flowair HMI User manual

HMI
MANUAL
INSTRUKCJA
РУКОВОДСТВО
ПОЛЬЗОВАТЕЛЯ
www.flowair.com

This documentation contains key information for HMI controller safety electrical connection and
configuration guidelines.
For your safety it is recommended to comprehensive study HMI manual, before any
operations related to electrical connection.
It is suggested to keep this HMI manual for later use.
The manufacturer reserves the right to make revisions and changes in the operation manual at any
time and without notice, and also to make changes in the device without influencing its operation.

www.flowair.com
HMI MANUAL
3
ENGLISHPOLSKIРУССКИЙ
TABLE OF CONTENTS
1. GENERAL DESCRIPTION ............................................................ 4
2. TECHNICAL DATA ....................................................................... 4
2.1 Dimensions ........................................................................................................ 5
3. HMI PANEL ................................................................................... 5
3.1 Buttons description ...................................................................................... 5
3.2 Main screen ....................................................................................................... 6
4. FUNCTIONS AND MODES ......................................................... 7
4.1 Function modes ............................................................................................. 7
4.2 Fan functions .................................................................................................... 7
4.3 Working modes .............................................................................................. 7
4.4 Temperature sensor ..................................................................................... 8
4.5 Antifreeze ............................................................................................................ 8
5. SETTINGS MENU ......................................................................... 8
5.1 Parameters setting ........................................................................................ 8
5.2 Button lock/unlock ....................................................................................... 9
5.3 Clock setting ..................................................................................................... 9
6. PROGRAMMING ......................................................................... 10
6.1 Setting mode ................................................................................................... 10
6.2 Setting fan speed ........................................................................................... 10
6.3 Programming weekly programmer ................................................... 10
7. INSTALLATION ............................................................................ 12
7.1 Wall–mounting ............................................................................................... 13
8. WIRING DIAGRAM ...................................................................... 13
9. BMS COMMUNICATION ........................................................... 14
10. DECLARATION OF CONFORMITY ........................................... 15

HMI MANUAL
www.flowair.com
4
1. GENERAL DESCRIPTION
• HMI controller is compatible with LEO FB V–type water heaters.
• Automatic or manual 3–step fan speed adjustment.
• Control room temperature (by opening/closing the valve, or by
adjusting air volume automatically).
• Antifreeze mode – protection against dropping room temperature
below critical level.
• HMI controls up to 6 LEO V–type units (it is required to use RX signal
distributor while connecting more than one unit).
• Possibility to connect external NTC temperature sensor.
Power supply 230VAC/50Hz
Regulation Panel buttons / LCD display
Setpoint range +5 ÷ +40°C
Speed of the fan control range 3 steps
Storage conditions temperature –10 ÷ +60°C
Ambient temperature range 0 ÷ +50°C
Temperature sensor Built–in internal/
external NTC (option)
IP 20
Montage surface
Casing ABS & Acrylic material
Weekly programmer ON: 5d+2d, OFF
Rated switching power 830 W (single–phase motor)
2. TECHNICAL DATA

www.flowair.com
HMI MANUAL
5
ENGLISHPOLSKIРУССКИЙ
3. HMI PANEL
3.1 Buttons description
15. Mode changing button
16. Changing the fan speed button
17. Power ON/OFF button
18. Temprature up button (or parameters setting)
19. Temprature down button (or parameters setting)
2.1 Dimensions
15
17
16
18
19
13836,5
94

HMI MANUAL
www.flowair.com
6
3.2 Main screen
1. Fan Speed: LOW, MED, HI and AUTO
2. ROOM TEMP. or NTC EXTERNAL SENSOR TEMP.
(measured temperature)
3. SET TEMP. (desired temperature)
4. Cooling Mode
5. Heating Mode
6. Weekday
7. Clock
8. Buttons Lock
9. ON/OFF Status of time zones
10. Automatic programable mode
11. Manual mode
12. 6 Time Zones for each day
13. Anti–freeze indication
14. Ventilation Mode
6
10
13
2
1
14
8
3
9
11 4 5 12
7

www.flowair.com
HMI MANUAL
7
ENGLISHPOLSKIРУССКИЙ
4. FUNCTIONS AND MODES
4.1 Function modes
MANUAL MODE – Fan is operating with chosen speed (LOW, MED or
HI). There are three additional modes: Heating, Cooling and Ventilation.
According to set temperature, valve is opened/closed.
AUTOMATIC MODE – air volume V is regulated automatically
depending on differential between pre–set Set Temperature (3) and
measured Room Temperature (2) (there is no possibility to change fan
speed manually). In this mode there is possibility to resign from the
valve, heating source will control ow and proper temperature of
water.
4.2 Fan function
To choose fan function see point 5.1.
Continuous – after reaching pre–set temperature (3) valve is closed,
fan operating with:
MANUAL MODE - pre set speed (1)
AUTO MODE - low speed
Thermostatic – after reaching pre–set temperature (3) valve is closed,
fan stops operating.
4.3 Working mode
Heating – valve is open and fan is on when Room Temp. < Set Temp.
Cooling – valve is open and fan is on when Room Temp. > Set Temp.
Ventilation – fan is turned ON and operate with pre–set V.

HMI MANUAL
www.flowair.com
8
4.4 Temperature sensor
To choose sensor see point 5.1.
Internal – room temperature is measured by built–in sensor.
External – room temperature measured by external sensor NTC
(optional). It is possible to connect one external NTC sensor to one HMI.
NOTE!
Alarm will appear if there is error with internal or external
temperature sensor: E0.
4.5 Antifreeze
When external sensor or internal sensor detect temperature below 5°C
(default setting), valve and fan is about to open immediately even if the
thermostat is set on OFF status.
5. SETTINGS MENU
5.1 Parameters setting
• When HMI is switched off, press and hold MODE for 3 seconds.
• To change option use MODE button.
• To change value use +/– buttons.

www.flowair.com
HMI MANUAL
9
ENGLISHPOLSKIРУССКИЙ
Menu
setting Option Value
1 Temperature
calibration
–9°C ~ +9°C
2 Fan status C1: Thermostatic mode
C2: Continuous mode
3 Temperature
sensor
0: Internal Sensor
1: External Sensor NTC
4 Antifreeze 0: Off
1: On
5 Antifreeze +5°C ~ +10°C
6 Modbus ID setting 1~247( 01~F7)
5.2 Button lock/unlock
• To LOCK all buttons press and hold + and then – buttons for
5 seconds.
• To UNLOCK all buttons press and hold + and then – buttons for
5 seconds.
5.3 Clock setting
• When HMI controller is turned off, press and hold FAN button for
3 seconds and enter into time clock setting.
• Option sequence as follows: hour, minute weekday.
• To change option use FAN button.
• To change value use + and – buttons.

HMI MANUAL
www.flowair.com
10
6. PROGRAMMING
6.1 Setting mode
• Push shortly MODE button (15) to select Manual Mode
and Programmable Mode.
• Push MODE button (15) for 3 seconds and select Cooling Mode,
Heating Mode or Ventilation Mode.
6.2 Setting fan speed
• Push shortly FAN button (16) to select the fan speed: LOW, MEDIUM,
HIGH, AUTO.
6.3 Programming weekly programmer
• Push and hold FAN button for 3 seconds and program time, setpoints
and time zones accordingly.
Monday to Friday
1st time setting (Hour and Minute), 1st time zone ON or OFF, 1st
setpoint setting …….. 6th time setting (Hour and Minute), 1st time
zone ON or OFF, 6th setpoint setting.
Saturday
1st time setting(Hour and Minute), 1st time zone ON or OFF, 1st
setpoint setting …….. 6th time setting(Hour and Minute), 1st time
zone ON or OFF, 6th setpoint setting.
Sunday
1st time setting(Hour and Minute), 1st time zone ON or OFF, 1st
setpoint setting …….. 6th time setting(Hour and Minute), 1st time
zone ON or OFF, 6th setpoint setting.

www.flowair.com
HMI MANUAL
11
ENGLISHPOLSKIРУССКИЙ
• Example settings
Weekday
Mon ~ Fri Sat. Sun.
S1 S2 S1 S2 S1 S2
Time Zone
1 06:00 ~ 08:00 ON 26°C ON 26°C ON 26°C
2 08:00 ~ 11:30 ON 24°C ON 24°C ON 24°C
3 11:30 ~ 13:30 ON 22°C ON 22°C ON 22°C
4 13:30 ~ 17:00 ON 22°C ON 22°C ON 22°C
5 17:00 ~ 22:00 ON 24°C ON 24°C ON 24°C
6 22:00 ~ 06:00 ON 24°C ON 24°C ON 24°C
S1: Status; S2: Setpoint
• Remarks
• During setting, displays can be set while they are flickering.
• When the beginning time is flickering, it is able to be set
(10 mins each step) via scrolling + – buttons. The time setting
is the beginning of current time zone, also the end time of last
time zone.
• When ON/OFF is flickering, it is able to be set via scrolling + –
buttons. When status is ON, thermostat will run according to
setpoint; when status is OFF, thermostat will be switch off
• When the setpoint is flickering, it is able to be set via
scrolling + – buttons. Even choosing OFF status, setpoint is able
to set. And this setpoint will be the working if someone switch
thermostat ON manually this time; however in next time zone,
it will run according to automatic programmable setting.

HMI MANUAL
www.flowair.com
12
• Example
• As ex–factory setting, press FAN button for 3 sec and enter into
programmable setting; from Mon to Fri display on the left top
of LCD; the time is flickering, and the beginning time of 1st
time zone we should enter 06:00( also it is ending time of 6th
time zone); then press FAN again, to choose ON by scrolling
+ – ; Continually press FAN again, to set 26°C by scrolling + –
buttons.
• Press FAN again, to set the beginning time of 2nd time zone
at 08:00 (also it is the ending time of 1st time zone); then press
FAN again, to choose ON by scrolling + – ; continually press
again, to set 24°C by scrolling + – buttons
• Press FAN again and follow the same steps to set time zones
from 3rd to 6th time, 22:00 is the beginning time of 6th time
zone, also the ending time of 5th time zone.
• After 6 time zones for Mon to Fri are done, keep pressing FAN
again and move to Sat. to set data by same steps; press FAN
again and move to Sun. to set data by same steps.
• After all settings are done, please press FAN or wait for
5 seconds to confirm settings.
7. INSTALLATION
NOTE!
Mind to disconnect HMI panel before starting work. Control panel
should be installed on height 1,5m in place where is proper air
circulation, away from heat/cold source.

www.flowair.com
HMI MANUAL
13
ENGLISHPOLSKIРУССКИЙ
7.1 Wall–mounting
1st Take off the baseplate from controller.
2nd Fix the baseplate using screwdriver on wall.
3rd Insert and clip the display unit on baseplate.
8. WIRING DIAGRAM
WARNING!
RISK OF ELECTRICAL SHOCK. Disconnect power supply before
making any electrical connections. Contact with components
carrying hazardous voltage can cause electrical shock and may
result in severe personal injury or death.

HMI MANUAL
www.flowair.com
14
• Wires must be finished with cord end terminals.
• Wires size should be chosen by the designer.
• Dimension of supplying wire is min. OMY 2 x 1 mm2.
• Close the cover before start–up.
9 1087
N
N L A/+ B/-
RS485
230V/50Hz Fan
Hi Med. Lo.
Valve
external NTC
(optional)
654321
9. BMS COMMUNICATION
The controller allows to connect to BMS. Register addresses are
available on www.flowair.com.
Communication parameters:
Physical layer RS485
Protokol MODBUS-RTU
Transmission speed [bps] 2400
Parity None
Data bits count 8
Stop bits count 1

www.flowair.com
HMI MANUAL
15
ENGLISHPOLSKIРУССКИЙ
10. DECLARATION OF CONFORMITY
FLOWAIR GŁOGOWSKI I BRZEZIŃSKI SP.J.
Office: ul. Chwaszczyńska 151E, 81–571 Gdynia
Headquarter: ul. Amona 84; 81–601 Gdynia
tel. (058) 669 82 20
tel./fax: (058) 627 57 21
e–mail: info@flowair.pl
www.flowair.pl
Declaration of conformity
FLOWAIR hereby confirms that room thermostat HMI was produced in
accordance to the following Europeans Directives:
2006/95/WE – Low Voltage Electrical Equipment (LVD),
2004/108/WE – Electromagnetic Compatibility (EMC),
and harmonized with below directives norms:
EN 62233:2008
EN 60335–1:2012
EN 55014–1:2012
EN 61000–3–2:2014–10
EN 61000–3–3: 2013–10
EN 55014–2:2015–06
CE: 15
Gdynia, 01.09.2015
R&D department manager

Niniejsza dokumentacja zawiera kluczowe informacje dla bezpiecznego podłączenia elektrycznego
oraz wskazówki dotyczące konfiguracji i eksploatacji sterownika HMI.
W celu zapewnienia bezpieczeństwa, przed rozpoczęciem jakichkolwiek prac związanych
z podłączeniem elektrycznym sterownika, zaleca się kompleksowe przestudiowanie
instrukcji obsługi.
Sugeruje się zachowanie niniejszej instrukcji obsługi w celu umożliwienia ponownego użycia
w późniejszym terminie.
Producent zastrzega sobie prawo do wprowadzenia poprawek i zmian w instrukcji obsługi
w dowolnym czasie i bez powiadomienia, a także zmian w urządzeniu nie wpływających na jego
działanie.

www.flowair.com
HMI INSTRUKCJA
17
ENGLISHPOLSKIРУССКИЙ
SPIS TREŚCI
1. CECHY .......................................................................................... 18
2. DANE TECHNICZNE .................................................................... 18
2.1 Wymiary ............................................................................................................... 19
3. PANEL HMI ................................................................................... 19
3.1 Opis przycisków .............................................................................................. 19
3.2 Ekran główny .................................................................................................... 20
4. FUNKCJE I TRYBY PRACY ........................................................... 21
4.1 Tryby pracy ........................................................................................................ 21
4.2 Funkcje pracy ................................................................................................... 21
4.3 Sposób pracy ................................................................................................... 22
4.4 Czujnik temperatury .................................................................................... 22
4.5 Zabezpieczenie antifreeze ....................................................................... 22
5. MENU ........................................................................................... 23
5.1 Ustawienia parametrów ............................................................................ 23
5.2 Blokada przycisków ...................................................................................... 23
5.3 Ustawienia zegara ......................................................................................... 24
6. PROGRAMOWANIE .................................................................... 24
6.1 Ustawienia trybu pracy .............................................................................. 24
6.2 Ustawienia prędkości wentylatora ...................................................... 24
6.3 Programator tygodniowy ......................................................................... 24
7. INSTALACJA ................................................................................ 27
7.1 Montaż ................................................................................................................. 28
8. SCHEMAT POŁĄCZEŃ ELEKTYCZNYCH .................................. 28
9. KOMUNIKACJA BMS .................................................................. 29
10. DEKLARACJA ZGODNOŚCI ....................................................... 30

HMI INSTRUKCJA
www.flowair.com
18
1. CECHY
• Sterownik HMI jest kompatybilny z wodnymi nagrzewnicami
LEO FB V.
• Umożliwia 3–stopniowa nastawa prędkości obrotowej wentylatora.
• Kontrola temperatury w pomieszczeniu (poprzez otwieranie/za-
mykanie zaworu, albo automatyczną nastawę prędkości obrotowej
wentylatora V).
• Antifreeze – zapobiega nadmiernemu spadkowi temperatury
w pomieszczeniu.
• HMI może może obsłużyć do 6 urządzeń LEO FB V (wymagane jest
użycie rozdzielacza sygnału RX w przypadku podłączenia więcej niż
jednego urządzenia).
• Możliwość podłączenia zewnętrznego czujnika temperatury NTC.
Zasilanie 230VAC/50Hz
Panel panel z przyciskami/
wyświetlacz LCD
Zakres regulacji temperatury +5 ÷ +40°C
Zakres regulacji obrotów 3 stopnie
Zakres temperatury pracy –10 ÷ +60°C
Temperatura przechowywania 0 ÷ +50°C
Czujnik temperatury wbudowany/
zewnętrzny NTC (opcja)
IP 20
Montaż natynkowy
Obudowa ABS & Akryl
Programator tygodniowy ON: 5 dni+2 dni, OFF.
Znamionowa moc obciążenia 830 W (silnik jednofazowy)
2. DANE TECHNICZNE

www.flowair.com
HMI INSTRUKCJA
19
ENGLISHPOLSKIРУССКИЙ
3. PANEL HMI
3.1 Opis przycisków
15. Przycisk zmiany trybu pracy
16. Przycisk zmiany prędkości wentylatora
17. Przycisk ON/OFF
18. Zwiększanie wartości edytowanego parametru
19. Zmniejszanie wartości edytowanego parametru
2.1 Wymiary
15
17
16
18
19
13836,5
94

HMI INSTRUKCJA
www.flowair.com
20
3.2 Ekran główny
1. Prędkość wentylatora: NISKA, ŚREDNIA, WYSOKA oraz AUTO
2. ROOM TEMP. (mierzona temperatura)
3. SET TEMP. (temperatura zadana)
4. Sposób pracy: chłodzenie
5. Sposób pracy: grzanie
6. Dzień tygodnia
7. Zegar
8. Blokada ekranu
9. Status nastawy stref czasowych
10. Tryb programowalny automatyczny
11. Tryb ręczny
12. Strefy czasowe
13. Sygnalizacja włączenia zabezpieczenia antifreeze
14. Sposób pracy: wentylacja
6
10
13
2
1
14
8
3
9
11 4 5 12
7