Genvex GE ENERGY 1 User manual

Version 1.02 - 0110
GB
Installations Manual
Passive Ventilation
Counter Current Heat Exchanger
GE Energy 1•
GE Energy 2•
GE Energy 3•

2
Table of contents
GES Energy 1 - Installation..........................................4
GE Energy 1 - Installation............................................4
Energy 2 - Installation ..................................................5
Energy 3- Installation ...................................................5
Duct connection ...........................................................6
Duct system ..................................................................6
Condensate drain .........................................................7
Insulation of ducts in cold loft spaces .......................7
Insulation of ducts in heated spaces..........................8
Reheating of supply air................................................8
Electrical installation....................................................9
Inspection and initial adjustment of appliance..........9
Optimum initial adjustment of plant .........................10
Maintenance of plant..................................................10
Fault finding................................................................12
Electric Diagram EC - engine ....................................13
Electric Diagram Optima 100.....................................14
EU-Declaration of conformity....................................15
Subject to Technical Modications

3
Installation
When installing the units follow these instructions:
1) Tilt the machine 10-15 mm towards the drainpipe
to allow condensing water to run to drain.
(Does not apply for GES)
2) Install an airtight water trap on a non-freezing
location, to compensate for fan pressure.
3) The water trap hight must be at least 100 mm.
4) Make sure that the drain flows downwards all the
way from the unit.
5) Pour 1 liter water into the driptray in the unit to
verify that it is drained properly. Up to the heating
season make sure that the drain is properly filled
with water.
6) If freezing of the water trap may occur, it is necessary
to install a thermostat and electrical heater to prevent
freezing, when the temperature drops below +2C°.
7) Airflow adjustments must be made on both supply
and exhaust sides for a normal use of the machine.
It is important to have a balance between supply
and exhaust air volumes
8) It is recommended to keep the ducts closed until
the unit is adjusted and used.
This instruction must be followed. If the drain is not
made according to this instruction, GENVEX A/S can
not be made responsible for any additional damages,
which have nothing to do with the GENVEX unit.
.IMPORTANT .IMPORTANT .IMPORTANT .IMPORTANT .IMPORTANT .
.IMPORTANT .IMPORTANT .IMPORTANT .IMPORTANT .IMPORTANT .
100 mm
Siphon
To internal drain
Extract AirFresh Air
Supply AirExhaust Air
Lack of water in siphon = water damage
1%

4
Installation
ø160
ø160
382 7
ø160
ø160
ø
15
175
580
1000
1000
191
310 380
150
5
3
4
9
1
276
8
10
12
12
11
13
GE Energy 1
Dimensions in mm
GE Energy 1 - Installation
The GE Energy 1 is available in a right-hand version (as
shown). For a mirror image unit, the front and rear panels
may be removed, the back panel mounted on the front
and the unit rotated 180°. This will cause the supply to
exchange places with the escaping and the fresh air with
the extract, with the cover on the correct side of the unit.
The drain connection will also be on the opposite side.
The unit must be positioned on a subsurface such that
vibrations from the unit cannot be transferred down through
ceiling and walls and such that the condensate drain with
the necessary trap can be led to an internal drain without
danger of freezing in cold weather, as in the winter period a
unit may produce up to 8 litres of condensate per day.
To allow access for service and maintenance, there must
be a clear space of a minimum of 600 mm in front of the
unit. If the unit is located in the loft, there must be free
access to the unit from the loft hatch.
Bypass:
The GE units can be delivered with modulising bypass or it
can be mounted on site.
Weight: 55 kg
GE Energy 2 - Installation
The GE Energy 2 is available in a right-hand version (as
shown). For a mirror image unit, the front and rear panels
may be removed, the back panel mounted on the front and
the unit rotated 180. This will cause the supply to exchange
places with the escaping and the fresh air with the extract,
with the cover on the correct side of the unit. The drain
connection will also be on the opposite side. The unit must
be positioned on a subsurface such that vibrations from the
unit cannot be transferred down through ceiling and walls
and such that the condensate drain with the necessary trap
can be led to an internal drain without danger of freezing in
cold weather, as in the winter period a unit may produce up
to 8 litres of condensate per day.
To allow access for service and maintenance, there must
be a clear space of a minimum of 600 mm in front of the
unit. If the unit is located in the loft, there must be free
access to the unit from the loft hatch.
Bypass:
The GE units can be delivered with modulising bypass or it
can be mounted on site.
Weight: 84 kg
1: Fresh (external) air
2: Escaping air
3: Extract air
4: Supply air
5: Countercurrent heat exchanger
6: Supply fan
7: Extract fan
8: Fresh air lter
9: Extract lter
10: Electrical cabinet
11: Condensate tray
12: Condensate drain 15 mm
13: Bypass
ø200
228
150
175
266
ø200
ø15
ø200
ø200
1000
580
580 10
4
3
1
2
5
89
76
12
10 12
11
13
GE Energy 2
Dimensions in mm
1: Fresh (external) air
2: Escaping air
3: Extract air
4: Supply air
5: Countercurrent heat exchanger
6: Supply fan
7: Extract fan
8: Fresh air lter
9: Extract lter
10: Electrical cabinet
11: Condensate tray
12: Condensate drain 15 mm
13: Bypass

5
Installation
GE Energy 3 - Installation
The GE Energy 3 is supplied in a right-hand version (as
shown) or left-hand version (mirror image), in which the
fresh air exchanges places with the extract air and the
supply air with the escaping air. The drain is also on the
opposite side. The unit has supports and can be installed
directly on a vibration-free sold sub-surface. If oscillation
dampers are provided (extra equipment), these should
be mounted under the supports. In addition it must be
ensured that the condensate drain with the necessary trap
can be led to an internal drain without danger of freezing
in cold weather, as a unit may produce up to 8-10 litres of
condensate per day.
To allow access for service and maintenance, there must
be a clear space of a minimum of 700 mm in front of the
unit. If the unit is located in the loft, there must be free
access to the unit from the loft hatch.
The units are installed with bypass.
Weight 185 kg
GE Energy 3
Dimensions in mm
1: Fresh (external) air
2: Escaping air
3: Extract air
4: Supply air
5: Countercurrent heat exchanger
6: Supply fan
7: Extract fan
8: Fresh air lter
9: Extract lter
10: Electrical cabinet
11: Condensate tray
12: Condensate drain 15 mm
13: By-pass damper
14: Water-based reheating
1.480
12
214 214
2
14
13
8
5
366
Ø250
Ø250
732
696
798
1
1
6
93
4
100
7

6
Installation
3 m
1 m
3 m
Friskluft
Incomming Air
Frischluft
Afkast
Exhaust Air
Fortluft
Udsugning
Extract Air
Abluft
Indblæsning
Supply Air
Zuluft
Afløb
Duct connection
All duct connections display a yellow sticker indicating the
type of ventilation channel to be connected.
Connect the supply air:
Duct system from the unit to the supply outlet in the living
room.
Connect the extract air:
Duct system from wet rooms to the unit.
Connect the fresh air:
Duct system from fresh air roof cowls/external grills from
the ground collector to the unit.
Connect the exhaust air:
Duct system from unit to the escaping roof cowls/external
grills.
Duct system
It is recommended that the duct system is executed in
spiral ducting connected with rubber ring seal fittings in
order to provide a leak-free and durable duct system.
To achieve a satisfactory low sound level from the unit,
sound locks must always be fitted to the supply and extract
duct system between the unit and the first supply and
extract fittings.
It is recommended that air speeds in the ducts are
dimensioned at sufficiently low level to prevent noise from
the supply and extract fittings.
When positioning fresh air and extract roof cowls/grills,
make sure the two air flows do not intercept, causing
escaping air to be drawn in again.
It is recommended that grills are placed on the north or
east side of the house to provide optimum comfort.
100 mm
Siphon
To internal drain
Extract AirFresh Air
Supply AirExhaust Air
Lack of water in siphon = water damage
1%

7
Installation
100 mm
Siphon
To internal drain
Extract AirFresh Air
Supply AirExhaust Air
Lack of water in siphon = water damage
1%
Duct insulation, alt. A
Duct insulation, alt. B
Faulty duct insulation
Condensate drain
The units produce up to 10 litres of condensate per day. It
is therefore important that the condensate drain is correctly
executed and that the unit has a slight fall towards the
condensate drain.
The condensate drain pipe must be air tight for example by
bending a copper pipe as an siphon (see sketch to the left).
Use an armed water hose between the drain connecting
piece on the unit and the siphon and tightend it in both
ends with a collar band.
From the siphon and to the internal outlet there must be
a necessary fall on 1%. The condensate drain must be
fitted with a water trap as there is negative pressure in the
chamber in which the condensate tray is mounted.
If the unit is installed in a cold loft space, the condensate
drain pipe must be insulated to prevent freezing of the
condensate in the pipe. However, it is recommended that
the water trap is installed in a heated space below to
ensure that the water in it does not freeze.
If installation problems make it impossible to secure the
condensate drain pipe from freezing by insulation, it will be
necessary to mount a thermostat-controlled heating tape
round the condensate drain pipe.
Insulation of ducts in cold loft spaces
In order to exploit the unit’s high recovery potential
(efficiency), it is necessary to insulate the ducts correctly.
Supply and extract ducts:
To minimise heat losses from the duct system in cold loft
spaces, the supply and extract ducts must be insulated
with a minimum of 100 mm insulation. If insulation form
alternative A is used, it is recommended that it is executed
with two layers of 50 mm lamella mats with paper or foil
externally and with staggered joints between the two
layers. If the ducts are laid on the rafter foot, alternative B
may be used. The insulation must always be tightly packed
round the ducts.
Fresh air and escaping ducts in cold spaces:
It is recommended that fresh air and escaping ducts
are insulated with a minimum of 50 mm insulation. The
fresh air duct is insulated to prevent warm air in the loft in
summer from heating up the fresh air. Take care to seal the
termination where the escaping duct is led through the roof
or through the gable end, in order to avoid condensation
damage.
GE Energy 1 - 3

8
Installation
Extract Air
Supply Air
With water-based reheating surface
500
Extract air
Supply air
With electrical reheating surface
500
Insulation of ducts in heated spaces
Supply and extract ducts:
In warm loft spaces the supply and extract channels must
be insulated with 50 mm insulation.
Supply and extract ducts led through heated spaces in
dwellings do not require insulation. If the supply air duct
has cooling, bypass or earth heat exchanger installed it
must be insulated.
Fresh air and exhaust ducts:
In warm loft spaces and heated rooms in dwellings the
fresh air and escaping ducts must be insulated with
minimum 50 mm insulation. In addition the insulation must
be covered externally with plastic film or aluminium foil in
order to avoid condensate in the insulation.
We recommend an insulation of 100 mm on the fresh air
duct when installing a earth heat exchanger.
Reheating of supply air
As the counter current heat exchanger cannot extract all
the heat from the extract air and supply it to the supply air,
the supply air will be about 1-4°C colder than the room
temperature in the dwelling for the whole winter season.
If this lower supply temperature is insupportable during
cold periods, a water-based or electrical reheating surface
can be mounted for reheating the supply air up to room
temperature.
Water-based reheating surface
To protect the water-based reheating surface from frost
burst, a frost protection thermostat must be fitted to the unit
and the surface insulated. The frost protection thermostat
sensor is mounted behind the fins of the water-based
reheating surface. The sensor for controlling the motor
valve is mounted in the supply air channels approx. 500
mm downstream of the water-based reheating surface
in order not to be affected by the radiant heat from the
heating element. The water supply to the water-based
reheating surface must be executed by an authorised
plumbing and heating engineer.
Electrical reheating surface
The sensor for controlling the electrical heating surface
is mounted in the supply air channel approx. 500 mm
downstream of the electrical reheating surface in order
not to be affected by the radiant heat from the heating
element.

9
Installation
Electrical installation
The electrical connection must be carried out by an
authorised electrical engineer.
See accompaning electric diagram.
The cable between the unit and the control panel is a 4-
conductor 0.25 mm2cable with a maximum length of 50 m.
Optima 100: The cable (RJ 45) between the unit and the
control panel must be max. 10 meters long.
Inspection and initial adjustment of appliance
To achieve optimum running of the unit it must be initially
adjusted with air measuring equipment.
To start up the unit before adjustment, do as follows:
Before starting up the unit:
1: Check that the Genvex unit is correctly mounted and
that all ducts are insulated as required.
2: Check that hatches can be opened so that service and
maintenance on the unit can be carried out.
3: Check that filters are clean (may be dirty from
installation work).
4: Check that the condensate drain is correctly mounted
with water trap and is protected from freezing. Pour 1
litre water into the condensate tray and make sure it
can run unhindered through the condensate drain pipe.
5: Set all supply valves such that the valve closest to the
unit is opened three turns from closed position, while
the furthest is open eight turns from closed position.
Open the intermediate valves by 4-7 turns depending
on how far they are from the unit.
6: If a reheating surface has been mounted on the unit,
set the supply temperature to 0-3°C below the room
temperature in the dwelling.
The unit can now be started up and be allowed to run until
initial adjustment with air measurement equipment has
taken place.

10
Installation
Optimum initial adjustment of plant
Air measuring equipment is used.
Before starting initial adjustment, check that the 6 points
in the inspection and initial adjustment section have been
carried out. Then start up the unit:
Maintenance of plant - Optima 250 DESIGN
Filters:
When the red lamp on the control panel ashes, the
lters must be changed/cleaned. Stop the unit with the
switch on the unit or the electrical panel. Open the front
cover and take out the lter. When the lter has been
changed or cleaned by shaking it and by removing the
worst dirt, switch on the unit and press the enter button
on the control panel for 10-15 seconds until the Genvex
logo starts ashing again and the equipment is back in
normal operation.
Careful handling of the plates is required.
They have sharp edges and must not be
damaged.
Do not vacuum or clean at high air pressure. It
will damage the lter!
Maintenance of plant - Optima 100
Please pay attension to the red diode wether it is ashing
or constant on. If it is constant on the lters must be
changed. If the diode ashes the lter in the exhaust
hood must be changed.
G4 = Standard lter
(Coarse lter class G4)
F5 = Fine lter (Fine lter class F5)
F7 = Pollen lter (Fine lter class F7)

11
Installation
Condensate drain:
When changing the filter in August/September,
before outside temperatures falls to 5°C, check the
condensate drain for blockage by dirt and check that
there is water in the water trap.
Pour 1 litre water into the condensate tray and make sure it
can run off without problems. If the condensate drain does
not work, this could lead to water damage in the dwelling.
Countercurrent heat exchanger:
Inspect the countercurrent heat exchanger every year. If it
is dirty, remove it and wash in warm soapy water and then
rinse, possibly in the bathroom using the shower head.
Fans:
Every year check the two fan wheels for dirt. If they are
dirty they may be cleaned with a brush, bottle washer
etc. Remember to shot down the power.
Supply and extract valves:
Clean the valves by wiping with a dry cloth. Make sure the
valve does not rotate, causing a change in the air volume.
Service
If you are unable to maintain your unit yourself, you
can sign a service agreement with the Genvex service
department. If any faults arise in the unit, contact the
Genvex service department.
100 mm
Vandls
Til indvendig aflłb
GE Energy 1, 2 and 3

12
Unit has stopped:
No light in any of the lamps on the control panel, even
though both buttons are pressed.
Error:
- Fuse on electric panel has blown, no power to unit
- One of the fuses on the circuit board has blown
- Loose wire, no power to unit
- Loose wire between unit and control panel
- Faulty or incorrectly set clock, (units with mounted clocks)
Red lamp on control panel constantly lit:
Error Optima 250 DESIGN:
- Frost protection thermostat disconnected, (Units with
water-based reheating surfaces).
- Defective sensor in unit.
- Defective sensor in control panel.
- If not supply sensor has been mounted, this has been
replaced by a resistor which is faulty.
- Loose sensor wire or loose jumper in terminal row on
control circuit board.
Error Optima 100:
- Change filter.
Condensate running out of appliance:
Error:
- Condensate drain blocked by dirt.
- No water in water trap.
- Condensate drain blocked by frozen water.
- Drain insufficiently insulated.
No supply air to living rooms:
Error:
- Defective fan.
- Blocked bag filter.
- Fresh air grill blocked by dirt and leaves in the autumn or
snow and ice in the winter.
- Fuse on control circuit board has blown.
- No power.
No extract air from wet rooms:
Error:
- Defective fan.
- Blocked flat filter.
- Fuse on control circuit board has blown.
Cold supply air:
Error:
- Counter current heat exchanger blocked with dirt or ice.
- Extract fan defective.
- Extract filter blocked.
- Electric reheating surface disconnected at the fire
thermostat.
(Only units with mounted electric reheating surface).
- No hot water circulation to water-based reheating surface.
(Only units with mounted water-based reheating surface).
- Blocked circulation pump, air in heating pipe, defective
thermostat/motor valve, incorrect setting of control panel.
Fault finding
The display shows Optima 250 DESIGN:
Data error:
- No communication between the display and controller.
- Cable between display and circuit board to long.
Version error:
- If the program in the display section does not suit the
controller.
Change filter:
- The filters must be changed.
Hold ON-OFF:
- The filters have not been changed within the last 14 days.
- The unit has stopped
Fault finding

Electrical Diagram
BY-PASS
Sensor Freezing water
Sensor Extract air
Sensor Exhaust air
Sensor Fresh air
Sensor Supply air
Genvex
Hygrostat
Potentialfree
Contact
Must be used
Run
signal
230VAC
Optima 250 EC Connections
Mains
1x230VAC, 50Hz
MAX Fuse 16A
Must be connected to earth
N
L
Water valve
Electrical Preheater Electrical Heater
N
N
L
External stop
Phase from
mains
Optional output 230VAC,
see operating manual
Damper
Sensor Option
EC-Fan
Supply
Max 1,6A
EC-Fan
Exhaust
Max 1,6A
Blue
Blue
Brown
Brown
Yell/Green
Yell/Green
Blue
Blue
Yellow
Yellow
L
N
Wire no 5
Is not used
No.3/White
Nr.1/Black
Nr.2/Red
No.1/Black
Nr.3/White
No.2/Red
Hy¬Set
T1
90°C
manu
T1
90°C
manu
N PEL L PEN
Optima
250
Controller
Remote controlller
0V +10V TX RX
Motor
Walve
24
VDC
0V 0-10V
Reheater
1.2KW Step 1
Relay 2
Extra cooling
preheater
0.8KW, Relay 3
5K
5K
5K
5K
5K
5K
Relay 8
10µF
T 500mA
T 1.6 A
T 3.15 A
T 500mA
1000µF
35V
1000µF
35V
47µF
25V 47µF
25V
1000µF
30
30
30
30
30
30
7805
4 MHz
Relay 9
T8
T7
T4
T3
T1
0-10V
0V
24VDC
1 23
0-10V
0V
24VDC
LM230
3
12
T2
21
22
23
24
T9
2L
3N
12
13
14
15
18
19
20
21
22
23
2425
26
27
28
29
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
60
61
62
63 PE1
M1
M2

Electric Diagram Optima 100
Blue
Brown
Yell/green
Yellow
Blue
Blue
Brown
Yell/green
Yellow
Blue
Genvex
Hygrostat
Potentialfree
Contact
Must be used
Mains
U:1x230V, 50Hz,13 A
230V Controlrelay
for Electrial Reheater
L1 N
Sensor Heatrelay
Sensor defrost
Optima 100
RJ 45
Hy¬Set
T1
M1
Supply
M2
Exhaust
OPT. 100
1N
2L
3PE
4PE
5PE
6
7
8
9 10 11 12 13 14 15 16 17 18 19
12 3
N
L1
PE
CONTROLLER OPT 100
T2

15
Installation
EU-Declaration of conformity

Genvex World Wide:
www.genvex.dk
Copenhagen
Billund
Hamburg
Intelligent ventilation system from Genvex
As ventilation specialists, we offer a product range that
covers all aspects of modern ventilation equipment, from
passive ventilation units with highly effective counter
current exchangers to units with integrated heat pumps
that are extremely power efficient for heating or cooling.
We can also provide units for ceiling mounting for
installation in existing office buildings, high-rise buildings
and industrial buildings.
Denmark
Genvex A/S
DK - 6100 Haderslev
Tel.: +45 73 53 27 00
Fax: +45 73 53 27 07
Norwegian
Varmeteknikk Norge
N - 2240 Magnor
Tel.: +47 62 83 21 50
Fax: +47 62 83 21 59
E-Mail: [email protected]
Germany
Novelan GmbH
D-95359 Kasendorf
Tel.: +49 (0) 92 28 / 99 60 7-0
Fax: +49 (0) 92 28 / 99 60 7-189
Belgium
Artiklima bvba
B - 9220 Hamme
Tel.: +32 (0) 52 41 25 41
Fax: +32 (0) 52 41 29 66
Great Britain
Total Home Environment Ltd
GB- Moreton in Marsh, GL 56 0JQ
Tel.: +44 (0) 845 260 0123
Fax: +44 (0) 1608 652490
Ireland / N.I.
ECO Systems Ireland Ltd
Co. Antrim BT54 6PH
Tel.: (UK 028) (ROI 048) +44 2076 8708
Fax: (UK 028) (ROI 048) +44 2076 9781
Schwitzerland
Wesco AG
CH-5430 Wettingen
Tel.: +41 (0) 56 438 11 11
Fax: +41 (0) 56 438 12 10
Austria
J.Pichler Lufttechnik GmbH
A-9021 Klagenfurt
Tel.: +43 (0) 463 / 3 27 69
Fax: +43 (0) 463 / 3 75 48
E-Mail: [email protected]
Slovenia
Pichler & CO d.o.o.
2000 Maribor
Tel.: +386/ (0) 2/460 13 50
Fax: +386/ (0) 2/460 13 55
E-Mail: [email protected]
Croatia
Pichler & CO d.o.o.
10000 Zagreb
Tel.: + 385/ (0) 1/ 65 45 407
Fax: + 385/ (0) 1/ 65 45 409
E-Mail: [email protected]
Portugal
Iberterm
PT-4475-493 Nogueira Maia
Tel: +351 229 065 123/4
Fax: +351 229 065 125
E-Mail: [email protected]
Web: www.iberterm.com Published by Genvex A/S, Sverigesvej 6, DK-6100 Haderslev
Presented by:
This manual suits for next models
2
Table of contents
Popular Heating System manuals by other brands

System air
System air Fantech SER260D installation manual

System air
System air SAVE VSR 150/B installation instructions

Armstrong
Armstrong 3760 ProDose Series Installation and operating instructions

Steffes
Steffes ThermElect 8150 Owner's and installer's manual

Sunquest
Sunquest SQ-1220 Installation & operation manual

S&P
S&P SLIM Series manual