GFA TS 959 User manual

Installation instructions
Door control
TS 959
Hold-to-run control
Version: 51171547
0000000 0000 51171547 XXXXX
– en
–
Status: j / 01.2020

2
GfA ELEKTROMATEN GmbH & Co. KG
Wiesenstraße 81 • 40549 Düsseldorf
www.gfa-elektromaten.de

3
Contents
1General safety information .............................................................................................. 5
2Technical data ................................................................................................................ 6
3Mechanical installation .................................................................................................... 7
4Electrical installation ....................................................................................................... 8
Connection cable connection overview ............................................................................. 9
Limit switch configuration, screwable version up to year of construction in 1997 ............ 10
Limit switch configuration, single limit switches ............................................................... 10
Carrying out the electrical installation.............................................................................. 11
Mains supply ................................................................................................................... 12
Mains connection to control ............................................................................................ 12
Completing the electrical installation ............................................................................... 12
Overview of control ......................................................................................................... 13
5Commissioning of the control ........................................................................................ 14
DES: Rapid adjustment of final limit positions ................................................................. 14
NES: Rapid adjustment of final limit positions ................................................................. 15
6Advanced electrical installation ..................................................................................... 16
Connection of door safety switches X2 ........................................................................... 16
External supply X1 .......................................................................................................... 17
Emergency STOP X3 ...................................................................................................... 17
X20 Relay contact ........................................................................................................... 17
External Control device X5 .............................................................................................. 17
7Control programming .................................................................................................... 18
8Table menu items ......................................................................................................... 19
Door operating modes ..................................................................................................... 19
Door positions ................................................................................................................. 19
Door functions ................................................................................................................. 20
Safety functions .............................................................................................................. 20
Maintenance cycle counter ............................................................................................. 21
Readout of data memory ................................................................................................. 22
Deleting of all settings / Readout GfA stick ..................................................................... 22
9Safety devices .............................................................................................................. 23
X2: Input, door safety switch ........................................................................................... 23
X3: Input, emergency STOP ........................................................................................... 24

4
10Functional description ................................................................................................... 24
X1: Mains supply of the control and supply of external devices ...................................... 24
X5: Input, control device .................................................................................................. 25
Door operating mode "Extended hold-to-run" .................................................................. 25
Potential-free X20 Relay contact ..................................................................................... 25
Force monitoring (DES only) ........................................................................................... 26
Travel time monitoring (NES only) ................................................................................... 27
Maintenance cycle counter .............................................................................................. 27
Short-circuit/overload display .......................................................................................... 27
Standby function ............................................................................................................. 2 7
11Status display ................................................................................................................ 28
Faults .............................................................................................................................. 28
Commands ...................................................................................................................... 30
Status indications ............................................................................................................ 31
12Explanation of symbols ................................................................................................. 32
13Declaration of incorporation / Declaration of conformity ................................................. 34
Symbols
Warning - Risk of injury or danger to life!
Warning - Danger to life from electric shock!
Note - Important information!
▶ Prompt - Required action!
Illustrations show example products. Differences from the delivered product are possible.

5
1General safety information
Specified use
The door control is intended for a power-operated door with a drive unit (NES/DES GfA limit
switch system).
The safe operation is only guaranteed with specified normal use. The drive unit is to be
protected from rain, moisture and aggressive ambient conditions. No liability for damage
caused by other applications or non-observance of the information in the manual.
Modifications are only permitted with the agreement of the manufacturer. Otherwise the
Manufacturer’s Declaration shall be rendered null and void.
Safety information
Warning ! Failure to follow these installation instructions may result in severe injury
or death.
Please read these instructions before using the product
Keep these instructions handy
Please include these instructions when you pass on the product
Installation and commissioning are to be performed by skilled personnel only.
Only trained electrical craftsmen are permitted to work on electrical equipment. They must
assess the tasks assigned to them, recognise potential danger zones and be able to take
appropriate safety measures.
Installation work is only to be carried out with the supply off.
Observe the applicable regulations and standards.
Coverings and protective devices
Only operate with corresponding coverings and protective devices.
Ensure that gaskets are fitted correctly and that cable glands are correctly tightened.
Spare parts
Only use original spare parts.

6
2Technical data
Series TS 959
Dimensions W x H x D 155 mm x 386 mm x 90 mm
Installation Vertical, free of vibration
Operating frequency 50 Hz / 60 Hz
Supply voltage (+/- 10%)
1 N~220-230 V, PE
3 N~220-400 V, PE
3~220-400 V, PE
Output power for drive unit, maximum 3 kW
Protection per phase, on-site 10 A …… 16 A
External mains supply: X1/L, X1/N
Protection via F1 micro-fuse
1 N~230 V
1,6 A time-lag
Control inputs 24 V DC, type. 10 mA
Relay contact 1 potential-free changeover contact
Loading of relay contacts,
ohmic/inductive
230 V AC, 1 A
24 V DC, 0,4 A
Control power consumption 4 W
Temperature range Operation
Storage
-10 °C …… +50 °C
+0 °C ….... +50 °C
Air humidity, non-condensing up to 93 %
Protection class of housing with CEE-plug IP 54 / IP 65
Protection class of housing IP 65
Compatible GfA - limit switch NES (mechanical limit switch)
DES (digital limit switch)

7
3Mechanical installation
Control installation!
Indoor use only
Mounting only on even ground that is free of vibration
Only mount in the vertical position
Door must be in clear view from place of installation
Requirements
The permissible loads on walls, mountings, connection and transmission elements must not
be exceeded.
Mounting
The control is mounted via 4 elongated holes

8
4Electrical installation
Warning - Danger to life due to electrical current!
Disconnect the cables (mains OFF) and check that the supply is off
Observe the applicable regulations and standards
Ensure proper electrical connection
Use suitable tools
On-site backup fuse and disconnector unit!
Connection to the indoor installation via an all-pole disconnector unit, with current
≥ 10 A as per EN 12453 (e.g. CEE plug connector, main switch)
Note! - The inputs of the following safety devices of the control are rated
Performance Level c (PLc):
Slack-rope switch
Pass-door switch
Safety edge
Limit switch system
Safety circuit of the drive unit
Emergency STOP control device
Connect only sensors that comply with the current EN 12453 and are suitable for
Performance Level c.
Observe the installation instructions of the drive unit!

9
Connection cable connection overview
Ⓐ DES → Ⓑ X12 DES Ⓒ MOT → Ⓓ X13
Pin Core Pin Description: Pin Core Term. Description:
① 5/wh ① +24 V safety circuit ① 3 W Phase W
② 6/bn ② Channel B (RS485) ② 2 V Phase
V
③ 7/gn ③ Ground ③ 1 U Phase U
④ 8/ye ④ Channel A (RS485) ④ 4 N Neutral conductor (N)
⑤ 9/gy ⑤ Safety circuit ⑤ PE PE
⑥ 10/pk ⑥ 8 V DC supply voltage
Ⓐ NES → Ⓔ X12 NES
Pin Core Term. Description:
① 5/wh 11 Limit switch common +24 V, wire link to: 7, 9, 5, 14
② 6/bn 12 S5 Auxiliary limit switch
③ 7/gn 6 S3 Open limit switch
④ 8/ye 15 S6 Auxiliary limit switch
⑤ 9/gy 8 S4 CLOSE limit switch
⑥ 10/pk 4 Safety circuit

10
Limit switch configuration, screwable version up to year of construction in 1997
56710 93214(N)
S6 S5 S3 S1 S2 S4
S10 F1
G1
Y1
1
3
2
4
5
X12
W1
M1
F1 Thermal contact X12 Limit switch board
G1 Rectifier S1 Emergency OPEN limit switch
M1 Motor S2 Emergency CLOSE limit switch
S10 Emergency manual operation S3 OPEN limit switch
W1 Connection cable S4 CLOSE limit switch
Y1 Spring-loaded brake S5
A
uxiliary limit switch
S6
A
uxiliary limit switch
Limit switch configuration, single limit switches
5 671093214PE
M1 S10 F1S4S3 S5 S6
W1
A1
A
1 Terminal box S3 OPEN limit switch
F1 Thermal contact S4 CLOSE limit switch
M1 Motor S5
A
uxiliary limit switch
S10 Emergency manual operation S6
A
uxiliary limit switch
W1 Connection cable
Other manuals for TS 959
1
Table of contents
Other GFA Controllers manuals
Popular Controllers manuals by other brands

Digiplex
Digiplex DGP-848 Programming guide

YASKAWA
YASKAWA SGM series user manual

Sinope
Sinope Calypso RM3500ZB installation guide

Isimet
Isimet DLA Series Style 2 Installation, Operations, Start-up and Maintenance Instructions

LSIS
LSIS sv-ip5a user manual

Rockwell Automation
Rockwell Automation 1769-L31 installation instructions