5
Numero dei poli / Number of poles 3 3
Corrente nominale Ie / Rated current Ie [A] 0,16 to 32 28 to 63
Tensione nominale Ue / Rated operational voltage Ue [V] 690 690
Frequenza nominale / Rated frequency [Hz] 50/60 50/60
Tensione nominale di isolamento Ui
Rated insulation voltage Ui [V] 690 1000
Tensione di tenuta ad impulso Uimp
Rated impulse withstand voltage Uimp [kV] 6 8
Categorie di utilizzazione / Utilization category
Interruttori / Circuit breaker IEC 60947-2 CAT. A CAT. 3
Categorie di utilizzazione / Utilization category
Avviatori / Motor starter IEC 60947-4-1 AC-3 AC-3
Classe d’intervento / Trip class IEC 60947-4-1 10 10
Caratteristica d’intervento istantaneo
Istantaneous trip characteristic 13 X Ie max 13 X Ie max
Potenza dissipata (3 poli)
Power loss (3-pole) 7W: In = 0,16 to 25A. 8,5W: In = 32A. 15W: In = 40 to 50A. 17W: In = 63A.
Durata meccanica / Mechanical durability [op] 100.000: In=0,16 to 25A 70.000: In=32A 50.000
Durata elettrica / Electrical durability [op] 100.000: In=0,16 to 25A 70.000: In=32A 25.000
Num. di operazioni per ora (motore avviato)
Max. operations per hour (motor start-up) [op/h] 25 25
Protezione mancanza fase / Phase-loss protection Fornito / Provided Fornito / Provided
Indicatore d’intervento / Trip indicator Fornito / Provided Fornito / Provided
Funzione di prova di intervento / Test trip function Fornito / Provided Fornito / Provided
Potere di interruzione [kA]
Rated breaking capacity [kA]
IEC 60947-2
Modello
Type
Tarature
Ratings 240V
230V
415V
400V
460V
440V 500V 690V
600V
240V
230V
415V
400V
460V
440V 500V 690V
600V
[A] Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
GH3RHB- P16 0,1-0,16 100 100 100 100 100 100 100 100 100 100 - - - - -
GH3RHB- P25 0,16-0,25 100 100 100 100 100 100 100 100 100 100 - - - - -
GH3RHB- P40 0,25-0,4 100 100 100 100 100 100 100 100 100 100 - - - - -
GH3RHB- P63 0,4-0,63 100 100 100 100 100 100 100 100 100 100 - - - - -
GH3RHB- 001 0,63-1 100 100 100 100 100 100 100 100 100 100 - - - - -
GH3RHB- 1P6 1-1,6 100 100 100 100 100 100 100 100 100 100 - - - - -
GH3RHB- 2P5 1,6-2,5 100 100 100 100 100 100 100 100 8 6 - - - - -
GH3RHB- 004 2,5-4 100 100 100 100 100 100 100 100 8 6 - - - - -
GH3RHB- 6P3 4-6,3 100 100 100 100 100 100 100 100 6 5 - - - - -
GH3RHB- 010 6.3-10 100 100 100 100 50 38 50 38 6 5 - - - - -
GH3RHB- 013 9-13 100 100 100 100 50 38 42 32 6 5 - - - - -
GH3RHB- 016 11-16 100 100 50 38 35 27 10 8 4 3 - - - - -
GH3RHB- 020 14-20 100 100 50 38 35 27 10 8 4 3 - - - - -
GH3RHB- 025 19-25 100 100 50 38 35 27 10 8 4 3 - - - - -
GH3RHB- 032 24-32 100 100 50 38 35 27 10 8 4 3 - - - - -
GH3RVB- 040 28-40 - - - - - 100 100 50 38 35 27 10 8 5 4
GH3RVB- 050 35-50 - - - - - 100 100 50 38 35 27 10 8 5 4
GH3RVB- 063 45-63 - - - - - 100 100 50 38 35 27 10 8 5 4
Dimensioni /dimensions WxHxD [mm] 45X90X79 55X110X96
Peso / Weight [g] 370 780
CONFORMITA’ / STANDARDS IEC 60947-1, 60947-2, 60947-4-1, UL 508, CSA C22.2.No. 14 IEC 60947-1, 60947-2, 60947-4-1, UL 508, CSA C22.2.No. 14
INTERRUTTORI AUTOMATICI SALVAMOTORI / MANUAL MOTOR STARTERS