AJAX FireProtect User manual

FireProtect User Manual
Updated March 22, 2022
FireProtect is a wireless indoor smoke detector with an in-built buzzer and a
battery, ensuring up to 4 years of autonomous operation. FireProtect can detect
smoke and rapid temperature increase.
Connecting to the Ajax security system via a secured radio protocol,
FireProtect communicates with the at a distance of up to 1,300 m in line of
sight.
The detector can be a part of third-party security systems, connecting to them
via the or integration module.
The detector is set up via the for iOS, Android, macOS, and Windows.
The system noties the user of all events through push notications, SMS, and
calls (if activated).
model also available for purchase. This model has an additional built-in
carbon monoxide (CO) sensor.
Jeweller
hub
uartBridge ocBridge Plus
Ajax apps
FireProtect Plus

Functional Elements
Operating Principle
The device detects smoke with an optocoupler which consists of an infrared
emitter and a photodetector placed in the smoke chamber. When smoke enters
the chamber, the photodetector detects it by the infrared beam distortion. This
distortion triggers a smoke alarm.
When the temperature exceeds 60°С or rises by 30°С during 30 minutes (not
necessary to reach 60°С), the detector registers temperature increase, which
triggers a re alarm.
Buy re detector FireProtect
1. Siren hole
2. Light indicator (acts as the sensor and Test button)
3. Smoke chamber hole with the temperature detector behind the net
4. SmartBracket attachment panel
5. Power button
6. Tamper button
7. QR code

The life span of the FireProtect detector lasts up to 10 years. In the event of a detector
failure, you will receive a corresponding notication — it will need to be replaced or
submitted for .
In case of alarm, the detector activates the built-in buzzer (the siren sound can
be heard from afar) and blinks with the light indicator. When connected to a
security system, both the user and the security company are notied of the
alarm.
The siren of the device can be turned off using three ways:
comprehensive diagnostics
1. By pressing the Ajax logo on the device lid (there is a touch button under the
logo).
2. Through the Ajax app. In case of re alarm, you will see a pop-up message
in the Ajax app suggesting to turn off the built-in sirens.

Please note that for this to work you need to priorly select Mute Interconnected
Fire Alarmcommand for this button in the KeyPad/KeyPad Plus settings.
If smoke and/or temperature levels do not restore to normal values, in 10
minutes, the FireProtect turns on the siren again.
Connecting the Detector to the Ajax Security System
Connecting to the hub
3. Using the / (if Interconnected Fire Detectors
Alarmfeature is enabled). To turn off the built-in sirens in case of re alarm,
press the “*” button on the KeyPad/KeyPad Plus.
KeyPad KeyPad Plus

Before starting connection:
Only users with administrator rights can add the device to the hub
Pairing the detector with hub:
1. Following the hub user guide, install the . Create the account, add
the hub, and create at least one room.
Ajax app
2. Switch on the hub and check the internet connection (via Ethernet cable
and/or GSM network).
3. Make sure that the hub is disarmed and does not update by checking its
status in the Ajax app.
1. Select Add Device in the Ajax app.
2. Name the device, scan, or type the QR Code (located on the detector body
and packaging), and select the location room.
3. Tap Add — the countdown will start.
4. Switch on the device.

To make sure that the detector is on, press the on/off button — the logo will light
up red for a second.
For detection and pairing to occur, the detector should be located within the
coverage area of the wireless network of the hub (at a single protected object).
The connection request is transmitted for a short time: at the moment of
switching on the device.
If pairing with the hub fails, the detector operates autonomously; switch off the
detector for 5 seconds and retry.
The detector connected to the hub is displayed in the list of devices in the app.
The update of the detector status in the list depends on the device inquiry time
set in the hub settings (the default value is 36 seconds).
Connecting to Third Party Security Systems
To connect the detector to a third party security central unit using the
or integration module, follow the recommendations in the manual
of the respective device.
The smoke detector always operates in the active mode. When connecting
FireProtect to third party security systems, it is appropriate to place it in a
permanently active protection zone.
uartBridge
ocBridge Plus

States
Parameter State
Temperature Temperature of the device. Measures on the
device processor and changes gradually
Jeweller Signal Strength Signal strength between the hub and the
detector
Connection Connection status between the hub and the
device
Battery Charge
Battery level of the device. Two states available:
Lid The tamper state of the device — reacts to the
detachment
ReX Displays the status of using a
Smoke Shows if smoke is detected
Temperature Threshold Exceeded The state of temperature threshold exceeded
alarm
Rapid Temperature Rise The state of rapid temperature increase alarm
Backup Battery Charge Backup battery level of the device
Smoke sensor The state of the smoke detector
Smoke Sensor Dust Level The dust level in the smoke chamber
Temporary Deactivation
Shows the status of the device: active,
completely disabled by the user, or only
notications about triggering of the device
tamper button are disabled
Firmware Detector rmware version
1. Devices
2. FireProtect
ОК
Battery discharged
How battery charge is displayed in
Ajax apps
radio signal
range extender

Device ID Device identier
Settings
Setting Value
First eld Device name, can be edited
Room Selecting the virtual room to which the device is
assigned
High Temperature Alarm If active, the detector reacts when the
temperature is 60°C and higher
Rapid Temperature Rise Alarm
If active, the detector reacts to rapid
temperature increase (30°С for 30 minutes or
less)
Alert with a siren if smoke is detected If active, added to the systemare
activated in case of smoke alarm
Alert with a siren if temperature threshold
exceeded
If active, added to the systemare
activated in case if temperature threshold
exceeded
Alert with a siren if rapid temperature rise
detected
If active, added to the systemare
activated in case if rapid temperature rise
detected
Jeweller Signal Strength Test Switches the device to the signal strength test
mode
Smoke Sensor Self Test Starts FireProtect self test
Temporary Deactivation Allows the user to disconnect the device
without removing it from the system.
Two options are available:
1. Devices
2. FireProtect
3. Settings
sirens
sirens
sirens
Entirely— the device will not execute
system commands or participate in
automation scenarios, and the system will
ignore device alarms and other notications

Note that a disabled device does not trigger an
interconnected alarm of re detectors. But if
smoke is detected, the built-in siren will sound
User Guide Opens the detector User Guide
Unpair Device Deletes device and its settings
Interconnected Fire Detectors Alarms Setup
The function activates built-in sirens of all re detectors if at least one of them
is triggered. Sirens are activated within the hub–detector ping interval according
to the Jeweller settings.
To enable Interconnected Alarms:
1. Open the Devices tab in the
2. Select a hub
3. Go to its Settings by pressing
4. Select the Service item
5. Go to the Fire detectors settings menu and activate the Interconnected Fire
Detectors Alarmsoption
Interconnected alarms are supported by FireProtect detectors with rmware versions
3.42 and later. Please note that when you turn on the interconnected alarms, you cannot
set the hub–detector ping interval (Jeweller settings) of more than 48 seconds.
6. If necessary, set the Delay of Interconnected Alarms from 0 to 5 minutes (in
1-minute increments). The option allows you to postpone the interconnected
alarm for a specied period of time.
When this option is inactive, the interconnected alarm is sent to all re detectors within a
Lid only— the system will ignore only
notications about the triggering of the
device tamper button
Learn more about temporary
deactivation of devices
Ajax app

minute.
The function works as follows:
1. One of the FireProtect detectors detects an alarm.
2. Delay of Interconnected Alarms starts.
3. The built-in siren of the re detector informs the alarm. Users receive
notications in the Ajax app (if are enabled). At the
object, are activated (if the are enabled).
4. An alarm conrmation event is sent to the monitoring station and security
system users, and the system starts the interconnected alarm for re detectors
if:
appropriate notications
Ajax sirens corresponding settings
The interconnected alarm delay time has passed, and the triggered detector
is still registering an alarm.

During the delay of the interconnected alarms, the triggered detector
reports a different type of alarm (for example, the detector report the
exceeding of the temperature threshold after a smoke alarm).
During the interconnected alarm delay, another re detector in the system
raised an alarm.
00:00
00:14
00:00
00:13
00:00
00:11

To give more time to eliminate the cause of false triggering of the detector, the
user can delay the propagation of the interconnected alarm for another 10
minutes:
If a triggered detector does not return to a normal state within 10 minutes after the user
postponed the interconnected alarm, another re detector reports an alarm, or a
triggered detector reports an alarm of another type (for example, temperature and
smoke), the system will send an alarm conrmation and activate interconnected alarm
for re detectors.
Through Ajax apps.
By pressing the KeyPad/KeyPad Plus function button (in the interconnected
re alarm muting mode).
By pressing the Button in the interconnected re alarm muting mode.
By eliminating the cause of the alarm (re detectors at the facility no longer
detect an alarm).
By pressing the touch button of the triggered re detector.

5. If necessary, activate the Ignore First Alarm option. This setting is
recommended for premises with potential sources of false alarms. For example,
if the device is installed in a place where dust or steam can get into the detector.
The option functions as follows:
1. The detector reports a smoke alarm and activates the built-in siren.
2. The built-in 30-second timer of the detector starts.
3. If after 30 seconds the detector still detects a threat, an alarm is sent to the
hub.
4. Hub sends alarms to all users and to the Central Monitoring Station (CMS) of
the security company.
Setting the Residential re alarm system
Residential re alarm system is an Ajax system feature that denes user and
device rights to mute the interconnected alarms of re detectors.
If the feature is enabled, users can silence re alarms of triggered detectors only
in the groups to which they have access. And Button, KeyPad, KeyPad Plus —
the alarms only of those re detectors that are in the same group.
The feature is useful for objects consisting of several rooms and protected by a
single hub. For example, for multi-apartment complexes where each at is a
group with at least one re detector installed. In this case, users can respond to
the alarms of their groups without silencing the alarms of other groups.

The feature is available for , and on and
later versions.
Indication
Event Indication
Detector switching on The logo lights up green for 1 second
Detector switching off The logo blinks red three times and the device
switches off
Registration failed The logo blinks green for a minute, then the
device switches to the autonomous mode
Smoke or temperature increase detected The siren switches on, the logo lights red during
the re/smoke alarm
Battery low
Performance testing
The Ajax security system allows conducting tests for checking the functionality
of connected devices.
The tests do not start straight away but within a period of 36 seconds when
using the standard settings. The test time start depends on the settings of the
detector scanning period (the paragraph on “Jeweller” settings in hub settings).
Hub Plus Hub 2, Hub 2 Plus OS Malevich 2.12
Learn more
One short sound signal per 90 sec — main
batteries low (CR2)
Two short sound signals per 90 sec —
backup battery low (CR2032)
Three short sound signals per 90 sec — both
batteries low
Jeweller Signal Strength Test
Smoke Sensor Self Test

According to the requirements of EN50131 standard, the level of the radio signal
sent by wireless devices is decreased during the test mode.
Detector Testing
Before installing the detector, check the smoke sensor. To test it, switch on the
detector and press the sensor button (the logo centre) for a few seconds – the
detector will test the smoke chamber with electronic simulation of smoke
generation and then will switch on the siren for 6 seconds.
You will receive the notication in the Ajax app regarding the test result and
detector status.
Installation
Selecting the Location
The location of the detector depends on its remoteness from the hub, and
obstacles hindering the radio signal transmission: walls, oors, large objects
inside the room.
The device developed only for indoor use.
If the signal level is low (one bar), we cannot guarantee the stable operation of
the detector. Take all possible measures to improve the quality of the signal. At
least, move the detector: even a 20 cm shift can signicantly improve the quality
of signal reception.
Check the Jeweller signal level at the installation location
Attenuation Test

If after moving the device still has a low or unstable signal strength, use a
.
Install the detector at the ceiling in the highest point where hot air and smoke
are concentrated in case of re.
If there are any beams at the ceiling, protruding by 30 or more centimetres from
the ceiling level, install the detector between every two beams.
Installation procedure
Before installing the detector, make sure that you have selected the optimal
location that follows the guidelines of this manual!
radio
signal range extender
How to install FireProtect re detector correctly
1. Fix the SmartBracket panel on the ceiling using bundled screws. If you use
any other attachment tools, make sure that they do not damage or deform
the attachment panel.
Use double-side adhesive tape only for temporary attachment of the detector. The
tape runs dry with time, which can cause falling, false triggering, and detector
malfunction.

If the LED doesn’t blink after xing in SmartBracket, check the status of the
tamper in the and then the xing tightness of the panel.
If someone detaches the detector from the surface or takes it off the
attachment panel, the security system noties you.
Do not install the detector:
Autonomous Use of the Detector
The detector can be used autonomously, without connecting to a security
system.
In case of autonomous use, the detector noties of the detected re/smoke with
the siren sound and light of the logo. To switch off the siren, press the logo
(there is a sensor button) or eliminate the cause of the actuated alarm.
2. Put the detector on the attachment panel by turning it clockwise on
SmartBracket. When the detector is xed in SmartBracket, it blinks with LED,
signalling that the tamper is closed.
Ajax app
1. outside the premises (outdoors);
2. nearby any metal objects or mirrors causing attenuation or screening of the
signal;
3. at any places with fast air circulation (air fans, open windows or doors);
4. closer than a meter to the cooking surface;
5. inside premises with the temperature and humidity beyond the range of
permissible limits;
6. closer than 1 m to the hub.
1. Switch on the detector by pressing the on/off button for 3 seconds (the logo
will light up green for 1 second) and conduct the smoke test.
2. Select the optimal location of the detector following the recommendations
in the second part of the section of this manual.Selecting the location
3. Install the detector as described in the section .Installation procedure

Maintenance and Battery Replacement
Check the operational capability of the detector regularly. Clean the detector
body from dust, spider web, and other contaminants as they appear. Use soft
dry napkin suitable for tech equipment.
Do not use any substances containing alcohol, acetone, petrol, and other active
solvents to clean the detector.
To a certain level, the detector ignores the dust in the smoke chamber. When the
chamber becomes too dusty, the detector noties the user of the need to clean
it via the app (and beeps every minute and a half). Such maintenance is
compulsory for the detector to operate correctly.
Pre-installed batteries ensure up to 4 years of autonomous operation. If the
batteries are discharged, the security system sends the respective notications
and the detector signal with a sound every 90 seconds:
Keep new and used batteries away from children. Do not ingest battery, Chemical Burn
Hazard.
Tech Specs
Smoke-sensitive element Photoelectric sensor
Temperature sensitive element Thermocouple
How to clean up the smoke chamber
if the main batteries are low — a single short signal;
if the backup battery is low — two short signals;
if both batteries are low — three short signals.
How long Ajax devices operate on batteries, and what affects this
Battery Replacement

Sound notication volume 85 dB at a distance of 3 m
Alarm threshold at the temperature +59°С ±2°С
Tamper protection Yes
Radio communication protocol
Jeweller
Radio frequency band
866.0 – 866.5 MHz
868.0 – 868.6 MHz
868.7 – 869.2 MHz
905.0 – 926.5 MHz
915.85 – 926.5 MHz
921.0 – 922.0 MHzDepends on the region of
sale.
Compatibility
Operates independently or with all Ajax ,
,
,
Maximum RF output power Up to 20 mW
Radio signal modulation GFSK
Radio signal range
Up to 1,300 m (any obstacles absent)
Power supply
2 × CR2 (main batteries), 3 V
CR2032 (backup battery), 3 V
Battery life Up to 4 years
Installation method Indoors
Operating temperature range From 0°С to +65°С
Operating humidity Up to 80%
Overall dimensions 132 × 132 × 31 mm
Learn more
hubs
radio signal range extenders
ocBridge Plus uartBridge
Learn more

Weight 220 g
Service life 10 years
Complete Set
Warranty
Warranty for the “AJAX SYSTEMS MANUFACTURING” LIMITED LIABILITY
COMPANY products is valid for 2 years after the purchase and does not apply to
the pre-installed battery.
If the device does not work correctly, you should rst contact the support
service — in half of the cases, technical issues can be solved remotely!
Technical support:
Compliance with standards
1. FireProtect.
2. SmartBracket mounting panel.
3. Batteries CR2 (pre-installed) — 2 pcs.
4. Battery CR2032 (pre-installed) — 1 pcs.
5. Installation kit.
6. Quick Start Guide.
The full text of the warranty
User Agreement
suppor[email protected]
Other manuals for FireProtect
9
Table of contents
Other AJAX Smoke Alarm manuals

AJAX
AJAX FireProtect Plus Jeweller User manual

AJAX
AJAX FireProtect Plus User manual

AJAX
AJAX FireProtect 2 RB Heat Jeweller User manual

AJAX
AJAX FireProtect User manual

AJAX
AJAX FireProtect User manual

AJAX
AJAX FireProtect 2 RB Heat Jeweller User manual

AJAX
AJAX FireProtect User manual

AJAX
AJAX FireProtect 2 Jeweller User manual

AJAX
AJAX FireProtect Plus User manual

AJAX
AJAX FireProtect 2 User manual