Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
Installing a Selectronic Certified Fronius
Primo in a Managed AC Coupled system
INTRODUCTION
The SP PRO FRONIUS Selectronic Certified (SCERT) Primo Managed AC Coupling provides a
method of linking the single phase Fronius Primo range of grid tie inverters to the SP PRO via
the AC Load supply so that regardless of whether the grid or a generator is connected, the
SP PRO can manage and control the Fronius grid tie inverters.
Each SP PRO can manage a maximum of five Fronius grid tie inverters by commanding each
one to output the required amount of power to simultaneously supply the load, export to the
grid and charge the battery bank as required at any particular point in time. This is done via a
communications link between the SP PRO and the Fronius Primo.
This document only applies to Fronius SCERT inverters that have been pre-programmed by
Selectronic and details the additional steps needed to install the managed system.
The SP PRO and Fronius inverters must be installed as per their individual installation
instructions with the additional allowance of communications cables linking all of the inverters
together.
Note: This document needs to be read in conjunction with the SP PRO Instruction Manual and
the Fronius Primo Instruction Manual.
Only make adjustments to the Fronius configuration as indicated in this document.
The SP PRO SCERT Primo Managed AC coupling CANNOT be used with Fronius Smart
Meter. Refer to Appendix III: Fronius Smart Meter Configuration (page 50).
Must contact Fronius for the Profile Settings access code.
Series 2 SPPRO : Single and Multi Phase compatible.
Series 1 SPPRO : Single Phase Only!
For Fronius SCERT that need to be re-programmed see
Appendix II: Fronius Step Through Configuration (page 37)
ADDITIONAL INFORMATION
Selectronic web site –http://www.selectronic.com.au or contact the Selectronic Sales Team.
No SP PRO - Important information
If Fronius inverter is not connected to an SP PRO today see Fronius SCERT Backup
Ready Connection instruction (page 3).

IN0049 Revision 05 (005273) –2 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
Installation check list
The follow table summarises the steps taken to set up a Programed Fronius SCERT in a
Managed AC Coupled system. Once the system has been installed, use the following table to
check off that each step has been completed.
Refer to the pages following the tables for detailed information on each of the installation steps.
Installation step
Pages
SP PRO
Series 1
SP PRO
Series 2
1
Install SP PROs as per manual
2
Install and Configure batteries
Installing Fronius SCERT without an SP PRO
Inverter
3
3
Fronius Inverter must be Selectronic Certified
4,5 & 7
4
SP PRO Firmware Requirement - 9.09 or higher
7
5
Fronius AC Wiring
8
6
Communications Link (RS485) (Installed AC
Coupled Interface PCA)
10
6a
RS485 Communication connection between SP
PRO Inverter and Fronius Inverter - Series II
ONLY
13
6b
RS485 Communication connection between SP
PRO Inverter and Fronius Inverter - Series I
ONLY
14
7
Fronius Communications connection for Fronius
Inverter 01 (Master)
16
8
Fronius Communications link for multiple installed
Fronius Inverters
17
9
Configure SP PRO Inverter
Note: SP PRO Inverter must be configured via SP
LINK “Site Configuration Wizard” before
configuring Fronius Inverter
19
10
Configure the Fronius Inverter for the first time
20
11
Test system function
32
12
Step Through Config –for Fronius SCERT
that need to be re-programmed
37
13
De-configure Fronius Smart Meter
50
Table key: –Applicable
–Not Applicable

IN0049 Revision 05 (005273) –3 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
FRONIUS SCERT “BACKUP READY”CONNECTION
When Selectronic certified Fronius inverters are installed without an SP PRO, a link must be
fitted to the orange “Fronius Datamanager Connector” from the “+” pin to IO “2” pin so that
Fronius inverters can produce full power.
PLEASE NOTE:
a. The link is ONLY required when the Fronius inverter is installed without an SP PRO
inverter.
Link fitted in Fronius Datamanager connector without an SP PRO inverter connected

IN0049 Revision 05 (005273) –4 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
OVERVIEW –SERIES 2
The diagram below shows a managed AC coupled system with five FRONIUS inverters.
SYSTEM REQUIREMENTS
To successfully install a SP PRO FRONIUS managed system, there are particular system
requirements that need to be met.
Combined maximum AC output of all the connected Fronius inverters must be checked in
the SP LINK Wizard.
Battery bank must be sized to suit the SP PRO model and the combined maximum AC
Output power of the Fronius inverters, check the SP LINK Wizard.
The SP PRO must have firmware 9.09 or higher to support Fronius.
The Fronius Primo must be Selectronic Certified.
Maximum of five Fronius inverters per SP PRO.
To configure the SP PRO Fronius system, the Site Configuration Wizard in SP LINKs Easy Start
Guide must be used.
The Site Configuration Wizard calculates and shows the sizing for:
the maximum AC Coupled power, and
the battery bank sizing.

IN0049 Revision 05 (005273) –5 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
OVERVIEW –SERIES 1
SUITABLE FOR SINGLE PHASE SYSTEMS ONLY
The diagram below shows a managed AC coupled system with five FRONIUS inverters.
SYSTEM REQUIREMENTS
To successfully install a SP PRO Series I - Fronius managed system, there are particular system
requirements that need to be met.
To install an AC coupled system using a Series I SP PRO inverter an additional AC
coupling adaptor (stock code 005077) is required.
Combined maximum AC output of all the connected Fronius inverters must be checked in
the SP LINK Wizard.
Battery bank must be sized to suit the SP PRO model and the combined maximum AC
Output power of the Fronius inverters, check the SP LINK Wizard.
SP PRO inverters must have firmware version 9.09 or higher installed.
The Fronius Primo must be Selectronic Certified.
Maximum of five Fronius inverters per SP PRO
To configure the SP PRO Fronius system, the Site Configuration Wizard in SP LINKs Easy Start
Guide must be used.
The Site Configuration Wizard calculates and shows the sizing for:
the maximum AC Coupled power, and
the battery bank sizing.
Coupling adaptor

IN0049 Revision 05 (005273) –6 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
MINIMUM BATTERY CAPACITY FOR SOLAR HYBRID &OFF GRID SYSTEMS
Each application will have a minimum battery capacity and a maximum allowable PV, please
refer to the battery manufacturers data sheet as well as the guidance given in the SP LINK Site
Configuration Wizard.
Note:
a. For a Solar Hybrid (grid connected) system, the minimum battery capacity that must be
connected to the SP PRO varies depending on SP PRO model.
When the system is islanded (e.g. during a grid outage) the SP PRO will limit the output
of the AC coupled solar based on the actual installed battery size.
b. For an Off Grid system, the minimum battery capacity that must be connected to the SP
PRO varies depending on SP PRO model, an overriding minimum battery capacity and
the combined maximum Fronius Primo AC Output.

IN0049 Revision 05 (005273) –7 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
SP PRO FIRMWARE REQUIREMENTS
1. All SP PRO Revisions are supported.
2. SP PRO Software Version 9.09 or higher is
required. To check firmware revision run
SP LINK, connect to the SP PRO and go to
Data View –Technical Data –“SP PRO
Revision” and “Software Version”.
Older revisions of firmware must be updated
to firmware revision 9.09 or higher.
Do NOT change any configuration settings
until firmware is updated.
Data View –Technical Data screen
Note: Selectronic web site –http://www.selectronic.com.au for latest SP LINK software with the
SP PRO firmware included.
FRONIUS PRIMO MUST BE SELECTRONIC CERTIFIED
The Fronius Primo inverter must be Selectronic Certified.
Other Fronius Primo inverters will not operate correctly
with the SP PRO in a managed AC coupled configuration.
NOTE: DO NOT UPDATE FRONIUS PRIMO FIRMWARE or DATAMANAGER FIRMWARE

IN0049 Revision 05 (005273) –8 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
INSTALLATION
The SP PRO and Fronius inverters must be installed as per their respective installation
instructions. Particular instructions directly related to Managed AC Coupling are listed below.
It is good practice to number each Fronius inverter from 1 up to 5 so that each inverter can be
easily referenced within SP LINK.
Series 2 Only - In a Multi (three or split) phase AC coupled system label each Fronius inverter
L1-1 to L1-5 for the Fronius inverters connected to SP PRO L1, L2-1 to L2-5 for those connected
to L2 and so on.
This number 1 to 5 is used for the Communications Link addressing. See Configuration section.
FRONIUS AC WIRING
The Fronius AC output wiring must be connected to the AC Load terminals of the SP PRO in
accordance with local wiring rules for correct operation.
Fronius AC Wiring guide for Grid connected installation

IN0049 Revision 05 (005273) –9 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
Fronius AC Wiring guide for Off Grid connected installation
Note: The system will NOT function correctly if the Fronius inverters are installed on the
AC Source side of the SP PRO.

IN0049 Revision 05 (005273) –10 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
COMMUNICATIONS LINK (RS485)
The communication link always starts at the SP PRO and links to the “AC Coupled Interface
PCA”, then connects to the first Fronius Inverter (Master). The Fronius link is used to connect
subsequent Fronius inverters ON the same phase as the SP PRO. Do Not Connect Fronius
inverters on different phases together.
To install the AC Coupled Interface PCA, remove the bottom two screws from the Expansion
Card and replace them with the provided 2x stand offs. Then mount the AC Coupled Interface
PCA to the Expansion Card inside the SP PRO close to the Serial Communication PCA and
connect the connector with the two blue wires to J2 on the Expansion Card as illustrated.
Connect the RJ45 Connector lead from the AC Coupled Interface PCA “To RS485 Port
2” to the SP PRO Serial Communication PCA RS485 Port 2.
Connect the second RJ45 lead from the AC Coupled Interface PCA “To Other AC
Coupled Inverters” to Fronius Inverter 01 (Master), Fronius Datamanger connector
(see section “Fronius RS485 Connection to Inverter 01 (Master)” page 11).
Connect the AC Coupled Interface PCA power loom (12V) from AC Coupled Interface PCA
“12V DC Power J4” to the SP PRO Serial Communication PCA 12V connector.
Note: Do not connect any RJ45 leads to the AC Coupled Interface PCA “To ABB AC Coupled
Inverter” connector as the pin out is different to the Fronius Inverter connection.
To Fronius
Inverter 01
Expansion Card bottom screws
replaced with stand offs.

IN0049 Revision 05 (005273) –11 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
Fronius Communication link to SP PRO Green Communication Card
SP PRO Connections (inside unit) –RS485 Port 2 RJ45 connector to AC Coupled Interface PCA
and to Fronius Datamanager connector
Sync 1
Sync 2
RS485 Port 2
RS232 Port 2
RS232 Port 1
Green Communications
Card
Expansion
Card
Fronius Inverter
12V DC Power
AC Coupled Interface
PCA supplied with
Selectronic Certified
Grid Inverters
To RS485
Port 2
SP PRO Inverter
Fronius Inverter COM
Fronius
Datamanager
Connector
Fronius Solar Net
Connector
(IN/OUT)
To Other AC
Coupled Inverters

IN0049 Revision 05 (005273) –12 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
Fronius Communication link to SP PRO Blue Communication Card
The below communication connection applies to the Universal Battery Communications Kit
(Order Code 005295) and LG Chem Rack mount module Battery Communications Kit (Order
code 005298) if installed in SP PRO.
Expansion
Card
AC Coupled Interface
PCA supplied with
Selectronic Certified
Grid Inverters
SP PRO Inverter
Blue Communications
Card
12V DC Power
To RS485
Port 2
Sync 2
RS485 Port 2
RS485 Port 1
CAN
DRM
SP PRO Connections (inside unit) –RS485 Port 2 RJ45 connector to AC Coupled Interface PCA
and to Fronius Datamanager connector
To Other AC
Coupled Inverters
Fronius Inverter
Fronius Inverter COM
Fronius
Datamanager
Connector
Fronius Solar Net
Connector
(IN/OUT)

IN0049 Revision 05 (005273) –13 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
RS485 CONNECTION TO FIRST FRONIUS INVERTER (MASTER)–SERIES II
Using the supplied ‘CAT5’ network cable connect one end to the AC Coupled Interface PCA “To
Other AC Coupled Inverters” on the SP PRO. At Fronius Inverter 01 (Master), cut off the
non-connected RJ45 connector, expose and crimp the wires using wire crimps or
alternatively use a longer cable as required (not supplied) as outlined in the table below.
The Fronius link is used to connect subsequent Fronius inverters ON the same phase
as the SP PRO. Do Not Connect Fronius inverters on different phases together.
PLEASE NOTE: There are two different colour coding for RJ45 plugs, T568A and T568B, it is
common that either colour code is used. To ensure correct connections please check that the
“RS485 RJ45 Adaptor pin #” (see below table) corresponds to the “Fronius RS485 Connector”
connection by buzzing out the lead before connecting it to the Fronius or the SP PRO inverter.
RS485 RJ45 Adaptor Pin 1 designation Cut off one RJ45 Connector
(T568A colour code shown)
RS485 adaptor to Fronius connections and wire colours
Note: Only the wires connected to Pins 2, 3 and 6 (on the RJ45) are used.
RS485 RJ45
Adaptor pin #
Signal
T568A colour code
T568Bcolour code
Fronius RS485
Connector
1
GND
Green/White
Orange/White
2
GND
Green
Orange
- (minus)
3
RS485 - B
Orange/White
Green/White
D+ (RS485)
4
GND
Blue
Blue
5
GND
Blue/White
Blue/White
6
RS485 - A
Orange
Green
D- (RS485)
7
GND
Brown/White
Brown/White
8
GND
Brown
Brown
Pin 1

IN0049 Revision 05 (005273) –14 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
RS485 COMMUNICATION TO FIRST FRONIUS INVERTER (RS485) –SERIES I
The communication link always starts at the SP PRO end via Coupling Adaptor (Sena LTC100)
and then connects to the first Fronius inverter (Master). The Fronius link is used to connect
subsequent Fronius inverters ON the same phase as the SP PRO.
To install the Coupling adapter, use the RJ45 to DB9 lead and connect the Coupling adapter to
the SP PRO Series I Serial Port 2. Then using ‘CAT5’ network cable or similar make, connect
the Coupling adaptor to Fronius inverter 01 (Master) as per Table 1, Fronius Datamanager
connector.
Note: Ensure that the Sena LTC100 adaptor switch is set to RS485.
Table 1: Coupling Adaptor to Fronius connections and wire colours
Coupling Adaptor
Connections
Signal
T568A colour code
T568Bcolour code
Fronius RS485
Connector
RX-
Not Used
RX+
Not Used
GND
Ground
Green
Orange
- (minus)
TX- / TRX-
RS485 - A
Orange
Green
D- (RS485)
TX+ / TRX+
RS485 - B
Orange/White
Green/White
D+ (RS485)
Fronius Datamanager
Connector
Interface
Communication
IN/OUT

IN0049 Revision 05 (005273) –15 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
SP PRO Port 2 RJ45 connector to Sena LTC100 and to Fronius Datamanager connector
To SP PRO Port 2
via RJ45 to DB9
cable
Sena LTC100
adaptor to Fronius
invert 01 (Fronius
Datamanagement
connector)
Fronius
Datamanager
Connector
Set Sena LTC100
adaptor Switch to
RS485

IN0049 Revision 05 (005273) –16 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
FRONIUS CONNECTION
Connect the three wires from the CAT5 network cable to the Fronius Datamanager connector,
D+ (RS485), D- (RS485) and “-” (GND). The RS485 terminals are located on the right hand side
edge of the connector as illustrated.
Connection of AC Coupled Interface PCA “To Other AC Coupled Inverters” to Fronius
Datamanager connector, colour code T568A is shown above
For Fronius inverter 01 only, set the Master/Slave switch (located on the left hand side of the
orange connector) to “MASTER” as illustrated.
Master/Slave switch set to “MASTER” for Fronius inverter 01
Make sure that the Datamanager 2.0 plug-in card –IP switch is set to position B for Fronius
inverter 01 (Master) only.
The Datamanager 2.0 plug-in card –IP switch is set to position B
Note: Make sure that the “X” LED is Green for Fronius inverter 01. If the LED is Red then the
Fronius Solar Net Connector IN/OUT might not be connected correctly to all inverters (e.g.
correct connection: Fronius Inverter 01 OUT connected to Fronius Inverter 02 IN…etc), or
termination connectors are not fitted, or connectors are not plugged in correctly.
Fronius Datamanager
Connector
Master/Slave Switch
“X” LED must
be Green

IN0049 Revision 05 (005273) –17 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
CONNECTING FRONIUS LINK BETWEEN INVERTERS 02 TO 05
The following configuration outlines the connection for multiple Fronius Inverters to the Master
Fronius Inverter (Fronius Inverter 01). If only a single Fronius Inverter is installed, skip
to the next section page 19 (CONFIGURATION –ADDITIONAL SETTINGS).
Note: When connecting multiple Fronius inverters together it is important that the IP Switch
must be set to position B for Fronius inverter 01.
The Datamanager 2.0 plug-in card –IP switch is set to position B
Inside the Fronius Inverter there are two RJ45 connectors (Fronius Solar Net Connector) with
termination connectors installed. The Fronius Solar Net connectors are designed to interface
with multiple Fronius inverters in a daisy chain arrangement via the input “IN” and output
“OUT” connectors.
Fronius Solar Net Connectors with termination: “IN”located on LHS & “OUT”located on RHS
NOTE: The Fronius Solar Net Connector MUST be fitted to any unused connectors
otherwise the SP PRO will not communicate to any Fronius inverters in the system.
Using a network patch lead connect the “OUT”(Fronius Solar Net) from Fronius Inverter 01
(Master) to the “IN”of Fronius Inverter 02.
Fronius link - Fronius Inverter 01 “OUT”
Fronius Solar Net
Connectors
IN
OUT
OUT

IN0049 Revision 05 (005273) –18 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
Fronius link - Fronius Inverter 02 “IN” & Fronius Inverter “OUT”
(Fronius connection on intermediate inverters)
Using another patch lead, connect the “OUT”from inverter 02 (above) to the “IN”of inverter 03
and so on until all inverters in the system are connected.
Fronius link - Last Fronius Inverter on communication link (“IN”)
For all the inverters numbered 02 and above, set the Master/Slave switch (located on the left
hand side of the orange connector) to “SLAVE” as illustrated.
Fronius Inverters 02 to 05: Master/Slave switch set to “SLAVE”
Note: When Master/Slave switch is set to “SLAVE”, the LED’s on the Datamanager 2.0 plug-in
card will be OFF.
IN
OUT
IN
Master/Slave Switch
ALL LED’s are
OFF

IN0049 Revision 05 (005273) –19 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
CONFIGURATION –ADDITIONAL SETTINGS
It is recommended that the Site Configuration wizard (in SP LINK 9.4 or higher) be
used to configure the SP PRO settings. Using the wizard will ensure all SP PRO
settings are compatible with the managed AC coupled system.
The settings detailed below will be set when the Site Configuration Wizard is used to configure
the SP PRO. Only the settings required to enable Fronius Managed AC Coupling are shown. The
remainder of systems settings will be set by the Site Configuration Wizard.
The SP PRO must be configured before any of the Fronius inverters are energised.
The Fronius inverters are configured to Solar Net as default and the Inverter Number must be
set sequentially from 01. (See “Programming the Fronius” section).
Make sure in the SP LINK tab CONFIGURATION SETTINGS > SYSTEM the follow settings are
set.
Set String Inverter to Fronius.
Number of Devices is set to the number of Fronius inverters installed in the system.
SP LINK - Configuration Settings –System tab
Note: Port 2 Communication settings will not be available once Fronius has been enabled. This
is normal operation.
In the example used above, two Fronius inverters are connected to the SP PRO.

IN0049 Revision 05 (005273) –20 of 53
POWER PERFORMANCE PASSION
Installing a Selectronic Certified Fronius Primo in
a Managed AC Coupled system
FRONIUS CONFIGURATION
The settings listed below are required to be configured in each Fronius inverter in order for the
system to operate correctly.
1. Isolate the DC solar from the Fronius inverter(s) (via the appropriate DC circuit breaker).
Note: DO NOT connect the PV solar until system is configured.
2. Ensuring that the SP PRO AC Load supply is present at the Fronius Inverter, switch ON
the AC supply to the Fronius inverter.
3. When the Fronius inverter is powered for the first time, select the “language” for the
inverter and press the ENTER (↵) key.
Then “Select Country”,
-For Grid connect, scroll to AU-Australia (↓) and press the ENTER (↵) key.
-For Off Grid,scroll to MG50-Microgrid 50Hz (↓) and press ENTER (↵).
This manual suits for next models
1
Other FRONIUS Control System manuals
Popular Control System manuals by other brands

Aprilaire
Aprilaire 6000 Series Safety & installation instructions

Myson
Myson iVECTOR Getting started guide

System Q
System Q PTZ725 Installation and operation manual

Di-soric
Di-soric IOL-Portable user manual

Honeywell
Honeywell Excel 800 Installation and commissioning instructions

Portos
Portos PPKR-313/2 owner's manual

Ag Leader Technology
Ag Leader Technology EZ-Guide Quick reference card

FrSky
FrSky Power Switch instruction manual

HandyTrac
HandyTrac Key Control Installation and operation

Evil Mad Scientist
Evil Mad Scientist Ostrich Eggbot 2.0 Assembly guide

ARCBRO
ARCBRO F2000 Tube Series user manual

Woodway
Woodway Micro-Link ZE0187 installation guide