
MR--05365 SM SERIES PUMPS
TROUBLESHOOTING PAGE B -- 3
Be certain to refer to the wiring diagram(s)
before reconnecting any electrical compo-
nents which have been disconnected.
Test Equipment
A volt/amp/ohmmeter and megohmeter of ade-
quaterangeandqualitywillberequiredtoconduct
thefollowingelectricaltests.Thesuggestedequip-
ment indicated below is commercially available, or
an equivalent substitute may be used.
Equipment Use
Ammeter/
Voltmeter To check AC Voltage
and current (amperage)
Ohmmeter To measure resistance
(ohms) to ground
Voltage Imbalance
Each phase of the incoming three-phase power
must be balanced with the other two as accurately
as a commercial voltmeter will read. If the phases
are balanced, check out the motor as described
below. If the phases are out of balance, contact
yourpowercompanyandrequestthattheycorrect
the condition.
a. Useavoltmeter,amprobe,orequivalentme-
ter to read the voltage across terminals 1 &
2,2&3,and1&3inthe controlbox. Allthree
measured voltages must be the same, as
accuratelyasthemeterwillread.Ifpossible,
measure the voltage with the pump off, with
the pump running but out of the water, and
with the pump running in the water at full
load.Allthemeasured voltagesateachcon-
dition must be the same.
b. Use an amprobe or equivalent meter to
measure the current draw of each phase
while the pump is running at fullload and at
no load. All three amperage readings must
be the same at each condition, as accurate-
ly as the meter will read. Nominalamperage
values are listed in Table 1, but these apply
onlywhentheactualvoltageatthesiteisthe
nominal voltage listed.
c. If the voltages are balanced with the pump
off, but are unbalanced when the pump is
running, a thorough check of the power
source, all interconnecting cables, and the
pumpmotorisrequiredtoisolatethedefect.
Motor And Motor Power Cable Continuity
To check continuity, zero-balance the ohmmeter
set at the RX1 scale, and test as follows:
a Disconnect the motor power cable leads
from the control box and connect the test
leadstoanytwoofthethreepowercable
leads(nottothegreengroundleadoryellow
ground check lead). If there is a high resis-
tance reading on the ohmmeter, there is an
open or broken circuit cause a break in the
power cable or motor windings, orby a bad
connectionbetweenthemotorandthepow-
er cable. Switch one test lead to the third
power lead, and test again.
b. If an open or broken circuit is indicated,
check the power cablefor obvious damage,
and replace as necessary (see MAINTE-
NANCE AND REPAIR). If there is no appar-
ent damage to the motor cable, remove the
terminal housing (see MAINTENANCE
AND REPAIR) and check the continuity of
eachpowercableleadattheterminalposts.
c. If an open circuit still exists after each lead
(terminal) has been tested and tightened,
then the entire motor power cable must be
replaced. Splicing or other means of repair
are not recommended.
d. If no break is found in the power cable,
check the motor leads for continuity. If the
testreadingindicatesanopenorbrokencir-
cuit, there is an open circuit in the motor.
NOTE
Itisrecommendedthatapumpwithadefectivemo-
tor be returned to Gorman-Rupp, or to one of the
Gorman-Rupp authorized Submersible Repair en-
ters.