FRIEDLAND SA3 PLUS Installation instructions

ZONE 1
1
4
23
56
78
0
ENTER
ESC
#
ZONE 2 ZONE 3 ZONE 4
TAM PERFIREZONE 6ZONE 5
POWER PART ARM ARM LOW BATT.
9
!
SA3 PLUS
with Telephone Dialler
Installation & Operating Manual

FOREWORD
This Wirefree Alarm System has been designed to
meet with the requirements of BS6799 Class 1 for
Wireless Alarms. All components are designed and
manufactured to provide a high standard of security
protection and long, reliable service. No radio
operating licence is required for this equipment. The
approved radio frequency is not protected from
interference, this frequency may also be used by other
systems and equipment. The radio devices in this
system have been tested by an independent
accredited test laboratory for conformity with the
R&TTE Directive for radio equipment.
The system is designed for ease of installation using
only conventional domestic tools. However, it is
essential that the installer reads and fully understands
the advice and procedures contained in this manual
and plans the system before proceeding with the
installation.
During installation, it is important that the procedures
described in this manual are followed in sequence.
This manual should be retained in a safe place for
future reference.
IMPORTANT
All components, with the exception of the External
Solar Siren are suitable for mounting in dry interior
locations only.
Tools and Equipment Required:
No.0 Philips Screwdriver
No.1 Philips Screwdriver
No.2 Philips Screwdriver
5 & 6mm Masonry Drill Bits
Drill
Small Spirit Level
Bradawl
LOCAL AUTHORITY REGULATIONS
Depending on your location within the country, you
may be required, by law, to notify the Local Authorities
and Police of your new alarm installation.
Local Authority requirements differ from area to area,
therefore, we recommend that you contact your Local
Borough Environmental Officer to obtain full details of
your area's requirements.
SYSTEM SECURITY
This system has been designed to both detect
intruders and act as a strong deterrent to would-be
intruders when installed correctly.
Please remember that given adequate knowledge and
time it is possible to overcome any alarm system and
we therefore recommend that an Intruder Alarm is
used in conjunction with good physical protection
such as security window and door locks.
All units in the system are encoded to operate
together using an 8 bit House Code which is
configured by the user/installer to provide the unique
identification code for your installation. The system
House Code can be changed at any time by the user.
IMPORTANT: All units forming part of your alarm
system must be set to the same House Code.
The system is operated from the Control Panel or one
or more Remote Control units (available as an
upgrade accessory). Care should be taken to ensure
that the User Access code for the Control Panel does
not become known to other people or any Remote
Control Unit(s) are not lost, as this will compromise
the security of your system. In either event the
system house code and User Access code should be
changed as soon as possible.
SAFETY
Always follow the manufacturers advice when using
power tools; steps, ladders etc. and wear suitable
protective equipment (e.g. safety goggles) when
drilling holes etc.
Before drilling holes in walls, check for hidden
electricity cables and water pipes, the use of a
cable/pipe locater maybe advisable if in doubt.
When using ladders, ensure that they are positioned
on a firm stable surface at the correct angle and
suitably secured before use.
The use of ear defenders is advisable when working in
close proximity to the Siren due to the high sound
level produced by this device.

CONTENTS
KIT CONTENTS 2
INTRODUCTION AND OVERVIEW
3
System Arming
3
Entry/Exit Delay 3
Zones 3
Zone Lockout 3
Voice Dialler 3
Tamper Protection 4
Jamming Detection 4
Battery Monitoring 4
System House Code 4
PLANNING AND EXTENDING YOUR WIREFREE
SOLAR ALARM SYSTEM 5
REMOTE CONTROL 6
General Information 6
Configuring the Remote Contro 6
CONTROL PANEL 7
Positioning the Control Panel 7
Installing the Control Panel 7
Configuring the Control Panel 9
Testing the Control Panel & Remote Control 9
PASSIVE INFRA-RED (PIR)
MOVEMENT DETECTORS 10
Positioning the PIR Movement Detectors 10
Installing and Configuring the PIR
Movement Detectors 11
Testing the PIR Movement Detectors 12
MAGNETIC CONTACT DETECTORS 12
(Optional Accessory)
Positioning the Magnetic Contact Detectors 13
Installing and Configuring the Magnetic
Contact Detectors 13
Testing the Magnetic Contact Detectors 14
EXTERNAL SOLAR SIREN 15
General Information 15
Positioning the Solar Siren 15
Installing and Configuring the Solar Siren 16
Power-up of the Solar Siren 17
Testing the Solar Siren 17
EXTERNAL CONNECTIONS 18
TESTING THE SYSTEM 18
Initial Testing 18
Testing An Installed System 18
Detector Test 18
Hard-Wired Siren Test 19
Siren Test 19
Control Panel LED Test 19
Solar Siren Service Mode 19
Voice Dialler Test 19
FACTORY DEFAULTS 19
Reset Factory Default Conditions 19
PROGRAMMING 20
User Access Code 20
System House Code 20
Instant/Delay Zones 21
Entry/Exit Delay 21
Alarm Duration 21
Part-Arm 21
Zone Lockout 22
Entry/Exit Warning Tone 22
Jamming Detection 22
Hardwired Siren 22
Zone Operating Modes 22
Phone Numbers 23
Alarm Message Play Time 23
Record Alarm Message 24
Replay Alarm Message 24
Call Routing 24
Call Attempts 24
Dial Method 24
OPERATING INSTRUCTIONS 25
Arming The System 25
Disarming The System 25
Personal Attack (PA) Alarm 26
Tamper 26
Siren Service Mode 26
Siren Operating Mode 27
Battery Monitoring 27
MAINTENANCE 28
ALARM RECORD 29
TROUBLE SHOOTING 30
EXTENDING YOUR ALARM SYSTEM 33
COMPONENT SPECIFICATION Back Cover
1

KIT CONTENTS
The Alarm System should contain the following
components.
1xExternal Solar Siren
1x6 Zone LED Control Panel
with Telephone Dialler
3xPIR Movement Detectors
1xRemote Control
Also included:
Power Supply Adaptor
Telephone Connection Lead
Installation & Operating Manual
Fixing pack
Batteries
IMPORTANT
Please check all items are present BEFORE breaking
open the packaging clamshell. No claims for missing
parts will be accepted unless the clamshell is unopened
and intact.
EXTENDING THE ALARM SYSTEM
The following additional accessories are available to
enhance your system and provide further protection
and a higher level of security where required.
Component: Product Code
Passive Infra-Red Movement Detector SA433P
Magnetic Contact Detector SA433K
Remote Control SA433R
Remote Keypad SA433KP
Additional Solar Siren SA433SS
Full details of these accessories are given on page 33.
2
ZONE 1
1
4
23
56
78
0
ENTER
ESC
#
ZONE 2 ZONE 3 ZONE 4
TAMPERFIREZONE 6ZONE 5
POWER PART ARM ARM LOW BATT.
9
!
External Solar Siren
Control Panel
Remote
Control
PIR Movement
Detector

SYSTEM ARMING
The system has a full ‘Arm’ and a ‘Part-Arm’ mode.
Full ARM will arm all zones while the ‘Part-Arm’
mode will only arm the zones that are enabled for
‘Part-Arm’.
For example:
The system could be configured such that during night
time, ‘Part-Arm’ would arm only zones protecting the
lower floor and outbuildings, leaving the upper floor
free for movement without triggering the alarm.
However, when the property is left un-occupied,
the full ‘Arm’ mode will arm all zones to protect the
entire property, (i.e. upper and lower floors and
outbuildings).
ZONES
The system incorporates 6 wirefree Alarm Zones for
the connection of the system detectors that are
used to independently monitor different areas of the
property. In addition to standard intruder protection,
each zone may also be configured to operate in one of
three other modes:
- ‘Personal Attack’ mode provides 24 hour monitoring
of any Personal Attack (PA) switches incorporated
into the system.
- ‘24-hour Intruder’ mode provides 24 hour intruder
protection for areas where continuous monitoring is
required, (e.g. gun cupboards).
- ‘Fire’ mode provides 24 hour monitoring of any
Fire/Smoke detectors incorporated into the system.
ENTRY/EXIT DELAY
Each zone can be programmed to be Armed in either
Instant or Delay mode.
Usually the zone covering the main entrance door and
the route to and from the Control Panel would be
configured in Delay mode. This allows time for the user
to exit the property after setting the system at the
Control Panel or to Disarm the system before an alarm
condition is triggered when re-entering the property.
The remaining zones would be configured as Instant
allowing them to initiate an alarm immediately a
detector on the zone is triggered.
Delay Armed zones will not become fully armed until
after the Entry/Exit delay period has expired. When a
detector on a Delay Armed zone is triggered, an alarm
condition will not be triggered until after the Entry/Exit
period has elapsed. If the system is not disarmed
during the delay period, an alarm condition will occur
when the delay period expires.
Instant Armed zones are immediately able to initiate
an alarm as soon as the system begins to arm.
ZONE LOCKOUT
If a detector on an active zone is triggered while the
system is armed, an alarm condition will occur. After
the programmed alarm duration has expired the alarm
will stop and the system will automatically reset.
Subsequent detectors triggered will again initiate an
alarm condition. If a single zone initiates an alarm
condition three times then that zone will be ‘Locked
Out’ and any further alarm signals from that zone will
be ignored until the system is disarmed.
Note: The ‘Zone Lockout’ feature can be disabled if
required.
VOICE DIALLER
This system incorporates a telephone voice dialer which
is used to call for help and/or notify the user that the
system has been triggered and an alarm has occurred.
If the Voice Dialer is enabled and an alarm condition
occurs, the system will call for help using your
recorded alarm message and up to four telephone
numbers. When the telephone voice dialer is
activated it will call the first enabled number in the
dialing sequence and replay the recorded alarm
messages for the configured ‘Play Time’. The
recipient must acknowledge the message by
pressing the button on their telephone keypad.
If the call is unanswered or an acknowledgment
signal is not received then the next active number in
the dialing sequence will be called. The dialer will
continue calling each number in turn until either all
numbers in the sequence have been dialed the set
number of times or the dialing sequence is cancelled
by an acknowledged signal from the recipient.
INTRODUCTION AND OVERVIEW
3

TAMPER PROTECTION
All system devices (except any Remote Control Units)
incorporate Tamper protection features to protect
against unauthorised attempts to interfere with the
device. Any attempt to remove the battery cover from
any device (except a Remote Control) or to remove the
Solar Siren or Control Panel from the wall will initiate
an alarm condition (unless the system is in Test or
Programming modes), even if the system is Disarmed.
JAMMING DETECTION
In order to detect any attempts to illegally jam the
radio channel used by your alarm system, a special
jamming detection function is incorporated into
the Control Panel and Solar Siren. If this feature
is enabled, and the radio channel is jammed
continuously for 30 seconds, when the system is
armed, the Solar Siren will emit a pre-alarm series
of rapid bleeps for 5 seconds. If the jamming
continues for a further 10 seconds or more a full
alarm condition will occur. In addition if the system
is jammed for more than three periods of 10 seconds
in a 5 minute interval, this will also generate a
Full Alarm condition. The jamming detection features
in the Control Panel and Solar Siren operate
independently.
The Jamming Detection circuit is designed to
permanently scan for jamming signals. However, it
is possible that it may detect other local radio
interference operating legally or illegally on the same
frequency. If it is planned to operate the jamming
detection feature we recommend that the system
is monitored for false jamming alarms for at least
2 weeks prior to leaving the Jamming Detection
function permanently enabled.
BATTERY MONITORING
In addition to the battery monitor and low-battery
indicators in each device, the Control Panel will also
indicate a low battery status within any Passive Infra-
Red or Magnetic Contact Detector on the system.
SYSTEM HOUSE CODE
In order to prevent any unauthorised attempt to operate
or disarm your system, you must configure your system
to accept radio signals only from your own system
devices. This is done by setting a series of eight
miniature (DIP) switches in all devices (except the
Control Panel) to the same ON/OFF combination
(the House Code) selected by the user/installer. The
Control Panel is then programmed to operate only
with devices set to this House Code. All detectors
and Remote Control Unit(s) must be configured with
the same House Code in order for the system to
operate correctly.
Inside the Siren, Detectors and Remote Control Unit is
a series of 8 DIP switches.
The House Code is set up by moving each of the
8 switches in each device to the same randomly
selected ON/OFF sequence. When setting the DIP
switches, ensure that each switch ‘clicks’ fully into
position. Use the tip of a ballpoint pen or a small
screwdriver to move each switch in turn.
Note: It is recommended that the system House Code
is always reset to a code other than the factory default.
4
e.g. Switch 1
set to the
ON position

The following example below shows a typical property
incorporating the suggested positions for the External
Siren, Control Panel, PIR and Magnetic Detectors for
optimum security. Use this as a guide for your installation
in conjunction with the recommendations contained in
this manual for planning your intruder alarm system.
Before attempting to install your Alarm System it is
important to study your security requirements and plan
your installation.
The alarm system may be extended to provide even
greater protection by fitting additional PlR Movement
Detectors and Magnetic Contact Detectors as required.
PLANNING AND EXTENDING YOUR WIREFREE
ALARM SYSTEM
LED
Control
Panel
Magnetic
Contact
Detector
Magnetic Contact
Detector
External Solar
Siren
PIR Movement
Detector
PIR Movement
Detector
Remote
Control
SHED
LOUNGE
GROUND FLOOR GARAGE
KITCHEN
HALL
DINNING
ROOM
PIR Movement
Detector
PIR
Movement
Detector
PIR
Movemen
t
Detector
Back Door
ZONE1
1
4
23
56
78
0
ENTER
ESC
#
ZONE2 ZONE3 ZONE4
TAMPERFIREZONE6ZONE5
POWER PARTARM ARM LOW BATT.
9
!
5
*
*
*Magnetic Contact Detectors
available as optional accessories

6
The Remote Control Unit(s) are used to Arm, Part-Arm
and Disarm the system.
The Remote Control Unit also incorporates a Personal
Attack (PA) switch. Activating the PA switch on the
side of the Remote Control will immediately trigger an
alarm (unless the Control Panel is in Test or Program
Modes) even if the system is disarmed. The alarm can
be cancelled by pressing the ’DISARM’ button on the
Remote Control or via the Control Panel.
Any number of Remote Control Units can be used with
your system, providing they are all coded with the
system House Code (DIP switch settings).
The Remote Control is powered by a CR2032 type
Lithium cell which under normal conditions will have an
expected life in excess of 1 year. Under normal battery
conditions the LED on the Remote Control will only
illuminate when a button is pressed. However, under
low-battery conditions this LED will continue to flash
after the button has been released. When this occurs
the battery should be replaced as soon as possible.
CONFIGURING THE REMOTE
CONTROL
1.
Remove the rear cover by undoing the small screw
on the rear of the Remote Control and keeping it
safe for later.
2.
Select and record (in the Alarm Record section of
this manual) a random combination of ‘ON’ and
‘OFF’ positions for the DIP switches. This will
become the system House Code that enables all
devices to communicate with the Control Panel.
IMPORTANT:
The House Code for your system
should be changed from the factory default setting.
3.
Ensure that the Jumper Link located immediately
below the House Code DIP switches is fitted in
position for use with this alarm system.
4.
Insert the battery under the clip ensuring that the
+terminal faces upwards away from the Circuit
Board.
5. Replace the rear cover and fixing screw. Do not over
tighten the screw as this could damage the thread.
Testing the Remote Control:
6. Press the button. The Transmit LED should
illuminate while the button is pressed and
extinguish within 1 second of releasing the button.
7. Press the and buttons in turn to
ensure that the Transmit LED illuminates as before.
REMOTE CONTROL UNIT
Slide up
to operate
Transmit LED
Personal Attack
Arm
Part-Arm
Disarm
House Code
DIP Switches
Jumper
Link
Battery Clip
Battery

POSITIONING THE CONTROL PANEL
When choosing a suitable location for the Control
Panel, the following points should be considered.
1.
The Control Panel should be located in a position
out of sight of potential intruders and in a safe
location, but easily accessible for system
operation.
2.
The Control Panel should be mounted on a sound
flat surface to ensure that the rear tamper switch
on the Control Panel is closed when the Panel is
mounted. The Control Panel should be mounted at
a convenient height of between 1.5 and 2m and in
a position where it will be seen each day.
Note: If small children are in the household, a
further consideration should be given to keeping
the units out of their reach.
3.
It is recommended that the Control Panel should
be positioned such that the Exit/Entry tone
(emitted by the Control Panel) can be heard from
outside the property.
4.
The Control Panel should be mounted within a
protected area so that any intruder cannot reach
the Control Panel without opening a protected door
or passing through an area protected by a PIR
movement detector when the system is armed.
5.
The Control Panel must be located within reach of
a mains socket.
6.
If the telephone voice dialler is to be used then the
Control Panel will need connecting to a convenient
telephone point.
7.
Do not locate the Control Unit closer than 1m to any
large metallic object, (e.g. mirrors, radiators, etc) as
this may affect the radio range of the Control Panel.
INSTALLING THE CONTROL PANEL
1. Undo the two captive fixing screws on top of the
panel and open the cover. The cover is hinged along
the bottom edge.
2. Unclip and remove the two back-up batteries on
either side of the panel.
3. Hold the Control Panel in position on the wall and
mark the positions of the four fixing holes. Remove
the Panel and drill four 5mm holes and fit the 25mm
Wall Plugs.
Note: The wall plugs supplied with the product are
not suitable for plasterboard walls, if mounting the
Control Panel onto plasterboard use proprietary
wall plugs.
CONTROL PANEL
ZONE 1
1
4
23
56
78
0
ENTER
ESC
#
ZONE 2 ZONE 3 ZONE 4
TA M PERFIREZONE 6ZONE 5
POWER PART ARM ARM LOW BATT.
9
!
Zone LEDs
Status LEDs
Keypad
Outside View of Control Panel
7

IMPORTANT: Do not drill the fixing holes with the
Control Panel in position; as the resulting dust and
vibration may damage the Control Panel’s internal
components and invalidate the guarantee.
4. Fit two 18mm No.4 screws into the top holes until
almost fully home and hang the Control panel over
these screws using the two keyhole slots in the top
corners of the panel casing.
5. Route the cable from the Power Supply Unit up
behind and on the right hand side of the Control
Panel and connect the plug to the DC power socket
in the panel. Ensuring that the cable is not trapped
between the panel and the wall.
6. Fix the Panel to the wall using two 18mm No.4
screws in the lower two fixing holes in the panel and
tighten the upper fixing screws until they just grip
the casing. Do not over tighten the fixing screws as
this could damage or distort the casing.
7. Ensure that the "Reset" and the "Hard-Wired Siren
tamper detect" jumper links are set in the OFF
position.
8. Connect battery leads to both back-up batteries
and refit batteries.
Battery 1 (left): Red lead to +ve battery terminal
Blue lead to
–
ve battery terminal
Battery 2 (right): Blue lead to +ve battery terminal
Black lead to
–
ve battery terminal
IMPORTANT: Take care when connecting battery
leads to the batteries as connecting incorrectly
could damage the batteries or the Control Panel.
Note: The Power LED may flash to indicate that the
unit is being operated from the back-up batteries
and that mains supply is not present.
9. Close the lid of the Control Panel and tighten the
captive fixing screws.
10.
Plug in and switch ON the Power Supply Unit, (the
Power LED should illuminate).
11.
If required, connect the Control Panel to the
telephone line using the cable supplied by
inserting small RJ11 plug into socket marked LINE
located on the bottom edge of the Control Panel.
TAMP GND B+ GND N.C. C N.O. GND V+ OUT GND
Upper Keyhole
Fixing Hole
-
ve Terminal
(Black Lead)
+ve Terminal
(Blue Lead)
Reset Jumper
Link P1
Power Supply
Jack Socket
Upper Keyhole
Fixing Hole
+ve Terminal
(Red Lead)
-
ve Terminal
(Blue Lead)
Lower Fixing
Hole
External Tamper
Switch Jumper
Link P51
Power Supply
Cable Access
Hole
Inside View of Control Panel
8

Connect the BT plug on the other end of the lead
to an appropriate telephone outlet.
If the cable supplied is not long enough to reach a
suitable phone point then it will need extending
using a coupler and extension lead (not supplied).
Note: If the Panel Tamper alarm sounds during the
installation reset the alarm by pressing:
, ,
on the Control Panel Keypad.
CONFIGURING THE CONTROL
PANEL HOUSE CODE
With unit in Standby mode (Power LED only
illuminated).
1. Press
, ,
The Control Panel will beep twice and the Arm
and Part-Arm LEDs will illuminate. All Zone, Fire
and Tamper LEDS will flash.
This puts the Control Panel into programming mode.
2. Press ,
The Zone LEDs 1-6, Fire and Tamper LEDs will
illuminate to indicate the current House Code
setting with an illuminated LED indicating a
setting of "1" in the House Code and LEDs
which are OFF indicating a "0".
For Example: A house code of 11110010, will
be indicated with zone LEDs 1-4 ON and 5-6
OFF, Fire LED ON and Tamper LED OFF.
3.
The system House Code can be programmed
either directly at the Control Panel or via a
Remote Control Unit:
At the Control Panel:
a) By pressing buttons 1-8 on the Control Panel,
configure the status LEDs so that they
indicate the required house code setting. The
LEDs will switch to the opposite state each
time the button is pressed.
LED ON = 1, (House Code DIP Switch On/Up)
LED OFF = 0, (House Code DIP Switch
Off/Down)
b) Press to save the new setting and return
to programming mode.
c) Press to return to programming mode
without saving.
Using a Remote Control Unit:
a)
With the required House Code already
configured, press the button on the
Remote Control.
The Control Panel will beep twice to
acknowledge the signal.
The Zone, Fire and Tamper LED status will be
updated to correspond with the House Code set
on the Remote Control and now programmed
into the Control Panel.
b) Press to return to programming mode.
4. Press to exit programming mode and return
to Standby.
5. Press , ,
The Control Panel will beep and the Arm and
Part-Arm LEDs will flash.
This puts the Control Panel into test mode
TESTING THE CONTROL PANEL &
REMOTE CONTROL
1. Arm the Panel by pressing the button on
the Remote Control.
The Zone LED will illuminate for a few seconds
to indicate which zones are being armed. As the
entry/ exit delay expires the Control Panel will
slowly beep and the Arm LED will flash. Towards
the end of the delay the beep rate will increase.
When the entry/exit delay is completed the
beeping will stop and the Arm LED will stop
flashing and be constantly illuminated.
2. Disarm the system by pressing the button
on the Remote Control.
The Panel will beep twice and the Arm LED will
turn OFF.
3. Activate the Personal Attack switch on the
Remote Control.
12 3 4
ENTER
12 3 4
ENTER
ENTER
ESC
12 3 4
ENTER
ENTER
ESC
2
9

10
The Control Panel alarm will sound and all Zone/
Fire/Tamper LEDs will flash.
4. Disarm the system by pressing the button
on the Remote Control.
The Control Panel alarm will stop. The LEDs will
continue to flash.
5. Press on the Control Panel to return to
Standby and cancel any warning LEDs.
6. Test the range of the Remote Control by pressing
the button on the Remote Control from in
and around the property and from all locations
where you plan to install detectors. Check that
the Control Panel acknowledges the signal from
the Remote Control by beeping twice each time
the button is pressed.
Note: Wait for 10s after pressing the button
before pressing it again.
7. Press , ,
The Control Panel will beep to acknowledge the
signal and the Arm and Part-Arm LEDs will flash.
This put the Control Panel into Test mode.
PASSIVE INFRA RED (PIR)
MOVEMENT DETECTORS
PIR detectors are designed to detect movement in a
protected area by detecting changes in infra-red
radiation levels caused, for example, when a person
moves within or across the devices field of vision. If
movement is detected an alarm signal will be
generated, (if the system and alarm zone is armed).
Note: PIR detectors will also detect animals, so
ensure that pets are not permitted access to areas
fitted with Passive Infra Red Movement Detectors
when the system is armed.
Any number of PIR Movement Detectors can be used
with your system, providing they are all coded with
the system House Code and are mounted within
effective radio range of the Control Panel.
The PIR Detector is powered by a PP3 Alkaline
battery which under normal conditions will have an
expected life in excess of 1 year. When the battery
level drops, with the PIR in normal operation mode
and the battery cover fitted, the LED behind the
detection window will flash. When this occurs the
batteries should be replaced as soon as possible.
POSITIONING THE PIR MOVEMENT
DETECTORS
The recommended position for a PIR Movement Detector
is in the corner of a room mounted at a height between
2 and 2.5m. At this height, the detector will have a
maximum range of up to 12m with a field of view of 110°.
Detection Zone Pattern for PCB in position 5
The Position of the PCB inside the PIR can be set to 5
different positions to adjust the range of the detection
pattern created by the PIR. Setting the PCB in position
3 will reduce the range to approximately 9m, with
position 1 providing a range of approximately 6m. The
recommended position setting for the PCB is in position 5.
When considering and deciding upon the mounting
position for the detector the following points should
be considered to ensure trouble free operation:
1. Do not position the detector facing a window or
where it is exposed to or facing direct sunlight.
PIR Movement Detectors are not suitable for use
in conservatories.
2. Do not position the detector where it is exposed
to draughts.
3. Do not position the detector directly above a heat
source, (e.g. fire, radiator, boiler, etc).
ESC
12 3 4
ENTER
2m - 2.5m
23416785910
Detector Range (metres)
5m
110°
180°
10m
3m

4. Where possible, mount the detector in the corner of
the room so that the logical path of an intruder would
cut across the fan detection pattern. PIR detectors
respond more effectively to movement across the
device than to movement directly towards it.
5. Do not position the detector in a position where it
is subject to excessive vibration.
6. Ensure that the position selected for the PIR
detector is within effective range of the Control
Panel. It is recommended that prior to installation
the detector is configured and tested with the
Control Panel in Walk test mode to ensure that
they are within effective range.
Note: When the system is Armed, pets should not
be allowed into an area protected by a PIR Detector
as their movement would trigger the PIR and trigger
an alarm.
Note: DO NOT fix the detector to metalwork or
locate the unit within 1m of metalwork (i.e. radiators,
water pipes, etc) as this could affect the radio range
of the Device.
INSTALLING AND CONFIGURING THE
PIR MOVEMENT DETECTORS
Ensure that the system is in Test mode, (see page 18).
1. Undo and remove the fixing screw from the
bottom edge of the PIR. Carefully pull the bottom
edge of the detector away from the rear cover and
then slide down to release the top clips.
2. Carefully drill out the required mounting holes in
the rear cover using a 3mm drill according to
whether the unit is being mounted in a corner or
against a flat wall.
3. Using the rear cover as a template, mark the
positions of the fixing holes on the wall.
4. Fix the rear cover to the wall using the two 18mm
No.4 screws and 25mm wall plugs, (a 5mm hole
will be required for the wall plugs). Do not over-
tighten the fixing screws as this may distort or
damage the cover.
Note: The wall plugs supplied with the product are
not suitable for plasterboard walls, if mounting the
Detector Panel onto plasterboard use proprietary
wall plugs.
5. Configure the House Code for the PIR Detector by
setting DIP switches 1-8 of SW2 to the same
ON/OFF combination as the House Code DIP
switches in all other system devices.
6. Configure the alarm zone which the detector will
operate on by setting DIP switches 1-3 of SW3 as
follows:
DIP 1 DIP 2 DIP 3
Zone 1 OFF OFF OFF
Zone 2 OFF OFF ON
Zone 3 OFF ON OFF
Zone 4 OFF ON ON
Zone 5 ON OFF OFF
Zone 6 ON OFF ON
7. DIP 4 of SW3 is used to configure the PIR Detector
for walk test mode, which allows the operation of
the detector to be checked during installation
without triggering a Full Alarm.
ON Walk Test mode
OFF Normal operation
Note: On initial installation the detector should be
configured into Walk-Test mode ready for testing.
8. The PIR Detector incorporates an anti-false alarm
feature designed to compensate for situations where
the detector may be affected by environmental
changes, (e.g. insects, air temperature, etc). This
feature is called "Pulse Count" and may be selected
for 1 or 2 pulse detection.
The recommended setting is for 1 pulse detection.
However, in cases of extreme environmental
problems or if unattributable false alarms are
experienced, it may be necessary to select 2 pulse
detection.
11
Mounting Hole
Positions
Fixing
Screw
Rear Cover

To select the required pulse count set DIP 5 of
SW3 as follows:
ON 1 pulse detection
OFF 2 pulse detection
Note: The higher the Pulse Count the more
movement will be necessary before the PIR
detector will trigger the alarm.
9. Connect the PP3 Alkaline battery to the battery
clip.
Note: When the 9V Alkaline battery is connected
the LED behind the lens will rapidly flash for
approximately 2-3 minutes until the PIR has
warmed-up and stabilised. The LED will then stop
flashing and turn OFF.
10.
Check that the detector PCB is located and set in
the correct position to give the detection zone
pattern required.
To adjust the PCB position simply slide it up or down
ensuring that the location legs are aligned with the
required position number marked on the board.
PCB Position Range
16m
39m
512m
11.
Refit the PIR detector to the rear cover by offering
the detector up to the rear cover and locate the
clips in the top edge into the rear cover. Push the
lower edge of the detector into place and refit the
fixing screw in the bottom edge of the PIR to
secure in position. Do not over-tighten the fixing
screws as this may damage the casing.
TESTING THE PIR MOVEMENT
DETECTORS
Ensure that the system is in Test mode, (see page 18).
Ensure that the PIR is configured in Walk Test mode,
(i.e. DIP 4 of SW3 ON) and mounted in position on
the wall.
Allow 2-3 minutes for the detector to stabilise before
commencing testing.
1. Put the Control Panel into "Walk Test" mode by
pressing on the Control Panel.
The Panel will beep and the Zone 1 LED will
illuminate.
2. Walk into and move slowly around the protected
area, each time the detector senses movement the
LED behind the lens will flash. In addition, the
Control Panel will bleep twice to indicate that the
alarm signal has been received and the
appropriate zone LED which the detector is
configured for will illuminate.
Note: In normal operation, the LED will not flash
on movement detection. If necessary re-adjust the
detection pattern by changing the mounting
position of the PCB within the PIR housing.
3. Press on the Control Panel to exit Walk
Test mode.
4. Reconfigure the PIR Detector into Normal
operation mode and refit in position.
Note: When the detector is fully installed i.e. battery
cover is refitted; the unit will not detect movement
for approximately 45 seconds after each activation.
(This feature is present to conserve battery power
and maximise the battery life).
MAGNETIC CONTACT
DETECTOR(S)
OPTIONAL ACCESSORY - See page 30 for
details of accessories available.
The Magnetic Contact Set comprises two parts; a
Detector and a Magnet. They are designed to be
fitted to either doors or windows with the Magnet
screwed to the moving/opening part and the Contact
screwed to the fixed door or window frame.
12
DIP Switches
(SW2 and SW3)
PCB Board
(slides up and
down to adjust
position)
5
4
3
2
1
PCB Position
Indicator
(positions 1-5)
ON
1 2 3 4 5 6 7 8
ON
12345
SW3SW2
1
ESC

When the protected door or window is closed the
Detector Contact Switch is held closed by the
Magnetic field from the Magnet. Opening the
protected door or window will remove the magnetic
field and allow the Contact Detector Switch to open
generating an alarm signal, (if the system and alarm
zone is armed).
The Magnetic Contact Detector has the facility to
connect an additional wired Magnetic Contact. This
additional contact must be of a normally closed
contact type with the contacts being opened in order
to generate an alarm condition.
Any number of Magnetic Contact Detectors can be
used with the system, providing they are all coded
with the system House Code and are mounted within
effective radio range of the Control Panel.
The Magnetic Contact Detector is powered by two
CR2032 type Lithium cells which under normal
conditions will have an expected life in excess of
1 year. Under normal battery conditions the LED on
the Detector will not illuminate when the Detector is
triggered, (unless in test mode). However, under
low-battery conditions this LED will be illuminated
for approximately 1s when the detector is triggered.
When this occurs the batteries should be replaced
as soon as possible.
POSITIONING THE MAGNETIC
CONTACT DETECTORS
The Magnetic Contact Detector is suitable for
mounting in dry interior locations only.
Decide which doors and windows are to be
protected by fitting Magnetic Contact Detectors,
(usually the front and back doors as a minimum will
have Magnetic Contact Detectors fitted). However
additional detectors may be fitted where required to
other more vulnerable doors or windows, (e.g.
garage, patio/conservatory doors etc).
Ensure that the position selected for the Magnetic
Contact detector is within effective range of the
Control Panel. It is recommended that prior to
installation the detector is configured and tested with
the Control Panel in Walk test mode to ensure that
they are within effective range.
Note: Take care when fixing the Detector to a metal
frame, or mounting within 1m of metalwork (i.e.
radiators, water pipes, etc) as this could affect the
radio range of the device. If required, it may be
necessary to space the magnet and detector away
from the metal surface using a plastic or wooden
spacer to achieve the necessary radio range.
INSTALLING AND CONFIGURING THE
MAGNETIC CONTACT DETECTORS
Ensure that the system is in Test mode, (see page 18).
1. Remove the battery cover by sliding and lifting it
off. (DO NOT use a screwdriver to lever off).
2. Remove the battery holder by carefully tilting up
the end and pulling the connector off of the
printed circuit board.
3. Mount the Detector to the fixed part of the frame
along the opening edge opposite the hinges
using either the double sided adhesive tape or
screws provided.
When fixing the Detector with screws the top of
the Detector is secured with a keyhole slot over
the screw head of the smaller pan head screw.
The bottom is secured using the 12mm
countersunk head screw fitted within the battery
compartment. Carefully drill out the centre of the
fixing screw hole in the battery compartment
using a 3mm drill. Do not over-tighten the fixing
screws as this may distort or damage the casing.
4. Fit the Magnet to the moving part of the
door/window opposite the Detector using the
two 15mm fixing screws. Ensuring that the
13
Double Sided Tape
OR Screw Fixing
Raised Head Screw,
Key-hole Slot Fixing
Small Counter-sunk
Screw Fixing
Battery
Connector Tilt and Remove
Battery Holder
and Insert
Two Batteries
Slide Open and Lift Off
Do Not Use A Screwdrive
r

parallel gap between the Magnet and Detector
is less than 10mm and that the arrow on the
Magnet is pointing towards and aligned with the
mark on the top section of the Detector.
5. If an additional wired Magnetic Contact is
required, this should be wired to the terminal
block provided in the battery compartment. The
wired contact should be connected using two
core (24AWG) wire of maximum length 1.5m.
If an additional wired contact is connected to the
Detector then jumper link S2 on the PCB must
be removed.
IMPORTANT: If an additional wired contact is
not connected, then the jumper link SW2 must
be fitted for the detector to operate correctly.
6. Configure the House Code for the Magnetic
Contact Detector by setting DIP switches 1-8 to
the same ON/OFF combination as the House
Code DIP switches in all other system devices.
7. Configure the alarm zone which the detector will
operate on with DIP switches 9-11 as follows:
DIP 9 DIP 10 DIP 11
Zone 1 OFF OFF OFF
Zone 2 OFF OFF ON
Zone 3 OFF ON OFF
Zone 4 OFF ON ON
Zone 5 ON OFF OFF
Zone 6 ON OFF ON
8. Slide the batteries supplied into the battery holder,
ensuring that the positive (+) side is uppermost on
each battery as it is installed.
9. Carefully refit the battery holder onto the Detector
ensuring that the spring connectors slide onto
either side of the circuit board.
10.
Fit the battery cover into position on the Detector.
TESTING THE MAGNETIC CONTACT
DETECTORS
Ensure that the system is in Test mode, (see page 18).
1. Put the Control Panel into "Walk Test" mode by
pressing on the Control Panel.
The Panel will beep and the Zone 1 LED will illuminate.
2. Remove the battery cover from the Detector.
The LED on the Detector will illuminate for approx.
1s as the battery cover is removed and the tamper
switch is activated. In addition, the Control Panel
will beep twice to indicate that the alarm signal has
been received and the Tamper LED will illuminate.
3. Open the door/window to remove the magnet from
the Detector.
As the magnet is moved away from the detector
the LED will illuminate for approximately 1s to
indicate that the Detector has been triggered. In
addition, the Control Panel will beep twice to
indicate that the alarm signal has been received
and the appropriate zone LED, which the detector
is configured for, will illuminate.
4. If any external Magnetic Contact Sets are
connected to the Detector, operate these one at a
time. Each time a contact is opened the LED on
the Detector should illuminate for 1s to indicate
that it has been triggered.
14
(Ensure back
s
urfaces are flush)
Detector
Magnet
Alternative
Mountin
g
House Code
Location of
Key-hole Screw
(underside)
Hole for
Mounting
Screw
Zone
Terminal Block for Additional
Wired Magnetic Contact
Jumper
Link S2
Anti-Tamper
Switch
1

5. Replace the battery cover on the Detector.
6. Press on the Control Panel to exit Walk Test
mode.
EXTERNAL SOLAR SIREN
The Siren and
Solar Panel are all encapsulated within a
tough polycarbonate housing. This housing provides
full protection against adverse weather conditions.
An LED/Strobe unit is built into the siren to act as a
visible deterrent/indication that the system is active.
The Strobe LEDs will slowly and alternately flash
whether the system is Armed or Disarmed. During an
alarm condition the Strobe LEDs will flash rapidly.
An integral anti-tamper switch provides additional
security protection to the Siren and will immediately
generate a full alarm should any unauthorised attempt
be made to interfere with and remove the siren cover.
The Siren is powered by a high capacity 6V/1.2Ahr
rechargeable sealed lead acid battery. A Solar Panel
mounted on the top of the housing charges the battery
during daylight hours. During darkness, only a small
amount of energy is required to operate the Siren unit.
A 9V Alkaline PP3 battery is supplied in the External
Siren to boost the initial power to the unit when the
system is first activated until the Solar Panel charges
the main battery.
POSITIONING THE SOLAR SIREN
The Siren should be located as high as possible in a
prominent position so that it can be easily seen and
heard. The Siren should be mounted on a sound flat
surface so that the rear tamper switch is not activated
when mounted. Ensure that the tamper switch does
not fall into the recess between brick courses as this
could prevent the switch from closing and give a
permanent tamper signal.
To provide the optimum amount of daylight to the
Solar Panel, you should ideally mount the Solar Siren
on a south facing wall. However, an easterly or
westerly position will suffice.
Although the Solar Siren is designed to work on any
aspect wall, for optimum performance you should
refrain from siting the unit on a north facing wall,
where possible.
Shadows cast by neighbouring walls, trees and roof
overhangs should also be avoided. If the Siren is to be
mounted below the eaves, it should be positioned a
distance of at least twice the width of the eaves
overhang below the eaves. Remember that in winter
the sun is lower in the sky and you should avoid winter
shadows where possible.
The External Solar Siren contains a sophisticated
radio receiver. However, reception of radio signals can
be affected by the presence of metallic objects within
the vicinity of the Solar Siren. It is therefore important
to mount the Solar Siren a minimum distance of 1m
away from any external or internal metalwork, (i.e.
drainpipes, gutters, radiators, mirrors etc).
Ensure that the position selected for the Solar Siren is
within effective range of the Control Panel. It is
recommended that prior to installation the Solar Siren
is configured and tested with the Control Panel to
ensure that they are within effective range.
15
ESC

INSTALLING AND CONFIGURING THE
SOLAR SIREN
1. Remove the fixing screw from the bottom edge of
the Siren housing and carefully hinge off the front
cover. All electronic components are housed within
the front cover.
2. Hold the mounting plate in position and mark the
positions of the four mounting holes. A spirit level
placed on the casing will ensure a perfect level.
Drill four 6mm holes and fit the wall plugs.
3.
Fit the two 30mm fixing screws in the top holes
leaving approximately 10mm of the screw protruding.
4. Fit the top keyhole slots of the mounting plate over
the screw heads. Remove the mounting plate and
adjust the screws until they form a neat fit with the
mounting plate with minimal movement.
5. Secure the mounting plate in position using the
two 25mm fixing screws in the bottom fixing holes.
6. Ensure that the Solar Siren main configuration
switch on the LED strobe board is set to "SIREN"
for use with this alarm system.
7. Undo the 3 screws holding the DIP Switch Cover
in place and remove the cover.
8. Under the cover you will find a series of 9 DIP
switches.
Note: When the Solar Siren is viewed as shown
above (Solar panel at top) the DIP switches are
‘upside down’.
9. DIP switches 1-8 are used to set the House Code
for the Siren and must be set to the same ON/OFF
combination as all other system devices.
10.
If required the maximum length of time that the
External Solar Siren will sound for when activated
under an alarm condition may be limited to 3
minutes using DIP switch 9 as follows:
OFF 3 minutes
ON as Control Panel setting
16
Tamper
switch
6 Volt 1.2Ahr
rechargeable
battery
9 Volt PP3 initial
power up battery
Siren
Printed circuit
board enclosure
Receiver
Aerial DIP switch
cover
Alarm duration
DIP switch 9
House Code
DIP switches 1-8
7.5 Volt DC
charging adaptor
input
Front cover
locating tabs
Beep Disable Lin
k
Siren Disable Link
Strobe PCB
Solar Panel
C.U.
Main Configuration Switch
(in SIREN Position)
SIREN
C.U. SIREN
Inside View of Siren
Alarm Duration DIP switch 9
(Always change from the factory setting)
House Code
Main Configuration Switch
(in SIREN Position)
C.U. SIREN

11.
The Solar Siren will acknowledge Disarm signals
from the Remote Control and Service Mode
signals from the Control Panel by beeping. It is
possible to disable these acknowledgement beeps
if required by removing the jumper link P2 on the
circuit board.
P2 fitted beep enabled
P2 removed beep disabled
12.
If for any reason you need to disable the Siren,
remove jumper link P3 on the circuit board. This
will prevent the Siren from sounding during an
alarm condition. However, the Siren will still beep
to acknowledge signals from the Remote Control,
(provided the beep feature is not disabled).
P3 fitted Siren enabled
P3 removed Siren disabled
13.
Refit the DIP switch cover and replace the three
cover fixing screws. Do not over tighten the screw
as this could damage the thread.
POWER-UP OF THE SOLAR SIREN
1. Connect the 9V PP3 initial power battery to the
battery clip.
Connect the rechargeable battery to the charging
leads. Connect the Red lead to the Red (+ve)
terminal and the Black lead the Black (-ve)
terminals.
IMPORTANT: Once the batteries have been
connected, the Siren will be operational and it is
important that the solar panel receives sufficient
light to maintain the battery charge. The Siren
should not be operated repeatedly during
installation and testing, as this will rapidly drain the
battery. It is recommended that the Siren be left for
at least a day in order to charge the battery before
the system is Armed.
2. Press the anti-tamper switch, the LEDs will flash
together to indicate that the unit is operational.
3. Hinge the front cover locating tabs over the top
edge of the back plate and carefully push the base
of the siren cover into place. Secure the Siren
cover in place by refitting the fixing screw in the
bottom edge of the cover. Do not over tighten the
screw as this could damage the thread.
IMPORTANT: Ensure that the rear tamper switch
is closed when you fit the siren cover to the back-
plate (i.e. listen for the switch to click). If the switch
does not close this will prevent the Solar Siren
from operating correctly. If necessary, remove the
siren cover again and adjust the screw on the
back-plate tamper plunger to ensure the switch
closes when the Siren is secured in position.
4. If fitted remove the protective film covering the
Solar Panel.
TESTING THE SOLAR SIREN
Ensure that the system is in Test mode, (see page 18).
1. Press on the Control Panel.
The Control Panel alarm and Solar Siren will
operate for a period of approximately 5 seconds
with the Solar Siren switching ON and OFF a few
seconds after the Control Panel.
Note: To stop the siren test before the 5s period
has elapsed press on the Control Panel.
17
3
ESC

EXTERNAL
CONNECTIONS
The Control Unit incorporates a terminal block for
connection of an external Hard-wired Siren or
Telephone Dialler unit. The connection terminal
block is located inside the Control Panel behind the
front cover.
To access the terminal block, press
, ,
This puts the system into Test Mode and prevents an
alarm occurring. Undo the two fixing screws on the
top edge of the Control Panel and open the front cover.
Before making any connections, ensure that the
memory jumper link P1 is in the ’OFF’ position and
then remove the DC power jack and disconnect the
back-up batteries.
Note: Jumper link P51 should be fitted into the ON
position only if the tamper circuit for a hardwired siren
is used, otherwise it must be in the OFF position.
After making your external connections reconnect the
power supply and Back-up Battery. Then close the
Control Panel cover and tighten the fixing screws on
the top edge of the Control Panel.
Press to leave Test mode and return to Standby.
TESTING THE SYSTEM
INITIAL TESTING
As the system is initially installed it is recommended
that each device is tested in turn as it is installed, (refer
to testing instructions for particular device).
TESTING AN INSTALLED SYSTEM
The Control Panel has a programmed test routine.
You may test the system at any time, however it is
recommended that the system is tested at regular
intervals not exceeding 3 months.
With the system in Standby Mode with the Power
LED ON.
Press , ,
The Arm and Part-Arm LEDs will flash.
The system is now in the Test Mode
Note: After completing all required test functions
press to leave Test mode and return to Standby.
DETECTOR TEST
Before commencing testing please ensure that there
is no movement in any PIR protected area, all
doors/windows protected by Magnetic Contact
Detectors are closed and that all battery covers are
correctly fitted.
Press
Zone LED 1 will illuminate.
Trigger each detector on the system by either walking
into a PIR protected area or by opening a
door/window protected by a Magnetic Contact
detector. As each detector is triggered the Control
Panel will beep and the LED of the zone which the
detector is configured for will be illuminated. The
Tamper switches of devices may also be tested in the
same way in which case the Tamper Led on the
Control Panel will be illuminated.
Press to exit detector test
18
ESC
ESC
User Access Code
Permanent
12Vdc power
supply output
(100mA max.)
V+
GND
Latching
relay contacts
(Volt-free)
N.O.
C
N.C.
Not Used
GND
B+
GND
TAMP
Switched
12Vdc output for
external Siren
(300mA max.)
GND
OUT
Terminal
Block
Reset
Jumper
Link P1
External Tamper Switch
Jumper Link P51
Tamper circuit
connections for
hardwired siren
Terminal Block Detail
Normally closed
tamper contact
Hardwired
Siren
TAMP GND B+ GND N.C. C N.O. GND V+ OUT GND
1
ESC
? ? ? ?
ENTER
User Access Code
? ? ? ?
ENTER
Table of contents
Other FRIEDLAND Security System manuals

FRIEDLAND
FRIEDLAND SA5 User manual

FRIEDLAND
FRIEDLAND Bronze Installation instructions

FRIEDLAND
FRIEDLAND MA7 User manual

FRIEDLAND
FRIEDLAND MA6 User manual

FRIEDLAND
FRIEDLAND MA10 User manual

FRIEDLAND
FRIEDLAND Spectra Plus L430N BLK User manual

FRIEDLAND
FRIEDLAND SA1 Installation instructions

FRIEDLAND
FRIEDLAND SA5 Installation instructions

FRIEDLAND
FRIEDLAND MA2 User manual

FRIEDLAND
FRIEDLAND PA4 Installation instructions