manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Gentex
  6. •
  7. Smoke Alarm
  8. •
  9. Gentex 8000 Series User manual

Gentex 8000 Series User manual

88000000
SSEERRIIEESS
PHOTOELECTRIC TYPE OPEN AREA SYSTEM DETECTORS
INTRODUCTION 8000 SERIES
The 8000 Series smoke detector is an open area photoelectric system smoke
detector, engineered to provide reliable early warning against smoke. Each smoke
detector is provided with a standard Form A/FormC relay for alarm and auxiliary
functions.
Supplied with each detector is a quick-disconnect wiring harness and universal
mounting bracket.
ODELS AVAILABLE
(SEE BACK OF SMOKE DETECTOR FOR EXACT MODEL)
8240/8243.........................................24VDC
8100/8103.........................................120VAC, 60 HZ
OPTIONS, SELECTIONS
* P......................................................BUILT-IN PIEZO HORN
T.......................................................INTE RAL 135°F THERMAL SENSOR
**H......................................................ISOLATED 135°F THERMAL SENSOR
Y.......................................................NON-LATCHIN /SELF-CLEARIN
* All detectors with the piezo horn option include smoke detector reverse polarity
horn activation. Relay contacts are not activated with the application of reverse
polarity power.
** The H Series 135°F normally open isolated thermal is not wired into the detection
circuit. It is for remote connection to the auxiliary annunciation circuit. The "H"
thermal is supervised with two wires in and two wires out.
The 8240P/8100P models produce a non-temporal audible alarm and are
therefore not intended for locations where the desired action of the
occupant(s) is evacuation.
The 8243P/8103P models produce a temporal 3 audible alarm. Per NFPA
72, the American National Standard Audible Emergency Evacuation
Signal as defined in ANSI S3.41, is required whenever the intended
response is to evacuate the building.
ELECTRICAL SPECIFICATIONS
ODEL NU BERS 8240 8100
Operating Voltage Nominal: 24VDC 120VAC
Range Min: 18VDC 110VAC
Max: 30VDC 130VAC
Frequency ------ 60Hz.
Current consumption at Normal Operating Voltage
Standby 6mA 70mA
Alarm 60mA 70mA
NOTICE: FOR "P" OPTION (HORN), ALARM CURRENT CONSUMPTION IS
UNCHAN ED. REVERSE POLARITY CURRENT IS 15MA.
Alarm Relay Contacts: 1 Form A.....................................................Rated Load (Resistive)
1 Amp at 24 Volt DC
0.5 Amp at 120 Volt AC
Auxiliary Relay Contact: 1 Form C..................................................Rated Load (Resistive)
1 Amp at 24 Volt DC
0.5 Amp at 120 Volt AC
Temperature................................................................................40ºF-100ºF(4.4ºC-37.8ºC)
Humidity...................................................................................10%-93% Relative Humidity
Size...................................................................................................5.7"W x 5.7"H x 2.8"D
HOW YOUR S OKE DETECTOR WORKS
The 8000 Series smoke detector operates on the photoelectric light scatter principle.
The unit's sensing chamber houses a light source and a light sensor.
The darkened sensing chamber is exposed to the atmosphere and designed to
permit optimum smoke entry from any direction while rejecting light from outside the
detector.
The light source is an infrared (invisible) LED which pulses every 4 to 8 seconds.
The light sensor is a photodiode matched to the light frequency of the LED light source.
Installation Instructions - Owner's Information READ CAREFULLY AND SAVE
Under normal conditions, the light generated by the pulsing infrared LED is not seen
by the light sensor. When smoke enters the sensing chamber, light from the pulsing
LED light source is reflected by the smoke particles onto the photodiode light sensor. At
the first sighting of smoke, the smoke detector is put into a pre-alarm mode. This is
indicated by a rapidly flashing LED on the face of the smoke detector.
Once the light sensor confirms smoke for 2 consecutive pulses inside the chamber,
the light sensor produces the signal necessary to trigger the alarm.
This technique of verifying the smoke condition, combined with a 5-to-1 signal-to-
noise ratio, substantially reduces the possibility of nuisance alarms.
PLACE ENT OF S OKE DETECTORS
THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE
NATIONAL FIRE PROTECTION ASSOCIATION’S
STANDARD 72 (National Fire Protection Association, Batterymarch Park, Quincy, MA
02269).
For your, information, the National Fire Protection Association’s Standard 72, 2010
Edition, Chapter 17 states the following:
17.7.3.1.1 The location and spacing of smoke detectors shall be based upon the
anticipated smoke flows due to the plume and ceiling jet produced by the anticipated
fire, as well as any pre-existing ambient airflows that could exist in the protected
compartment.
17.7.3.1.2 The design shall account for the contribution of the following factors in
predicting detector response to the anticipated fires to which the system is intended to
respond:
(1) Ceiling shape and surface
(2) Ceiling height
(3) Configuration of contents in the protected area
(4) Combustion characteristics and probable equivalence ratio of the anticipated fire
involving the fuel loads within the protected area
(5) Compartment ventilation
(6) Ambient temperature, pressure, altitude, humidity, and atmosphere
17.7.3.1.3 If the intent is to protect against a specific hazard, the detector(s) shall be
permitted to be installed closer to the hazard in a position where the detector can
intercept the smoke.
17.7.3.1.4 If the intent is to initiate action when smoke/fire threatens a specific object or
space, the detector shall be permitted to be installed in close proximity to that object or
space.
17.7.3.2 Spot-Type Smoke Detectors
17.7.3.2.1 Spot-type smoke detectors shall be located on the ceiling or, if on a sidewall,
between the ceiling and 12 in. (300 mm) down from the ceiling to the top of the detector.
17.7.3.2.2 To minimize dust contamination, smoke detectors shall be in accordance with
17.7.3.2.3.1 through 17.7.3.2.3.5.
17.7.3.2.3.1 In the absence of specific performance-based design criteria, smooth
ceiling smoke detector spacing shall be a nominal 30 ft (9.1 m).
17.7.3.2.3.2 In all cases, the manufacturer’s published instructions shall be followed.
17.7.3.2.3.3 Other spacing shall be permitted to be used depending on ceiling height,
different conditions, or response requirements.
17.7.3.2.3.4 For the detection of flaming fires, the guidelines in Annex B shall be
permitted to be used.
17.7.3.2.3.5 For smooth ceilings, all points on the ceiling shall have a detector within a
distance equal to 0.7 times the selected space.
17.7.3.2.4 For solid joist and beam construction, spacing for spot-type smoke detectors
shall be in accordance with 17.7.3.2.4.1 through 17.7.3.2.4.6.
550-0139
Pg. 8-1
NOTICE:
120 AC VOLTAGE (8100 & 8103 SERIES):
HOT (BLACK) WIRE: PIN 3 AND PIN 6
NEUTRAL (WHITE) WIRE: PIN 12 AND PIN 15
24 DC VOLTAGE (8240 & 8243 SERIES):
POSITIVE (RED) WIRE: PIN 3 AND PIN 6
NE ATIVE (BLACK) WIRE: PIN 12 AND PIN 15
17.7.3.2.4.1 Solid joists shall be considered equivalent to beams for smoke detector
spacing guidelines.
17.7.3.2.4.2 For level ceilings, the following shall apply:
(1) For ceilings with beam depths of less than 10 percent of the ceiling height (0.1H),
smooth ceiling spacing shall be permitted. Spot-type smoke detectors shall be
permitted to be located on ceilings or on the bottom of beams.
(2) For ceilings with beam depths equal to or greater than 10 percent of the ceiling
height (0.1H), the following shall apply:
(a) Where beam spacing is equal to or greater than 400 percent of the ceiling
heights (0.4 H), the following shall be permitted for spot detectors:
i. Smooth ceiling spacing in the direction parallel to the beams and at one-half
smooth ceiling spacing in the direction perpendicular to the beams
ii. Location of detectors either on the ceiling or on the bottom of the beams
(3) For beam pockets formed by intersecting beams, including waffle or pan-type
ceilings, the following shall apply:
(a) For beam depths less than 10 percent of the ceiling height (0.1H), spacing shall
in accordance with 17.7.3.2.4.2(1).
(b) For beam depths greater than or equal to 10 percent of the ceiling height
(0.1H), spacing shall be in accordance 17.7.3.2.4.2(2).
(4) For corridors 15ft (4.6 m) in width or less having ceiling beams or solid joists
perpendicular to the corridor length, the following shall apply:
(a) Smooth ceiling spacing shall be permitted
(b) Location of spot-type smoke detectors on ceilings, sidewalls, or the bottom of
beams or solid joists.
(5) For rooms of 900 ft2(84 m2) or less, the following shall be permitted:
(a) Use of smooth ceiling spacing
(b) Location of spot-type smoke detectors on ceilings or on the bottom of beams
17.7.3.2.4.3 For sloping ceilings with beams running parallel up slope, the following shall
apply.
(1) Spot-type detector(s) shall be located on the ceilings within beam pocket(s).
(2) The ceiling height shall be taken as the average height over slope.
(3) Spacing shall be measured along a horizontal projection of the ceiling
(4) Smooth ceiling spacing shall be permitted within beam pocket(s) parallel to the
beams.
(5) For beam depths less than or equal to 10 percent the ceiling height (0.1 H),
spot-type detectors shall be located with smooth ceiling spacing perpendicular to
the beams.
(6) For beam depths greater than 10 percent of the ceiling height (0.1 H), the following
shall apply for spacing perpendicular to the beams:
(a) For beam spacing greater than or equal to 40 percent of the ceiling height (0.4
H), spot-type detectors shall be located in each beam pocket.
(b) For beam spacing less than 40 percent of the ceiling height (0.4 H), spot-type
detectors shall not be required in every beam pocket but shall be spaced not
greater than 50 percent of smooth ceiling spacing.
17.7.3.2.4.4 For sloping ceilings with beams running perpendicular across slope, the
following shall apply:
(1) Spot-type detector(s) shall be located at the bottom of the beams
(2) The ceiling height shall be taken as the average height over slope
(3) Spacing shall be measured along a horizontal projection of the ceiling
(4) Smooth ceiling spacing shall be permitted within beam pocket(s).
(5) For beam depths less than or equal to 10 percent of the ceiling height (0.1 H),
spot-type detectors shall be located with smooth ceiling spacing.
(6) For beam depths greater than 10 percent of the ceiling height (0.1 H), spot-type
detectors shall not be required to be located closer than (0.4 H) and shall not
exceed 50 percent of smooth ceiling spacing.
17.7.3.2.4.5 For sloped ceilings with beam pockets formed by intersecting beams, the
following shall apply:
(1) Spot-type detector(s) shall be located at the bottom of the beams.
(2) The ceiling height shall be taken as the average height over slope.
(3) Spacing shall be measured along a horizontal projection of the ceiling.
(4) For beam depths less than or equal to 10 percent of the ceiling height (0.1 H),
spot-type detectors shall be spaced with not more than three beams between
detectors and shall not exceed smooth ceiling spacing
(5) For beam depths greater than 10 percent of the ceiling height (0.1 H), spot-type
detectors shall be spaced with not more than two beams between detectors, but
shall not be required to be spaced closer than (0.4 H), and shall not exceed 50
percent of smooth ceiling spacing.
17.7.3.2.4.6 For sloped ceilings with solid joists, the detectors shall be located on the
bottom of the joist.
17.7.3.3 Peaked. Detectors shall first be spaced and located within 36 in. (910 mm) of
the peak, measured horizontally. The number and spacing of additional detectors, if
any, shall be based on the horizontal projection of the ceiling.
17.7.3.4 Shed. Detectors shall first be spaced and located within 36 in. (910 mm) of the
high side of the ceiling, measured horizontally. The number and spacing of additional
detectors, if any, shall be based on the horizontal projection of the ceiling.
17.7.3.5 Raised Floors and Suspended Ceilings. Spaces beneath raised floors and
above suspended ceilings shall be treated as separate rooms for smoke detector
spacing purposes. Detectors installed beneath raised floors or above suspended
ceilings, or both, including raised floors and suspended ceilings used for environmental
air, shall not be used in lieu of providing detection within the room.
17.7.3.5.1 For raised floors, the following shall apply:
(1) Detectors installed beneath raised floors shall be spaced in accordance 17.7.3.1,
17.7.3.1.3, and 17.7.3.2.2.
(2) Where the area beneath the raised floor is also used for environmental air, detector
spacing shall also conform to 17.7.4.1 and 17.7.4.2.
17.7.3.5.2 For suspended ceilings, the following shall apply:
(1) Detector spacing above suspended ceilings shall conform to the requirements of
17.7.3 for the ceiling configuration
(2) Where detectors are installed in ceilings used for environmental air, detector
spacing shall also conform to 17.7.4.1 and 17.7.4.2.
INSTALLATION OF 8000 SERIES
OUNT ROUGH-IN BOX & RUN WIRING
I PORTANT: INSURE THAT ALL FLUORESCENT LI HTIN FIXTURES ARE
PROPERLY ROUNDED.
1. Use a 2" x 3" switch box or a 4" square or octagon junction box. Mount a box for
each smoke detector and run the system fire detection circuit plus the power circuit to
all smoke detector locations. See Wiring Diagrams, FI URES A and B, for Latching
Models, and FI URES C and D for Self Clearing Models.
NOTICE: THE WIRIN TO BE USED SHALL BE IN ACCORDANCE WITH THE
PROVISIONS OF ARTICLE 300.3(B) OF THE NATIONAL ELECTRICAL CODE,
NFPA 70, AS WELL AS ARTICLE 210.
CAUTION: Break wire runs to provide supervision for connections made to each wire
pair.
FI URE A
CLASS B PANEL WIRIN DIA RAM
550-0139
Pg. 8-2
CLASS A PANEL WIRIN DIA RAM
FI URE B
SECURE S OKE DETECTOR TO OUNTING PLATE
1. Plug the wire connector into the detector base.
2. Place the smoke detector up to the mounting plate, rotating it clockwise until smoke
detector firmly snap locks into place. Keep the smoke detector parallel to the
mounting plate so upper and lower tabs on plate seat correctly into detector,
FI URE H.
FI URE H
FI URE
FI URE C
CLASS B PANEL WIRIN DIA RAM - ONE SMOKE DETECTOR PER ZONE
FI URE D
CLASS A PANEL WIRIN DIA RAM - ONE SMOKE DETECTOR PER ZONE
2. If wall mounting is desired, be sure the box screws are oriented to upper right and
lower left corners, FI URE F. The volume of the box is determined by the number of
conductors entering and exiting the box. Use 1-3/4 cubic inches per conductor (#16
AW ).
INSTALL OUNTING PLATE & CONNECT WIRES
1. Remove the plug and wire assembly from the shipping container and wire it in
junction box as follows:
2. Major Circuits (power in, power out, and alarm contacts) have two wires, one for the
incoming circuit and one for the outgoing circuit. Auxiliary relay contacts are single
wire circuits. Make connections as detailed on wiring diagrams, FI URE .
3. Lace the connector through the provided mounting plate and secure the plate to the
junction box.
NOTICE: FOR TROUBLE AREAS WHERE THERE CAN BE A LAR E VOLUME OF
AIR BLOWIN OUT THROU H THE ELECTRICAL JUNCTION BOX. YOU MUST
FIRST INSERT THE CARDBOARD SHIELD PACKA ED WITH YOUR SMOKE
DETECTOR TO THE BACKSIDE OF THE SMOKE DETECTOR BEFORE SECURIN
IT TO MOUNTIN PLATE.
CHECKOUT & TROUBLESHOOTING
1. Turn test knob on each unit to the NORMAL position and supply power to the system
Control Unit.
a. If the fire alarm sounds, one or more smoke detector connections to the fire
detection circuit may be reversed. Check wire color codes and trace.
b. If the trouble buzzer sounds, the fire detection circuit may be reversed or
disconnected at the Control Unit.
2. Testing with the Test Knob.
a. Rotate the test knob on the front of the unit to TEST 1 position (counter-
clockwise). See FI URE I. The alarm should sound in less than 20 seconds.
b. To reset the system, return the knob to its NORMAL position and use the reset
switch on the system Control Panel. Hold in reset for 5 or more seconds.
c. To test smoke detector for high sensitivity, rotate test knob clockwise to the TEST
2 position. Alarm should remain silent. Return test knob to normal position. If
your smoke detector alarmed during TEST 2, the smoke detector's sensitivity has
become too high and may cause false alarms. This may mean your smoke
detector is dirty and should be cleaned as described in the below maintenance
procedure.
d. If your detector still alarms in TEST 2 position following washing and
recommended drying time, return it to entex Corporation for service. The test
knob actually tests the sensitivity of the unit by using the same principle involved
as when smoke enters the smoke detector. When you turn the test knob to the
TEST 1 position, you are scattering the detector's LED light to the equivalent of
3.4% actual smoke. TEST 2 position is equivalent to 0.85%.
550-0139
Pg. 8-3
SMOKE
DETECTOR
SMOKE
DETECTOR
RELEASING
DEVICE
120VAC (Neutral) (WHITE) or 24VDC (Negative) (BLACK)
120VAC (Hot) (BLACK) or 24VDC (Positive) (RED)
IN
IN
OUT
OUT
YELLOW
POWER
SUPPLY
YELLOW
ORANGE
ORANGE
FI URE E
RELEASIN DEVICE WIRIN DIA RAM
FI URE F
NOTICE: ONLY IVORY® DISHWASHIN LIQUID IS TO BE USED. OTHER BRANDS
ARE NOT RECOMMENDED AND MAY CAUSE YOUR DETECTOR TO
MALFUNCTION.
6. Allow smoke detector to soak for approximately 10 minutes (longer if extremely
dirty). Then agitate for 5 or 10 seconds to flush out any remaining dirt left inside
detector's housing.
7. Remove detector from wash water and transfer directly to one of the first rinse
buckets containing clear water. Again, allowing smoke detector to become
completely submerged, agitate once more for 5 or 10 seconds to remove soap
residue.
8. Finally, transfer detector to your second and final rinse bucket, repeating method
found in Step 7, then remove smoke detector to a clean dry area for a period of 48
hours to allow it to thoroughly dry.
I PORTANT: It is recommended to change wash and rinse water after five (5) smoke
alarms. If your devices are extremely dirty, water should be changed more frequently.
NOTICE: SMOKE DETECTORS ARE TO AIR DRY ONLY. DO NOT PLACE SMOKE
DETECTOR IN OVEN OR USE A HOT AIR BLOWER TO ACCELERATE DRYIN
TIME. THIS COULD RESULT IN DAMA E TO YOUR SMOKE DETECTOR.
In the event you experience difficulty in the cleaning of your smoke detectors or if you
have any questions, please contact entex Corporation or your local entex distributor
If the smoke detector does not work properly, do not try and fix
it yourself. This will void your warranty. See "To Return a Smoke Detector" for
instructions to return smoke detectors that do not operate properly. DO NOT TRY
TO FIX IT YOURSELF.
I PORTANT: entex recommends smoke detectors be tested a minimum of once a
week.
Never use an open flame of any kind to test your smoke
detector. You may ignite and damage the smoke detector as well as the
surrounding area. The test feature of your smoke detector accurately simulates
smoke conditions and tests the smoke detector’s functions as required by
ANSI/UL 268.
Do not cover, tape, or otherwise block the openings of your
smoke alarm. These openings are designed to allow air to pass through your
smoke detector, thus sampling the air around the smoke detector.
Smoke detectors are not to be used with detector guards
unless the combination has been evaluated and found suitable for that purpose.
NOTICE: FAILURE TO RE ULARLY CLEAN THIS SMOKE DETECTOR MAY RESULT
IN NUISANCE ALARMS. A BUILD UP OF DUST CREATES AN OBSCURATION THAT
\SIMULATES SMOKE. THIS MEANS THE UNIT MAY O INTO ALARM WITHOUT A
SMOKE CONDITION.
TO RETURN A S OKE DETECTOR
Should you experience problems with your smoke detector, proceed as follows:
1. Turn off electrical power to the detector.
2. Rotate the detector counter-clockwise to remove it from its mounting plate.
3. Unplug the connector from the back of the detector. Do not remove the wire
connection; leave the connector for your replacement detector. If the system is to
remain active while the detector is removed, a jumper plug must be installed.
Contact factory for part.
4. Carefully pack (the manufacturer cannot be responsible for consequential damage)
and return to the manufacturer. Include complete details as to exact nature of
difficulties being experienced and date of installation.
5. Return to: entex Corporation, 10985 Chicago Drive, Zeeland, Michigan 49464.
Prior to returning, call 1-800-436-8391 or e-mail [email protected] to obtain a
RMA number from our return department.
LIMITED WARRA TY
For a period of 24 months from the date of purchase, or a maximum of 20 months from the date of manufacture,
Gentex warrants to you, the original consumer purchaser, that your Smoke Detector will be free from defects in
workmanship, materials, and construction under normal use and service. If a defect in workmanship, materials, or
construction should cause your Smoke Detector to become inoperable within the warranty period, Gentex will repair
your Smoke Detector or furnish you with a new or rebuilt replacement Smoke Detector without charge to you except
for postage required to return the Smoke Detector to us. Your repaired or replacement Smoke Detector will be
returned to you free of charge and it will be covered under this warranty for the balance of the warranty period.
This warranty is void if our inspection of your Smoke Detector shows that the damage or failure was caused by
abuse, misuse, abnormal usage, faulty installation, improper maintenance, or repairs other than those performed by
us. A Y WARRA TIES IMPLIED U DER A Y STATE LAW, I CLUDI G IMPLIED WARRA TIES OF
MERCHA TABILITY OR FIT ESS FOR A PARTICULAR PURPOSE, APPLY O LY FOR THE WARRA TY
PERIOD SPECIFIED ABOVE. PLEASE OTE THAT SOME STATES DO OT ALLOW LIMITATIO S O HOW
LO G A IMPLIED WARRA TY LASTS, SO THE ABOVE EXCLUSIO MAY OT APPLY TO YOU.
GE TEX WILL OT BE LIABLE FOR A Y LOSS, DAMAGE, I CIDE TAL OR CO SEQUE TIAL DAMAGES
OF A Y KI D ARISI G I CO ECTIO WITH THE SALES, USE OR REPAIR OF THIS SMOKE DETECTOR.
PLEASE OTE THAT SOME STATES DO OT ALLOW THE EXCLUSIO OR LIMITATIO OF I CIDE TAL OR
CO SEQUE TIAL DAMAGES, SO THE ABOVE EXCLUSIO MAY OT APPLY TO YOU.
If a defect in workmanship, materials, or construction should cause your Smoke Detector to become inoperable
within the warranty period, you must return the Smoke Detector to Gentex postage prepaid. You must also pack the
Smoke Detector to minimize the risk of it being damaged in transit. You must also enclose a return address. Smoke
Detectors returned for warranty service should be sent to: Gentex Corporation, 10985 Chicago Drive, Zeeland, MI
49464.
If we receive a Smoke Detector in a damaged condition as the result of shipping, we will notify you and you must
file a claim with the Shipper.
THIS LIMITED WARRA TY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS
WHICH VARY FROM STATE TO STATE.
GE TEX CORPORATIO
10985 CHICAGO DRIVE, ZEELA D, MI 49464
PHO E: 1-800-436-8391
www.gentex.com
550-139-LAC 9-29-97
Important otice:
These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes only, are necessarily summary, and are not purported to serve as legal advice and should not be used as such. Gentex makes no representations and warranties, express or implied, that these
materials are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws, regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws, regulations and rules and the application of
such laws, regulations and rules to particular fact patterns. Each person's activities can differently affect the obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be used only for informational purposes and should not be used as a substitute for seeking
professional legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material.
Pg. 8-4
e. The test knob is not an electrical switch, nor is it connected in any way to the
alarm horn. Therefore, when you test with the test knob, you are simulating the
smoke condition in the detector and testing all elements of the smoke detector
that are necessary for the detection of actual smoke. To check for proper smoke
entry into your smoke detector's sensing chamber, entex recommends using the
Home Safeguard Smoke Detector spray or CHEKKIT® SMOKE Detector Tester
from SDI. This test should be performed once a year and should be sprayed from
a distance no closer than 12 inches from smoke detector (refer to NFPA 72 for
details).
3. A trouble buzzer will sound if any detector is removed from its socket in supervised
circuits. CAUTION: When a smoke detector is removed it may cause other smoke
detectors to have a loss of power and become inoperative. If this happens,
reconnect the smoke detector until a replacement can be installed, or use a jumper
plug which can be ordered separately from the factory.
4. Power-On- Alarm Light. The LED on the face of the smoke detector blinks every
15-30 seconds, indicating electrical power is being supplied, see FI URE I. If the
smoke (or test knob) persists for about 20 seconds, the LED will be on continuously
for latching models or flash rapidly for non-latching models to indicate the alarm
condition of the smoke detector. It will stay on until the system is reset.
AINTENANCE
After your smoke detector has been in operation for a period of time or if it was
installed prior to the completion of all building construction, your smoke detector may
have become more sensitive due to dirt build-up in the smoke detector's optic sensing
chamber. This could cause nuisance alarms or cause the smoke detector to activate
from small amounts of smoke build-up. If this should occur, following this simple
washing procedure will restore your smoke detector back to its original condition.
For further information regarding frequency of maintenance and testing, refer to
NFPA 72, NFPA, Batterymarch Park, Quincy, MA 02269.
NOTICE: FAILURE TO FOLLOW FULL CLEANIN INSTRUCTIONS COULD
RESULT IN DAMA E TO THIS SMOKE DETECTOR.
1. Turn off electrical power to the detector.
2. Twist the smoke detector counter-clockwise to remove it from its mounting plate.
The fire alarm system shall remain active during all
maintenance. Therefore, while servicing one smoke detector, either use a
replacement smoke detector or jumper plug to keep the fire alarm system
operative. Contact your local Gentex distributor for the proper jumper plugs to
use with your fire system.
3. Unplug the connector from the back of the smoke detector. Do not remove the wire
connection; leave the connector for your replacement smoke detector or jumper plug.
4. Select three (3) standard size wash buckets and fill them each with one gallon of
normal tap water (distilled or de-ionized treated water is recommended as a final
rinse if water is extremely hard in your area).
5. Add 1/8 cup of Ivory® dishwashing liquid to the first bucket of water and allow it to
mix thoroughly, then place dirty smoke detector in the soap water mixture until it
becomes completely covered or submerged. NOTE: If the smoke detectors are
exceptionally dirty, you may wish to first wipe off any excess dirt before washing
smoke detector so as not to dirty the wash water too quickly.
DO NOT open smoke alarm for cleaning. IF S OKE ALAR IS
OPENED DURING CLEANING, PRODUCT WARRANTY BECO ES VOID.
FI URE I

This manual suits for next models

2

Other Gentex Smoke Alarm manuals

Gentex 710LS User manual

Gentex

Gentex 710LS User manual

Gentex 7109CS User manual

Gentex

Gentex 7109CS User manual

Gentex S1209 Service manual

Gentex

Gentex S1209 Service manual

Gentex 710LS Installation instructions

Gentex

Gentex 710LS Installation instructions

Gentex 700 SERIES Quick start guide

Gentex

Gentex 700 SERIES Quick start guide

Gentex 7109CS User manual

Gentex

Gentex 7109CS User manual

Gentex S1209 Series User manual

Gentex

Gentex S1209 Series User manual

Gentex 710LS User manual

Gentex

Gentex 710LS User manual

Gentex 700 SERIES User manual

Gentex

Gentex 700 SERIES User manual

Gentex 913 SERIES Quick start guide

Gentex

Gentex 913 SERIES Quick start guide

Gentex 9000 SERIES User manual

Gentex

Gentex 9000 SERIES User manual

Gentex 7109CS User manual

Gentex

Gentex 7109CS User manual

Gentex 7109CS User manual

Gentex

Gentex 7109CS User manual

Gentex Smarter Vision GN-200 Series User manual

Gentex

Gentex Smarter Vision GN-200 Series User manual

Gentex UL 1971 COMPLIANT User manual

Gentex

Gentex UL 1971 COMPLIANT User manual

Gentex 7000 Series User manual

Gentex

Gentex 7000 Series User manual

Gentex Smarter Vision CO1209 Series User manual

Gentex

Gentex Smarter Vision CO1209 Series User manual

Popular Smoke Alarm manuals by other brands

Kidde WFP user guide

Kidde

Kidde WFP user guide

Evolution EVC-H instruction manual

Evolution

Evolution EVC-H instruction manual

Kidde 10Y29 user guide

Kidde

Kidde 10Y29 user guide

PSA Products homeguard HG1000 Installation and user manual

PSA Products

PSA Products homeguard HG1000 Installation and user manual

Harrington FireSpy Tracker T1000 installation manual

Harrington

Harrington FireSpy Tracker T1000 installation manual

DEGA FWL Home instruction manual

DEGA

DEGA FWL Home instruction manual

Red Arrow Trading SMAB-2 installation instructions

Red Arrow Trading

Red Arrow Trading SMAB-2 installation instructions

FCI 7100 SERIES Installation & operating manual

FCI

FCI 7100 SERIES Installation & operating manual

Bosch D285 installation instructions

Bosch

Bosch D285 installation instructions

System Sensor 2112 Installation and maintenance instructions

System Sensor

System Sensor 2112 Installation and maintenance instructions

Siemens Cerberus DOT1151A-Ex Technical description

Siemens

Siemens Cerberus DOT1151A-Ex Technical description

Abus RM 03 VdS Operating and installation instructions

Abus

Abus RM 03 VdS Operating and installation instructions

HIK VISION DS-PDSMK-E-WE quick start guide

HIK VISION

HIK VISION DS-PDSMK-E-WE quick start guide

Abus FURM30000 user manual

Abus

Abus FURM30000 user manual

Homeguard HG3000 Installation and user manual

Homeguard

Homeguard HG3000 Installation and user manual

Abus RWM90 user manual

Abus

Abus RWM90 user manual

Abus RWM50 user manual

Abus

Abus RWM50 user manual

Abus RM23 NF user manual

Abus

Abus RM23 NF user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.