manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ADEMCO
  6. •
  7. Security System
  8. •
  9. ADEMCO Alpha Vista 5130XT User manual

ADEMCO Alpha Vista 5130XT User manual

This manual suits for next models

1

Other ADEMCO Security System manuals

ADEMCO LYNXR User manual

ADEMCO

ADEMCO LYNXR User manual

ADEMCO 4286 - Ademco Phone Module User manual

ADEMCO

ADEMCO 4286 - Ademco Phone Module User manual

ADEMCO VISTA-20PS User manual

ADEMCO

ADEMCO VISTA-20PS User manual

ADEMCO VISTA 10 User manual

ADEMCO

ADEMCO VISTA 10 User manual

ADEMCO 5800WAVE Assembly instructions

ADEMCO

ADEMCO 5800WAVE Assembly instructions

ADEMCO Vista AT User manual

ADEMCO

ADEMCO Vista AT User manual

ADEMCO via30+ User manual

ADEMCO

ADEMCO via30+ User manual

ADEMCO Vista-10 User manual

ADEMCO

ADEMCO Vista-10 User manual

ADEMCO VISTA-50P User manual

ADEMCO

ADEMCO VISTA-50P User manual

ADEMCO VIA-30PSE User manual

ADEMCO

ADEMCO VIA-30PSE User manual

ADEMCO Security System VISTA-10SE User manual

ADEMCO

ADEMCO Security System VISTA-10SE User manual

ADEMCO TI110B1 User manual

ADEMCO

ADEMCO TI110B1 User manual

ADEMCO VISTA-32FB Assembly instructions

ADEMCO

ADEMCO VISTA-32FB Assembly instructions

ADEMCO VISTA-20SEA User manual

ADEMCO

ADEMCO VISTA-20SEA User manual

ADEMCO Alert II User manual

ADEMCO

ADEMCO Alert II User manual

ADEMCO VISTA User manual

ADEMCO

ADEMCO VISTA User manual

ADEMCO Vista-10SEa User manual

ADEMCO

ADEMCO Vista-10SEa User manual

ADEMCO VISTA-32FB User manual

ADEMCO

ADEMCO VISTA-32FB User manual

ADEMCO VISTA-20P Series User manual

ADEMCO

ADEMCO VISTA-20P Series User manual

ADEMCO 4140XMPT2 User manual

ADEMCO

ADEMCO 4140XMPT2 User manual

ADEMCO LYNXR24 User manual

ADEMCO

ADEMCO LYNXR24 User manual

ADEMCO Security System VISTA-10SE Operating instructions

ADEMCO

ADEMCO Security System VISTA-10SE Operating instructions

ADEMCO VISTA-250BP Assembly instructions

ADEMCO

ADEMCO VISTA-250BP Assembly instructions

ADEMCO Vista-20 User manual

ADEMCO

ADEMCO Vista-20 User manual

Popular Security System manuals by other brands

Polon-Alfa 4000 Installation and maintenance manual

Polon-Alfa

Polon-Alfa 4000 Installation and maintenance manual

Nexcom NViS 14162 Series user manual

Nexcom

Nexcom NViS 14162 Series user manual

Eminent EM8670 Quick install

Eminent

Eminent EM8670 Quick install

urmet domus alpha 1060 INSTALLATION AND USE BOOKLET

urmet domus

urmet domus alpha 1060 INSTALLATION AND USE BOOKLET

SmartPool YardGuard YG03 manual

SmartPool

SmartPool YardGuard YG03 manual

DSC PC5964 Mounting instructions

DSC

DSC PC5964 Mounting instructions

Secure USAB-1 operating instructions

Secure

Secure USAB-1 operating instructions

B&B 480 SERIES Operation & maintenance manual

B&B

B&B 480 SERIES Operation & maintenance manual

Inner Range Concept 2000 user manual

Inner Range

Inner Range Concept 2000 user manual

Johnson Controls PENN Connected PC10 Install and Commissioning Guide

Johnson Controls

Johnson Controls PENN Connected PC10 Install and Commissioning Guide

Aeotec Siren Gen5 quick start guide

Aeotec

Aeotec Siren Gen5 quick start guide

Swann SW-P-MC2 Specifications

Swann

Swann SW-P-MC2 Specifications

Ecolink Siren+Chime user manual

Ecolink

Ecolink Siren+Chime user manual

EDM Solution 6+6 Wireless-AE installation manual

EDM

EDM Solution 6+6 Wireless-AE installation manual

Siren LED GSM operating manual

Siren

Siren LED GSM operating manual

Detection Systems 7090i Installation and programming manual

Detection Systems

Detection Systems 7090i Installation and programming manual

FRIEDLAND MA10 Installation and operating instructions

FRIEDLAND

FRIEDLAND MA10 Installation and operating instructions

Se-Kure Controls MicroMini SK-4841 instructions

Se-Kure Controls

Se-Kure Controls MicroMini SK-4841 instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

INSTALLATION INSTRUCTIONS
7
ADEMCO ALPHA VISTA
\
NO. 5130XT
SECURITY SYSTEM I
N3122-3 3/89
Previous Menu
“. .-----
Specifications ............................ ....... ...... ...... . ... ... . ....... . .... ... .. . .. .. .... . .... ............... 86
5130XT Security Control ............................................. . 86
4171XTDigital Communication interface Board . . . ... ..... ...... .. ... .. . .. ..... . . .. ... . .... . ..... 86
5137 Remote Console ... ...... ...... ....... .... . .. ... ...... .... .. ...... .... .. .... .. . . 86
4131 Remote Keypad ..... ...... ...... ...... ....... ..... ...... ...... . .. . ... . ....... .. . . . . . .... .. ... 87
4152LM Loop Module ...................... ...... .............. ...... . . 87
4208 Zone Expander ............................................................. . .. 87
The Limitations ofthis Alarm SyWem ....... . .... ...... .. . . . .... . .... .. ... .. . .. .. . . . . . .... .. ....... .. 91
Limited Warranty . .... . ...... ....... ...... ... .. ...... ..... ... . ....... .... . . ... ...... .. .... .. .... ............ 93
Appendix A. Cabinet Mounting, ....... ....... ........ . ... ... . ... . .. .... ...... ... .. . .... ... .. .... . 88
Diagrams
Diagraml.
Diagram 2.
Diagram 3.
Diagram 4.
Diagram 5.
Diagram 6.
Diagram 7.
Diagram 8.
Diagram 9.
Diagram 10.
Summary of Connections ......................................................................................................... 17
24-Pin Connector with Flying Leads
(5130XT Field Wiring interface) ... ....... ...... .... .... . . .... . . .. ...... ....... . . . ...... .. 18
KeyswitchWiring .,.......,,.,.,..,,.. .... ...... ....... ...... ...... ...... .. . .. . .. . .... . . . .... 19
Installing the Digital Communication
interface Board (4171 XT) ....... ...... ...... ...... . ... ....... ...... .. .... ... . . . .. .... . .... .. 21
4152LMlnstaHation and Wiring to4208 ..... .... .. ...... .. ... .... . .. .... .. .... ..... ....... .... .. .. 22
5130XTConnection interfacing and 4171XTWiring Connections 25
Inserting Nameplate ................................................................................................................ 26
Wall Preparation for Flush Mounting 28
Flush Mounting the5130XT/5137/4137 . . 29
Removing Main Circuit Board for Fuse Replacement .. . ....... ...... ..... .. ...... ... .. . . . .. . .. 83
Templatefor Mounting the5130XT/5137/41 37 (provided onseparate sheet)
The ALPHA VISTA 5130XT is amicroprocessor-based security control
which provides up to 9wired zones in the basic product, with expansion
to an additional 8wired zones when connected to a2-wire zone expan-
sion bus driven by the optional No. 4152LM Loop Module. The security
control is housed in awall-mounted plastic enclosure measuring only
8.4” (21.3 cm) wide x4.75” (12 cm) high x1.1” (2.8 cm) deep, and is
equipped with amultifunction 12-key digital keypad, a2-line, 32-
character multipurpose LCD English language display and a built-in 85
db piezoelectric sounder that meets UL requirements as an alarm
sounder (an external sounder is therefore optional), Connections to the
security control are made via a24-pin plug-in connector equipped with
flying leads which interface to the wired loops, plug-in DC Power Pack,
back-up battery, optional external alarm sounder, etc.
The security control can be easily programmed from its own keypad, or
from an optional 5137 or 4137 remote console; the control can also be
programmed locally from the 699 Programmer (using a695-30XT car-
tridge). Programmed options to establish specific alarm and reporting
features are stored in electrically erasable, non-volatile EEPROM
memory. This means that the unit can be reprogrammed many times
(unlike units equipped with PROMS) and that information which has been
programmed will not be lost in the event of acomplete loss of power, For
installer convenience, the control is factory-programmed to aset of
values that is designed to meet the needs of many installabons. However,
these can be altered by the installer 10suit the specific needs of apaflic-
ular installation or installation company, following the instructions pro-
vided in the programming section of this manual (factory-programmed
values are also shown there).
This system also contains abbreviated operating instructions in memory,
designed primarily as an aid to the end user. This feature, which func-
tions when the system is in the armed or the disarmed mode, is activated
by simply pressing any of the function keys for 5seconds. The display on
the control will then scroll information related to the use of that function.
Aplug-in Communication Interface board (4171XT) provides communi-
cation capability (central station reporting, etc.) over existing telephone
lines as well as zone expansion connections.
An optional, economical, remote keypad (4131) can be used for arming,
disarming, etc., from aremote indoor location within the protected premises.
This unit is acompact 12-button keypad with two system status indicators
(LEDs) and a built-in piezoelectricsounder that provides warning and alarm
sounds. Requires a10-wire connection to reconnection to the control.
An optional remote console (4137) pmwdes functions similar to that of
the 5137 with one notable exception. It utihzes an LCD display that dis-
plays numerics for zone identification and predefine words for mode,
status, and alarms.
Acomplete list of optional accessories will be found in asection toward
the end of this manual under the heading “Optional Accessories” (see
Index).
Zone Characteristics
Zone 1: Programmable Zone, may be used as EOLR supervised Fire
Zone (supports 2-wire Smoke Detectors) or for non-fire usage,
or may be used as anon-fire zone with N.C. contacts only
350-500 msec response.
Zones 2-8 Programmable Zones, EOLR supervised, 350-500 msec
response.
Zone 9: Programmable Zone, N.C. contacts only, fast 10-15 msec
response.
Back-up 12V DC Battery DC Power Pack
Mounted externally, Aspecial backbox (4132) is available for mounting the Plug-in Power Pack (DC power converter), Plugs into unstitched 2-prong
battery in the wall behind the Control. Rechargeable 12-volt, 1.2 AH Lead
Acid. 110 volt AC outlet providing 24-hour service Power Pack (1350) supplies
unregulated 18V DC outpui (700 mA max) for powering the Control.
The No. 5130XT allows the installer to call it using switched network phone
lines so that the control/communicator can be remotely programmed and/
or commanded from aNo. 699MD Intelligent Programmer or an IBM com-
patible Personal Computer (PC). See Note 2under Remote Capabilities in
this section.
Accessing of the No, 5130XT from aremote location is protected against
compromise by someone attempting to defeat the system, using 4levels of
security protection
1. Security Code Handahake An 8-digit Central Station ID code must be
matched between the No. 5130XT and the Central Station.
2. Hang-up and call back Calling the No.5130XT does not directly allow
programming, as asuccessful handshake merely results in the No.
5130XT breaking the phone line connection and then calling back the
(internally stored) central station service phone number*.
3. Data Encryption: Data passed between the central station and the No.
5130XT ISencrypted for security so that it is very difficult for aforeign
device tapped mto the phone line to take over communication and sub-
stitute system compromising information.
*NOTE: In situations where aservice person is on site and the system is
installed inside aPABX, it is ~ossible to initiate adownload from
the protected premises by keying [installer or master security
code] +[#] +[1].
4. Central Station Advisory Note Any condition that causes the system
to initiate acall back to atelephone number from which Itcan be
reprogrammed or commanded (in fact, even for alocal reprogramming
of the EEPROM) causes aunique report to be sent to the central sta-
tion’s alarm logging digital receiver.
Equipment Required
At the premiaas
The No. 5130XT must be used with Its No, 4171 XT Communication inter-
face board if remote programming and/or control is desired,
At the centrai station (or the installer’s office/home):
●ANo 699MD Intelligent Programmer that incorporates an internal
modem and a No. 695-30XT Program Carfndge,
OR
●An IBM PC compatible computer, aModem (check with Ademco Fac-
tory Technical Support for the specific brand and model to be used),
No. 4130PC Downloading Software Dlakette, and appropriate inter-
connecting cables.
Remote Capabilities (See Note 2)
Programming:
All programming functions accessible from the unit’s keypad or via local
No. 699 direct programming.
Commanding:
There are two types of commands that can be issued to the system:
t. Control Commands
-To Arm the System in the Away Mode* (1)
-To Disarm the System’ (1)
-To Bypass aZone
-To Force the System to Accept aNew Program Download
-To Shut Down Communication (dialer) Functions (non-payment
of monitoring fees in an owned system)
-To Shut Down all Security System Functions (non-payment for a
leased system)
-To Inhibit Local Keypad Programming (prevents takeover of your
accounts)
2. Status Commands
-To Cause the System to Upload aCopy of its Resident Program to
the central station
-To Read System Status:
Arming Status
Ready Status and Current Faults
Presence of Alarms (pastor present)
Presence of Troubles (pastor present)
AC Power Status
Bypass Status and Current Bypasses
‘NOTES:
1, If the system is programmed for open/close repofling by user, User
#7 will be reported,
2. After the5130XT and the 699 or PC have established valid communi-
cation, each console will become inactive The 5130XT will resume
the normal security functions (including responding to faults that took
place during the downloading) after it is commanded to hang up. See
the 4130PC or 695-30XT instructions for details.
The detailed operation of the functions described below is covered in the
Installation Instructions for the No. 695-30XT Program Cartridge and for
the 4130PC Download Software Diskette.
-To Read List of Faulted Sensors
-To Read List of Bypassed Sensors
-To Read 10 Day Alarm History Log
-To Read 10 Day Trouble History Log
-To Read List of Sensors Currently in Alarm
-To Read List of Sensors Currently in Trouble
Remote Communication Specifications:
.Program Download Time -fminute for acomplete program
.Typical Total Time Including Call Up/Call-Back -3-4 minutes
Remote Command/Programming Advisory Notes:
.Alarm and Trouble Reporting are disabled during the time that the sys
tern and the central station are linked to each other for the described
functions, following avalid exchange of codes.
.Keypad entries are ignored during the same time Interval cited above.
●Should an alarm transpire during the remote program/control Interval, ●
the system would not respond to the alarm condition until the remote
mode was ended, The local zones and the Nos. 4139WH, 4190WH,
4192S0, 4194WH, 4196, 4208 and 4275 all store their fault conditions
until they are read by the Control, As such, alarm conditions from the
local and expansion zones would not be missed, only delayed
Acopy of the program downloaded may be produced from either the
No, 699 Intelligent Programmer or the IBM PC compatible computer,
using those products’ internal report generators, when an optional prin-
ter is connected.
For each zone used, one of the following zone types must be selected:
1.
2.
3.
4.
Entry/Exit Burglary (Delay #l). Assigned to sensors on doors
through which entry and exit will normally take place when the sys-
tem is armed.
Entry/Exit Burglary (Delay #2), May be set for different delay than
above. For use with sensors on overhead garage doors, etc., where
longer delay is needed 10reach the keypad in the main portion of
the house or building, and more delay is needed to exit the
premises.
Perimeter Burglary. Normally assigned to all sensors on exterior
doors and windows requiring instant alarm,
Interior, Follower. Delayed alarm only if the Entry /Extt zone IS
faulted first; otherwise, produces an instant alarm, Assigned to zone
covering an area such as afoyer or lobby through which one must
pass upon entry to reach the keypad to disarm the system.
Designed to provide instant intrusion alarm in the event an intruder
hides on the premises prior to the system being armed or gains
access to the premises through an unprotected area.
5. Trouble by Day/Alarm by night, Can be assigned to azone which
contains a-foil-protected d-oor& window (such-as in astore), or to a
zone covering a“senstive” area such as astockroom, drug supply
room, etc., or other controlled access area where immediate notifica.
bon of an entry is desired. During the disarmed state (day), the sys-
tem will provide latched Control/Console annunciation (and central
station report, if desired) of openings or troubles (such as sensor
malfunctions or foil breaks) During the armed state (night), viola-
tions will initiate an alarm.
6. 24-hour Silent Alarm. This type generally assigned to azone con-
taining an Emergency button that is designed to irutiate an alarm
report to the Central Station, but which produces no local displays
or alarm sounds.
7. 24-hour Audible Alarm. This type also assigned to azone contain-
ing an Emergency button, but which will initiate an audible alarm in
addition to an alarm report to the Central Station
8.
9.
24-hour Auxiliary Alarm (Control internal sounder only). This type 10. Interior that always has Entry/Exit Delay #1 (except that Entry
assigned to azone containing abutton for use in personal emer- delay is suppressed in the INSTANT mode). This type typically
gencies, or to azone containing monitoring devices such as water ass!gned to an interior zone containing aPIR that covers an area
sensors, temperature sensors, etc. Designed to initiate an alarm through which the user must pass to reach the Control for disarming
report to the Central Station and also provide Control/Console purposes (whether inside or first entering). ideal for an area such as
alarm sounds and alarm displays. an apartment entrance foyer in which akeypad is located.
Superslsed Fire [alarm on short/trouble on open).
The following isadescription ofthe vaflous zone types available which must be
selected for each physical zone.You may wish to use Table Aat the end of this
description to record your selections.
Type 1. BURGLARY ENTRYEXIT (DELAY #l): This zone type is not
enabled after arming until termination of the (EEPROM defined) Exit
delay #1. Upon entry, the Control will simply emit short beeps as a
warning that the system must be disarmed, If Code +OFF is not
entered before termination of the (EEPROM defined) Entry delay
#1, an alarm will be initiated at the built-in sounder, if program
enabled, and an external alarm and latched LCD display. A
system-wide EEPROM defined number of alarm reports for this
zone will be allowed to be transmitted (swinger suppression) in one
armed period, Restorals will be sent when the zone is restored for a
time greater than its physical response time (less than 1second).
During the disarmed state, afaulted zone will result in a
“DISARMED-Press Ato show faults” display. Subsequent
depression of the* key will cause all the descriptors of the faulted
zones to be sequentially displayed. No communicator reports will
be initiated.
Type 2.
Type 3.
BURGLARY ENTRY/EXIT (DELAY #2): This zone type is not
enabled after arming until termination of the (EEPROM defined) Exit
delay #2. Upon entry, the Control will simply emit short beeps as a
warning that the system must be disarmed. If Code +OFF ISnot
entered before termination of the (EEPROM defined) Entry delay
#2, an alarm will be initiated at the built-in sounder, if program
enabled, and an external alarm and latched LCD display. A
system-wide EEPROM defined number of alarm reports for this
zone WIIIbe allowed to be transmitted (swinger suppression) in one
armed interval, Restorals will be sent when the zone is restored for
atime greater than its physical response time (less than 1second).
During the disarmed state, afaulted zone will result n a
“DISARMED-Press *to show faults” display. Subsequent
depression of lhe *key WIIIcause all the descriptors of the faulted
zones to be sequentially displayed. No communicator reports will
be initiated.
BURGLARY PERIMETER While the System is armed, afaulted
zone WIIIinitiate an alarm at the built-in sounder, if program
Type 4.
enabled, and an external alarm, alatched LCD display, and a
(EEPROM selected) communicator report. Depression of any key
will silence the Control’s local alarm sounder for 10 seconds, A
system-wide EEPROM defined number of alarm reports for this
zone will be allowed to be transmitted (swinger suppression) by the
communicator in one armed period. The communicator will trans-
mit arestoral message when the zone is restored for atime greater
than its physical response time (less than 1second).
During the disarmed state, afaulted zone will result in a
“DISARMED-Praaa *to show faults” display. Subsequent
depression of the* key will cause all the descriptors of the faulted
zones to be sequentially displayed. No communicator reports will
be initiated.
BURGLARY INTERIOR, FOLLOWER: This zone will always
have Exit Delay W. The zone has an Entry Delay if preceded by a
fault man Entry/Exit zone (type #1 or #2). If not pracadad by an
Entry/Exit zone fault, an immediate audible local (Control) and
external alarm, latched display, and a (EEPROM selected) com-
municator report are initiated. Depressing any key at the Control
will silence the Control sounder for 10 seconds. Asystem-wide
EEPROM defined number of alarm reports for this zone will be
allowed to be transmitted (swinger suppression) by the communi-
cator in one armed period. The communicator will transmit ares-
toral message when the zone is restored for atime greater than its
phys!cal response time (less than 1second),
During the disarmed state, afaulted zone will result in a
“DISARMED-Press xto afrow faulta” display. Subsequent
depression of the* key will cause all the descriptors of the faulted
zones to be sequentially displayed, No communicator reperk will
be initiated,
Type 5.
TyfJs 6.
BURGLARY PERIMETER, TROUBLE BY DAY/ALARM BY
NIGHT During the disarmed state (day), faulting the zone will
initiate a‘trouble” display and a latched sounder (beeping), The
Control will beep rapidly along with alatched display of the faulted
zone and the word CHECK. Pressing any key will silence the beep-
ing for 10 seconds, Code +OFF will silence the beeping but will
only clear the display of azone that had the fault condition
removed.
Each trouble will result in a“trouble” report (if programmed). A
trouble restoral message will be sent as each zone is restored to
normal condition. The maximum number of trouble reports per
armed petiod will be limited by the system-wide EEPROM number
of alarm reports option (swinger suppression).
During the armed state (night), the local (Control) and external (if
used) alarm sounders will activate and the communicator will
report alarms, Asystem-wide EEPROM defined number of alarm
reports for this zone will be allowed to be transmitted in one armed
period. Restorals will be sent when the zone is restored for atime
greater than its physical response time (less than 1second).
24-HOUR SILENT ZONE: Sensors assigned to this zone, when
faulted, will initiate acommunicator report. There will be no local
displays or alarm sounds. Upon keying Code plus OFF, there will
be a memory indication of the faulted zone
Asystem-wide EEPROM defined number of alarm reports for this
zone will be allowed ‘to be transmitted (swinger suppression) by the
communicator until an OFF sequence is performed. The communi-
cator will transmit arestoral message when the zone is restored for
atime greater than its physical response time (less than 1second).
During the disarmed state, afaulted zone will result in a
“DISARMED-Prees Ato show faults” display. Subsequent
Type 7.
Type 8.
Type 9.
depression of the *key will cause all the descriptors of the faulted
zones to be sequentially displayed. No additional communicator
reports will be initiated.
The burglary portion of the system cannot be armed if this zone is
faulted. An OFF sequence (code plus OFF) should be performed
ptior to arming the system or viewing the faulted zones,
24-HOUR AUDIBLE ZONE: Faulting azone of this type will
initiate aloud audible alarm externally and at the Control, an LCD
display, and a (EEPROM selected) communicator report. Pressing
any key will silence the Control sounder for 10 seconds. Keying
Code plus OFF will permanently silence the alarm, Asystem-wide
EEPROM defined number of alarm reports for this zone will be
allowed to be transmitted (swinger suppression) by the communi-
cator until an OFF sequence is performed The communicator will
transmit arestoral message when the zone is restored for atime
greater than its physical response time (less than 1second),
24-HOUR AUXILIARY ZONE: Faulting azone of this type will
initiate asteady alarm sound at the Control, an ALARM display, and
a(EEPROM selected) communicator report Pressing any key will
silence the Control sounder for 10 seconds. Keying Code PIUSOFF
will permanently silence the alarm. Asystem-wide EEPROM
defined number of alarm reports for this zone will be allowed to be
transmitted (swinger suppression) by the communicator until an
OFF sequence is performed. The communicator WIIItransmit ares-
toral message when the zone is restored for atime greater than its
physical response time (less than 1second)
FIRE ZONE: Opens in this zone will result in “troubles”. Shorts will
result in alarms. Note: Zone 1will support 2-wire Smoke Detectors
Type +0.
(using the EOL resistor configuration), Zones 2through 8can be
used for heat detectors and pull stations and for 4-wire Smoke
Detectors with external (manual) power interrupt; Zone 9cannot be
used for Fire.
Fire zones may not be bypassed. Afire zone in trouble will not pre-
vent the burglary system from being armed in any mode.
Asystem-wide EEPROM defined number of alarm reports for this
zone will be allowed to be transmitted (swinger suppression) by the
communicator in one armed period. The communicator will transmit
arestoral message when the zone is restored (less than 1second,)
INTERIOR DELAY ZONE: This type of zone will always have Ent~
delay #1 and Exit delay #1. This zone is not enabled after arming
until termination of the (EEPROM defined) Exit delay #1. If this zone
is faulted, beeps will be emitted by the Control. If Code +OFF is not
entered before termination of the (EEPROM defined) Entry delay #l,
an alarm will be initiated Asystem-wide EEPROM defined number
of alarm reports for this zone will be allowed to be transmitted
(swinger suppression) by the communicator in one armed period,
The communicator will transmit arestoral message when the zone
is restored for atime greater than its physical response time (less
than 1second).
During the disarmed state, afaulted zone will result in a
“DISARMED-Press Xto show faults” display. Subsequent
depression of the *key will cause all the descriptors of the faulted
zones to be sequentially displayed No communicator reports will
be initiated.