
SYSTEM OPERATION
17
• Extremely cold weather
• Long vent connectors
• Masonry chimneys with no air gap between the liner and
the bricks. (In practice, this can be dicult to detect.)
• Exterior chimneys (The tables in National Fuel Gas
Code NFPA 54/ANSI Z223.1 - latest edition and in the
National Standard of Canada, CAN/CGA B149.1 and
CAN/CGA B149.2 - latest editions and amendments
assume interior chimneys.)
If, in the judgment of the local gas utility, installer, and/or local
codes; one or more of the above factors is likely to present a
problem, the chimney must be relined (Fix 4).
Any cap or roof assembly used with a liner must be approved
by the liner manufacturer for such use. The liner and cap/roof
assembly must then terminate above the roof in accordance
with the manufacturer’s instructions.
In some cases, a shorter extension above the roof may be
possible with a liner than would be required with a masonry
chimney.
For further information on relining, see Fix 4.
If the masonry chimney has more than one channel, it may be
possible to vent the gas appliances into one channel and vent
the solid or liquid fuel appliance(s) into another channel(s).
Do not vent an 80% furnace inside of a metal liner with other
appliances vented outside the liner.
Alternatively, the homeowner may agree to discontinue use
of the replace (solid fuel appliance). If so, the tile liner must
be cleaned to remove creosote buildup. The replace opening
must then be permanently sealed.
If oil-fired appliance(s) are being replaced by gas-fired
appliance(s), the tile liner must rst be cleaned to remove
the fuel oil residue.
If none of the above options are practical, the 80% furnace
may need to be vented vertically with B vent.
Under some conditions a 90%+ furnace could be installed
rather than an 80%. The 90% furnace can be vented
horizontally or vertically through PVC pipe.
If the chimney crown is damaged, a qualied mason must
repair it in accordance with nationally recognized building
codes or standards. One such standard which may be
referenced is the Standard for Chimneys, Fireplaces, Vents,
and Solid Fuel Burning Appliances, ANSI/NFPA 211.
Relining options include B vent and exible liners.
If the chimney has diagonal osets, B vent probably cannot
be used.
If B vent is to be used, it must be supported adequately.
Supports (such as re stops or thimbles) must be used to
prevent the B vent from coming into direct contact with the tile
liner or chimney walls. Direct contact would result in higher
heat loss, with an increased possibility of poor venting system
performance.
It is not acceptable to vent one appliance inside the B vent
and other appliances outside. The excess space between the
B vent and the chimney walls must be covered at the top of
the chimney by a weatherproof, corrosion resistant ashing.
The B vent should then be topped with a listed vent cap. The
listed vent cap will, when installed per the manufacturer’s
instructions, prevent problems due to rain, birds, or wind
eects.
A B vent installed as described in this section is considered to
be an enclosed vent system, and the sizing tables in National
Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in
the National Standard of Canada, CAN/CGA B149.1 and CAN/
CGA B149.2 - latest editions and amendments may be used.
If a exible liner is to be used, it must be made of the proper
materials:
• For most residential applications, an aluminum liner
should be acceptable.
• If the combustion air supplied to the furnace will be
contaminated with compounds containing chlorine
or uorine, a liner of AL29-4C stainless steel should
be used. Common sources of chlorine and uorine
compounds include indoor swimming pools and chlorine
bleaches, paint strippers, adhesives, paints, varnishes,
sealers, waxes (which are not yet dried) and solvents
used during construction and remodeling. Various
commercial and industrial processes may also be
sources of chlorine/uorine compounds.
• Heavier gauge 300 and 400 series stainless steel liners
were developed for use with oil or solid fuel appliances.
They are not suitable for use with gas-red appliances.
Flexible liners specically intended and tested for gas
applications are listed in the UL “Gas and Oil Equipment
Directory”. (UL Standard 1777).
For sizing of exible liners, see Note 22 and the tables in the
National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition
and in the National Standard of Canada, CAN/CGA B149.1
and CAN/CGA B149.2 - latest editions and amendments.
To install the liner, read and follow the liner manufacturer’s
instructions and your local codes. Excess liner length should
be pulled out of the chimney and cut o. Use caution when
doing this, as the cut edges of exible liners may be sharp.
Do not spiral excess liner inside of the chimney. Support the
liner as recommended by the liner manufacturer.
Some manufacturers of exible liners oer an insulation
sleeve designed to be added to the liner before it is installed
in the chimney. (Poured insulation, either vermiculite or other
materials, is no longer recommended.) Insulation will need to
be added to the exible liner if:
• •It is required by the liner manufacturer’s instructions.
• •The previous liner was properly sized and installed,
and suered from condensation damage.
• •It is required by your local building codes.