Graf AquaControl+ Operation manual

User information
AquaControl +
Fill level measuring device and drinking
water supply
Item no.: 351021
Otto Graf GmbH Carl-Zeiss-Str. 2-6 Tel .: 07641-5890
unststofferzeugnisse D-79 331 Teningen Fax: 07641-58950
Page 1

Figure 1: View of equipment
1: LED for power supply display
2: Display
3: LED for drinking water operation
4: LED for faults and malfunction
5: Operating uttons
6: Lower cover of the System Control
7: Main connection ca le with coupling for data lead and analogue
outlet (0-10V)
8: Alarm indicator contact and valve connection for filter cleaning
the rainwater filter
9: Valve connection with power coupling
10: The mains circuit reaker of the system controls are under this
cover.
11: Mains power supply ca le and pump connection with power
coupling
Page 2

Figure 2: Sensor assembly
12: Data ca le
13: screw cap 3
14: Connection of the data ca le is reverse protected.
15: connect white ca le here
16: connect red ca le here
17: data ca le terminal
18: screw cap 2
19: screw cap 1
Page 3

20: active measuring length
22: Stainless steel pro e
23: Tank floor
24: Screws must e lunted ! (danger of injury)
25: overflow
26: Tank side in dome
27: Sensor
28: Sensor control ox ( measurement pick-up )
1. Safety Instructions
Please read carefully t e safety and instruction manual before using t is
device! Follow all instructions t at are in t e User Guide (Manual) to ac ieve
t e optimal performance. Please keep t ese safety and operating instructions
safe for furt er use.
General Safety Instructions
Symbol Explanation
- refers to an information
- means warning and indicates a special situation
- indicates a hazardous situation which may cause to heavy or
serious injury or
even death
1.1 Personnel
The installation, commissioning and dismantling of the device
must e done only y trained and authorized personnel. During
installation, it is necessary to pay attention to the safety
regulations defined y the user and local laws and rules.
Page 4

1.2 Proper Use of t e Device
T e equipment is designed exclusively for t e intended purpose specified in
t e manual. Any ot er use and / or misuse of t e device can lead to unpre-
dictable risks including deat and causes t e loss of all t e claims against t e
manufacturer.
1.3 Limitation of Liability
The manufacturer would not take over any lia ility for damages resulting from:
- the usage of the device y untrained and unauthorized personnel,
- use of device for not intended purpose
- opening and/or manipulation of the device
- not following the manual and safety instructions
1.4 Electric Current
!!Danger of life from electric current!!
Direct contact to the parts of the device will cause an electric shock. In
case of damage to the insulation, the device must e switched off
immediately and the damaged area must e de-energized.
While maintaining on the device, ensure that the power supply is off at
all times and make sure the device is de-energized.
1.5 Electric S ock
If o jects (e.g. hairpins, needles or coins) or liquids fall into the device,
it can cause life threatening electrical short-circuits, which can lead to
fire. The user has to make sure that a ove mentioned o jects, especially
made of metal and/ or liquid things, will not fall in to the device
intentionally or unintentionally.
1.6 Safety Operations
The operation and use of the device is to e done y instructed and
authorized personnel only.
Page 5

1.7 Power Supply
The equipment exclusively operates with the operating voltage indicated in the
manual.
1.8 Cable Connection
When installing the ca le connections, the user needs to pay attention to
the safety regulations. Always pay attention to the connection to the
protective earth ground! Pay attention when connecting with other
devices, that those have to e of the same earth potential (same heavy
current/voltage side).
1.9 Ventilation
The equipment must e installed in so that good ventilation to the device is
ensured. Do not put any covering o jects on the device, such as newspapers, ooks
or towels.
1.10 Water and Moisture
The device is not allowed to operate in close vicinity of electrical
conductive liquids or moist areas. It is not allowed to place any liquid
things on the device or in the near y area of the device.
Attention: Danger of Electric S ocks!
1.11 Temperature and Heat
The operating temperature of the device is defined in the specifications. The device
must not e placed near things which produce heat such as to lowers, heaters,
furnaces or other devices.
1.12 Opening t e Device
Disconnect t e mains plug before opening t e device!
There is a risk of electrical shock when touching the parts inside the
device. It is not permitted to make any changes in the device.
Page 6

1.13 Cleaning
Do not use any volatile solvents such as alcohol, diluents, gasoline etc.
to clean the device. Only use a dry, clean cloth.
1.14 Unusual Smell
If any unusual smoke or smell occurs, immediately switch off of the
device and remove it from the main power supply! Contact your dealer
or the manufacturer.
1.15 Fuses
T e replacement of t e fuses in t e device is only permitted by
trained and aut orized tec nical staff.
The change of the fuses is only allowed when the device is switched off
and is removed from the main power supply. Otherwise there is a risk of
electric shocks. The security functions and safety values are mentioned
in the manual. The guarantee for this equipment will expire in case of
using other fuses than those specified in the manual.
1.16 Repairing
The user is not allowed to perform the maintenance work y himself, except for
those specified in the manual. All maintenance and repair work must e done y
trained and authorized technical personnel.
1.17 Important notes on safety
Special Safety Instruction
Please, read and follow safety instructions carefully before assembly or using
t e device!
During installation and when working with 230 V ~ mains supply the VDE
regulations must e followed. Equipment using a 230 V ~ supply may only e
installed and commissioned y a qualified tradesman. The assem ly place must
allow all possi le safety precautions when laying the attached ca les.
Page 7

Power supply ca les and data ca les may not e damaged or squeezed for any
reasons. Plan the assem ly place so that you can reach the mains plug easily and
unplug it from the electrical outlet in dangerous situations.
Choose the assem ly place so that children cannot play or e near to the device and
at its connections without supervision.
Before opening the device disconnect it from the mains supply (unplug) otherwise
there is a serious danger of an electrical shock.
Fuses may only e replaced with standard-compliant parts with the same nominal
value.
All lia ility is excluded for damages which result from non-compliance of these in-
structions or from an improper handling of the device. At chosen intervals in this
hand ook we will give directions for safety precautions. These safety precautions
have een specially marked.
2. Description and intended use
The AquaControl+ is an electronic water management control system.
It has een developed especially for rain water usage systems. It can e used with a
wide variety of tank systems.
Tanks made from metal or steel reinforced cement may only e used when the fol-
lowing conditions have een correctly followed.
Metal tanks lead to faulty readings. Helpful is to assem le the device so that the
sensor is as far as possi le from the metal sides so for example, in the centre of a
cylindrical tank. The system controls offer an easy to use guide for the switch pro-
gramming. Using an LCD display the fill measurement is shown in 1 % stages (in
relation to the height of the tank).The sensor operates with a 12 volt supply. All
programmed values such as the tank height are retained after disconnection of the
power supply or after a power-cut.
3. Description
Performance features:
–Fill level measurement readout in 1% steps and with an additional ar
type indicator
–In 1% steps freely varia le choice of the switching points for the
drinking water refill
–Automatic flushing of the system (choice of intervals in day and time
are possi le)
–Dialogue oriented user guidance (choice of language)
–Equipment indication using 3 additional LED
–Supervision of the measurement pick-up and the sensor
–Error indication in simple text
Page 8

Technical data:
Control electronics Measurement sensors
Operating current :230V AC Measurement voltage :12V DC
Fused :T50mA Measuring frequency :(0,2-20)kHz
Power consumption :3VA Data ca le length :20m
Tank height :3m (optional 6m)
Measurements [mm] :155x165x90 Measurements [mm] :90x80x50
Pump connection Valve connections
Operating voltage :230V AC Operating voltage :230V AC
Pump capacity :max. 1200VA Valve effective performance : max. 1A
Note:
Only the control electronics in the device are protected by the fuse. Valves
and pump connections are not protected. These are protected only by the
mains supply via the mains fuse.
The yellow LED indicating Drinking water operation”[3] is lit as soon
as the valve switches over to the mains supply. The user is made aware
that the system now uses water from the mains supply. The red LED for
Faults and malfunctions” [4] is lit as soon as the system identifies a fault. The
display will then show a warning that describes the cause of the fault in plain text.
4. Assembly
4.1 Control system
The mains plug of the device serves as an on / off switch.
Before opening t e equipment pull t e plug out from t e mains
socket!
–Loosen the fastening screws of the lower cover [6] and remove the cover
–Mark out drilling points and drill according to sketch
–Fasten the device with the enclosed installation material (rawlplugs and screws)
Page 9

Figure 3: Drilling outline for housing outline
4 .2 Connection sensors and data cable:
The sensor electronics comprise of a stainless steel pro e [22] with a red and a
white connecting ca le [27] and the sensor measurement pick-up [28].
Figure 4: Sensor technology
1. Now the sensor measurement pick-up [28] (cover removed) should e
installed on the tank wall (prefera ly in the man hole shaft of the Graf
synthetic tank). The location of the mounted sensor pick-up should e
etween 10 and 15 cm a ove the overflow [25]. The enclosed screws
should e used to secure the device. After fully tightening the screws, the
points that are showing themselves on the outside of the tank must e
lunted to avoid injury [24].
2. Measure the height from the ottom of the tank [23] to the end of the
terminals [15] and [16] on the measurement pick-up [28].
3. Shorten the connection ca le to suit the measured height.
4. Connect the sensor ca le to the sensor as descri ed in the following
instructions: Remove etween 5-7 mm of the insulation from oth of the
ca les. Next, pass the red ca le through the screw mounting 1 [19] and
Page 10

tighten this lightly, then connect the red ca le to the terminal [16]. The
free white ca le is now passed through the screw mounting 2 [18] and
tightened lightly, then connect the white ca le to the terminal [15].
5. Now pass the end of the data ca le that has no plug connector [12]
through the screw mounting 3 [13]. Lightly tighten the screw mounting
and connect the ca le wire cores of the data ca le [12] to the dou le
terminal [14]. The connection of the data ca le is reverse polarity
protected. Attention! T e screws s ould be tig tened wit care to
ensure t at t ey are not damaged t roug over tig tening.
6. Now recheck that all the screwed items and the sensor components have
een fitted correctly. Replace the cover of the measurement pick-up and
secure this with the appropriate fastening screws.
7. The installation of the data ca le [12] to the system control must e
according to good professional practice to constitute a correct completion
of the sensor technology: A protective ca le conduit must e used. (The
data ca le is not suita le for installing directly in the earth).
The end of the data ca le that is still unconnected is fitted with a plug
connector. This is to e plugged into the appropriate socket [7] of the
system control. Diagram 2 on page 3 makes clear the interrelation:
Note:
The red and the white cable going down to the probe should be straight
and smooth to be drawn taught by the weight of the stainless steel probe.
The stainless steel probe must hang just above the tank floor.
Page 11

4.3. Electrical wiring diagram
The AquaControl+ offers the rain water system a dry run protection for the pump
or the house water system. So that the dry run protection will function properly the
rain water system must e wired according to the following diagram.
Figure 5: electrical wiring diagram
Note:
Should the existing pump or house water system already have a dry run
protection it may be appropriate and is possible to order the
AquaControl+ without a dry run protection.
4.4 Connection of t e solenoid valve
Connect the plug of the solenoid valve with the centre coupling [8] of the control
electronics (see figure 1).
5. Commissioning
Before the putting the equipment into operation check and e sure that all electrical
connections are correctly insulated and all covers are properly closed.
Page 12
AquaControl+
Sensor pick up
element
Sensor
Data cable
( 12V )
Valve
230V AC
(Net) ressure
switch
ump

Now open the transparent cover of the system controls. Plug the equipment into the
mains socket (this socket must e exclusively for the equipment and e on its own
fuse). The system then runs a system check through automatically.
For the duration of the system check (approx. 10 seconds) the following signal will
e displayed in the window:
Figure 6: Display during the equipment check
The equipment type is shown on the first line and the software check in progress is
shown in the second line.
If after the initial installation check all is correct, the LCD indicator will display the
fill level (in %).
The figure 7 shows the LCD-display in the operation mode. The display shows the
filling level and the operating modes as a reviations: "FV" and "P". These a re-
viations correspond as follows:
–FV+ : filter valve opened
–FV- : filter valve closed
–P+ : (pump on) house waterworks in operation
–P- : (pump off) no water currently eing withdrawn
Figure 7: Display in the operation mode
Page 13
AQ +
REV 3.1
Tank: FV- P-
50%
Status of rain water
filter flashing valve
Fill level in % Visual check of the fill level
Status house waterworks
(pump on / - off)

6. Set up of t e system control:
After putting into operation, the system control must e adjusted and programmed
according to the conditions and requirements of the individual users system. The
required settings are easily programmed. There are four uttons for this purpose.
All necessary programming data entries follow a menu displayed y the LCD. For
the set up follow all the points listed in ta le 1 in the sequence as shown. Should
any error in the sequence occur then it is necessary to egin the set up again from
the eginning starting with the tank height. Begin the programming of the settings
y pressing the utton marked “MENU”.
With the uttons “+” or “-” the menu may e scrolled ackwards and forwards.
With the respective menu point shown the values may e altered. For this the
utton “ENTER” must e used. The “?” displayed in the LCD will now change to a
“>”graphic character. With the “+” or “-” the desired value may now e entered
according to individual requirements. When the desired value has een entered this
must e confirmed y pressing the “ENTER” utton. The value is only then taken
over and stored in the programming of the unit.
Through pressing the “MENU” utton again the display changes ack to the
operation mode.
It is possi le to reset the unit to the factory setting standard values at any time.
The resetting can only e carried out in the operation mode (Display see Figure 7):
To do this press the “ENTER” utton and hold it pressed. Now simultaneously in
addition press the “MENU” utton. After a short wait the following display will e
shown:
Figure 8: Message reset to standard factory settings
As soon as this message is displayed the uttons may e released
The menu structure integrated in the system control is introduced to familiarise the
user in diagram 9. To ring up the menu, press and hold the „MENU“ utton for
longer than 5 seconds. All outlets are inactive when the menu level has een activ-
ated. The operation of the device is suspended. The system control switches auto-
matically ack to the operating mode when no entries have een received for ap-
proximately 30 seconds.
Page 14
DEFAULT VALUES
23%

key „MENU“ (>5s)
+/- +/-
Figure 9: Main menu level
Press the “ENTER” utton to arrive at each of the listed su -menu functions.
Through pressing the “MENU” utton again the display changes ack to the opera-
tion mode.
Page 15
SWITCHING POINTS
DEVICE
ADJUSTMENT
MANUAL OPERATION
TANK: FV- P+
23%
SWITCHING POINTS
PUMP ON
0-100% 8%
PUMP OFF
0-100% 6%
Pump OFF (The numerical value is always smaller
than with Pump ON.)
key „ENTER“
+ / -
Pump ON (The numerical value is always smaller
than with Valve ON.)
VALVE ON
0-100% 10%
VALVE OFF
0-100% 12% Supply with mains drinking water - OFF
+ / -
Supply with mains drinking water - ON (The
numerical value is always smaller than with Valve
OFF.)
+ / -
DW INTERVAL
0-14 DAYS 14
Flush the drinking water supply piping every 14
days. The value „0“ switches the flushing off.
+ / -
Main menu level

Figure 10: Sub-menu “Switching points”
Press the „ENTER“ utton to alter the respective switching points The value to e
altered will egin to link. The value may then e adjusted y using the „+“ and the
„-“ uttons. Press the “ENTER” utton again when the displayed value should e
accepted.
The following is an introduction to the general device settings:
Page 16
+ / -
Flush the drinking water supply pipes for 30
seconds.
+ / -
DW DURATION
0-60 SEC 30
Cleaning the rainwater filter every 14 days
The value 0 switches the cleaning process off.
+ / -
CLEANER INTERVAL
0-14 DAYS 14
Cleaning the rainwater filter for 5 seconds
CLEANER DURATION
0-60 SEC 5
CLEANER RINSE AT
INCREMENT 2%
Cleaning the rainwater filter when the fill level
has increased y 2% after rainfall. If the fill level
continues to increase, the rinsing will e repeated
every 3 hours. The value 0 switches the cleaning
process off.
+ / -
+ / -

Figure 11: Sub-menu “General device description”
The last part of the operation level covers the manual functions:
Figure 12: Sub-menu “Manual functions”
Page 17
DEVICE
ADJUSTMENT
LANGUAGE
ENGLISH
key „ENTER“
+ / -
[20] in Figure 2
(A 6m Sensor may e ordered.)
MEASURING LENGHT
30-600cm 200
+ / -
MANUAL OPERATION
LAST FLUSH
DW 0
key „ENTER“
+ / -
HAND FLUSH
DW NO
Time scale in days; the time elapsed since the
last flush using mains drinking water
LAST RINSE
CLEANER 1
+ / -
HAND RINSE
CLEANER NO
Time scale in days; the time elapsed since the
last filter rinse
+ / -
Activation of the filter rinse
Main menu level
Main menu level
Activation of the flushing process for the mains
drinking water inlet pipe. The switch-over valve
remains permanently switched on.

7. Error messages and fault correction:
T e operation of t e system control is to be c ecked at regular intervals (at
t e latest every 4 weeks).
The read out reports always represent only pro a ilities; e.g. no clear localization
y the device is possi le for overlaying faults.
Please also take note that the system control device cannot identify any
malfunction of the house water system. (No malfunction signal is supplied
by the house water system to the system control device).
If faults are recognized y the sensors the system control cannot continue to work
independently.
The particular faults are shown on the plain text in the display:
Page 18
ERROR
SENSOR
The reason for this error is that the white
sensor ca le has een damaged.
ERROR
DL SHORT CIRCUIT
Error possi ilities:
-The data ca le of the measurement pick-up
is not connected to the data ca le terminal
[14] ut has een connected to the sensor
terminal [15/16]
- Cinch plug or the cinch connector has a short
circuit
- Wires of the data ca le have een damaged
ERROR
SENSOR CONTROL
The measurement sensor delivers no signal
and must e replaced.
ERROR
SENSOR SYSTEM
For further diagnosis, remove the stainless steel
weight [22] out of the water. If the error indication
has now stopped, then the sensor it self was the
cause of the fault. If the error indication should
continue, this implies that the measurement pick-up
is defect.

Figure 13: Error messages
If the device shows no function at all then check whether the main electrical supply
provides current and also check the house fuses.
Before opening t e equipment pull t e plug out from t e mains
socket!
If the electrical outlet is under current, then unplug the mains plug from the system
control. Without connection to current open the lower cover of the system control
(see Figure 1) and check the equipments mains fuse.
If your efforts are unsuccessful, please consult the manufacturer y E-Mail:
Gm H
Niederlassung Prenzlau
Franz Wienholz Str. 40
17291 Prenzlau
Tel. : +49 (3984)- 80 87 17
Fax : +49 (3984)- 80 69 61
Internet : http:// www.aktuatorikundsensorik.de/
E-Mail : [email protected]
Page 19
ERROR
NO SIGNAL
The communication etween the system
control to the measurement pick-up is
interrupted.
ERROR
MEMORY
First try re-setting the system control to the
factory default settings . If the error message
continues to e displayed then it is necessary
to contact your service partner.
Note: After re-setting to the factory
default settings all the newly
programmed setting values will
have been overwritten and must be
re-programmed!

Please have the serial num er of the device ready when you contact us! The serial
No. is to e found on the Serial num er plate on the lower cover of the system con-
trol.
8. Upgrade options:
The SILENTIO control device can also e equipped with a num er of additional
special functions.
1. Optional pressure sensor
Using a pressure sensor, alternative mediums or depths
may e adapted to the use of the device. The sensor must
e matched the required specifications of the device.
2. Optional drain pump
If the fill level of the tank reaches a specified value, then
a valve or a pump can e activated. This is to prevent the
fill level of the tank from exceeding a specified
maximum level.
3. Optional refill
If the fill level in the main tank sinks elow a specified
level, then a second tank is employed to ack up and re
fill the main tank. The pump used in this process must
also e equipped with a mechanism to prevent it from
running dry.
If this system is required, then the device must e sent to the manufacturer. There
follows an additional calculation.
Note:
The standard system control device may be equipped with a maximum
of three additional switch output point.
Page 20
Other manuals for AquaControl+
1
This manual suits for next models
1
Table of contents
Other Graf Control System manuals
Popular Control System manuals by other brands

CSI
CSI COMPACT CIP Installation operation & maintenance

StarLogixs
StarLogixs CybaMICRO 2011 quick start guide

Crestron
Crestron 4K DigitalMedia 3-Series quick start guide

heat-timer
heat-timer Genesis Installation and operation manual

ZIEHL-ABEGG
ZIEHL-ABEGG ZETADYN 1DV Series System description

Crestron
Crestron FlipTop FT2 Series Getting started