
7
2.8.4 Setting ‘Normal Running’ Speed
The normal running speed is FACTORY SET AT 44% for intake and exhaust fans. These can be altered in steps of 1%
thus you can adjust the fan speed whilst measuring the airflow at the ducting.
Please note that the normal running speeds cannot be set higher than the boost speeds or vice versa (boost speeds
lower than normal speed).
To change the configuration to normal speed:
i. Initially, the left hand readout will be flashing
ii. Alter the intake running speed by using the [+] or [–] buttons accordingly
iii. Press [OK] to select the right hand readout (the image will start to flash)
iv. Alter the extract running speed by using the [+] or [–] button accordingly
v. When adjustment is completed, press [OK].
2.8.5 Altering the ‘Boost Running’ Speed
The boost running speed is FACTORY SET AT 66% for intake and exhaust fans. These can be altered in steps of 1%
thus you can adjust the fan speed whilst measuring the airflow at the ducting.
Following the set up of the normal speed, the display should now be as
opposite and the left hand readout should be flashing:
To change the boost speed settings, use the instructions as above for the
‘normal’ running speed.
When desired settings have been achieved press [OK], when the right hand
readout is flashing and the unit will advance to the run time counter display.
2.8.6 Run Time Counters
The unit records its run-time hours, which are displayed in two separate screens as follows:
The first screen shows years:months. This example represents
0 years and 11 months.
Press [OK] to advance to the next screen (all other buttons
have no effect).
The second screen displays days:hours.
The example below represents 24 days and 13 hours.
Press [OK] on this screen to exit configuration mode
and return to normal running status.
Note:
1. One month = 30 days (for the purpose of the run-time counter)
2. Run-time counters are written to memory once a day only, so in the event of a power failure, the hours only on
that day will be lost
3. The run-time counters are set to zero at manufacture and cannot be reset.
HRV1
Installation Instructions and User Manual