Technical Parameters
Power supply: AC85-260V 50Hz
Dimensions: 86*86mm
Display: LCD
Outer Shell: ABS Flame retardant materials + Toughened glass
Installation: Standard 86 box (Hole Pitch 60mm)
Wireless communication: WiFi
Wire communication: RS485
Wiring: Terminals
Sensors: PM2.5, CO2, Temperature, Humidity, VOC(A8-5 Multi-sensor is optional)
Sensor option: external, equipped with WS130

Key and Display Instructions
Operation Instruction
1. ON/OFF:ON:After powered on, it will display “OFF”, press and hold on for 3~6 seconds, it will enter in to normal working interface.
OFF:Under normal working interface, press and hold on for 3~6 seconds to turn off the device, “OFF” displays and all outputs are off.
Button
Instruction
Press and hold on 5 seconds to turn ON/OFF
Press to adjust the brightness at 3 levels
Press and hold on 5 seconds to control the damper to be ON/OFF
Press to switch and check each sensor’s parameter
Press and hold on 5 seconds to check the counting time of the filter
Press to change the fan speed at High, Medium, Low manually
Press and hold on 5 seconds to lock or unlock the keys
Press to set timer mode
Under normal working status, press and hold on 5 seconds to configure
WIFI signal for the controller
Press to switch the mode among: Auto, Manual, Mute

2. Working Mode Setting: Under normal working interface, press to switch the mode among Auto, Manual, Mute .
● During auto mode, the controller can control the fan speed to work automatically based on the values of PM2.5, CO2 or VOC.
No.
PM2.5 value
CO2 value
VOC level
Fan Speed
1
≤50
≤800
≤ 2
Low Speed
2
>50
>800
>2
High Speed
If any value of PM2.5, CO2 or VOC exceeds the limit, the fan will work at high speed directly. When the detected PM2.5 value is below 50 - its backlash , the
detected CO2 value is below 800 - its backlash, and the detected VOC value is below 2 - its backlash, the fan will run at low speed.(PM2.5 default backlash is
10ug/m3, CO2 default backlash is 50ppm,VOC default backlash is 1)
● Manual Mode: Set the fan speed at high, medium, low manually.
● Mute Mode: the fan runs at low speed.
3. Timer off setting:Press to set the shutdown time. The timer icon is flashing, 00:00 displays on the screen, press again, the time will increase up to
12:00 incrementally and then loops back to 00:00, increasing unit: 30minutes. Wait for 3sec or press to confirm and return. When timer mode is on, only the
timer icon displays on the screen but not the exact counting time. After setting the time, press in the future to check the rest counting time. If the time is set to
00:00, the timer mode is off.
4. Fan speed setting: Note:the fan speed can not be modified manually in Mute mode and Auto mode, it can only be set in Manual mode. In Manual mode, press

to switch the fan speed in no-wind, low, medium, high four statuses. Under non-manual mode, press to change the fan mode. In non-manual mode, the fan
speed can not be set.
5. Key lock: under normal interface, press and hold on 5 seconds to lock the keys. When the lock icon displays on the LCD, it indicates that the buttons are
locked. When the lock icon disappears, it indicates that the buttons are unlocked. When the buttons are locked, only ON/OFF button is active, other buttons are
invalid.
6. Filter parameters setting: Under normal working interface, press and hold on 5 seconds to check the remaining counting time to clean or change the filter,
the time increasing unit is 1day. (Note: only when the fan is on, the accumulated time of the filter is valid).
The filter alarm resetting: Under normal working interface, press and hold on 5 seconds to check the remaining counting time to clean or change the filter or
press + and hold on 5 seconds to reset the filter alarm time. After setting, the filter alarm time is stored correspondingly in the secret menu.
7. Sensors parameters checking: Under normal working interface, press to check the parameters of CO2, PM2.5, Temperature, Humidity etc . If there is
error of the sensor, it will skip to display the next sensor parameter. Same logic to VOC.
8. Valve Control: Under normal working interface, press and hold on 5 seconds, the valve is on, the valve-on icon displays on the screen. Press and
hold on 5 seconds again, the valve will be off with the valve off icon displayed on the screen.
9. Screen brightness setting: Under normal working interface, press the ON/OFF button to set the brightness at 3 levels (All bright, half bright, slightly bright).

Secret Menu:
Under OFF status, press and hold on 5 seconds to enter into the secret menu password interface, press to set the first number of the password, press
to switch to the next number of the password until the password 1234 is inserted, then press to enter into the secret menu.
No.
Description
Default Value
Range
Note
01
Factory Default
53
0~99
Default value is 53, after adjusting the data to 55,press the to make the setting
valid.
02
Temperature calibration
0
-9.5-9.5
03
Filter alarm time
360
30-360
04
PM2.5 limit
50
50-500
05
CO2 limit
800
800-1500
06
VOC limit
2
2-3
07
Fresh air fan speed voltage
300, 700, 1000
0~1000
08
Exhaust fan speed voltage
300, 700, 1000
0~1000
09
Sound level
9
OF,0~9

10
Power state
OF
OF/ON/OR
= OF: Once powered on again to be in OFF mode;
= ON: Once powered on again to be in ON mode;
= OR: Remember the last powered on status
11
Software version
10
Can not be set. 10 means V 1.0.
12
WIFI icon clear
0
0/1 clear
Once valid, will display automatically.
13
Slave address
1
1~64
reserved
Optional Models Category
Category
No.
Specifications
Outlook
Model No.
AC 2-Speed
Fan (AC220V)
AC 3-Speed
Fan
(AC220V)
On-Off
Output
(220V)
Analog Output
(0-10V)
RS485
(Optional—E)
External Sensors
(Optional—T)
External
Sensors WS130
Function
instruction
GT11
all-in-one
controller
1
GT11-A2
█
□
□
●PM2.5
●CO2
●Temperature
●Humidity
●VOC
(optional
sensor modules)
●Working Mode:
Manual, Auto, Mute
●Timer function:
0-12h
●Filter alarm
●WIFI( optional )
GT11
2
GT11-A2V
█
█
□
□
3
GT11-A2VD
█
█
█
□
□
4
GT11-A3
█
□
□

5
GT11-A3V
█
█
□
□
WS130
6
GT11-A3VD
█
█
█
□
□
7
GT11-2A3
2 ways█
□
□
8
GT11-D2V
█
2 ways█
□
□

Diagrams