
DETECTOR SOUNDER/ BEACON ADDRESS SETTINGS
MORE INFO >> WWW.GLOBALFIRE-EQUIPMENT.COM
D.I.L. SWITCHES CONFIGURATION
1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8
01 02 03 04 05 06 07 08
1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8
09 10 11 12 13 14 15 16
1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8
17 18 19 20 21 22 23 24
1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8
25 26 27 28 29 30 31 32
1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8
57 58 59 60 61 62 63
1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8
33 34 35 36 37 38 39 40
1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8
41 42 43 44 45 46 47 48
1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8
49 50 51 52 53 54 55 56
1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8
94 95 96 97 98 99 100 101
Sounder 1 Sounder 2 Sounder 3 Sounder 4 Sounder 5 Sounder 6 Sounder 7 Sounder 8
1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8
102 103 104 105 106 107 108 109
Sounder 9 Sounder 10 Sounder 11 Sounder 12 Sounder 13 Sounder 14 Sounder 15 Sounder 16
1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8
110 111 112 113 114 115 116 117
Sounder 17 Sounder 18 Sounder 19 Sounder 20 Sounder 21 Sounder 22 Sounder 23 Sounder 24
1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8 1234 5 6 7 8
118 119 120 121 122 123 124 125
Sounder 25 Sounder 26 Sounder 27 Sounder 28 Sounder 29 Sounder 30 Sounder 31 Sounder 32
Switches 1-5
Used to configure the
Sounder/Beacon address
Switch 6
Only used for Detector Sounders Address
Switch 7
OFF Beacon stops with ALARM SILENCE
ON Beacon stops with RESET
Detector Sounder/ Beacon - The Vulcan 2 Detector Sounder/ Beacon is a Base Sounder and/or Beacon which is also used to interface one
conventional detector to the Analogue Addressable Loop. The number of Detector Sounders/ Beacons connected to each Loop is dependent on
Loop loading and in any case the total number/ loop should not exceed 64. If only detector sounders are used then this number may be
increased to 96 sounders per loop. This includes normal addressable sounder beacons placed between address 94 and 125. These are fully
programmable in sounder groups.
Detector Sounders are always placed between address 1 and 63 and cannot be included in sounder groups. Device will report to the panel as
either a SMOKE or HEAT detector depending on MODE jumper position.
CAUTION: SHADOW Sounder/ Beacon - The Vulcan 2 Addressable Detector Sounder/ Beacon should NOT be configured as a Shadow
Sounder/ Beacon using the 8 – way dip switch provided. Switch 8 should always be in the ON position.
SOUNDER/ BEACON ADDRESS SETTINGS
Address Switches
Binary Weights
1 ON = 1
2 ON = 2
3 ON = 4
1 2 345678
ON (1)
OFF (0)
ON
OFF
Sounder Type
Switch No. 8
OFF = Shadow
ON = Normal
4 ON = 8
5 ON = 16
6 ON = 32
INSTALLATION