393278
Getting Started
• Plan where you will mount each receiver and transmitter.
• Avoid transmitting along a length of wall, sharp angles and large obstructions.
• Avoid mounting inside a metal enclosure.
• Typical range is 100’ line of sight.
• Link devices to each other before installing. See linking instructions (per application) on following pages.
• All FDLR products must be powered during Link.
• PHC Gateway Controller can also link with an FDLR product and be bi-directional.
• Relay state at power-up can be set to ON, OFF, or LAST STATE (default).
• Each FDLR product can be Linked to up to 30 transmitters of any combination.
page 1
902 MHz Model Power Input (Vac) Contact Rating (A) Transmission Source EEP
FDLR20GV 120-277Vac 20 Status Change/Heartbeat A5-11-01
FDLTMAG None NA Contact Closure D5-00-01
FDLTS2 None NA Button Press F6-02-02
FDLTKEY None NA Insert/Remove Card F6-04-01
FDLTVC None NA Occupancy Detected A5-07-01
FDLTVW None NA Occupancy Detected A5-07-01
FDLR20GV FDLTMAG FDLTS2
(Switch and
cover plate)
LRN CLR
FDLTKEY
Functional Devices, Inc.’s EnOcean®Manufacturer ID is 0x055.
FDLTVC FDLTVW
B2489
ESRB and ESRN
Installation & Safety Instructions
Compatible Device from other Manufacturers
PHC Gateway Controller EEP A5-38-08 0x02 (Dimming Profile)
Light Level Sensor EEP A5-06-02

Functional Devices, Inc.
101 Commerce Drive
Sharpsville, IN 46068
Toll Free: (800) 888-5538
Oce: (765) 883-5538
Fax: (765) 883-7505
Email: [email protected]
Website: www.functionaldevices.com
Bi-directional Mode: FDLR20GV and a Central Command Gateway
• Both devices must be able to receive and transmit.
• Gateway can control the relay and 0-10V outputs of the FDLR20GV.
• FDLR20GV re-transmits status every 70-140 seconds.
• Optional modes: Repeater (see page 4)
Bi-directional Link Procedure
1. Apply power to FDLR product.
2. Get FDLR Product in Learn mode by pressing the LRN button until LED starts flashing slowly (approximately 1/2 second).
3. Transmit Link telegram from Central Command Gateway
• LED on FDLR product will stay ON for 4 seconds to acknowledge and then transmit a Link telegram.
Note: To clear memory, hold CLR button for 3 seconds.
Device Power
Device Power
0-10V Output
FDLR20GV
Relay Output
Central
Command
Gateway
LRN CLR
Building Automation Applications
393278
page 2
Lighting Applications
Simple Lighting Control: FDLR20GV and FDLTS2 or FDLTKEY
60Hz A/C Power
Yel
Org
Blk
Red
FDLR20GV
FDLTS2
(Rocker Switch)
or
FDLTKEY
(Keycard Switch) Prp Gry
0-10V
Controlable
Load
LRN CLR
FDLTS2 Modes
A. Dimming Mode
• Relay activates when Rocker ON is pressed and released, and the
Analog Output ramps to previous value.
• Relay activates when Rocker ON is held, and the Analog Output
ramps up from minimum until ON is released.
• When Rocker OFF is pressed and released, the Analog Ouptut
ramps down to minimum, and then the Relay deactivates.
• If the Relay is activated, the Analog Output will ramp up or down
when the Rocker ON or OFF is held, and the Analog Output will
go to MAX if Rocker ON is pressed and released.
• Optional modes: Repeater
Dimming Mode Link Procedure
1. Apply power to FDLR Product.
2. Press and hold LRN button on FDLR Product until LED starts
flashing slowly (approximately 1/2 second).
3. Press and release the button on the switch you are linking three
times quickly.
4. LED on FDLR Product will stay ON for 4 seconds indicating telegram
reception.
5. To link another switch, repeat steps 2-4.

Functional Devices, Inc.
101 Commerce Drive
Sharpsville, IN 46068
Toll Free: (800) 888-5538
Oce: (765) 883-5538
Fax: (765) 883-7505
Email: [email protected]
Website: www.functionaldevices.com
Momentary Mode Link Procedure
1. Apply power to FDLR product.
2. Press and hold LRN button on FDLR product until LED starts flashing
slowly (approximately 1/2 second).
3. Press and hold LRN button on FDLR product for 3 seconds until LED
pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and hold LRN button on FDLR Product for 3 seconds until LED
pattern changes again, to FLASH, FLASH, FLASH, OFF (3 flashes).
5. Press and release the button on the switch you are learning three
times quickly.
6. LED on FDLR product will stay ON for 4 seconds indicating telegram
reception.
7. To learn another switch, repeat steps 2-5.
D. Toggle Mode
• Each press and release of the switch causes the relay to
change state.
• Optional mode: Repeater (see page 4)
Toggle Mode Link Procedure
1. Apply power to FDLR product.
2. Press and hold LRN button on FDLR product until LED
starts flashing slowly (approximately 1/2 second).
3. Press and hold LRN button on FDLR product for 3 seconds
until LED pattern changes to FLASH, FLASH, OFF (2
flashes).
4. Press and hold LRN button on FDLR product for 3 seconds
until LED pattern changes again, to FLASH, FLASH, FLASH,
OFF (3 flashes).
5. Press and hold LRN button on FDLR product for 3 seconds
until LED flashes continuously.
6. Press and release the button on the switch you are learning
three times quickly.
7. LED on FDLR product will stay ON for 4 seconds indicating
telegram reception.
8. To learn another switch, repeat steps 2-6.
FDLTKEY Mode
Momentary Mode
• Relay activates when card is inserted and deactivates
when card is removed.
• Optional mode: Repeater (see page 4)
Momentary Mode Link Procedure
1. Apply power to FDLR product.
2. Press and hold LRN button on FDLR product until LED
starts flashing slowly (approximately 1/2 second).
3. Press and hold LRN button on FDLR product for 3 seconds
until LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and hold LRN button on FDLR Product for 3 seconds
until LED pattern changes again, to FLASH, FLASH, FLASH,
OFF (3 flashes).
5. Insert and remove the card on the switch you are learning
three times quickly.
6. LED on FDLR product will stay ON for 4 seconds indicating
telegram reception.
7. To learn another switch, repeat steps 2-5.
page 3
FDLTS2 Modes (Continued)
Occupancy Detection
A. Manual ON – Auto OFF: FDLR product receiving from both an Occupancy / Vacancy Sensor (FDLTVW or FDLTVC) and a Wall
Switch (FDLTS2)
• Relay activates when Rocker ON is pressed. Relay deactivates when Rocker OFF is pressed or 30 minutes after last detection of
occupancy.
• It may take up to 2 minutes for the FDLR product to respond to the Occupancy / Vacancy Sensor immediately following Link.
• Optional mode: Repeater (see page 4)
Manual ON – Auto OFF Learn Procedure
1. Be sure the Occupancy / Vacancy Sensor is charged
2. Apply power to FDLR product.
3. Press and hold LRN button on FDLR product until LED starts flashing slowly (approximately 1/2 second).
4. Trigger a Teach telegram from the Occupancy / Vacancy Sensor by pressing the Menu button once.
5. LED on FDLR product will stay ON for 4 seconds acknowledging telegram reception.
6. Press and hold LRN button on FDLR product for ½ second. LED will flash slowly.
7. Press and release rocker switch three times quickly.
8. LED on FDLR product will stay ON for 4 seconds acknowledging telegram reception.
9. To learn another switch, repeat steps 6-8.
B. Rocker Mode
• Relay activates when Rocker ON is pressed; relay deactivates when
Rocker OFF is pressed.
• Optional mode: Repeater (see page 4)
Rocker Mode Link Procedure
1. Apply power to FDLR product.
2. Press and hold LRN button on FDLR product until LED starts flashing
slowly (approximately 1/2 second).
3. Press and hold LRN button on FDLR Product for 3 seconds until LED
pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and release the button on the switch you are learning three
times quickly.
5. LED on FDLR product will stay ON for 4 seconds indicating telegram
reception.
6. To learn another switch, repeat steps 2-4.
C. Momentary Mode
• Relay activates while switch is pressed and deactivates when switch
is released.
• Optional mode: Repeater (see page 4)
393278

Functional Devices, Inc.
101 Commerce Drive
Sharpsville, IN 46068
Toll Free: (800) 888-5538
Oce: (765) 883-5538
Fax: (765) 883-7505
Email: [email protected]
Website: www.functionaldevices.com
Occupancy / Vacancy Sensor Only Learn Procedure
1. Charge the Occupancy / Vacancy Sensor per instructions.
2. Apply power to FDLR product.
3. Press and hold LRN button on FDLR product until LED starts flashing slowly (approximately 1/2 second).
4. Trigger a Teach telegram from the Occupancy / Vacancy Sensor by pressing the Menu button once.
5. LED on FDLR product will stay ON for 4 seconds acknowledging telegram reception.
6. Repeat steps 3-5 for additional Occupancy / Vacancy Sensors.
Optional Modes
page 4
• Relay state after power-up can be set to ON, OFF or LAST STATE
• Relay state after power-up is LAST STATE by default.
Setting Relay State to OFF at Power-up:
1. While device is not powered, press and hold the LRN button.
2. Power-up the device.
3. Wait approximately 3 seconds until the LED blinks 3 times.
4. Release the LRN button.
Relay will always be OFF at power-up.
Setting Relay State to ON at Power-up:
1. While device is not powered, press and hold the CLR button.
2. Power-up the device.
3. Wait approximately 3 seconds until the LED blinks 2 times.
4. Release the CLR button.
Relay will always be ON at power-up.
Setting Relay State to LAST STATE at Power-up: (Default Mode) **
1. While device is not powered, press and hold the LRN and CLR buttons.
2. Power-up the device.
3. Wait approximately 3 seconds until the LED blinks 1 time.
4. Release the LRN and CLR buttons.
Relay will return to LAST STATE at power-up.
Relay State
• Activating Repeater Mode allows FDLR product to repeat signals from other EnOcean devices within range. The FDLR product “hears”
the signal and echoes it but will not respond to it unless it has been linked to the transmitting device.
• FDLR product will allow a signal to be repeated up to two times.
Enabling Repeater Mode
1. Apply power to FDLR product.
2. Press and hold LRN button on FDLR product until LED starts
flashing slowly (approximately 1/2 second).
3. Press and hold the CLR button for 3 seconds until LED flashes
twice indicating Repeater Mode is enabled.
Disabling Repeater Mode
1. Apply power to FDLR product.
2. Press and hold LRN button on FDLR product until LED
starts flashing slowly (approximately 1/2 second).
3. Press and hold the CLR button for 3 seconds until LED
flashes three times indicating Repeater Mode is disabled.
Repeater Mode
B. Auto On: FDLR Product and an Occupancy / Vacancy Sensor (FDLTVW or FDLTVC)
• Relay activates when occupancy is detected and deactivates 30 minutes after last detection of occupancy.
• It may take up to 2 minutes for the FDLR product to respond to the Occupancy / Vacancy Sensor immediately following Link.
• Optional mode: Repeater (see page 4)
393278

Functional Devices, Inc.
101 Commerce Drive
Sharpsville, IN 46068
Toll Free: (800) 888-5538
Oce: (765) 883-5538
Fax: (765) 883-7505
Email: [email protected]
Website: www.functionaldevices.com
page 5
Delay Mode
• Typically used with Hotel Room Energy Control (see page 7).
• Activating Delay Mode allows the FDLR product to ignore temporary changes in switch states.
• The Delay Mode causes a delay of 10 seconds before relay will turn ON and a delay of 90 seconds before it will turn OFF. It also pre
vents the relay from activating following a deactivation for 90 seconds (see Figure 4, below).
• The OFF delay allows the load to continue to run while the switch or transmitter is temporarily open. This is helpful when monitoring
window and door contacts that may be briefly opened and then closed. If the contact remains open for longer than 90 seconds the
relay will deactivate.
• The ON delay prevents the relay from immediately responding to a closed contact.
• The 90 second OFF to ON delay is intended specifically for HVAC units so that they will not short cycle.
Enabling Delay Mode
1. Apply power to FDLR product.
2. Press and hold LRN button on FDLR product until LED starts
flashing slowly (approximately 1/2 second).
3. Press and hold LRN button on FDLR product for 3 seconds until
LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and hold LRN button on FDLR product for 3 seconds until
LED pattern changes again, to FLASH, FLASH, FLASH, OFF
(3 flashes).
5. Press and hold the CLR button for 3 seconds until LED flashes
twice indicating Delay Mode is enabled.
Disabling Delay Mode
1. Apply power to FDLR product.
2. Press and hold LRN button on FDLR product until LED
starts flashing slowly (approximately 1/2 second).
3. Press and hold LRN button on FDLR product for 3
seconds until LED pattern changes to FLASH, FLASH,
OFF (2 flashes).
4. Press and hold LRN button on FDLR product for 3
seconds until LED pattern changes again, to FLASH,
FLASH, FLASH, OFF (3 flashes).
5. Press and hold the CLR button for 3 seconds until LED
flashes three times indicating Delay Mode is disabled.
<10s
O
On
O
On
>10s10s
90s 90s 90s
Wireless
Command
Relay
State
Alarm Mode
• Activating Alarm Mode requires all learned contact switches, FDLTMAG, to transmit a CLOSED telegram before
relay will activate. Relay will deactivate if any contact switch transmits an OPEN telegram.
Enabling Alarm Mode
1. Apply power to FDLR product.
2. Press and hold LRN button on FDLR product until LED starts
flashing slowly (approximately 1/2 second).
3. Press and hold LRN button on FDLR product for 3 seconds until
LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and hold the CLR button for 3 seconds until LED flashes t
wice indicating Alarm Mode is enabled.
Disabling Alarm Mode
1. Apply power to FDLR product.
2. Press and hold LRN button on FDLR product until LED
starts flashing slowly (approximately 1/2 second).
3. Press and hold LRN button on FDLR product for 3
seconds until LED pattern changes to FLASH, FLASH, OFF
(2 flashes).
4. Press and hold the CLR button for 3 seconds until LED
flashes three times indicating Alarm Mode is disabled.
393278

Functional Devices, Inc.
101 Commerce Drive
Sharpsville, IN 46068
Toll Free: (800) 888-5538
Oce: (765) 883-5538
Fax: (765) 883-7505
Email: [email protected]
Website: www.functionaldevices.com
page 6
FDLRxxx with Door/Window Sensor(s) FDLTMAG
• Relay activates with closed command from FDLTMAG and deactivates
with open command.
• FDLTMAG retransmits contact state every 20-30 minutes.
• Optional modes: Repeater,(see page 4) Alarm, Delay (see page 5)
FDLTMAG Link Procedure
1. Charge the FDLTMAG per Instructions provided with unit.
2. Apply power to FDLR product.
3. Press and hold LRN button on FDLR product until LED starts
flashing slowly (approximately 1/2 second).
4. Press and release Link button on FDLTMAG to transmit Teach
telegram.
5. LED on FDLR product will stay ON for 4 seconds acknowledging
telegram reception.
6. To learn more FDLTMAG, repeat steps 3-5.
WDWS-EN3
Rocker Switch
PTAC unit with RIBWxxxB-EN3
in Hotel Room Energy Control Mode
in Momentary Mode with Keycard Switch
and in Dimming Mode with FDLTS
(Wired through J Box)
FDLR20GV
FDLTMAG
FDLTS2
PTAC unit with FDLR20x or FDLR05x
Energy Saving Applications
0-10V Dimmable Fixture
Clearing ID’s from Memory
Global Clear (Reset to default settings)
Clears all linked devices, disables optional modes, turns relay OFF, and sets 0-10V output to minimum.
Performing Global Clear
1. Press and hold CLR button on FDLR product for 3 seconds until
LED begins slowly flashing.
a. Clear Mode will time out and exit in 30 seconds.
• Allows the user to Un-link a single transmitter from FDLR product.
• Maintains all optional mode settings.
Performing Single Device Clear
1. Repeating the Link procedure for a currently Linked device will
Un-link that device.
Single Device Clear
393278
FDLTKEY
Keycard Switch

Functional Devices, Inc.
101 Commerce Drive
Sharpsville, IN 46068
Toll Free: (800) 888-5538
Oce: (765) 883-5538
Fax: (765) 883-7505
Email: [email protected]
Website: www.functionaldevices.com
Hotel Room Energy Control FDLR Product with FDLTMAG and FDLTKEY
Consult factory.
393278
page 7
This manual suits for next models
5
Table of contents
Other Functional Devices Lighting Equipment manuals
Popular Lighting Equipment manuals by other brands

Lightolier
Lightolier Calculite ProSpec PA3P3075 specification

Lumen Dynamics Group
Lumen Dynamics Group OmniCure S2000 user guide

MJ LED LIGHTNING
MJ LED LIGHTNING MJ-2020 3W25DRGBW user manual

EuroLite
EuroLite IP AUDIENCE BLINDER user manual

Hello Light
Hello Light HL-PL54-54PCS-LED manual

LIGMAN
LIGMAN ODESSA 13 installation manual

LED Group
LED Group ROBUS VEGAS RVA12RGBW6710-30 quick start guide

Daisy
Daisy Below Ground Pool Cover Box installation guide

Meteor
Meteor Stem Dext 2.0 Series installation instructions

Sealey
Sealey LED042 instructions

Lithonia Lighting
Lithonia Lighting TWA installation instructions

NETO
NETO RENEGADE XB user manual