Galvin Engineering CliniMix CMV2 Instruction sheet

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Document No.: 001.00.10.24
Version 1, 19 October 2022, Page 1of 24
CliniMix®CMV2 Wall Mounted Hands Free POU,
Wave on/off sensor with Temp. Monitoring
PRODUCT CODE:
- 100.41.11.20 –CP Faceplate
- 100.41.11.30 –Glass Faceplate
TABLE OF CONTENTS
1.0 INTRODUCTION 2
2.0 SAFETY 2
3.0 DESCRIPTION 2
4.0 DIMENSIONS 2
4.1 TECHNICAL DATA 3
4.2 SENSOR DETAILS 3
5.0 WATER SUPPLY CONDITIONS 3
5.1 INTRODUCTION 3
5.2 SUPPLY PRESSURE REQUIREMENTS 3
6.0 PRE-INSTALLATION 4
7.0 INSTALLATION 5
7.1 OPERATION AND TESTING 8
7.2 SENSOR SETTING INSTRUCTIONS 8
8.0 COMMISSIONING 9
9.0 OPERATION 11
10.0 SERVICING 11
10.1 FREQUENCY OF REGULAR SERVICING 11
10.2 GENERAL SERVICING 12
10.2.1 STRAINER AND NON-RETURN VALVES 12
10.2.2 THERMOSTATIC CARTRIDGE 13
11.0 MAINTENANCE 15
11.1 MIXED WATER TEMPERATURE ADJUSTMENT 15
11.2 REMOVAL AND INSPECTION OF CARTRIDGE 17
11.3 IMPORTANT NOTES ON DEBRIS 17
11.4 MAINTENANCE CLEANING 17
12.0 DISINFECTION 18
13.0 TROUBLESHOOTING 19
14.0 WARRANTY 20

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 2of 24
1.0 INTRODUCTION
CliniMix®CMV2 Wall Mounted Hands Free Point Use Wave on/off sensor is a high-performance thermostatic
mixing valve suitable for a wide range of applications. The mixing valve has the following features:
−This point of use thermostatic mixer provides state of the art features to comply with healthcare
requirements.
−Suitable for high and low water pressure systems.
−Provides high stability of mixed water temperature even under changing inlets conditions.
−Ensures rapid shut down of mixed outlet flow in the event of hot or cold water supply failure.
−Designed for quick and simple in-situ servicing.
−Suitable for installation into AS3500 compliant systems with hot water temperature as low as 55°C.
−Smooth internal components and body reduces scale build-up and bacteria growth.
−Maximum temperature limiter fitted for protection from accidental scalding.
−Clean smooth lines facilitate fast and easy cleaning.
−Complies with the requirements of AS 4032.4 Thermostatic Mixing Valves.
−Self-draining spout design.
−Unique hygiene flush feature for in-situ disinfection.
−Remote activation and mixed water temperature monitoring.
−Suitable for connection with CliniMix CMM for continuos outlet temperature monitoring.
2.0 SAFETY
The CliniMix®CMV2 Wall Mounted Hands Free Point Of Use Wave on/off sensor is a high-performance valve
designed to give stable and dependable operation, provided it is installed, commissioned, operated and
maintained as per the recommendations outlined in this manual. It should be noted however that this valve
should not be considered as an alternative to adequate supervision and duty of care during its use and
operation.
3.0 DESCRIPTION
This manual covers the CliniMix®CMV2 Wall Mounted Hands Free Point Use Wave on/off sensor mixer. This
product is designed to provide water in a safe temperature for washing. This mixing valve is supplied with
integral isolating valves, strainers, check valves, flow regulators located in-body and a facility for thermal
disinfection of the cold inlet side and mixed water outlet.
Avoid using heat for soldering near the mixer inlets to prevent damage to internal components.
4.0 DIMENSIONS

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 3of 24
4.1 TECHNICAL DATA
Inlet
Outlet
Flow Straightener
Headwork
Thermostatic mixing valve
Solenoid
Mains Powered (Transformer)
90 264V - 47/63Hz 0.15A
6.75V DC 0.5A
0.7m
Finish
Chrome
NOTE: Galvin Specialised continually strive to improve their products. Specifications may change without notice.
Table 1. Technical information
4.2 SENSOR DETAILS
Input Voltage
6.75V DC 0.5A
Sensor function
Wave on / Wave off
Pre-set line purge feature interval:
72 hours after last flush, water flow duration 60 sec
Pre-set continuous run:
10 min
5.0 WATER SUPPLY CONDITIONS
5.1 INTRODUCTION
This thermostatic mixer with wave on / wave off sensor is manufactured to the highest standards and has
approval to AS4032.4 which permits it to be installed in healthcare establishments such as hospitals, nursing
homes and residential care homes. When installed in healthcare establishments the supply conditions
detailed in Table 2 must be observed and the commissioning and servicing requirements detailed on section
8.0 COMMISSIONING & 10.0 SERVICING must be followed.
5.2 SUPPLY PRESSURE REQUIREMENTS
This mixer is designed to be installed on all types of plumbing systems. Hot and cold water supply pressures
should be reasonably balanced; however, the mixer will function within specification on unequal pressures up
to 10:1. The mixer has integral isolating valves which permit servicing of the strainer, check valve/flow
regulator and thermostatic cartridge. They are also used for thermal disinfection. The minimum pressure for
the correct thermal operation is 30kPa. However, to achieve an acceptable flow performance at very low
pressures it may be necessary to remove the combined check valve and flow regulators and replace them with
simple check valves to facilitate thermal disinfection.
Working Temperature Range (°C)
Min
5
Max
80
Minimum Temperature Differential (between the supply and the outlet temperature) (°C)
Min
10
Adjustable Temperature Range (°C)
Min
35
Max
45
Working Pressure Range (kPa)
Min
30
Max
500
Permitted Supply Pressure Variation
10:1
Factory Set Thermostatic Temperature (°C)
41
Maximum Thermostatic Temperature (°C)
45
Nominal Flowrate (LPM)
8
Table 2 Water supply conditions
Note: Tapware must be installed in accordance with the provisions of AS/NZS 3500. Installations not complying with
AS/NZS 3500 may void the product and performance warranty provisions.

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 4of 24
6.0 PRE-INSTALLATION
MOUNTING DETAILS WALL PREPARATION
1. Cut out hole in wall as per dimensions shown below. The depth of the hole must be between 75 and 95mm
from the finished wall face.
2. Drill four holes located as per picture below using drill diameter suitable for mounting system (not supplied)
that will be used for the box installation.

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 5of 24
7.0 INSTALLATION
The CliniMix®CMV2 Wall Mounted Hands Free Point Use mixing valves must be installed using the
appropriate Standard, Code of Practice and legislation applicable to point of install.
The CliniMix®CMV2 Wall Mounted Hands Free Point Use mixing valves must be installed by a licensed
plumber.
If the valve is not installed correctly then it will not function correctly and may put the user in danger. It may
also void the warranty of the valve.
Prior to the installation of the valve, the system must be checked to ensure that the system operating
conditions fall within the recommended operating range of the CliniMix®CMV2 Wall Mounted Hands Free
Point Of Use mixing valve. If the hot water supply temperature is greater than 80° Celsius, the valve may be
damaged. If the temperature of the hot water will rise above 80° Celsius a suitable temperature limiting valve
must be fitted to the hot water supply, prior to the inlet fittings. This temperature limiting valve must be
installes dynamic supply pressures are
500kPa or less. If either supply pressure exceeds 500kPa then a suitable pressure reducing valve must be
fitted prior to the inlet control valve to reduce the pressure to an acceptable limit.
performance from the valve it is recommended that the inlet pressures are balanced to within 10% of each
other.
To ensure that the mixing valve operates correctly, it is necessary that the pipe-work is thoroughly flushed
with clean water before the valve is installed. This will remove any physical contaminants from the pipe-work,
ensuring trouble-free operation. During the flushing procedure, care should be taken to prevent water
damage occurring to the surrounding area.
The valve should be installed so it can be easily accessed for maintenance or servicing.
During installation or servicing, heat must not be applied near the mixing valve or inlet fittings, as this will
damage the valve and inlet fittings internals. Failure to comply with this requirement will damage the valve
and fittings. It will put the user at risk, and it will void the warranty of the valve.
Note: To effectively control microbial hazards during system design, installation, commissioning and maintenance, the
requirements of local legislation shall be adhered to.
Note: In some installations, certain types of tapware devices such as flick mixers and solenoid valves are used. The water
pressure may be seen to spike outside that recommended for the valve, during rapid shut off conditions with these types of
devices. Even if the spike only lasts a split second it is still considered to be outside the operating conditions and may cause
the valve to operate incorrectly. In the event that this does occur, measures must be taken to control the spike, such as the
installation of an inline pressure reducing valve directly before the valve inlets.

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 6of 24
IMPORTANT: Galvin Specialised products must be installed in accordance with these installation
instructions and in accordance with AS/NZS 3500, the PCA and your local regulatory requirements. Water
and/or electrical supply conditions must also comply to the applicable national and/or state standards.
Failing to comply with these provisions shall void the product warranty and may affect the performance of
the product.
1. Fit box and connect with mains
−Create an opening on the left or right side
of the box. Push the transformer cable
through the supplied grommet and leave
around 150mm of free cable inside the
box.
−Using suitable fittings, attach the box
inside the wall. Box must be leveled and
installed parallel to the finished wall.
Ensure the box is not twisted.
−Connect supplied inlets to the
thermostatic mixer and then with mains.
Attach the middle section of the box.
−Attach one part of the supplied 3M Dual
Lock fastener on the relay unit, and the
other one in the most convenient spot of
the box. Recommended position shown
on the picture above. Align both sides of
the fastener and press the relay unit to fix
it on the box.
−Check if the isolating valves are in the
Note: Avoid using heat for soldering near the mixer
box and inlets.
2. Preparation for wall finishing
−Fix installation cover to protect the mixer
against dust.
−Leave cover attached until wall is
finished.
Temperature Sensor
Relay Unit
Middle section of box
Installation cover
Transformer cable
Sensor connection cable

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 7of 24
3. Trimming box
−When the finished wall is ready, detach
the installation cover. Retain the
screws.
−Cut off the protruding part of the box.
4. Flush the pipe-work
−Attach flushing kit (not supplied) to P/T
port.
−Direct the hose into basin. Slowly
change the ball valve position to
−When all pipework is correctly flushed
position, detach flushing kit and plug
back the P/T port.
Note: A flushing kit is available. For more information,
please visit www.galvinengineering.com.au.
5. Attach frame
−Screw in the inner part of the spout to the
mixing valve body until it stops. Tighten to
a torque of 10Nm.
−Attach frame using the screws removed
from the installation cover.
−Align the position of the back nut with the
faceplate recess in frame and secure
using grab screw. The back nut must
support the back of the faceplate when
installed.
6. Sensor activation.
-
position.
- Connect the temperature relay cable and
solenoid cable to the sensor, temperature
monitoring cable with temperature relay
cable and then the sensor with
transformer.
- (see
section 7.2 Sensor Setting Instructions).
-
position.
Note: There are two male connectors in the controller. The
solenoid can be connected to any of them.
Note:
Installation cover

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 8of 24
7. Fit the faceplate
- Fit the faceplate in position, it will be held
in place by a set of magnets.
- Ensure the backnut is supporting the
faceplate.
- Insert the flange and screw in the locking
nut.
- Lock the locking nut using grub screw.
8. Install Spout and plug
- Ensure there are two O-rings on the inner
part of the spout before installing the outer
spout.
- Push spout to the end and lock with grub
screw to secure.
- Ensure the disinfecton key cover is fitted
to the open hole as shown
7.1 OPERATION AND TESTING
After installation, check for leaks and correct operation.
Hand Movement (Wave on/Wave off) activates the mechanism and delivers the water with
the pre-set temperature.
7.2 SENSOR SETTING INSTRUCTIONS
Signs and
symbols
Touch function
Hand/object within sensor area
Water flows
LED flashes Green
Water flow stops
LED flashes Red
H –hours / min. –minutes / sec. - seconds
XXX
Locking nut
Grub Screw
Flange
Backnut
O-rings

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 9of 24
FUNCTION
PROCEDURE
FEEDBACK
SIGNAL
INFORMATION
DEFAULT
SETTING
RANGE
Via IQUA
Touch
First startup
After installation
1x app. 4 sec. till
Remove hand/object from sensor
area
-.
-
wait
+
2x/sec., keep out of sensor area
wait till
1x
Confirmation, ready for operation
Temporary off
«Cleaning mode»
Activate
1x app. 2 sec. till
1x
Extended function mode is active
2 min.
2x a app. 0.5 sec
Pulsing during active function
Temporary off
Stop
1x app. 2 sec.
1x
Manual stop
or automatic
1x
Automatic after preset time
Continuous run
Activate
1x app. 2 sec. till
1x
Extended function mode is active
5 min.
0.5-20 min.
(in 0.5
steps
)
min.
1x minimum 3 sec.
(max. 5 sec.)
Water flows after releasing
Continuous run
Stop
1x app. 2 sec.
Manual stop
or automatic
Automatic after preset time
line purge feature
activate /
deactivate
<< Automatic
flush on set
interval>>
(time of
waterflow: 3 min)
1x app. 2 sec. till
1x
extended function mode is active
12h
Off
12 h
24 h
48 h
1x app. 25 sec. till
1x - 4x
1x= off,
2x=12h,
3x= 24h,
4x=
48h
ignore flashes after 5 sec. and 10
sec. –keep touched till 1x - 4x
after app. 25 sec., releasing defines
interval
Wait till
1x
Confirmation, ready for operation
restart electronics
1x app. 2 sec. till
1x
extended function mode is active
2x a app. 0,5 sec
pulsing during active function
1x app. 5 sec. till
4x
1x/sec.
Release and wait till
+
1x/sec., keep out of sensor area
Wait till
1x
confirmation, ready for operation
8.0 COMMISSIONING
Initial Test for Correct Operation
The following must be checked to ensure the correct performance of the progressive thermostatic mixer:
−the supply pressures and temperatures are within the range of operating pressures and temperatures for
the thermostatic valve.
−the supply temperatures are within the range permitted for the unit.
Please record the testing done during the commissioning and record the temperature of the hot and cold-water
supplies and the temperature of the mixed water at the full hot setting.
A calibrated digital thermometer having rapid response time with maximum temperature hold will be required to
check and set the outlet mixed temperature of the mixer.
To Commission
To test the temperature, open the valve and allow the mixed heated water to flow for at least 30 to 60 seconds
so the temperature can stabilise before taking a temperature reading at the outlet with a digital thermometer. The
flow rate should be at least 4L/min.
adjustment,
then follow the temperature adjustment in the installation instructions.
XXX
XXX

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 10 of 24
Shut Down Test
Once the correct outlet temperature has been achieved, the valves internal mechanism should be exercised at
least 3 times by alternately shutting off the hot and cold supplies while the mixer is set in the full hot position.
Shut Down Test 1
With the mixer still on and with both supplies turned on, allow the mixed water temperature to stabilise for at
least 15 seconds and note the outlet temperature. While holding a digital thermometer in the outlet flow, quickly
isolate the cold water supply to the valve
The outlet flow should quickly reduce to be less than 0.1L/min following the isolation. Recording of the
temperature should continue after isolation and should not exceed the maximum temperature set out in the
applicable standard or code of practice for each state.
Restore the cold-water supply to the valve. After the mixed water temperature has stabilised note the outlet
temperature ensuring the outlet temperature has re-established. The time taken to stabilise the temperature
should not exceed the maximum time set out in the applicable standard or code of practice for each state.
Shut Down Test 2
With the mixer still on and with both supplies turned on allow the flow to stabilise for at least 15 seconds and
record the temperature. Quickly isolate the hot water supply to the valve.
The outlet flow should quickly reduce to be less than 0.4L/min following the isolation. The volume of mixed water
discharged for a period of between 5-35 seconds should be measured and should not exceed the maximum
volume set out in the applicable standard or code of practice for each state.
Restore the hot water supply to the valve and measure and record the outlet temperature after the mixed water
temperature has stabilised. The time taken to stabilise the temperature should not exceed the maximum time
set out in the applicable standard or code of practice for each state.
Ensure that all details of the Commissioning Report are completed, and a copy is kept with the installer and
owner of the premises.
The valve is now commissioned, and it can be used within the technical limits of operation.
NOTE: In some installations, certain types of tapware devices such as flick mixers and solenoid valves
are used. The water pressure may be seen to spike outside that recommended for the valve, during rapid
shut off conditions with these types of devices. Even if the spike only lasts a split second it is still
considered to be outside the operating conditions and may cause the valve to operate incorrectly. In the
event that this does occur, measures must be taken to control the spike, such as the installation of an
inline pressure reducing valve directly before the valve inlets.
To ensure that the mixing valve operates correctly, it is necessary that the pipe-work is thoroughly flushed with
clean water before the valve is installed. This will remove any physical contaminants from the pipe-work,
ensuring trouble-free operation. During the flushing procedure, care should be taken to prevent water damage
occurring to the surrounding area.

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 11 of 24
9.0 OPERATION
The wave on / wave off sensor starts the water flow when waved in front of the faceplate
surface above the spout.
The delivered water temperature is factory set to approximately 41°C.
10.0 SERVICING
The need for servicing is normally identified as a result of the regular performance testing.
Table 3. A guide to maximum temperature sets. Please refer to AS3500 for temperature settings
Application
Maximum mixed water temperature
during normal operation
Permitted maximum temperature
rise recorded during site testing
Washbasin
41°C
45°C
10.1 FREQUENCY OF REGULAR SERVICING
The purpose of servicing regularly is to monitor any changes in performance due to changes in either the system
or the product. This may highlight the need to adjust either the supply system or the product. These products
should be checked at 6 to 8 weeks and again at 12 to 15 weeks after commissioning. The results are to be
compared against original commissioning settings.
If there are no significant changes at the mixed temperature outlet then a 6 monthly servicing cycle may be
adopted. Otherwise, servicing checks should be carried out more frequently (e.g. every 4 months).
Follow the recommended maintenance procedures detailed in Section 11.0 Maintenance.
During servicing, note the following:
/valve, line
strainer and non-
TMV will ensure this requirement is met. If the CliniMix®Thermostatic Mixing Valve is to be installed without the
supplied inlet control valves then it will be necessary to install a separate isolating valve, non-return valve and
strainer to both inlets to the valve.
Strainers must be fitted to prevent any particulate contamination from entering the valve. These strainers should
be 60 mesh stainless steel (0.250mm). Isolating valves are required so that the water supply to the valve can be
isolated when servicing is required. Non-return devices must also be fitted to both the hot and cold inlets to
prevent cross-contamination.
Ensure that the test plugs in the top of the inlet fittings are tight.
The valve should be installed so it can be easily accessed for maintenance or servicing.
During installation or servicing, heat must not be applied near the mixing valve or inlet fittings, as this will
damage the valve and inlet fittings internals. Failure to comply with this requirement will damage the valve and
fittings. It will put the user at risk and it will void the warranty of the valve.
Note: The CliniMix®Thermostatic Mixing Valve is intended mainly for use in applications with set
temperatures below 45° Celsius. When installed at higher set temperature, the performance may be less
than specified in AS4032.4. In such situations consideration should be given to the question of whether
an alternative device, i.e. a tempering valve approved to AS4032.2 would provide a greater margin for
safety in reducing scalding accidents.

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 12 of 24
1. Repeat the procedure of recording and checking supply temperatures. (The same type of measuring
equipment should be used).
2. If the temperature has changed significantly from the previously recorded valves, the following should be
checked:
a. All in-line or integral valve filters are clear of obstruction.
b. All in-line or integral check valves are clean and working properly to prevent backflow.
c. Any isolating valves are fully open.
d. The thermostat is free of debris.
3. When satisfied with the mixed outlet temperatures re-record the temperatures.
10.2 GENERAL SERVICING
General Servicing of the CliniMix® CMV2 Wall Mounted Hands Free Point Of Use Thermostatic Mixers
10.2.1 STRAINER AND NON-RETURN VALVES
1. Activate the
(See section 7.2 Sensor Setting Instructions).
Disassemble spout and faceplate (reverse steps 6
and 7 in section 7.0 Installation. Disconnect the
sensors cables. INSTALLATION7.2 SENSOR SETTING INSTRUCTIONS
2. Turn the isolating ball valves to the
3. Unscrew and remove service cartridges using metric
spanner 22mm. Remove non-return valves.
4. The strainers and non-return valves should be
cleaned with a dilute water solution of suitable de-
scaling solvent (such as CLR), checked for physical
damage, and then thoroughly rinsed with clean
water. Replace the service cartridges if damaged or
faulty non-return valves.
Strainers
Non-return valves
Service cartridges
Spout
Locking nut
Flange
Faceplate
Sensor

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 13 of 24
5. Re-fit service cartridges and then reassemble faceplate and spout (See section 7.0 Installation points 6 to 8).
10.2.2 THERMOSTATIC CARTRIDGE
1. Disassemble spout and faceplate (refer to 10.2.1
Strainer and Non-Return Valves - step 1).
2.
3. Break/remove the plastic lock in the center of the
thermostatic mixing valve.
4. Use spanner size 28mm and turn the cartridge in the
counterclockwise fashion until it reached the end of
its threads. Pull the thermostatic cartridge out of the
mixer body.
Plastic lock

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 14 of 24
5. Remove the cartridge by hand and clean all
components thoroughly. Inspect components for
damage. If components are damaged, the cartridge
must be replaced.
6. Cleaned cartridge (or a new cartridge, if this is
required) can now be re-installed, by screwing into
the mixer body until it reaches a firm stop and
tightened. The cartridge should be tightened to a
torque of 15Nm. Re-install or install new plastic lock.
Note: Plastic locks are available. For more information, please visit
www.galvinengineering.com.au.
7. When service is complete, slowly turn the cold-water
isolation ball valve and inspect
mixer body for leaks. Repeat with hot water isolation
ball valve.
8. Re-commission the mixer as per commissioning
procedure (See section 8.0 Commissioning).

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 15 of 24
Annual Maintenance Procedure
−Every 12 months the thermostatic mixer must be inspected & tested. The valve should be inspected for
leaks or water damage and appropriate action taken if required.
−Carry out the general servicing of the valve as set out in this document
−A thermal shut down test is performed (Shut Down Test 1 and 2 as set out in this document), and the
temperature is reset as required.
−If the valve fails to shut down or fails to maintain its set temperature, then refer to Troubleshooting
section.
5 Year Maintenance Procedure
−Every five years the thermostatic mixer needs to have a full service carried out. This service consists of
must be replaced.
−After replacing the thermostatic mixer cartridge, a thermal shut down test is performed, and the
temperature re-set as required. If the valve fails to shut down or fails to maintain its set temperature, then
refer to the troubleshooting section.
−Once the 5 yearly maintenance procedure is complete, the thermostatic mixer should then be
commissioned as per instructions.
11.0 MAINTENANCE
When installed as an AS/NZS 4032.4 application it is a requirement that the Commissioning (Section 8.0
Commissioning) and maintenance procedures (Section 11.0 Maintenance) are carried out before use.
11.1 MIXED WATER TEMPERATURE ADJUSTMENT
1.
Disassemble spout, locking nut, flange and
faceplate. Do not disconnect the sensors
cables.
2. Screw back the locking nut, without the
faceplate.
Faceplate
Flange
Locking nut
Spout
Locking nut

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 16 of 24
3. Insert spout (without faceplate and flange) and
secure.
4. Using wrench size 23mm untight the tightening
ring and
using wrench 16mm adjust the temperature by
turning the adjustment rod in direction marked
on the body. When the mixing temperature is
set, holding the adjustment rod tight the
tightening ring to prevent changing the
adjustment.
Note: Turning the adjustment rod clockwise will decreasing the
mixed water temperature and turning it counterclockwise will
increasing the mixed water temperature (see marking on the body).
5.
Spout
Faceplate
Flange
Locking nut
Spout
Spout
Tightening ring
Adjustment rod

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 17 of 24
11.2 REMOVAL AND INSPECTION OF CARTRIDGE
1. After checking that supply conditions are within
the specified parameters (See Table 2), if the
mixer malfunctions or should the test results fail to
fall within the specified limits consider replacing
the cartridge with a new one (See section 11.3
Important Notes On Debris). Afterwards, Follow
the steps in section 10.2.2 Thermostatic Cartridge
to remove and inspect cartridge.
2. Set the temperature as per step 5 in section 11.1
MIXED WATER TEMPERATURE
ADJUSTMENT.
3. Re-commission the mixer as per commissioning procedure
(See section 8.0 Commissioning). Record the mixed water temperature.
11.3 IMPORTANT NOTES ON DEBRIS
Although this product is protected by built-in filters, debris can still find its way to the thermostat housing area.
This can happen during servicing for example. Remove cartridge (See section 11.2 Removal And Inspection Of
Cartridge) and carry out an inspection.
11.4 MAINTENANCE CLEANING
On a regular basis the anti-splash nozzle should be inspected and cleaned if necessary. This should be done
immediately before sterilising is carried out.
In areas where lime scale build-up is prevalent this will have to be removed. An inhibited proprietary scale
After descaling it is important to rinse the parts thoroughly in clean water. Clean carefully and do not use
abrasive materials or scrapers.

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 18 of 24
12.0 DISINFECTION
1. Remove the Disinfection Key cover.
2. Hang the warning tag plate on the Disinfection
Key, insert the Disinfection Key and turn it 180°
(direction not important). Place the warning tag in
Function (See section 7.2 Sensor Setting
Instructions).
WARNING: Spout and water temperature flowing out from spout
during disinfection period might be very hot and cause scalding.
3. Turn the Disinfection Key 180° to remove it and install the key cover.
Note: A disinfection kit is available. For more information, please visit www.galvinengineering.com.au.

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 19 of 24
13.0 TROUBLESHOOTING
PROBLEM
CAUSE
RECTIFICATION
Sensor Not
Responding
-
Damaged or scratched lens
-
Sensor length to short
-
Lead damaged
-
No power
-
Waving hand too fast
-
Transformer faulty
-
Replace the sensor unit
-
Adjust beam to correct length.
-
Replace connected item.
-
Check power is on
-
Slow down the action in front of the sensor
-
Replace transformer
False Activation
-
Sensor length too long
-
Reflection from a light source
-
Adjust sensor length to correct length
-
Re-align sensor or shield light source
The desired mixed
water temperature
cannot be
obtained, or valve
is difficult to set.
-
Hot and cold supplies are fitted to the
wrong connections
-
Thermostatic cartridge contains
debris or is damaged
-
Strainers contain debris
-
Non-return devices are damaged
-
Refit the valve with Hot/Cold supplies fitted to
the correct connections
-
Clean the Cartridge ensuring that all debris is
removed, and components are not damage.
Replace if necessary
-
Clean strainers ensuring debris is removed
-
Check non-return device is not jammed. Clean it
if necessary
-
Check for airlocks in the water supply
When the water is
set at cold, the
blended
temperature is too
hot
-
Hot & Cold water supply connections
are installed in reverse.
-
Refit the valve with Hot/Cold supplies fitted to
the correct connections
The thermostatic
mixing valve will
not shut down
-
The hot to cold mix temperature
differential is not 10°C or greater
-
Thermostatic cartridge contains
debris or is damaged
-
Non-return devices are damaged
-
Raise hot water temperature
-
Clean the cartridge ensuring that all debris is not
jammed. Clean if necessary
Mix temperature
unstable
-
Flow rate below 6 L/min
-
Thermostatic cartridge contains
debris or is damaged
-
Strainers contain debris
-
Non-return devices are damaged
-
Rectify any pressure deterioration
-
Clean the cartridge ensuring that all debris is
removed and components are not damaged.
Replace if necessary
-
Clean strainers ensuring debris is removed
-
Check non-return device is not jammed. Clean if
necessary
Mix temperature
changing over time
-
Inlet conditions (pressure or
temperatures) are fluctuating
-
Strainers contain debris
-
Install suitable pressure control valves to ensure
inlet conditions
-
Clean strainers ensuring debris is removed
Either full hot or
cold flowing from
outlet fixture
-
Hot/Cold water has migrated to
another inlet
-
No flow from Hot and Cold supplies
damaged check valves
-
Re-set temperature to between 35-45°C as
required
-
Replace faulty check valves
Water is not
flowing from outlet
-
Hot or cold water failure
-
Thermostatic cartridge contains
debris or damage
-
Strainers contain debris
-
Remove aerator and clean then reinstall
-
Restore inlet supplies and check mix
temperature
-
Clean the cartridge ensuring that all debris is
removed and components are not damaged.
Replace if necessary
-
Clean strainers

© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 19 October 2022, Page 20 of 24
14.0 WARRANTY
The warranty set forth herein is given expressly and is the only warranty given by the Galvin Engineering Pty
Ltd. With respect to the product, Galvin Engineering Pty Ltd makes no other warranties, express or implied.
Galvin Engineering Pty. Ltd. hereby specifically disclaims all other warranties, express or implied, including
but not limited to the implied warranties of merchantability and fitness for a particular purpose.
warranty available for download
from www.galvinengineering.com.au Galvin Engineering Pty Ltd expressly warrants that the product is free
from operational defects in workmanship and materials for the warranty period as shown on the schedule in
the manufact
defective products manufactured by Galvin Engineering without charge, so long as the terms of the
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for
breach of warranty, and Galvin Engineering Pty Ltd shall not be responsible for any incidental, special or
consequential damages, including without limitation, lost profits or the cost of repairing or replacing other
property which is damaged if this product does not work properly, other costs resulting from labour charges,
delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions,
chemical, electrical or any other circumstances over which Galvin Engineering has no control. This warranty
shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or
alteration of the product.
Other manuals for CliniMix CMV2
3
This manual suits for next models
2
Table of contents
Other Galvin Engineering Accessories manuals

Galvin Engineering
Galvin Engineering Flowmatic TZ-IQWAVEB User manual

Galvin Engineering
Galvin Engineering CliniMix CMV2 Instruction sheet

Galvin Engineering
Galvin Engineering CliniMix CMV2 Instruction sheet

Galvin Engineering
Galvin Engineering CliniMix Lead Safe 100.30.79.00 Instruction sheet

Galvin Engineering
Galvin Engineering CliniMix CMV2 Instruction sheet

Galvin Engineering
Galvin Engineering Flowmatic TZ-FLOWSENC24B User manual