GE OTEF-72 User manual

Instruction Manual
© GE Grid Solutions
INSTRUCTION MANUAL NUMBER MIITR101
INDUCTIVE VOLTAGE TRANFORMER
OTEF-72 / OTEF-123 / OTEF-145 / OTEF-245

Instruction Manual
© GE Grid Solutions
GE Grid Solutions
Av. Nossa Senhora da Piedade, 1021
37504-358 Itajubá - MG – Brazil
AIB 01 30/10/2017 PRB TAA
AIB 00 24/11/2013 TAA TCRP
Owner revision Date Prepared Approved

Instruction Manual
© GE Grid Solutions
Warning!
Any person involved with transport, installation, energizing, operation and maintenance of
Inductive Voltage Transformer (VT) type OTEF must read these instruction prior to any action
related to these voltage transformers.
These VT is built under strict conditions which guarantee the Highest Quality achievement. In
order to keep this high quality during VT’s lifetime, it is utmost important that the instructions in
this Book be thoroughly read and complied with.
THESE VOLTAGE TRANSFORMERS CAN NOT BE STORED IN A HORIZONTAL POSITION FOR MORE
THAN FOUR MONTHS.
IN CASE OF HORIZONTAL TRANSPORTATION, IF THE TIME OF TRANSPORT AND STORAGE
EXCEEDS FOUR MOUNTHS, IT IS MANDATORY TO UNPACK THE VT AND FIX IT TO THE GROUND.
Preliminary Remarks
During reception of the VT, it is important to check unpacking attentively to control the condition
of the transport crate and transformer itself. Any irregularities should be recorded on the
transport delivery note a formal communication sent to the responsible person immediately.
The supplied insulator can be made of porcelain, avoid sudden movements that could cause
damage due to cracks for example.

Instruction Manual
© GE Grid Solutions
INDEX
1. GENERAL DRAWING ................................................................................................................... 5
2. TRANSPORT, RECEPTION, UNPACKING AND STORAGE .................................................................... 6
2.1. Transport ........................................................................................................................... 6
2.2. Reception ........................................................................................................................... 6
2.3. Unpacking .......................................................................................................................... 7
2.4. Storage .............................................................................................................................. 9
3. ANCHORING .............................................................................................................................. 9
4. CONTACT SURFACES PREPARATION .............................................................................................. 9
5. CONECCTIONS............................................................................................................................ 9
5.1. Primary terminal ................................................................................................................. 9
5.2. Secondary terminals ............................................................................................................ 9
5.3. Terminal marking .............................................................................................................. 10
5.4. Grounding ........................................................................................................................ 10
6. BELLOWS BLOCKING SYSTEM FOR TRANSPORTATION ................................................................... 10
7. OIL LEVEL INDICATOR................................................................................................................ 11
8. INSPECTION BEFORE FIRST ENERGIZING ...................................................................................... 11
9. MAINTAINENCE AFTER ENERGIZING ........................................................................................... 12
10. TESTS AT SITE ....................................................................................................................... 12
11. FINAL DISPOSAL OF THE TRANSFORMER PARTS AFTER LIFETIME ................................................ 12

Instruction Manual
© GE Grid Solutions
1. GENERAL DRAWING
Description and characteristics of the OTEF voltage Transformers
1- High voltage terminal
2- Insulation system (paper impregnated with oil)
3- Secondary terminal box
4- Oil level indicator
5- Metallic bellow
6- Insulator: porcelain or composite
7 – Aluminum tank
8- Feet with hole for anchoring
1
2
3
4
5
6
8
7

Instruction Manual
© GE Grid Solutions
2. TRANSPORT, RECEPTION, UNPACKING
AND STORAGE
2.1. Transport
The VT shall be transported as indicated
by the manufacturer in an appropriate
packing. Depending on the limits of
transport heights, some of the VT can be
transported in vertical position. To
confirm this information on the packing
documentations.
Example of vertical packing
Example of horizontal packing
It is important to follow Factory
instructions regarding the stacking of the
packing in terms of transport and
storage when applicable.
ATENTION: The VT has fragile parts
(insulator, bellows top cover, etc.) that
can be damaged during transportation,
by sea, air or by road (being the road
paved or no). The transportation and
handling shall be made with care.
Sudden movements can cause impact
and damage to the equipment.
2.2. Reception
Whether the shipment is of
manufacturer’s or customer’s
responsibility, the customer inspector or
the service agent has to check the
following on receipt of delivery:
If the crates show any signals of impact,
blows or fractures, or if the transformers
have any signal of damage, or oil
leakage, the customer inspector or the
service agent in charge of receipt shall
make a written remark on shipment
documents. The receipt control, mainly
for the porcelain insulators and the
secondary terminal box, shall be done in
the presence of the forwarding agent, if
possible. The remarks regarding the
condition of the goods shall clearly state
details of the damages found at the time
of reception.
In case of damages, the customer
inspector in charge of receipt shall notify
GE and the insurance representative. All
contact information shall be indicated on
shipment insurance documents. This
declaration shall be made within
maximum of eight days after receipt of
the material.

Instruction Manual
© GE Grid Solutions
2.3. Unpacking
Material required for unpacking, lifting
and put the transformer into service:
Qty Description
1 Crane, munck or hoist.
1 Contact grease type PENETROX or
equivalent.
1 Graphite grease MOLYKOTE type
P37 or equivalent.
4 Slings of 4,5m of length (capacity
10.000 N)
1 Sling of 1,5m of length (capacity
1.000 N)
Unpacking of the transformer should be
made with care.
VT packed in vertical position:
1) Remove upper cover.
2) Remove the smaller extremities.
3) Remove the wood blocking pieces.
4) Remove the larger extremities
5)Remove the four screws at the
equipment feet.
6) Lift the VT
Example of wood blocking pieces
Example of lfting a VT
NEVER lift a transformer by its
primary terminal. Always lift it by
the four lifting holes on the
bottom tank.
VT packed in horizontal position:
1) Remove upper cover.
2) Remove the four screws at the
equipment feet.
3) Remove the smaller extremities.
4) Remove the larger extremities
5) Remove the green nylon slings pieces

Instruction Manual
© GE Grid Solutions
6) Remove the VT from the packing and
lift it following the next steps:
Use two slings, one at the neck of
the insulator and other at the hole
for lifting
Remove the VT keeping it in
horizontal position.
Gradually put the VT in vertical
position by lifting the sling
positioned in the neck of the
insulator. Always keep the sling in
vertical position. Handle with care
in order do not damage the top
cover.
After confirming that the VT is in
vertical position and supported in
the ground, change the lift system
by four slings positioned at the four
lifting holes located in the bottom
tank. Also use the 1,5m sling to
connect the other ones near the
area of the neck of the insulator to
guarantee that the VT will not move
horizontally when lifting.
VT handled with its package:
To lift the packaged transformer with
crane or munck follow the marks on the
wood crate, once it indicates the right
position for the slings (nylon belts
reinforced) and avoid blows and
vibrations. Handle with care

Instruction Manual
© GE Grid Solutions
Example of lifting the VT on its packing
2.4. Storage
- The transformers can be stored in
vertical position in homogeneous
surface. Every time that storage is
outside, remove the bellows blocking
system used for transportation only as
shown in 6.0 below.
NOTE: Always fix the transformer to the
ground even the stored is forecasted for
a short period of time.
- It is not allowed to store the VT in
horizontal position.
3. ANCHORING
The transformer should be set up in vertical
position. It is very important that the surface
on which the VT will be set up is flat
(tolerance no more than 1mm). Verify if the
four feet are supported on the structure. If
not, it is necessary to insert a shim before
putting the fixation screws.
4. CONTACT SURFACES PREPARATION
It is recommended to clean all aluminum
contact surfaces with sandpaper 150 grain to
eliminate the oxidation layer. Scrub the
contact surfaces with a metallic brush
(diameter of the thread 0,3mm) and
impregnate with grease of the type
“PENETROX” or equivalent. All the surfaces
must be completely covered with grease.
For silver or tinned contacts, only clean (do
not use sandpaper) and polish the side of the
aluminum. Cleaning silver or tinned surfaces
with sandpaper could cause damage to the
protection layer.
5. CONECCTIONS
5.1. Primary terminal
Connect the high voltage cable, or
tube, to the primary terminal with an
appropriate connector, so that they
assure a good contact. Be sure that
the instructions of the item 4.0 is
followed.
To fix the connect to the high voltage
terminal use a M12 screw applying
5,0 kgf.m (50 N.m) of tightening
torque.
Remark: The screw thread shall be
covered with graphite grease
MOLYKOTE type P37 or equivalent. Do
not use this Grease in the contact
surface.
5.2. Secondary terminals
For this connection, it is important to
have the set of drawings for this
equipment to confirm the type of
secondary terminals and the cables
accepted.
Use proper connectors to guarantee a
good connection. Tightening torque is
indicated in the drawing of the
secondary terminal box.

Instruction Manual
© GE Grid Solutions
The neutral point of each secondary
shall be connected ti the grounding
terminal located in the terminal block,
in order to have a reference for the
voltage.
Secondary terminals not used must
be kept opened and a point be
grounded.
Never short circuit secondary
terminals of a VT. I can cause damage
and fail to the VT.
5.3. Terminal marking
Primary and secondary terminal
marking are done according to the
specified standard. See set of
approved drawings.
Primary and secondary connection
scheme are shown on the name plate,
fixed on the VT secondary box cover.
5.4. Grounding
The transformer tank has two
earthing terminals located at the
bottom tank that should be linked to
the substation ground system through
an appropriated grounding connector,
if requested, supplied with the
equipment. See set of drawings to
confirm rage of cable that can be
used.
Example of grounding terminal
Example of grounding connector
6. BELLOWS BLOCKING SYSTEM FOR
TRANSPORTATION
For transportation purposes, the bellows is
fixed (no movement) using a KIT of synthetic
cushion lightly compressed by the top cover
as shown in the picture below:
Example of bellows blocking system
Before putting the VT in the pedestal or
when storing, first it is necessary to remove
the bellows blocking system for
transportation following the steps below:
•Mark a reference line for the top cover
relative to the primary terminal (using a
marker or a pencil or any similar device) with
the aim of at the end of the procedure the
top cover Will be at the original position.
•Remove the four M6 screws that fix the top
cover to the bellows flange.
•Remove the top cover, with care, keeping a
vertical movement. Do with care in order do

Instruction Manual
© GE Grid Solutions
not damage the bellows.
•Remove the bellows blocking system (kit of
synthetic cushion).
•Confirm by visual inspection that the
bellows are in good condition.
Geometry:
- The bellows cover in at horizontal: it is not
tilted by a possible deformation in the
bellows.
- The bellows is neither distorted nor
asymmetric: the convolutions are equally
distributed around the bellows
circumference.
Surface:
- There is no damage or deformation like
those caused by blows.
•Confirmed that the bellows is in good
condition, put the top cover in the original
position.
•Tight the four M6 screws with torque of
2kgf.m.
In case bellows show any type of
deformation or blow the VT should not be
put into service unless there is a formal
release from GE. In case of doubts, to contact
the technical assistance support of GE for
further information.
7. OIL LEVEL INDICATOR
The position of the oil level indicator can be
verified through the window of the top
cover. The plate of the indicator is divided in
three areas. Central green area shows the
normal operation condition and higher and
lower areas are shown with a red strip. In
normal conditions, the indicator shows the
central green area.
In case of oil level indicator is in either of the
red areas, the VT shall be taken off from
operation and GE informed immediately.
Example of oil level indicator
8. INSPECTION BEFORE FIRST ENERGIZING
•Confirm terminals connections to assure the
correct tightening torque.
•Confirm that there are no short-circuited
secondary terminals. If so they must be
opened and earthed.
•Confirm the ground connections of
transformer tank.
•Confirm that the oil level indicator is in the
central green area.
The VT are routine tested in the factory and
do not require repeated electric test. Look
for Project routine test reports for more
details.
Whilst al care is taken in the factory during
oil filling, the surface near of screws and
bellows could have a small quantity of oil.
This should not be considered as an oil
leakage provided that the bellows are
positioned within the green strip area.
It is not necessary to remove oil samples for
analysis. The VT is hermetically sealed.
If required, small quantity of oil can be taken.
Always verify oil level indicator before take
oil samples.

Instruction Manual
© GE Grid Solutions
Never complete oil volume without prior
formal authorization of GE.
Important remark: During commissioning, it
is recommended to register the values
founded for each of the performed test to
compare with future measurements during
the VT lifetime. The measurements taken in
the factory are important and also the
measurements during commissioning of each
VT. Comparison between test results makes
sense to the field measured once it is
possible to follow the evolution of each
parameter.
9. MAINTAINENCE AFTER ENERGIZING
After installation and energizing, the VT
should not require any further intervention.
However, it is suggested to perform a visual
inspection during the first weeks of service
to:
•Confirm the position of oil level indicator. If
the indicator is significantly below or above
the central green area, in comparison with
other VT, it is recommend to check that there
is no oil leakage and, if an oil leakage is
discovered remove the VT from operation
and inform GE.
•With an infrared device, check if
connections are not overheating. Compare
with other VT from the same circuit.
After one year of operation, it is
recommended a detailed inspection of
tightening torques and oil leakage and
thereafter twice per year according to the
substation maintenance contract.
If posible GE suggests disconnecting the VT
and to perform the following examination:
•Insulator: Depending on the pollution level
it is necessary to clean the porcelain.
•Metallic components: check for corrosions.
•Tightening torque of primary and secondary
connections. Any adjustments should be
carried out.
•Secondary terminal box: If necessary clean
inside the terminal box.
•Confirm oil level indicator and if there is oil
leakage.
•Remove top cover to have access to the
bellows and confirm if there is an oil leakage
near the fixation of the bellows and / or if the
bellows is in good condition (no
deformations
10. TESTS AT SITE
The following test could be performed during
VT lifetime according to the best practice of
the user:
a) Voltage ratio (T.T. R)
b) Polarity (Polarimeter)
c) Winding resistance (Wheatstone
bridge).
e) Insulation resistance (Megger)
f) Infrared measurement.
11. FINAL DISPOSAL OF THE TRANSFORMER
PARTS AFTER LIFETIME
The high voltage instruments transformers
are made of the following components,
which after life time require a properly
disposal to prevent environmental
contamination:

Instruction Manual
© GE Grid Solutions
Components Recommended
Disposal
Metallic materials Metal recycling
company
Resin and materials
saturated with resin
Industrial landfill,
properly licensed by the
state’s responsible
agency.
Oil (PCB-free) –
classified as Class I
hazardous residue
Oil refinery at a
company which is
properly licensed to
perform such an
activity
Material contaminated
with oil
Co-processing or
incineration at a
company which is
properly licensed by the
state’s responsible
agency.
Porcelain insulator Industrial landfill,
properly licensed by the
state’s responsible
agency
Other materials Industrial landfill,
properly licensed by the
state’s responsible
agency
The disposal of oil and components
contaminated with oil directly into the soil or
water is prohibited.
For further information or clarifications,
contact GE environment department:
+55 35 36297112.
This manual suits for next models
3
Table of contents
Other GE Transformer manuals