Functional Devices RIBW24B-EN3 User manual

393231
Bulletin B1867
902 MHz Wireless Relays Application Manual
Getting Started
• Plan where you will mount each receiver and transmitter.
• Avoid transmitting along a length of wall, sharp angles and large obstructions.
• Avoid mounting inside a metal enclosure.
• Typical range is 100’ line of sight.
• Link devices to each other before installing.
• All RIBs must be powered during Link.
• RIBWxxxB-EN3 is both a transmitter and a receiver.
• RIBWxxC-EN3 is only a receiver.
• Linking a RIB with another RIB puts the pair in Bi-directional mode.
• PHC Gateway Controller can also link with a RIB and be Bi-directional.
• Relay output state is saved at power loss. Relay output is restored when power is recovered.
(Exception: RIBW24B-EN3 will not save last state when powered from 24Vdc).
• Each Relay can be Linked to up to 30 transmitters of any combination.
page 1
902 MHz Model Power Input (Vac) Contact Rating (A) Transmission Source EEP
RIBW24B-EN3 24 ac/dc 20 Dry-Contact A5-30-02
RIBW01B-EN3 120 20 Dry-Contact A5-30-02
RIBW208-EN3 208 20 Dry-Contact A5-30-02
RIBW240B-EN3 240 20 Dry-Contact A5-30-02
RIBW277B-EN3 277 20 Dry-Contact A5-30-02
RIBW01C-EN3 120 5 NA A5-30-02
RIBW02C-EN3 208-277 5 NA A5-30-02
WDWS-EN3 None NA Contact Closure D5-00-01
WWS-EN3 None NA Button Press F6-02-02
Device EEP
PHC Gateway Controller A5-38-08
Keycard F6-02-02
Occupancy Sensor A5-07-01
Compatible Devices from other Manufacturers
RIBWxxxB-EN3 RIBWxxC-EN3
WDWS-EN3 WWS-EN3

902 MHz Wireless Relays Application Manual B1867 page 2
Uni-directional Mode: Only one of the RIBs must transmit. Two RIBWxxxB-EN3 or one RIBWxxxB-EN3 and one RIBWxxC-EN3.
• Only one RIB is the transmitter while the other is the receiver.
• Transmitter RIB Dry contact closure will transmit a relay ON command; dry contact open will transmit a relay OFF command.
• Re-transmits dry contact input state every 70-140 seconds.
• Optional modes: Repeater, Alarm (see pages 4)
Uni-directional Link Procedure
1. Apply power to both RIB’s.
2. Get RIB-1 in Learn mode by pressing the LRN button for ½ second. (LED will blink).
3. On RIB-2 hold LRN button for 3 seconds to transmit a Teach telegram.
a. LED on RIB-1 will stay ON for 4 seconds to acknowledge and then transmit a Teach telegram.
b. LED on RIB-2 will stay ON for 4 seconds to acknowledge the Teach telegram from RIB-1.
Device Power
Dry Contact
RIBWxxxB-EN3
RIB-1
Device Power
RIBWxxxB-EN3
or
RIBWxxC-EN3
RIB-2
Load
Bi-directional Mode: Two RIBWxxxB- or one RIBWxxB-EN3 and a PHC Gateway Controller
• Both devices must be able to receive and transmit.
• Dry contact closure will transmit a relay ON command; dry contact open will transmit a relay OFF command.
• RIBWxxB-EN3 Re-transmits dry contact input state every 70-140 seconds.
• Optional modes: Repeater, Alarm (see pages 4)
Bi-directional Link Procedure
1. Apply power to both RIB’s.
2. Get RIB-1 in Learn mode by pressing the LRN button for ½ second. (LED will blink).
3. On RIB-2, hold LRN button 3 seconds to transmit a Teach telegram.
a. LED on RIB-1 will stay ON for 4 seconds to acknowledge and then transmit a Teach telegram.
b. LED on RIB-2 will stay ON for 4 seconds to acknowledge the Teach telegram from RIB-1.
Device Power Device Power
Dry Contact Dry Contact
RIBWxxxB-EN3
RIB-1
Relay Output Relay Output
RIBWxxxB-EN3
RIB-2
Building Automation Applications

902 MHz Wireless Relays Application Manual B1867
B. Momentary Mode
• Relay activates while switch is pressed (card inserted, for example) and deactivates when switch is released.
• Optional modes: Repeater (see page 4)
Momentary Mode Link Procedure
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and release the button on the switch you are learning three times quickly.
5. LED on RIB will stay ON for 4 seconds indicating telegram reception.
6. To learn another switch, repeat steps 2-5.
C. Toggle Mode
• Each press and release of the switch causes the relay to change state.
• Optional modes: Repeater (see page 4)
Toggle Mode Link Procedure
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH, FLASH, OFF (2 flashes).
4. Press and hold LRN button on RIB for 3 seconds until LED pattern changes again, to FLASH, FLASH, FLASH, OFF (3 flashes).
5. Press and release the button on the switch you are learning three times quickly.
6. LED on RIB will stay ON for 4 seconds indicating telegram reception.
7. To learn another switch, repeat steps 2-6.
page 3
Lighting Applications
Simple Lighting Control: RIBWxxxB-EN3 or RIBWxxC-EN3 and WWS-EN3
A. Rocker Mode
• Relay activates when Rocker ON is pressed; relay deactivates when Rocker OFF is pressed.
• Optional modes: Repeater (see page 4)
Rocker Mode Link Procedure
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
3. Press and release the button on the switch you are learning three times quickly.
4. LED on RIB will stay ON for 4 seconds indicating telegram reception.
5. To learn another switch, repeat steps 2-4.
Load
60Hz A/C Power
Yel
Org
Blk
Wht or Red
RIBWxxxB-EN3 or RIBWxxC-EN3
WWS-EN3
Occupancy Detection
A. Manual ON–Auto OFF: RIB receiving from both an Occupancy Sensor and a wall switch WWS-EN3
• Relay activates when Rocker ON is pressed. Relay deactivates when Rocker OFF is pressed or 30 minutes after last detection of Occupancy.
• It may take up to 2 minutes for the RIB to respond to the Occupancy Sensor immediately following Link.
• Optional modes: Repeater (see page 4)
Manual ON – Auto OFF Learn Procedure
1. Be sure the Occupancy Sensor is charged
2. Apply power to RIB.
3. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
4. Trigger a Teach telegram from the Occupancy Sensor per Manufacturer’s instructions.
5. LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
6. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
7. Press and release rocker switch three times quickly.
8. LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
9. To learn another switch, repeat steps 6-8.
Continued on Page 4

902 MHz Wireless Relays Application Manual B1867 page 4
Occupancy Detection
B. Auto On: RIB and an Occupancy Sensor
• Relay activates when occupancy is detected and deactivates 30 minutes after last detection of occupancy.
• It may take up to 2 minutes for the RIB to respond to the Occupancy Sensor immediately following Link.
• Optional modes: Repeater (see page 4)
Occupancy Sensor Only Learn Procedure
1. Charge the Occupancy Sensor per Manufacturer’s instructions.
2. Apply power to RIB.
3. Press and hold LRN button on RIB for 1/2 second. LED will blink slowly.
4. Trigger a Teach telegram from the Occupancy Sensor per Manufacturer’s Instructions.
5. LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
6. Repeat steps 3-5 for additional occupancy sensors.
Continued from Page 3
Alarm Mode
• Activating Alarm Mode requires all learned contact switches, such as WDWS-EN3 or RIBWxxxB-EN3, to transmit a CLOSED telegram before relay will activate. Relay will
deactivate if any contact switch transmits an OPEN telegram.
Enabling Alarm Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to
FLASH, FLASH, OFF (2 flashes).
4. Press and hold the CLR button for 3 seconds until LED blinks twice indicating
Alarm Mode is enabled.
Disabling Alarm Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH,
FLASH, OFF (2 flashes).
4. Press and hold the CLR button for 3 seconds until LED blinks three times indicating
Alarm Mode is disabled.
Delay Mode
• Typically used with Hotel Room Energy Control (see page 5).
• Activating Delay Mode allows the relay to ignore temporary changes in switch states.
• The Delay Mode causes a delay of 0 seconds before relay will turn ON and a delay of 90 seconds before it will turn OFF. It also prevents the relay from activating following a
deactivation for 90 seconds (see Figure 4, below).
• The OFF delay allows the load to continue to run while the switch or transmitter is temporarily open. This is helpful when monitoring window and door contacts that may be
briefly opened and then closed. If the contact remains open for longer than 90 seconds the relay will deactivate.
• The ON delay prevents the relay from immediately responding to a closed contact.
• The 90 second OFF to ON delay is intended specifically for HVAC units so that they will not short cycle.
Enabling Delay Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to
FLASH, FLASH, OFF (2 flashes).
4. Press and hold LRN button on RIB for 3 seconds until LED pattern changes again,
to FLASH, FLASH, FLASH, OFF (3 flashes).
5. Press and hold the CLR button for 3 seconds until LED blinks twice indicating
Delay Mode is enabled.
Disabling Delay Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold LRN button on RIB for 3 seconds until LED pattern changes to FLASH,
FLASH, OFF (2 flashes).
4. Press and hold LRN button on RIB for 3 seconds until LED pattern changes again, to
FLASH, FLASH, FLASH, OFF (3 flashes).
5. Press and hold the CLR button for 3 seconds until LED blinks three times indicating
Delay Mode is disabled.
• Activating Repeater Mode allows relay to repeat signals from other EnOcean devices within range. The relay “hears” the signal and echoes it but will not respond to it unless it
has been linked to the transmitting device.
• Relay will allow a signal to be repeated up to two times.
Enabling Repeater Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold the CLR button for 3 seconds until LED blinks twice indicating
Repeater Mode is enabled.
Disabling Repeater Mode
1. Apply power to RIB.
2. Press and hold LRN button on RIB for ½ second. LED will flash slowly.
3. Press and hold the CLR button for 3 seconds until LED blinks three times indicating
Repeater Mode is disabled.
Optional Modes
Repeater Mode
<10s
O
On
O
On
>10s10s
90s 90s 90s
Wireless
Command
Relay
State

902 MHz Wireless Relays Application Manual B1867 page 5
Clearing ID’s from Memory
Global Clear (Reset to default settings)
Clears all linked devices, disables optional modes, and turns relay OFF.
Performing Global Clear
1. Press and hold CLR button on RIB for 3 seconds until LED begins slowly blinking.
a. Clear Mode will time out and exit in 30 seconds.
Single Device Clear
• Allows the user to Un-link a single transmitter from RIB receiver.
• Maintains all optional mode settings.
Performing Single Device Clear
1. Repeating the Link procedure for a currently Linked device will Un-link that device.
Energy Saving Applications
RIB with Door/Window Sensor(s) WDWS-EN3
• RIB activates with closed command from WDWS-EN3 and deactivates with open command.
• WDWS-EN3 retransmits contact state every 70-140 seconds.
• Optional modes: Repeater, Alarm, Delay (see pages 4)
WDWS-EN3 Link Procedure
1. Charge the WDWS-EN3 per Instructions provided with unit.
2. Apply power to RIB.
3. Press and hold LRN button on RIB for ½ second. LED will blink slowly.
4. Press and release Link button on WDWS-EN3 to transmit Teach telegram.
5. LED on RIB will stay ON for 4 seconds acknowledging telegram reception.
6. To learn more WDWS-EN3, repeat steps 3-5.
WDWS-EN3
Keycard Switch
PTAC unit with RIBWxxxB-EN3 or RIBWxxC-EN3
in Hotel Room Energy Control Mode
RIBWxxxB-EN3 or RIBWxxC-EN3
in Momentary Mode with Keycard Switch
(Wired through J Box)
Hotel Room Energy Control RIB with WDWS-EN3 and a Keycard Switch
Consult factory.

902 MHz Wireless Relays Application Manual B1867 page 6
Load
60Hz A/C Power
DO
BAS Panel
BAS Controller
Wht/Red
Wht/Blu
Yel
Org
Blk
Wht or Red
Transmitter
RIBWxxxB-EN3 or RIBWxxC-EN3
Other Common Applications
Unidirectional Control with a BAS System
In this application the BAS system dry-contract output controls the transmitter and a RIBWxxxB-EN3 or RIBWxxC-EN3 is the receiver.
Thermostat
Thermostat
Power Dry Contact Output (Call)
Dry Contact Input
RIBWxxxB-EN3
RIBWxxxB-EN3
or
RIBWxxC-EN3
Relay Output
Device Power
Hot Neutral or Other Phase
Heater, A/C,
or Fan
Device Power
Unidirectional Control with a Thermostat
In this application the thermostat dry-contract output controls the transmitter and a RIBWxxxB-EN3 or RIBWxxC-EN3 is the receiver.
Bidirectional Control with a BAS System
In this application the BAS system dry-contract output controls the transmitter on a RIBWxxxB-EN3. A second RIBWxxxB-EN3 receives the signal and activates it relay. A current
switch detects current flow through the load and closes the dry-contract input on the second RIBWxxxB-EN3. The first RIBWxxxB-EN3 receives the transmission and closes its
relay. This contact closure to the BAS system lets the controller know the load status.
Load
60Hz A/C Power
DO
DI
BAS Panel
BAS Controller
Org
Yel
Wht/Red and Wht/Blu
Wht/Blu
Wht/Red
Yel
Org
Blk
Wht or Red
RIBWxxxB-EN3
RIBWxxxB-EN3
RIBX Series
(not included)
This manual suits for next models