
Specifications Single Phase Three Phase
Product Code T2DDT0 T3DDT0
Supply Voltage (Un) 110 – 240 VAC [-20% to +15%], 50/60 Hz
Power Consumption 8 VA @ 300 VAC
Storage Temperature -10 °C to +60 °C
Operating Temperature -10 °C to +50 °C
Switching Contacts 2 3
Contact Rating 8A (Res.) @ 240 VAC and 5A (Res.) @ 30 VDC
Utilization Category AC-15 and DC-13
Power Reserve (For Clock Only) 1000 h
Shortest Switching Time (Daily) 1 Minute
Clock Deviation (max) +/- 1 second per day over the operating
temperature range
Geographical Co-ordinates Resolution 1°1´
DST Settable
Manual Override Provided. Use keys on keypad.
Display Backlit LC Graphics display for diagnostic view
Under/Over Voltage (UV/OV)
trip value
Not Applicable Settable UV: 0–220V
And OV: 130–330V
Trip Time for UV/OV Not Applicable 5-16 seconds
Recovery Time Not Applicable 1-4 seconds
Mounting Base/ DIN Rail
Dimension (in mm) 72 X 90 X 67
Weight (Unpacked) 190 g 208 g
EMC tests
Harmonic Current Emissions IEC 61000-3-2 Ed. 3.0 (2005-11) Class A
ESD IEC 61000-4-2 Ed. 1.2 (2001-04) Level II
Radiated Susceptibility IEC 61000-4-3 Ed. 3.0 (2006-02) Level III
Electrical Fast Transients IEC 61000-4-4 Ed. 2.0 (2004-07) Level IV
Surge IEC 61000-4-5 Ed. 2.0 (2005-11) Level IV
Conducted Susceptibility IEC 61000-4-6 Ed. 2.2 (2006-05) Level III
Voltage Dips and Interruption (AC) IEC 61000-4-11 Ed. 2.0 (2004-03) All 7 Levels
Conducted Emission CISPR 14-1 Ed. 5.0 (2005-11) Class A
Radiated Emission CISPR 14-1 Ed. 5.0 (2005-11) Class A
Safety
Test Voltage between I/P and O/P IEC 60947-5-1 Ed. 3.0 (2003-11) 2 kV
Test Voltage between all terminals
and enclosure
IEC 60947-5-1 Ed. 3.0 (2003-11) 4 kV
Impulse Voltage between I/P and O/P IEC 60947-5-1 Ed. 3.0 (2003-11) Level IV
Single Fault IEC 61010-1 Ed. 2.0 (2001-02)
Insulation Resistance UL 508 Ed. 17 (1999-01) 2000 MΩ
Leakage Current UL 508 Ed. 17 (1999-01) < 3.5 mA
Environmental testing
Cold Heat IEC 60068-2-1 Ed. 6.0 (2007-03)
Dry Heat IEC 60068-2-2 Ed. 5.0 (2007-07)
Vibration IEC 60068-2-6 Ed. 7.0 (2007-12) 5 g
Repetitive Shock IEC 60068-2-27 Ed. 4.0 (2008-02) 40 g, 6 ms
Non-repetitive Shock IEC 60068-2-27 Ed. 4.0 (2008-02) 30 g, 15 ms
Appendix A – Selecting a required menu
This section describes how to select a menu. The menu
selection is required either for selecting a sub-menu or for
viewing a functional block for setting parameters. The
following example illustrates how to view today’s
sunrise/sunset.
1.At power ON this screen will
be displayed. Press ‘ESC’ key to
view main menu.
2. Press ‘Z2’ or ‘Z4’ key to
move cursor to "VIEW" Menu.
Then Press ‘OK’ key.
3. Press ‘Z2’ or ‘Z4’ key to
move cursor to "SUN TODAY"
Menu. Then Press ‘OK’ key
4. The Sunrise and set values
will be displayed.
Appendix B - Setting the value of parameter
The following example illustrates the procedure to set the value
of parameter in detail. This procedure can be used for setting any
parameter in function block. Here the Slave ID for MODBUS is to
be set as 224.
1. When user selects “MODBUS CONFG”
option from “TRANSFER” menu, this
screen appears. Press OK to go the next
screen.
2. This screen shows slave ID as 001.
For example to set slave ID as 254,
follow the steps 3 & 4.
3. Now cursor is on the first digit.
Press ‘ALT’ key to edit that digit, then
press ‘Z2’ or ‘Z4’ keys to change the
digit. In order to make first digit as 2 so
press Z2 twice. Then press ‘OK’ to save
the change.
4. Now to move cursor to the next digit
press ‘Z3’ key.
Repeat same procedure to change last
two digits. After changing all digits press
‘OK’ to save settings.
You will again return to “SET MB ID”
screen. Then Press ‘ESC’ until you return
to the main screen.
Degree of Protection:
IP-20 for Terminals;
IP-40 for Enclosure
Pollution Degree: II
Mechanical Life: 10 million
Electrical Life: 0.1 million
Slave modbus ID is 1.
Preset single register function code is 6.
Starting address 0.
Value to be written is 3.
Query: 01, 06, 00, 00, 00, 03, CRC HI, CRC LO.
Response: 01, 06, 00, 00, 00, 03, CRC HI, CRC LO.
Example 4: Preset Multiple Register to change
mode of coils 1, 2, 3 using Function 16[0x10].
To change Q1, Q2, Q3 status.
Slave modbus ID is 1.
Preset Multiple Registers function code is 10.
Starting address is 0.
Values to be writing are 0, 3, and 4.
Query: 01, 10, 00, 00, 00, 03, 06, 00, 00, 00, 03,
00, 04, CRC HI, CRC LO.
Response: 01, 10, 00, 00, 00, 03, CRC HI, CRC LO.
Example 5: Get the description of the type of
controller present at the slave address using
Function 17[0x11].
Slave modbus ID is 1.
Report slave ID function code is 11.
Query: 01, 11, CRC HI, CRC LO.
Response: 01, 11, 0E, 30, 30, 2E, 31, 30, 2E, 30, 30, 32,
AA, 01, 03, 03, 00, CRC HI, CRC LO.
Response Parameters –
Version String [4 to 12 bytes]:
Size of Version String = 9. In response device give ASCII
values of version string.
Example: 00.03.000.
Manufacture code [13th byte] & Set feature code [14th byte]
Product Information [15th byte]: 00 - for single Phase Astro,
03 - for 3 Phase Astro.
Stabilizer Interface [16th byte]: 03- Stabilizer with 3 Phase
Astro.
Reserved- [17th byte].
Note: For Modbus related DST and Season settings, refer
help-file provided with Application Software- ‘Astro-Soft’.
MODBUS: Memory map:
Coil Status
Modbus
Address Parameters Value
Modbus
Address
00001 Relay 1 Status 1- On , 0- OFF 00001
00002 Relay 2 Status 1- On , 0- OFF 00002
00003 Relay 3 Status 1- On , 0- OFF 00003
Holding Registers
Modbus Address Parameter Value Validation
Default
Value
40001 Relay 1 Mode 00 - AUTO 0 to 4 0
04 - Auto On
03 - Auto OFF
40002 Relay 2 Mode 00 - AUTO 0 to 4 0
04 - Auto On
03 - Auto OFF
40003 Relay 3 Mode 00 - AUTO 0 to 4 0
04 - Auto On
03 - Auto OFF
Example 1: Read Status of coil 1, 2, 3 using
Function 1[0x01].
Request to read coils 1-3 from slave device.
Slave modbus ID is 1.
Read coil function code is 1.
To read coil 1 - 3 modbus coil address is 0 -2.
Number of coils to be read is 3.
Query: 01, 01, 00, 00, 00, 03, CRC HI, CRC LO
Response: 01, 01, 01, 07, CRC HI, CRC LO
Here Data-07[111] i.e. Q3, Q2, Q1 are ON.
Example 2: Read mode of coil 1, 2, 3 using
Function 3[0x03].
Slave modbus ID is 1.
Read holding register function code is 3.
Coil starting address 0
Number of coils to be read are 3.
Query: 01, 03, 00, 00, 00, 03, CRC HI, CRC LO
Response: 01, 03, 06, 00, 03, 00, 00, 00, 04,
CRC HI, CRC LO
Example 3: Preset Single Register to
change mode of coil 1, using Function
6[0x06].
To change Q1 status to Auto OFF mode
Page 2
Q1-A Q2-A
Q3-A
18/09/09 WED
11:00 ESC
EDIT…
VIEW…
SETTINGS…
TRANSFER…
SUN TODAY
Q TODAY…
VOLTAGE NOW
DST DATE
RISE
06:15
SET
17:47
SET MB ID
SLV ID 001
SLV ID 201
SLV ID 224
Terminology used in this leaflet:
Under Voltage is voltage below
which load will become OFF.
Over Voltage is voltage above
which load will become OFF.
Once Load becomes OFF due to
Under Voltage condition, it will
become ON only when Voltage
becomes = (Under Voltage +
Hysterisis). If Load becomes OFF
due to Over Voltage condition, it will
become ON only when Voltage
becomes = (Over Voltage -
Hysterisis). Hysterisis is kept as 15
Volts. This is to avoid chattering of
contactor.