manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Franke
  6. •
  7. Control System
  8. •
  9. Franke DVS SH07-020 Manual

Franke DVS SH07-020 Manual

Page 8
MT04-001 AquariTherm Tap (Manual) www.dartvalley.co.uk
Revision No. MAQTIN16071301
ON
Single valve operation (Switch C OFF)
When single valve operation is selected, a solenoid valve is
connected to channel 1 only. With two sensors connected the
valve is either opened for the selected time (channel 1 sensor) or
for half the selected time (channel 2 sensor).
In both operating modes each solenoid can be closed before the
set time is reached by operating the corresponding sensor again.
Step 7 : Time settings and basic operation
Step 6 : Option setup
Bath Control System
Installation & Operating Instructions
SH07-020
PP00-150 100119
PP00-150 100119
On the board you will notice three in-line switches fitted to the
right side of the DIP switches (Fig. 4).
Settings
Switch A ON = Adds 15 seconds to the valve open time, as
selected on the DIP switches.
Switch B ON = Adds 30 seconds to the valve open time, as
selected on the DIP switches.
Switch A & B can be used together if required, this will allow 15,
30 and 45 seconds to be added.
Switch C ON = Selects dual valve operation.
Switch C OFF = Selects single valve operation.
Dual valve operation (Switch C ON)
This allows two solenoid valves to be connected and operated by
two sensors, each valve can be operated independently. The open
time selected applies to both valves.
AB C
ON ON ON
When all DIP switches are set to OFF, the system enters a test
routine. This should only be used when advised.
The numbers printed on the switches (1, 2, 3, 4) simply identify
the switch number; the actual time settings available are shown
below:
Switch 1 ON = 1 minute
Switch 2 ON = 2 minutes
Switch 3 ON = 3 minutes
Switch 4 ON = 4 minutes
Any combination of DIP switches can be set to ON, the settings
add up so that the range available is 1-10 minutes.
Example above shows switch 2 and switch 4 ON, giving a total
valve open time of 6 minutes.
When all connections and settings are made and checked, replace
lid and secure. After installation and setting of external equipment,
e.g. sensors, valves etc. the supply should be connected.
Wave-on / Wave-off settings
Switch 4 ON enables Wave-on / Wave-off operation which allows
the valves to be waved off before the set time has finished. If not
waved off manually the valves will close automatically at the set
time as usual.
Power up
When all connections and settings are made and checked, replace
the lid and secure.
After installation of external equipment, such as sensors and
valves etc, the supply should be connected.
Operation
When the control box is powered any connected valves will be
opened for 2 seconds, the valves will close, and after a short
period normal operation will begin.
The time period between the valves opening and normal operation
will depend on the set time, therefore this could be up to 10
minutes.
When a sensor is operated the corresponding valve will open for
the set time, if DIP switch 4 has been set to on, the valve can be
closed before the set time by operating the sensor a second time.
Each off the two channels operates independently, but both use
the same settings.
Page 4
IMPORTANT : Changes to settings can only take place when
power has been disconnected for at least 5 seconds.
IMPORTANT : Changes to settings can only take place when
power has been disconnected for at least 5 seconds.
Dart Valley Systems | Kemmings Close | Long Road | Paignton | Devon | TQ4 7TW | UK
T +44 (0)1803 529 021 | F +44(0)1803 559 016 | www.dartvalley.co.uk | techsupport@dartvalley.co.uk
A B C
1 2 3 4
Page 3
MT04-001 AquariTherm Tap (Manual) www.dartvalley.co.uk
Revision No. MAQTIN16071301
Page 2
MT04-001 AquariTherm Tap (Manual) www.dartvalley.co.uk
Revision No. MAQTIN16071301
The control box should be located in a dry location and not
exposed to dirt, dust or damp. The unit should be accessible when
required, but not within easy reach of unauthorised persons.
It will be necessary to make adjustments and service the control
box after installation, and in the future. Secure access areas and
duct spaces are recommended.
The control box is not designed for direct surface mounting into
washroom areas. Never open the cover with the supply live.
The routes that cables will take when connecting external
equipment to the control box should also be planned at this stage.
The bath control system is typically used with a bath filling back
plate or spout
Important: Thermostatic mixing valve
It is recommended that hot water is supplied through an approved
TMV3 thermostatic mixing valve to prevent scalding (sold
seperately).
Step 3 : Typical installation
Step 2 : ContentsStep 1 : Safety First
These instructions relate to the use of the Bath Control System
only, any external or ‘add-on’ parts will be supplied with separate
instructions.
It is recommended that the electrical part of the installation be
carried out by a qualified electrician in accordance with the latest
electrical regulations. It is also recommended that any plumbing
is carried out by a qualified plumber.
*Not to scale
IMPORTANT : Please read these instructions carefully
and follow each stage in order!
IMPORTANT : It is recommended that hot water is supplied
through an approved TMV3 thermostatic mixing valve (sold
seperately), in order to prevent scalding.
Step 5 : Fixing & wiring
Step 4 : Board layout
Input connection - Sensor 1
Output connection - Valve 1
Input connection - Sensor 2
Output connection - Valve 2
Cable entry - Sensor 1
Cable entry - Valve 1
Cable entry - Sensor 2
Cable entry - Valve 2
Mains supply
Time setting switches
Option switches
LED 1 - For engineers / testing only
LED 2 - For engineers / testing only
LED 3 - For engineers / testing only
Fuse (replace with exact same type)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
915 12 10 11
14
13
43876521
DO NOT extend cables
DO NOT leave badly fitted cables
DO NOT interfere with the mains flex
DO check all cables and connections
DO ask for advice if / when necessary
The box should be securely fixed in a suitable location in a
horizontal orientation, so that the front label is read correctly.
Remove lid to expose four fixing locations around the edge of the
enclosure (see Fig. 3). These areas allow the fastening of the unit
without removing the printed circuit board.
Drill through these marked areas away from the wall to avoid dust
entering the control box, then hold control box in position against
the wall and mark holes with a pencil. Remove box, drill and plug
marked areas and fix the control unit with suitable fixings.
Connect the mains supply lead to a 230V ac supply via a fused
spur, the fuse rating should be 3 Amps. The mains supply should
NOT be initiated until all external equipment has been installed
and wired.
Always read instructions supplied with external components and
ensure that only the supplied equipment is connected to the
control box.
Cables should enter the enclosure through the cable glands. Keep
all connections tidy and do not allow cable to finish or hang in the
transformer area.
It is recommended that each cable is fed through the relative
cable gland into the enclosure; the cable can then be pulled out
towards the fitter to allow the connector plugs to be fitted.
The connector plugs can be disconnected from the mating
sockets when wiring external equipment, double check positions
with the plug orientations as they only fit one way!
When each plug has been wired the cables can be pulled back
through the cable glands, and the plug re-connected to the
corresponding socket. Cables should not be left to torte or slack.
When all connections are made and checked, replace the lid and
secure.
Fixing locations
Fuse
Connector plug
Fixing screw
Control box
Bath Control System box only*:
Always isolate
power when
opening the
control unit!
3 AMP
fused
spur
Bath
control
system
Solenoid
valve
TMV3
Spectrum
backplate
Spouts
Sensors
Cold
Hot Bath
(Spare Secondary Fuse Included)
IMPORTANT : The control should be connected to a clean,
dedicated mains supply, via a 3A rated spur

Other Franke Control System manuals

Franke DVS SH07-002 Manual

Franke

Franke DVS SH07-002 Manual

Franke DVS UC07-001 Manual

Franke

Franke DVS UC07-001 Manual

Franke DVS SH07-001 Manual

Franke

Franke DVS SH07-001 Manual

Popular Control System manuals by other brands

Motorola DOCKCONTROLLER DC-200 quick start guide

Motorola

Motorola DOCKCONTROLLER DC-200 quick start guide

INIM SmartLiving 515 user manual

INIM

INIM SmartLiving 515 user manual

Estun E21S Operation manual

Estun

Estun E21S Operation manual

GSK 218M Connection and PLC Manual

GSK

GSK 218M Connection and PLC Manual

EOS LSG 36 Assembly and operating instruction

EOS

EOS LSG 36 Assembly and operating instruction

flamco Flexcon M-K Series Installation and operating instructions

flamco

flamco Flexcon M-K Series Installation and operating instructions

Ier Automatic Systems BL52 operating manual

Ier

Ier Automatic Systems BL52 operating manual

Siemens SINUMERIK ONE MCP 1500 Equipment manual

Siemens

Siemens SINUMERIK ONE MCP 1500 Equipment manual

Hydac DATA+BOX Operating	 instruction

Hydac

Hydac DATA+BOX Operating instruction

Phase AxN series installation manual

Phase

Phase AxN series installation manual

Siemens SIMATIC PCS 7 Service manual

Siemens

Siemens SIMATIC PCS 7 Service manual

CSI Alfa Laval IndiTop Mounting instruction

CSI

CSI Alfa Laval IndiTop Mounting instruction

Waterous Aquis 2.5 SSP Installation & operation instructions

Waterous

Waterous Aquis 2.5 SSP Installation & operation instructions

ACC SmarTouch Digital user manual

ACC

ACC SmarTouch Digital user manual

Siemens LMV 5 Series manual

Siemens

Siemens LMV 5 Series manual

PROMETHEUS MR-20 Operator's guide

PROMETHEUS

PROMETHEUS MR-20 Operator's guide

Pakedge Device & Software NP36 user manual

Pakedge Device & Software

Pakedge Device & Software NP36 user manual

CAME G4000 manual

CAME

CAME G4000 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.