
MD-2(4).( A ) Control Unit, User’s Manual edition 2U3en gazex’2011 v1108 Page 10 /14
PROBLEM ?
Before you call MD manufacturer check and compare the effects with those described below
4.9. TABLE of exceptional unit state after turning the power on:
EFFECT WHY WHAT TO DO
[Zasilanie] (Power) lamps are on,
[Zasilanie modułu] (Module power)
lamp is blinking, no siren
detectors heating period in progress
(alarm outputs are interlocked)
wait approx. 1 min.
Input State [ALARM2] and/or
[ALARM1] lamps are permanently lit
for several/several tens of seconds
and start blinking afterwards
if DEX has been stored for a long
time or at low ambient temperature;
heating period was longer than the
assumed 1 min. time (applies to
detectors with low calibration levels)
temporary pressing [KASOWANIE
PAMIĘCI] (MEMORY RESETTING)
button while the lamps are blinking
(and none of them is permanently
lit) should bring the unit back to
normal state
Input State [ALARM1] or [ALARM2]
lamps of a specific detector are
permanently lit all the time
wrong power polarity or damaged
„A” connecting cable or wrong
sequence of signal conductors
change polarity and sequence of
conductors to the proper one or
replace „A” connecting cable
Output State [ALARM1] and
[ALARM2] lamps and/or Input State
[ALARM1] or [ALARM2] lamps of a
specific detector are permanently lit,
intermittent sound emitted by the
internal siren, green [ZASILANIE]
(POWER) lamp of the specific
detector is blinking, green [AWARIA
SYSTEMU] (SYSTEM FAILURE)
lamp is on
overload above 200mA or shorting
of power circuit of the specific
detector
remove the cause of the short
circuit or the line overload;
turn the power off for 5 seconds
signalling device(s) connected to
„NAP.12V” (12V VOLTAGE) outputs
is/are not operating in A2 or A1 states
short circuit in connecting cable or
damaged signalling device; self-
resetting fuses have tripped
Turn MD power off. Remove the
short circuit in the cable or repair
the signalling device. Turn the
power on; Check the signalling
devices using „TEST” button.
power lamps: on; Output State
[ALARM2] and/or [ALARM1] lamps:
on; Input State lamps: off; internal
siren emitting intermittent sound;
alarm indication system: on
voltage connected to 12V Alarm
Inputs on A2 and/or A1 terminals
(cascade connection)
ALARM signal from external
devices, (mother detectors in
normal state), Alarm Inputs work
without delay!
all lamps are out no power or main power fuse burnt turn the power on or replace the
fuse (with identical, slow blow fuse),
carry out the replacement with
power shut off
When effects other than those described above are observed contact the Authorized Distributor or Manufacturer.