
13
SYSTEM OPERATION f. Afterithasbeendeterminedthateachapplianceconnectedtothe
venting system properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace dampers and any
other gas burning appliance to their previous conditions of use;
g. Ifimproperventingis observedduringanyoftheabovetests,the
common venting system must be corrected.
Correctionsmustbeinaccordancewiththelatesteditionof
the National Fuel Gas Code NFPA 54/ANSI Z223.1 and/or
CSAB149InstallationCodes.
If resizing is required on any portion of the venting system,
usetheappropriatetableinAppendixGinthelatestedition
oftheNationalFuelGasCodeANSIZ223.1and/orCSAB149
InstallationCodes.
Thermostat Requirements
Atwo stageheat/coolthermostatis recommended. Asingle
stageheatingthermostatmay be used. It is recommended
thata high quality thermostat witha "C"terminal isusedto
operatethe furnace.
Thermostat Location
Inanarea having good air circulation, locate the thermostat
about five feet high on a vibration-free inside wall. Do not
install the thermostat where it may be influenced by any of
thefollowing:
• Drafts,ordeadspotsbehinddoors,incorners,orun-
dercabinets.
• Hot or cold air from registers.
• Radiantheatfrom the sun.
• Lightfixturesor other appliances.
• Radiantheatfrom a fireplace.
• Concealed hot or cold water pipes, or chimneys.
• Unconditioned areas behind the thermostat and de-
humidistat, such as an outside wall.
COMBUSTION AND VENTILATION AIR
REQUIREMENTS
WARNING
POSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH MAY OCCUR
IF THE FURNACE IS NOT PROVIDED WITH ENOUGH FRESH AIR FOR PROPER
COMBUSTION AND VENTILATION OF FLUE GASES. MOST HOMES REQUIRE
OUTSIDE AIR BE SUPPLIED TO THE FURNACE AREA.
Improvedconstructionand additional insulation in buildings
have reduced heat loss by reducing air infiltration and es-
capearounddoorsandwindows.Thesechangeshavehelped
in reducing heating/cooling costs but have created a prob-
lem supplying combustion and ventilation air for gas fired
and other fuel burning appliances. Appliances that pull air
out of the house (clothes dryers, exhaust fans, fireplaces,
etc.)increasethe problem by starving appliances for air.
When the furnace is installed as a direct ven (2-pipe) fur-
nace, no special provisions for air for combustion are re-
quired.However, if thisfurnaceisto be installed inthesame
space with other gas appliances, such as a water heater,
FurnaceSuspension
If suspending the furnace from rafters or joist, use 3/8"
threadedrodand2”x2”x1/8”angleironas shown in the fol-
lowing figure. If the furnace is installed in a crawl space it
mustalso be suspended fromthefloorjoistor supported by
a concrete pad. Never install the furnace on the ground or
allow it to be exposed to water. The length of rod will de-
pendon the application andthe clearancesnecessary.
TILT OUTWARD TO ALLOW FOR
DOOR AND CIRCULATOR BLOWER
REMOVAL.
3/8" DIAMETER
THREADED ROD
(6 PLACES)
PROVIDE 8" MINIMUM CLEARANCE BETWEEN
CENTER ROD AND FURNACE CABINET
TO ALLOW FOR CIRCULATOR BLOWER REMOVAL.
ASSURE FURNACE IS LEVEL FROM
END TO END.
ON 90% FURNACES MAKE SURE
THE UNIT HAS A SLIGHT
FORWARD TILT WITH THE FRONT
OF THE FURNACE 0"-3/4"
BELOW THE BACK OF THE FURNACE.
POSITION AS CLOSE AS POSSIBLE
TO BLOWER DECK TO ALLOW FOR
CIRCULATOR BLOWER REMOVAL.
2"X2"X1/8" ANGLE IRON
(3 PLACES)
HOLD DOWN
NUTS
SUPPORT
NUTS
CONDENSATE
DRAIN
GAS PIPING
ALTERNATE
GAS PIPING
90% Suspended Furnace Shown
EXISTING FURNACE REMOVAL
NOTE:When anexistingfurnace isremovedfrom aventing
system serving other appliances, the venting system may
be too large to properly vent the remaining attached appli-
ances.
The following vent testing procedure is reproduced from the
AmericanNationalStandard/NationalStandardofCanadafor
Gas-Fired Central Furnaces ANSI Z21.47, latest edition,
CSA-2.3b,latestedition Section 1.23.1.
Thefollowingsteps shallbe followedwitheach applianceconnectedto
the venting system placed in operation, while any other appliances
connected to the venting system are not in operation:
a. Seal any unused openings in the venting system;
b. Inspect the venting system for proper size and horizontal pitch,
as required by the National Fuel Gas Code, ANSI Z223.1 or the
CSAB149InstallationCodes andtheseinstructions. Determine
that there is no blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe condition;
c. In so far as practical, close all building doors and windows and
alldoors betweenthespacein whichthe appliance(s)connected
totheventingsystemarelocatedandotherspacesofthebuilding.
Turn on clothes dryers and any appliance not connected to the
venting system. Turn on any exhaust fans, such as range hoods
and
bathroom exhausts, so they shall operate at maximum speed.
Do not operate a summer exhaust fan. Close fireplace dampers;
d. Follow the lighting instructions. Place the appliance being in-
spected in operation. Adjust thermostat so appliance shall
operate continuously;
e. Test for draft hood equipped spillage at the draft hood relief
openingafter 5minutesof mainburneroperation. Usetheflame
of a match or candle;