Glastender Dixell User manual

Dixell
Digital Controller operation
Glastender, Inc. · 5400 North Michigan Road · Saginaw, MI · 48604-9780
800.748.0423 · 989.752.4275 · Fax 989.752.4444 · www.glastender.com
© 2017 Glastender, Inc.11-02-17
A Family Company Manufacturing
In The USA Since 1969
This manual is specic to the operation and diagnostic
guides of the Dixell digital controller used in Glastender
self-contained back bar coolers.
To view the manual specic to the Full Gauge digital controller used in Glastender
self-contained back bar coolers visit:
http://www.glastender.com/PDF/Full_Gauge_digital_controller_operation.pdf
Dixell
Full Gauge

Dixell Digital Controller operation & DiagnostiC guiDe
Factory Settings Range of Adjustment
Set Point Operating
Range†
Minimum Set
Point
Maximum Set
Point
Standard Cooler Setting 34º F 34º F to 39º F 33º F 65º F
Two Zone Cooler Settings*
B = Beer 34º F 34º F to 39º F 33º F 65º F
W = White Wine 50º F 50º F to 55º F 33º F 65º F
R = Red Wine 60º F 60º F to 65º F 33º F 65º F
†Adjusting the factory set point will also adjust the operating range by the same amount
*To determine a Two Zone Cooler refrigeration conguration, refer to the 2 digits immediately preceding the
rst hyphen of the model number found on the cooler data tag. These 2 digits will always be BW (Beer/
White Wine), BR (Beer/Red Wine), or WR (White Wine/Red Wine). Example: MODEL: BB60BR-L1-
XS(LR).
The refrigerator is programmed to automatically
defrost four times daily for approximately twenty
minutes. During defrost, the fan inside the cooler
will remain on and the refrigeration system will
turn off. To initiate defrost manually, push and hold
the DEFROST button for more than two seconds.
The thermostat controller does not have an “OFF”
function. To turn refrigerator off, the unit must be
unplugged or power to the electrical branch circuit
has to be turned off via a circuit breaker or switch.
To change the set point - push and hold the SET
button for more than two seconds. When the º F
display begins ashing, push the up arrow or down
arrow buttons to adjust the set point to the desired
value.
To save the new set point and return to the tem-
perature display mode - push and release the SET
button or wait ten seconds.
The operating temperature range is preset at the
factory according to the table below and can be
adjusted up or down within the limits shown.
To see the set point - push and immediately release
the SET button. The set point will be displayed.
To return to normal visualization - Push and
immediately release the SET button or wait ve
seconds.
Glastender, Inc. • 5400 North Michigan Road • Saginaw, MI • 48604-9780
800.748.0423 • 989.752.4275 • Fax 989.752.4444 • www.glastender.com
Rev. 11-11-14
Models BB, ND, LP, FV, MFV, UCR Self Contained
Coolers using Dixell digital thermostat controller
The thermostat control probe wire connector
may become disconnected when the compressor
compartment cover and/or grill are removed. This
will result in thermostat P1 code. While the P1 code is
ashing the compressor will cycle 5 minutes on and 5
minutes off and may cause icing of the evaporator coil.
Service calls to reconnect the probe wiring are not
covered by factory warranty.
Probe wire
connector

Warning: Performance and reliability issues that result from the controller parameters being changed from
the factory default settings are not covered under warranty.
Controller error codes:
➢P1- Room Probe Failure
•Check to make sure the probe is connected to the controller
•Check the probe resistance (see “Checking the probe resistance” below)
➢P2- vaporator Probe Failure
•This error should only occur on MFV units. Verify that the unit is an MFV model.
•Check to make sure the probe is connected to the controller
•Check the probe resistance (see “Checking the probe resistance” below)
➢dF- Indicates that the unit is in defrost
•Normal Scheduled defrosts can last up to 20 minutes at the factory default values
•If abnormal defrosts are suspected see “Resetting the program to factory default settings” below
➢HA- Maximum Temperature Alarm
•The box temperature has exceeded the 75° maximum for more than 30 minutes
•See diagnostic flow charts below
➢LA- Minimum Temperature Alarm
•The box temperature has deceeded the 25° minimum (-15° for MFV) for more than 30 minutes
•See diagnostic flow charts below
Checking the controller set point:
➢Press the set button once to display the controller set point. Press again to return to the temp display.
Changing the controller set point:
➢Hold the S T key for 3 seconds, release, and use the arrow keys to change the set point. The set point can be
changed from 33° to 65° on coolers and 0° to 28° on MFV's
•Factory Default set points are as follows: MFV 10°, Beer 34°, White Wine 50°, Red Wine 60°
•There is a 5° (8° for MFV) differential between cut in and cut out temps. If the controller set point is 35°
the range will be 35° to 40°. (MFV controller set point 10°, range will be 10° to 18°)
Checking the probe resistance:
➢Verify the probe resistance is accurate at the box temperature
•Use a calibrated thermometer to check the cooler's temperature at the evap inlet where the probe is located
•Disconnect the probe from the controller
•Use a calibrated Ohm meter to measure the resistance of the probe at the box temperature
•The resistance of the probe should match the associated box temperature of the following table
➢Fill a cup full of ice water (use a lot of ice), put the probe into the ice bath, stir for 1 minute, then measure the
resistance with a calibrated Ohm meter. Make sure to keep the probe in the center of the cup.
•The probe should have 27,280 Ohms of resistance in the ice bath. Replace the probe if it is not within 2
degrees Ohms range from Table 1 above.
F-755-028 Rev. 9/16/16
Table 1
Temp Deg F Temp Deg F Temp Deg F Temp Deg F Temp Deg F
-4 67770 22 34852 42 21596 64 13246 86 8313
-2 64579 23 33900 44 20687 66 12668 88 8008
0 61388 24 33164 46 19778 68 12090 90 7703
2 58197 26 31693 48 18869 70 11626 92 7398
5 53410 28 30222 50 17960 72 11161 94 7093
8 49763 30 28751 52 17233 74 10697 95 6940
10 47332 32 (Ice Water) 27280 54 16507 76 10232 96 6816
12 44901 34 26118 56 15780 77 10000 98 6569
14 42470 36 24956 58 15053 78 9813 100 6322
16 40566 38 23793 59 14690 80 9438 102 6074
18 38661 40 22631 60 14401 82 9063 104 5827
Ohm
Re i tance
Ohm
Re i tance
Ohm
Re i tance
Ohm
Re i tance
Ohm
Re i tance

Checking the controller display temperature accuracy:
➢After verifying the probe resistance to the box temperature, plug the probe into the controller and check the
temperature displayed
•The controller should display the associated temperature of Table 1 above when compared to the
resistance measured
Note: the probe cannot be plugged into the controller when measuring resistance
➢Fill a cup full of ice water (use a lot of ice), put the Ohm verified probe into the ice bath, stir for 1 minute.
Make sure to keep the probe in the center of the cup.
•The controller should display 32°
Checking the controller compressor relay:
Does the controller relay open and close at the operating range specified on the data tag?
•If the controller is calling for cooling, the compressor relay (terminals 8 & 9) will have continuity
Note: there is a 1 minute anti-short cycle delay programmed into the controller. The snowflake will
flash on the display indicating this delay. When the snowflake is solid, the controller is calling for
cooling and the relay will be closed.
Resetting the program to factory default settings:
➢Hold the S T and DOWN ARROW for 3-4 seconds until the display changes and release; the display will
either read “r ” or “d2” and the °F symbol will be flashing. Immediately hold the S T and DOWN ARROW
for another 7-8 seconds until the display changes to L2, release the buttons and Hy will be displayed; this is
the controllers hidden menu where you can set the parameters of the chart below.
Note: The S T and DOWN ARROW must be pressed at the same time. If one is accidentally
released, the process will need to be restarted.
Note: If no keys are pressed, the hidden menu access will time out after 15 seconds and revert to
normal operation.
•Use the arrow keys to scroll to the desired set point
•Press set to access the value
•Use the arrow keys to change the value
•Press set again to lock in the value
The chart below represents the factory default settings of MFV, Beer, White and Red Wine controllers
Set the values to the associated product for the proper control of the unit
F-755-028 Rev. 9/16/16
Label De cription
MFV Beer Wht Wine Red Wine
Label De cription
MFV Beer Wht Wine Red Wine
0-35 34-40 50-55 60-65 0-35 34-40 50-55 60-65
Regulation Defro t
Hy Differential 8 5 5 5 td Defro t type in
LS Min Set Point 0 33 33 33 dE Defro t Termination Temp 75 50 50 50
US Max Set Point 35 65 65 65 id Interval Between Defro t Cycle 4 6 6 6
ot Fir t Probe Calibration 0 0 0 0 Md Max Length For Defro t 20 20 20 20
P2 Second Probe Pre ence y n n n dd Start Defro t Delay 0
oE Second Probe Calibration 0 0 0 0 dF Di play During Defro t dE dE dE dE
od Delay At Startup 0 0 0 0 dt Drip Time 2
AC Anti- hort Cycle Delay 1 1 1 1 dP Defro t at Power On n
Cy Comp On Time Faulty Probe 5 5 5 5 Alarm
Cn Comp Off Time Faulty Probe 8 5 5 5 AU Max Temp Alarm 75 75 75 75
Di play AL Min Temp Alarm -15 25 25 25
CF Unit of Mea ure Ad Temp Alarm Delay 30 30 30 30
rE in in in in dA Exclu ion Of Temp Alarm At Startup 99 99 99 99
Ld Default Di play P1 P1 P1 P1 Other
dy Di play Delay 0 0 0 0 tb tb y y y
d1 Thermo tat Probe Di play
d2 Evap Probe Di play nP nP nP
Pt Parameter Code Table 1 5 5 5
rL Firmware Relea e 1.5 1.5 1.5 1.5
°F °F °F °F
Re olution (For °C Only)
Read
input
Read
input

Diagnostic flow charts:
F-755-028 Rev. 9/16/16
HA
Is the box temp cycling at the
set point plus the differential?
See Checking the controller
Set point
No
Y S
Is the “AU” Set point
programmed for factory default?
See Resetting the program to
factory default settings
Replace the
Controller
Y S
No
See Warm ox
Diagnostic Flow Chart
LA
Does the probe resistance
match the associated
temperature of Table 1?
YesNo
Replace the
Probe
Y S
Is the “AL” Set point
programmed for factory default?
See Resetting the program to
factory default settings
Y S
Does the probe resistance
match the associated
temperature of Table 1
No
No
No Yes
Replace the
Controller
Replace the
Probe
Is the controller relay
stuck closed?
See Checking the
Controller compressor
relay
Is the refrigeration
system running?
Is the box temp cycling at the
set point plus the differential?
See Checking the controller
Set point
Replace the
Controller
No
No
Reprogram
See Resetting the program to
factory default settings
Yes
Does the probe resistance
match the associated
temperature of Table 1?
Yes
Replace the
Probe No
Yes
Reprogram
See Resetting the program to
factory default settings
Reprogram
See Resetting the program to
factory default settings
Warm
Box
Are the
compressor
and all
fans running?
No
Is the controller calling for
cooling? A snowflake will
appear on the display
Is the controller set
at the desired set point?
See Checking the
Controller set point
Y S
No
Y S
Reprogram
See Changing the
controller set point
Y S
No
Is the probe
touching the
evaporator?
No
Yes
Is there continuity
across the controller
compressor relay?
See Checking the
controller compressor
relay
Reposition the
probe
Does the probe resistance
match the associated
temperature of Table 1?
YesNo
Replace the
Probe
Replace the
Controller No
Yes
Check for bad
compressor,
fans, or wiring
Check for
refrigeration issues
or air infiltration
Table of contents