alarm
When the battery voltage becomes too low, the battery indicator comes on. When the battery
indicator is on, as soon as possible, install a fresh and new battery as detailed in the chapter
maintenance.
Fig. 6: Example of low-battery alarm.
Alarm
When "alarm" is displayed, please consult Appendix B: Problem Solving.
RUN
LOW BATTERY

FW_F133-P_M_v0601_01_EN
Page 10
2.4. DISPENSER FUNCTIONAL DIAGRAM
The function of the F133-P depends on the different settings in the setup menu. The example is
given for a typical configuration.
START THE DELIVERY
PAUSE / STOP THE DELIVERY (pause is enabled)
STOP THE DELIVERY (overrun timer is set)
LEGEND:
I: Idle, waits for new delivery.
A: Start, the START key is pushed to start a new delivery, the F133-P will reset itself.
B: Delay, time for the pump to start up.
C: Begin, pump is at delivery speed.
D: Startup, valve opens to build up the flow, flow detection is active.
E: Started, flow is present at required rate.
F: Not started, there is no flow or the flow is not sufficient, the valve closes and the display shows
NOT STARTED.
Pump, stopped
Timer, predefined by software
Pump, running
61
Timer, set by setup menu CONTROL
Valve, closed
Flow OK, restart timer active
Valve, open
Flow NOK, restart timer elapsed
Reset, predefined by software

FW_F133-P_M_v0601_01_EN
Page 11
3. CONFIGURATION
3.1. INTRODUCTION
This and the following chapters are exclusively meant for electricians and non-operators. In these,
an extensive description of all software settings and hardware connections are provided.
Mounting, electrical installation, start-up and maintenance of the instrument may only
be carried out by trained personnel authorized by the operator of the facility. Personnel
must read and understand this Operating Manual before carrying out its instructions.
The F133-P may only be operated by personnel who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Ensure that the measuring system is correctly wired up according to the wiring
diagrams. The housing may only be opened by trained personnel.
Take careful notice of the " Safety rules, instructions and precautionary measures " at
the beginning of this manual.
3.2. PROGRAMMING SETUP-LEVEL
When a dispense session is active, it is not possible to enter the setup menu.
3.2.1. GENERAL
Configuration of the F133-P is done at SETUP-level. SETUP-level is reached by pressing the
PROG/ENTER key for 7 seconds; at which time, both arrows will be displayed. In order to return
to the operator level, PROG will have to be pressed for three seconds. Alternatively, if no keys are
pressed for 2 minutes, the unit will exit SETUP automatically.
SETUP can be reached at all times while the F133-P remains fully operational.
A Password may be required to enter SETUP. Without this Password access to SETUP is denied.
Matrix structure SETUP-level:
Each function has a unique number, which is displayed below the word "SETUP" at the
bottom of the display. The number is a combination of two figures. The first figure
indicates the function-group and the second figure the sub-function.
Additionally, each function is expressed with a keyword. After selecting a sub-function,
the next main function is selected by scrolling through all "active" sub-functions
(e.g. 1, 11, 12, 13, 14, 1, 2, 3, 31 etc.).

FW_F133-P_M_v0601_01_EN
Page 12
To enter the SETUP-level
Selection of function-group and function
Press the PROG/ENTER
key for 7 seconds.
Select the function group
with the STOP/key.
Select the function with the
START/key.
To change or select a value
Momentarily, press the PROG/ENTER key.
The program indicator starts to flash.
Select or enter a value with the START/key and/or
the STOP/key.
Press the PROG/ENTER key to confirm the value/selection.
To change a value, use to select the digits and to increase that value.
To select a setting, both and can be used.
If the new value is invalid, the increase signor decrease-signwill be displayed while you are
programming.
When data is altered but ENTER is not pressed, then the alteration can still be cancelled by waiting
for 20 seconds or by pressing ENTER for three seconds: the PROG-procedure will be left
automatically and the former value reinstated.
Note: alterations will only be set after ENTER has been pressed!
To return to OPERATOR-level:
Press the PROG/ENTER key for 3 seconds.
In order to return to the operator level, PROG will have to be pressed for three seconds. Also, when
no keys are pressed for 2 minutes, SETUP will be left automatically.

FW_F133-P_M_v0601_01_EN
Page 13
3.2.3. OVERVIEW FUNCTIONS SETUP LEVEL
SETUP FUNCTIONS AND VARIABLES
1
TOTAL
11
UNIT
L - m3 - kg - lb - GAL - USGAL - bbl - no unit
12
DECIMALS
0000000; 111111.1; 22222.22; 3333.333
13
K-FACTOR:
0.000010 - 9999999
14
DECIMALS K-FACTOR
0 - 6
15
BATCH MAX
0 - 9999999
16
BATCH TOTAL
0.001 - 9999999 unit
17
BATCH COUNT
0 - 9999999 batches
2
FLOWRATE
21
UNIT
mL - L - m3 - mg - g - kg - ton - GAL - bbl - lb - cf - REV -
no unit - scf - Nm3 - NL - P
22
TIME UNIT
sec - min - hour - day
23
DECIMALS
0000000; 111111.1; 22222.22; 3333.333
24
K-FACTOR
0.000010 - 9999999
25
DECIMALS K-FACTOR
0 - 6
26
CALCULATION
per 1 - 255 pulses
27
CUT-OFF
0.1 - 999.9 seconds
28
LOW FLOWRATE ALARM
0.001 - 9999999 unit / time unit
29
HIGH FLOWRATE ALARM
0.001 - 9999999 unit / time unit
2A
DELAY TIME ALARM
0.0 - 999.9 seconds
3
DISPLAY
31
LIGHT
0% (off); 20%; 40%; 60%; 80%; 100% (full)
32
BL ALARM
off; on. flash
4
POWER MANAGEMENT
41
LCD NEW
fast - 1 sec - 3 sec - 15 sec - 30 sec - off
42
BATTERY MODE
operate - shelf
5
FLOWMETER
51
SIGNAL
npn - npn_lp - reed - reed_lp - pnp - pnp_lp - namur -
coil_hi - coil_lo - act_8.2 - act_12 - act_24
6
CONTROL
61
DELAY time
0.1 - 999.9 seconds
62
BEGIN time
0.1 - 999.9 seconds
63
START-UP time
0.1 - 999.9 seconds
64
NO PULSE time
0.1 - 999.9 seconds
65
PAUSE
disable - enable
66
RESTART time
0.1 - 999.9 seconds
67
OVERRUN time
0.1 - 999.9 seconds
7
STATUS
71
STATUS 1
start - stop - continues - off
72
STATUS 2
stop - pause - both - off
8
COM MODB
81
SPEED
1200 - 2400 - 4800 - 9600
82
ADDRESS
1 - 255
83
MODE
ASCII - rtu - off
84
DATABITS
7 bits; 8 bits
85
PARITY
Odd; even; none
86
COMM. LOCK
disable - time-out - full
9
OTHERS
91
MODEL
F133-P
92
SOFTWARE VERSION
03.xx.xx
93
SERIAL NR.
xxxxxxx
94
PASSWORD
0000 - 9999
95
TAG-NR
0000000 - 9999999

FW_F133-P_M_v0601_01_EN
Page 14
3.2.4. EXPLANATION OF SETUP-FUNCTIONS
1 - TOTAL
UNIT
11
This setting gives the measurement unit for the indication of the batch
total and the accumulated batch total. The following units can be selected:
L - m3 - kg - lb. - GAL - USGAL - bbl –no unit.
When you change the measurement unit, you must recalculate and
enter the K-factor for the (accumulated) total. When you recalculate
and enter the new K-Factor, the history for (accumulated) total is not
correct anymore, because the (accumulated) total is not
recalculated. For future reference, best practice is to make a note of
the accumulated total before you enter the recalculated K-Factor.
DECIMALS
12
This setting sets, for the (accumulated) total indication, the amount of
digits behind the decimal pointer.
The following can be selected:
0000000 - 111111.1 - 22222.22 - 3333.333
K-FACTOR
13
With the K-factor, the flowmeter pulse signals are converted to a quantity.
The K-factor is based on the number of pulses generated by the
flowmeter per selected measurement unit (SETUP 11), for example per
cubic meter. The more accurate the K-factor, the more accurate the
functioning of the system will be.
Example 1: Calculating the K-factor.
Assume that the flowmeter generates 2.4813 pulses per liter
and the selected unit is “cubic meters / m3”. A cubic meter
consists of 1000 parts of one liter which implies 2,481.3 pulses
per m3. So, the K-factor is 2,481.3. Enter for SETUP - 13:
“2481300” and for SETUP - 14 - decimals K-factor “3”.
Example 2: Calculating the K-factor.
Assume that the flowmeter generates 6.5231 pulses per gallon
and the selected measurement unit is gallons.
So, the K-Factor is 6.5231. Enter for SETUP - 13: “6523100”
and for SETUP - 14 decimals K-factor “6”.
When you recalculate and enter a new K-Factor, the history for
(accumulated) total is not correct anymore, because the
(accumulated) total is not recalculated. For future reference, best
practice is to make a note of the accumulated total before you enter
the recalculated K-Factor.
DECIMALS K-FACTOR
14
This setting sets, for the K-factor, the amount of digits behind the decimal
pointer. The following can be selected:
0 - 1 - 2 - 3 - 4 - 5 - 6
Please note that this setting influences the accuracy of the K-factor
indirectly. (i.e. the position of the decimal point and thus the value given)
This setting has NO influence on the displayed number of digits for total
(SETUP 12)!
BATCH MAXIMUM
15
With this setting you can set the batch maximum.
BATCH TOTAL
16
Batch total - also displayed at operator level - displays the accumulated
quantity of product being delivered. From here, this total can be
programmed to zero or to any desired quantity.
BATCH COUNTER
17
Batch count - also displayed at operator level - displays the number of
deliveries executed. From here, this total can be reset to zero or being
programmed to any desired quantity

FW_F133-P_M_v0601_01_EN
Page 15
2 - FLOWRATE
The settings for preset and flowrate are entirely separate. In this way, different units of measurement
can be used for each e.g. cubic meters for total and liters for flowrate.
The display update time for flowrate is one second or more.
UNIT
21
SETUP - 21 determines the measurement unit for flowrate.
The following units can be selected:
mL - L - m3 - mg - g - kg - ton - GAL - bbl - lb - cf - REV - no unit -
scf - Nm3 - NL - P
When you change the measurement unit, you must recalculate and
enter the K-factor for the flowrate.
TIME
22
The flowrate can be calculated per second (SEC), minute (MIN), hour
(HR) or day (DAY).
DECIMALS
23
This setting determines for flowrate the number of digits following the
decimal point. The following can be selected:
00000 - 1111.1 - 2222.22 - 3333.333
K-FACTOR
24
With the K-factor, the flowmeter pulse signals are converted to a flowrate.
The K-factor is based on the number of pulses generated by the
flowmeter per selected measurement unit (SETUP 21), for example per
liter. The more accurate the K-factor, the more accurate the functioning of
the system will be. For examples read SETUP 13.
DECIMALS K-FACTOR
25
This setting determines the number of decimals for the K-factor
(SETUP 24). The following can be selected:
0 - 1 - 2 - 3 - 4 - 5 - 6
Please note that this SETUP - influences the accuracy of the K-factor
indirectly.
This setting has NO influence on the displayed number of decimals for
“flowrate” (SETUP 23)!
CALCULATION
26
The flowrate is calculated by counting the number of pulses within a
certain time, for example 1 second. The longer the time the more accurate
the flowrate will be. The maximum value is 999.9 seconds.
This setting does influence the update time for the analog output
directly (maximum update 10 times a second). If the output response is
too slow, decrease the number of pulses.
The shorter the time, the higher the power consumption of the unit will
be (important for battery powered applications).
CUT-OFF TIME
27
With this setting, you determine a minimum flow requirement thresh-hold,
if during this time less than XXX-pulses (SETUP 26) are generated, the
flowrate will be displayed as zero.
The cut-off time has to be entered in seconds - maximum time is 999
seconds (about 15 minutes).
LOW FLOWRATE
ALARM
28
The minimum allowed flowrate is determined with this setting.
The measuring units are according setup 21-23.
An alarm will be generated as long as the actual rate is under this value.
With value 0.0 the function is disabled.
HIGH FLOWRATE
ALARM
29
The maximum allowed flowrate is determined with this setting.
The measuring units are according setup 21-23.
An alarm will be generated as long as the actual rate is above this value.
With value 0.0 the function is disabled.
DELAY TIME ALARM
2A
An alarm generated by setting 28-29 can be ignored during X-time.
Is the actual flowrate still incorrect after this delay time, then an alarm will
be generated.

FW_F133-P_M_v0601_01_EN
Page 16
3 - DISPLAY
LIGHT
41
The brightness of the backlight can be set in following range:
0% (OFF) –20% - 40% - 60% - 80% - 100% (FULL BRIGHTNESS).
BL ALARM
42
This function determines the behavior of the backlight (BL) during an alarm.
The following can be selected:
OFF: during a flowrate alarm, the backlight does not change;
ON: during a flowrate alarm, the backlight comes on red;
FLASH: during a flowrate alarm, the backlight blinks red;.
4 - POWER MANAGEMENT
When used with the internal battery option, the user can expect reliable measurement over a long
period of time. The F133-P has several smart power management functions to extend the battery life
time significantly. Two of these functions can be set:
LCD NEW
41
The calculation of the display-information influences the power
consumption significantly. When the application does not require a fast
display update, it is strongly advised to select a slow refresh rate.
Please understand that NO information will be lost; every pulse will be
counted and the output signals will be generated in the normal way.
The following can be selected:
Fast - 1 sec - 3 sec - 15 sec - 30 sec - off.
Example 3: Battery life-time
battery life-time with a coil pick-up, 1KHz. pulses and FAST
update: about 2 years.
battery life-time with a coil pick-up, 1KHz. pulses and 1 sec
update: about 5 years.
Note: after a button has been pressed by the operator - the display
refresh rate will always switch to FAST for 30 seconds. When “OFF” is
selected, the display will be switched off after 30 seconds and will be
switched on as soon as a button has been pressed.
BATTERY-MODE
42
The unit has two modes: operational or shelf.
After “shelf” has been selected, the unit can be stored for several years; it
will not count pulses, the display is switched off but all settings and totals
are stored. In this mode, power consumption is extremely low.
To wake up the unit again, press the SELECT-key twice.
5 - FLOWMETER
SIGNAL
51
The F133-P is able to handle several types of input signal. The type of
flowmeter pickup / signal is selected with SETUP 51.
Note: The selections “active pulse” offer a detection level of 50% of the
supply voltage.
Read also par. 4.4.3. Flowmeter input terminal 09-11.
TYPE OF SIGNAL
EXPLANATION
RESISTANCE
FREQ./MV
REMARK
NPN
NPN input
100K
pull-up
6 kHz.
(open collector)
NPN - LP
NPN input
with low pass filter
100K
pull-up
2.2 kHz.
(open collector)
less sensitive
REED
Reed-switch input
1M
pull-up
1.2 kHz.
REED - LP
Reed-switch input
with low pass filter
1M
pull-up
120 Hz.
Less sensitive
PNP
PNP input
100K
pull-down
6 kHz.
PNP - LP
PNP input
with low pass filter
100K
pull-down
700 Hz.
Less sensitive

FW_F133-P_M_v0601_01_EN
Page 17
NAMUR
Namur input
820 Ohm
pull-down
4 kHz.
External power
required
COIL HI
High sensitive coil input
-
20mV
p.t.p.
Sensitive for
disturbance!
COIL LO
Low sensitive coil input
-
90mV
p.t.p.
Normal sensitivity
ACT_8.2
Active pulse input
8.2 VDC
4K
10KHz.
External power
required
ACT_12
Active pulse input
12 VDC
4K
10KHz.
External power
required
ACT_24
Active pulse input
24 VDC
3K
10KHz.
External power
required
6 - CONTROL
Two open-collector outputs (Optional: mechanic relays or active outputs) are available to control
relays or small valves (max. 50VDC –300mA).
It is advised to use relay one for pump-start and relay two for the valve control.
DELAY TIME
61
This is the time between the moment of a start-signal and the moment before
relay 2 will be switched on. In the mean time, relay 1 will be switched to
control e.g. a pump. With time 0.0 seconds, this function is disabled.
BEGIN TIME
62
After the delay-time (51), relay 2 will be switched-on as well. and the
“begin-time” becomes valid.
The unit has to receive about twice the number of pulses as programmed
with setting 26, before “start-up time” (setup 63) becomes valid.
If not enough pulses have been received within this time, the delivery will
be cancelled. With time 0.0 seconds, this function is disabled.
START-UP TIME
63
Now, the start-up time allows the system to become operational without
having a low-flowrate alarm. After this time, the system will become full
operational. With time 0.0 seconds, this function is disabled.
NO PULSE TIME
64
As soon as the unit is full operational, the flow can be monitored.
The F133-P will switch-off relay 1 and 2 (or relay 2 only: see setting
65/66) as soon as during X-seconds no pulses have been received from
the flowmeter. In most cases, this is “end of process” (see 65).
With time 0.0 seconds, this function is disabled.
PAUSE
65
With this function, a “pause-function” can be enabled: if during the
process “stop” will be pressed, or the process is interrupted for another
reason like “no pulse time”, “flowrate alarm” or with the “status input”, the
batch will be stopped but can be resumed. If the unit comes in “PAUSE”,
relay 2 will be switched-off but relay 1 (pump control) remains energized.
Applications where this function is useful is delivery of sub-batches for
example where you want to have one “overall” total.
RESTART TIME
66
Following setup 65, the F133-P allows the Operator to restart a delivery
within X-seconds. If this does not happen within this time, the delivery will
be finished completely. With time 0.0 seconds, this function is disabled.
OVERRUN TIME
67
As soon as a delivery has been finished, the relays will be switched-off
but there may still be some flow till the valve is closed.
During this “overrun-time” all pulses will be counted as being part of the
delivery. We advise to program a time of one second or a couple of
seconds, depending on the response time of your system to close the
valve. With time 0.0 seconds, this function is disabled.
7 - STATUS
For external control of the F133-P, the unit can be started and/or stopped with two external switches.
STATUS INPUT 1
71
Following functions can be selected:
OFF: status input is disabled.
START-function: do generate a short pulse to start a delivery.
STOP-function: do generate a short pulse to stop the delivery.
CONTINUOUSLY: do switch the input continuously to execute a delivery;
first “disconnect” when the delivery is READY.
When it is interrupted during the batch, the unit goes
always to “READY”. To start-up a new batch, the input

FW_F133-P_M_v0601_01_EN
Page 18
must be interrupted for at least 100msec. in-between
deliveries
STATUS INPUT 2
72
Following functions can be selected:
OFF: status input is disabled.
PAUSE-function: do generate a short pulse to pause the delivery.
STOP-function: do generate a short pulse to stop the delivery.
BOTH-function: do generate a short pulse to pause the delivery.
One more pulse will stop the delivery.
8 - COMMUNICATION (OPTIONAL)
The functions described below deal with hardware that is not part of the standard delivery.
Programming of these functions does not have any effect if this hardware has not been installed.
Consult Appendix C for a detailed explanation.
SPEED
81
For external control, the following communication speeds can be selected:
1200 –2400 –4800 –9600 –9600HP –19200 –38400
ADDRESS
82
For communication purposes, a unique identity can be attributed to every F133-P.
This address can vary from 001-247.
MODE
83
The communication protocol is Modbus ASCII or RTU mode. Select OFF, to
disable this communication function.
DATABITS
84
This setting determines for communication the number of databits.
Select 8 bit for BUS-RTU and 7 bits for BUS-ASC.
PARITY
85
As demanded by the connected equipment, select a parity bit (odd, even or none).
COMM. LOCK
86
With this setting, you determine if the unit will be locked after a delivery
till the unit will be released through communication (read appendix C
value 157 (9Dh).
Following can be selected:
disable: function is disabled
time-out: the unit will be locked for 10 minutes or till communication
release. If nothing happens within 10 minutes, the unit will
release itself automatically.
full: the unit can only be released through communication. When
the delivery is waiting to be released, the display will show
‘FINISHING’. Note that all keys and external controls are
disabled during this time.
When you select this option you can ONLY release the unit to normal
operation after each delivery through communications. If you accidentally
lock yourself out, please remove all power (including the battery) so the unit
will restart. You can then enter the setup-level to change this setting.
9 - OTHERS
MODEL
91
For support and maintenance it is important to have information about the
characteristics of the F133-P. Your supplier will ask for this information in
the case of a serious breakdown or to assess the suitability of your model
for upgrade considerations.
SOFTWARE VERSION
92
For support and maintenance it is important to have information about the
characteristics of the F133-P. Your supplier will ask for this information in
the case of a serious breakdown or to assess the suitability of your model
for upgrade considerations.
SERIAL NR
93
For support and maintenance it is important to have information about the
characteristics of the F133-P. Your supplier will ask for this information in
the case of a serious breakdown or to assess the suitability of your model
for upgrade considerations.
PASSWORD
94
All SETUP-values can be Password protected.
This protection is disabled with value 0000 (zero).
Up to and including 4 digits can be programmed, for example 1234.
TAG-NR
95
For identification of the unit and communication purposes, a unique tag
number of maximum 7 digits can be entered.

FW_F133-P_M_v0601_01_EN
Page 19
4. INSTALLATION
4.1. GENERAL DIRECTIONS
Mounting, electrical installation, start-up and maintenance of this instrument may only be carried
out by trained personnel authorized by the operator of the facility. Personnel must read and
understand this Operating Manual before carrying out its instructions.
The F133-P may only be operated by personnel who are authorized and trained by the operator
of the facility. All instructions in this manual are to be observed.
Ensure that the measuring system is correctly wired up according to the wiring diagrams.
Protection against accidental contact is no longer assured when the housing cover is removed
or the panel cabinet has been opened (danger from electrical shock). The housing may only be
opened by trained personnel.
Take careful notice of the " Safety rules, instructions and precautionary measures " at the front
of this manual.
4.2. INSTALLATION / SURROUNDING CONDITIONS
Take the relevant IP classification of the casing into account (see manufactures plate). Even an IP67
Type 4(X) casing should NEVER be exposed to strongly varying (weather) conditions.
When panel-mounted, the unit is IP65 Type 4(X)!
When used in very cold surroundings or varying climatic conditions, take the necessary precautions
against moisture by placing a dry sachet of silica gel, for example, inside the instrument case.
Mount the F133-P on a solid structure to avoid vibrations.

FW_F133-P_M_v0601_01_EN
Page 20
4.3. DIMENSIONS- ENCLOSURE
Aluminum enclosures:
Fig. 7: Dimensions aluminum enclosures.
75 mm (2.95")
130 mm (5.12") 112 mm (4.40")
120mm(4.72”)
M20 x 1,5
PG9 PG9
30mm 30mm
M20 x 1,5
M16 x 1,5 M16 x 1,5
30mm 30mm
M20 x 1,5
M20 x 1,5 M20 x 1,5
25mm 25mm
1/2"NPT
0.9”
3x 1/2"NPT
0.12" 0.12"
HA
HM
HN
HO
HP
HT
HU
6 x M12
12mm 12mm
24mm24mm
36mm
36mm
14mm17mm
115 mm (4.53”)
HB
29.1 mm (1.15”)
31 mm
(1.22”)
HZ
4x M20 x 1,5
15 15
HV
2323
16
mm
1/2"NPT 1/2"NPT
25mm 25mm
22,5mm
HL
22,5mm22,5mm22,5mm22,5mm
0.9”
15
60mm(2.36”)
98mm(3.86”)
This manual suits for next models
1
Table of contents
Popular Controllers manuals by other brands

Rosslare
Rosslare AC-225? AC-225IP? AC-225U Installation and user guide

Daikin
Daikin EHS157034 operating instructions

Rockwell Automation
Rockwell Automation Allen-Bradley AADvance T9110 Solutions handbook

Lunos
Lunos 5/UNI-FR installation manual

LinTronic
LinTronic RELAY 208 manual

marklin
marklin Central Station 3 manual